Installation guide: Electric expansion valve AKVA 20
Specifications
Refrigerants: R717, HCFC, HFC
- Maximum Working Pressure (MWP): PS 42 bar (609 psig)
- Maximum Operating Pressure Difference (MOPD max.): (P1-P2) max. 18 bar (261 psig)
Temperature Limits:
- Ambient Temperature: -40 °C < tamb < 50 °C (-40 °F < tamb < 120 °F)
- Media Temperature: -40 °C < tmedia < 60 °C (-40 °F < tmedia < 140 °F)
Diagram shows temperature limits for ambient and media.
Materials
Cover / Deckel / Raccordement / Lock / Anslutning Material: P285QH EN 10222-4
The valve must be installed stress-free in the pipe system by qualified personnel and processes only. After welding, the valve should be surfaced to be corrosion-proof.
Diagram shows the valve body with labeled parts: Cover, Lock/Anslutning.
Installation Notes & Diagrams
Diagram shows a schematic of the AKVA 20 valve with inlet (P1) and outlet (P2) ports, and a filter symbol labeled "FIA 100 μm (Mesh 150)", indicating a required filtration level.
Diagram depicts a valve connection with a torque specification of "30 ± 3 Nm" for tightening.
Diagram shows the valve with "On" and "Off" indicators, and a screwdriver, suggesting manual operation or adjustment.
Valve Sizing
Each line marking on the piston indicates the valve size. The AKVA 20-3 is shown as an example.
No. of Line Markings | Valve Type |
---|---|
1 | AKVA 20-1 |
2 | AKVA 20-2 |
3 | AKVA 20-3 |
4 | AKVA 20-4 |
5 | AKVA 20-5 |
Diagram shows an exploded view of the AKVA 20 valve assembly.
Diagram shows a connection point on the valve with a torque specification of "75 Nm ± 5 Nm".
Service and Maintenance Warnings
Important:
- Service must not be carried out when the valve is under internal pressure.
- Use only original Danfoss spare parts.
- All service and installation must only be performed by authorized personnel.
Diagram illustrates the process of replacing a gasket. It shows a disassembled valve part and indicates "New" and "Used" gaskets.