Owner's Manual for ideal HEATING models including: CB 299W, CB 399W, CB 470W, CB 500W, CB 299W Water Tube Commercial Boilers, CB 299W, Water Tube Commercial Boilers, Tube Commercial Boilers, Commercial Boilers

Commodore Water Tube Commercial Boilers CB 299/399 ...

(Flow switch manual reset high limit). Low water cutoff. Fixed speed high efficiency circulator. Fixed speed standard efficiency circulator. Variable speed ...

PDF preview unavailable. Download the PDF instead.

Commodore Wall CB Submittal Sheet rev1
Commodore Submittal Sheet Model
CB 299W CB 399W CB 470W CB 500W
Commodore Water Tube Commercial Boilers

Job Name: Location: Engineer: Wholesaler:

Date: Model No.: Gas Type: Contractor:
CB 299/399 Dimensions

CB 470/500 Dimensions

Product Selection

Model Number
CB 299W

S/R Water Vic. Conn.
1-1/2"

Gas Conn. NPT

Dimensions and Specifications Vent Conn. Vent Length

1"

4"

200'

Height 33-1/3"

Width 17-1/3"

Depth 21-1/5"

Weight lbs 174

CB 399W

1-1/2"

1"

4"

121'

33-1/3"

17-1/3"

21-1/5"

183

CB 470W

1-1/2"

1"

6"

200'

33-1/3"

17-1/3"

21-1/5"

187

CB 500W

Product Selection

Model Number
CB 299W CB 399W CB 470W CB 500W

1-1/2"

1"

6"

200'

33-1/3"

17-1/3"

21-1/5"

187

Commodore Water Tube Commerical Boiler Performance Data

Input, MBH

Min

Max

Output, MBH

Maximum Net AHRI Supply Rating WaTemp., F ter, MBH

AFUE %

46

299

289

194

238

95.1%

Thermal Combustion Efficiency, % Efficiency. %

-

-

72

399

381

194

329

-

95.5%

95.4%

83

470

453

194

394

-

95.6%

95.1%

83

500

475

194

413

-

95.1%

94.5%

Standard Features and Equipment
 Fold out panel with boiler control and display  Graphic LCD display with easy to use controls  On/Off Power Switch  Laptop computer connection  Supply and Return water temperature sensors  Integrated pressure sensor  Flue gas temperature sensor  Burner door temperature sensor  Rear wall thermal fuse  Integrated flue gas check valve (non-return valve)  Full stainless steel heat exchanger  Premix burner  Internal automatic air vent with drain connection  Integrated low water cutoff  Condensate trap  External ignition transformer connection

Boiler and External Controls
 Large backlit LCD with full text information programming and errors  Modbus connection standard  0-10 VDC remote flow temperature set point control  0-10 VDC remote boiler power output  Bacnet module for remote access available

Cabinet
 Removable stainless steel side panels for easy access
 Compact design with small footprint  Light weight design for wall hung
applications (187lbs)  Narrow width of 17.4 inches

Data Logging
 Real time and date clock  Days of operation  Successful ignition attempts  Ignition failures  Flame failures  Up to 48 readable lockout errors  Hours since last service  Hours until next service  Total days of boiler operation

Low Voltage Connections
 Outdoor temperature sensor  System temperature sensor  DHW temperature sensor  Modbus  Cascade connection  On/Off thermostat or OpenTherm  0-10V VDC input  Flow switch DHW  PWM pump control  External low water cut off  Gas pressure switch  Universal safety contact set 1 & 2
High Voltage Connections
 Boiler pump  System pump  DHW pump  DHW twv (3-way valve)  Alarm
Additional Features
 Two level frost protection  Short cycle protection  Adjustable minimum & maximum
power  Temperature boost function  Multiple levels of security  PWM control for variable speed
pumps  Domestic hot water priority time
control  Selectable priority for domestic hot
water or heating

Cascade
 Integrated cascade control  Cascade control of up to 16 boilers  Remote operation and heat demand
indication from each boiler  Four cascade power program modes  Boiler sequencing and rotation
control  Following boilers fully operational
on failure of lead boiler
Accessories
External flow temperature sensor
Indirect tank temperature sensor PC software+interface cable for programming boiler
BACNET module
Propane conversion kit
Air filter kit
Gas pressure kit
0-10V Modulating circulator signal converter
2 Circulators relay kit 3 Circulators relay kit ASME CSD-1 kit option 1 (Flow switch + manual reset high limit) Low water cutoff
Fixed speed high efficiency circulator
Fixed speed standard efficiency circulator
Variable speed high efficiency circulator
75 psi relief valve 3/4"
85 psi relief valve 3/4"
Neutralizer 400MBH - 7000MBH

CommodoreWallCBSubmittalSheet_rev1

2024-23


Adobe PDF Library 17.0 Adobe InDesign 19.4 (Windows)