Mitsubishi Electric PAC-IF013B-E R32 Air Handling Unit Controller
Air Conditioning Product Information
Product Overview
The Mitsubishi Electric PAC-IF013B-E R32 Air Handling Unit Controller is designed to interface Mitsubishi Electric Mr Slim outdoor units with third-party air handling units. It supports the connection of up to six Mr Slim outdoor units to a single air handling unit, offering a wide spectrum of heating and cooling capacities.
Key Features & Benefits
- Simplified installation, leveraging Mr Slim as a unified source for heating and cooling.
- Enables BEMS (Building Energy Management System) external monitoring and control via direct Modbus, digital switches, or analogue input.
- Supports Intelligent Multiple Outdoor Unit Control (IMOUC) for up to six Mr Slim outdoor units in external manual control, accommodating different capacities or series of units.
- Incorporates anti-cycling measures to enhance the lifespan of outdoor units.
- Provides precise capacity control across up to 11 individual steps for optimal comfort levels.
- Features an SD card slot for recording operational history and facilitating software upgrades.
- Supports a maximum airflow equivalent to 5 x standard Mr Slim specifications.
- Complete Air Handling Unit (AHU) systems with this pre-installed controller are also available.
Technical Specifications
Controller Details
Model | Dimensions (mm) (W x D x H) | Weight (kg) | Control Options |
---|---|---|---|
PAC-IF013B-E | 336 x 69 x 278 | 2.5 | Remote Controller Set, Modbus, 0-10V, 1-5V, 4-20mA, 0-10kΩ |
Outdoor Unit Compatibility
The following table details specifications for compatible Mitsubishi Electric Mr Slim outdoor units:
Outdoor Unit Model | Capacity (kW) | Weight (kg) | Dimensions (mm) (W x D x H) | Sound Pressure Level (dBA) | Pipe Size (mm) (in) | Heat Exchanger Requirements (Volume dm³) | Max Header Diameter (mm) | Pressure (MPa) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Heating (nominal) | Cooling (nominal) | Width | Depth | Height | Heating | Cooling | Gas | Liquid | >30m pipe run | 20m pipe run | 10m pipe run | Min Volume | Design | Burst | |||
PUZ-ZM35VKA | 4.1 | 3.5 | 46 | 809 | 300 | 630 | 46 | 44 | 12.7 (1/2") | 6.35 (1/4") | 1.05 | 1.35 | 1.65 | 0.35 | 5/8" | 4.15 | > 12.45 |
PUZ-ZM50VKA | 6 | 5 | 46 | 809 | 300 | 630 | 46 | 44 | 12.7 (1/2") | 6.35 (1/4") | 1.5 | 1.8 | 2.1 | 0.5 | 5/8" | 4.15 | > 12.45 |
PUZ-ZM60VKA | 7 | 6 | 70 | 950 | 330+25 | 943 | 49 | 47 | 15.88 (5/8") | 9.52 (3/8") | 1.8 | 2.7 | 3.6 | 0.6 | 5/8" | 4.15 | > 12.45 |
PUZ-ZM71VKA | 8 | 7.1 | 70 | 950 | 330+25 | 943 | 49 | 47 | 15.88 (5/8") | 9.52 (3/8") | 2.13 | 3.03 | 3.93 | 0.71 | 5/8" | 4.15 | > 12.45 |
PUZ-ZM100VKA/YKA | 11.2 | 10 | 137 | 1050 | 330+40 | 1338 | 51 | 49 | 15.88 (5/8") | 9.52 (3/8") | 3 | 3.9 | 4.8 | 1 | 7/8" | 4.15 | > 12.45 |
PUZ-ZM125VKA/YKA | 14 | 12.5 | 138 | 1050 | 330+40 | 1338 | 52 | 50 | 15.88 (5/8") | 9.52 (3/8") | 3.75 | 4.65 | 5.55 | 1.25 | 7/8" | 4.15 | > 12.45 |
PUZ-ZM140VKA/YKA | 16 | 14 | 129 | 1050 | 330+40 | 1338 | 52 | 50 | 15.88 (5/8") | 9.52 (3/8") | 4.2 | 5.1 | 6 | 1.4 | 7/8" | 4.15 | > 12.45 |
PUZ-ZM200YKA | 22.4 | 20 | 138 | 1050 | 330+40 | 1338 | 62 | 59 | 28.58 (1 1/8") | 12.7 (1/2") | 6 | 7.8 | 9.6 | 2 | 7/8" | 4.15 | > 12.45 |
PUZ-ZM250YKA | 27 | 25 | 138 | 1050 | 330+40 | 1338 | 62 | 59 | 28.58 (1 1/8") | 12.7 (1/2") | 7.5 | 9.3 | 11.1 | 2.5 | 7/8" | 4.15 | > 12.45 |
PUZ-M 200YKA | 22.4 | 20 | 138 | 1050 | 330+40 | 1338 | 60 | 58 | 28.58 (1 1/8") | 9.52 (3/8") | 6 | 7.8 | 9.6 | 2 | 7/8" | 4.15 | > 12.45 |
PUZ-M 250YKA | 27 | 25 | 138 | 1050 | 330+40 | 1338 | 62 | 59 | 28.58 (1 1/8") | 12.7 (1/2") | 7.5 | 9.3 | 11.1 | 2.5 | 7/8" | 4.15 | > 12.45 |
System Configuration Notes
- A single air handling unit controller is required for each outdoor unit.
- Cooling conditions: Indoor 27°C DB / 19°C WB, Outdoor 35°C DB / 24°C WB.
- Heating conditions: Indoor 20°C DB, Outdoor 7°C DB / 6°C WB.
- For systems using multiple air handling unit controllers on a single AHU, two options exist:
- Connect one PAC-IF013B-E unit per heat exchanger. These will operate as separate circuits, each with its own controller.
- Connect one PAC-IF013B-E for the first heat exchanger, followed by up to five additional slave PAC-SIF013B-E units. The primary PAC-IF013B-E controller will manage the slave units.
- Consult your local sales office for more detailed information on this feature.
Diagram Description
The system diagram illustrates the interconnection of a Mitsubishi Electric Outdoor Unit, the PAC-IF013B-E Air Handling Unit Controller, and a field-supplied Air Handling Unit. It shows the flow of control wiring, thermistor wiring, and piping between these components.
Further Information & Contact
For detailed product dimensions, please visit: Mitsubishi Electric Product Catalogue.
Contact Mitsubishi Electric UK:
- Telephone: 01707 282880
- Email: air.conditioning@meuk.mee.com
- Website: les.mitsubishielectric.co.uk
Company Information:
United Kingdom: Mitsubishi Electric Europe Living Environment Systems Division, Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, England.
Ireland: Mitsubishi Electric Europe, Westgate Business Park, Ballymount, Dublin 24, Ireland.
Country of origin: United Kingdom - Japan - Thailand - Malaysia.
© Mitsubishi Electric Europe 2020. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make variations in technical specifications or withdraw products without prior notification. Mitsubishi Electric is committed to continuous product development.
Refrigerant Information: Mitsubishi Electric's air conditioning equipment and heat pump systems utilize refrigerants such as R32 (GWP:675) and others, with GWP values based on EU regulations.
Effective as of September 2020.