HV600 Drive

AC Drive for HVAC Fan and Pump Applications

Manual Supplement

Affected documents:

  • HV600 Installation & Primary Operation (TOEPC71061732)
  • HV600 Technical Reference (SIEPC71061732)
  • HV600 Quick Setup Procedures (TOEPC71061774, TOEPC71061775, TOEPC71061776)

Document Overview

[Image: Yaskawa HV600 AC Drive unit]

[Diagram: Circular indicator with segments in green, red, and blue]

Simplify drive start-up. Get DriveWizard Mobile.

Visit: https://www.yaskawa.com/dwm

1 Supplemental Information - Applicable Documents

The contents of this supplement apply to the product instructions in Table 1.1.

Table 1.1 Affected Documents

Drive SeriesDocument
HV600Installation & Primary Operation (TOEPC71061732)
Technical Reference (SIEPC71061732)
Quick Setup Procedure (TOEPC71061774)
Quick Setup Procedure (TOEPC71061775)
Quick Setup Procedure for IP55/UL Type 12 (TOEPC71061776)

2 Short Circuit Protection Requirements for UL Listing

[Warning Symbol] WARNING Electrical Shock Hazard. After the input protective device trips, do not immediately energize the drive or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral devices, it can cause serious injury or death.

UL Compliance

Install one of the types of short circuit protection devices in Table 2.1 or Table 2.2 to comply with UL 508C. Semiconductor protective type fuses are recommended, but the tables also show alternative short circuit protection devices.

Molded Case Circuit Breaker (MCCB) Ratings

  • Maximum MCCB rating is 250% of the drive full load output amp (FLA) rating.
  • When you use MCCBs you must mount the drive in a ventilated enclosure according to the minimum enclosure volume specified in this document.

Note: When you use MCCBs, current limiting type are recommended, but not required.

Semiconductor Fuse Ratings

  • When you use semiconductor fuses as UL listed drive protection, the drives and fuses must be in the same enclosure.

Non-Semiconductor Fuse Ratings

  • Maximum CC, J, or T fuse rating is 175% of the drive full load output amp (FLA) rating.

2 Short Circuit Protection Requirements for UL Listing

Short Circuit Current Rating (SCCR)

The maximum SCCR provided by drive and fuse, or drive and MCCB combinations in this document, is 100,000 RMS symmetrical amps.

  • 240 V models: Use the protection specified in this document to prepare the drive for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amps and not more than 240 Vac.
  • 480 V models: Use the protection specified in this document to prepare the drive for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amps and not more than 480 Vac.

Electric Code Compliance

The user must provide short circuit protection to protect input branch circuits as specified by the National Electric Code (NEC), the Canadian Electric Code, Part 1 (CEC), and local codes.

Required Short Circuit Protection

Table 2.1 Required Short Circuit Protection for HV600 AC Drives (240 V Class)

Drive Catalog Code HV60UProtected Enclosure Not RequiredVentilated Protected Enclosure Required
Semiconductor Fuse Part Number Manufacturer: Eaton/BussmanClass CC, J, or T Fuse *1 Maximum AmpsMCCB Maximum AmpsMCP Part Number Manufacturer: SchneiderEnclosure Volume Minimum (in³)
2011FWH-40B17.525HLL36030M713056
2017FWH-45B2540HLL36030M713056
2024FWH-80B4060HLL36050M723056
2031FWH-125B5075HLL36050M723056
2046FWH-125B80110HLL36100M735520
2059FWH-175B100125HLL36100M735520
2075FWH-200B125175HLL36150M745520
2088FWH-225A150200HLL36150M745520
2114FWH-225A200250HLL36150M745520
2143FWH-250A250350JLL36250M7514657
2169FWH-275A250400JLL36250M7514657
2211FWH-600A350500LLL36400M37X14657
2273FWH-800A450600LLL36400M37X14657

*1 Class T fuses are fast-acting (non-time-delay) only. You can substitute a Class J time-delay fuse for a Class J non-time-delay fuse.

2 Short Circuit Protection Requirements for UL Listing

Table 2.2 Required Short Circuit Protection for HV600 AC Drives (480 V Class)

Drive Catalog Code HV60UProtected Enclosure Not RequiredVentilated Protected Enclosure Required
Semiconductor Fuse Part Number Manufacturer: Eaton/BussmanClass CC, J, or T Fuse *1 Maximum AmpsMCCB Maximum AmpsMCP Part Number Manufacturer: SchneiderEnclosure Volume Minimum (in³)External HeatsinkInternal Heatsink
4005FWH-25A14F815HLL36030M7130563056
4006FWH-30A14F915HLL36030M7130563056
4008FWH-30A14F1215HLL36030M7130563056
4011FWH-40B17.525HLL36030M7130563056
4014FWH-45B2035HLL36030M7130563056
4021FWH-60B3550HLL36030M7130563056
4027FWH-80B4560HLL36050M7230563056
4034FWH-100B6080HLL36050M7230563056
4040FWH-125B70100HLL36100M7355205520
4052FWH-150B90125HLL36100M7355205520
4065FWH-200B110150HLL36100M7355205520
4077FWH-225A125175HLL36100M7355205520
4096FWH-225A150225HLL36150M7455205520
4124FWH-225A200300JLL36250M7555205520
4156FWH-325A250350JLL36250M752158214657
4180FWH-500A300450JLL36250M7552800 *214657
4240FWH-600A400600LLL36400M37X52800 *214657
4302FWH-700A500700LLL36400M37X52800 *252800

*1 Class T fuses are fast-acting (non-time-delay) only. You can substitute a Class J time-delay fuse for a Class J non-time-delay fuse.

*2 External heatsink installations on models 4180, 4240, and 4302 require a heatsink shroud and filter.

Revision History

Date of PublicationRevision NumberRevised Content
August 2021-First release

Yaskawa Locations

YASKAWA AMERICA, INC.
2121, Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone: +1-800-YASKAWA (927-5292) or +1-847-887-7000 Fax: +1-847-887-7310
www.yaskawa.com

DRIVE CENTER (INVERTER PLANT)
2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan
Phone: +81-930-25-2548 Fax: +81-930-25-3431
www.yaskawa.co.jp

YASKAWA EUROPE GmbH
Hauptstraße 185, 65760 Eschborn, Germany
Phone: +49-6196-569-300 Fax: +49-6196-569-398
E-mail: info@yaskawa.eu.com
www.yaskawa.eu.com

YASKAWA ELÉTRICO DO BRASIL LTDA.
777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil
Phone: +55-11-3585-1100 Fax: +55-11-3585-1187
www.yaskawa.com.br

In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.

Specifications are subject to change without notice for ongoing product modifications and improvements.

Original Instructions

©2021 YASKAWA AMERICA, Inc.

Document Number: TOEPYAISUP16A
Revision: A <0>-0
Published: August 2021

Models: HV600 Drive AC Drive for HVAC Fan and Pump, HV600, Drive AC Drive for HVAC Fan and Pump, Drive for HVAC Fan and Pump, HVAC Fan and Pump, Fan and Pump

File Info : application/pdf, 6 Pages, 2.50MB

PDF preview unavailable. Download the PDF instead.

pillar-hv600-protecciones-para-corto-circuito-hv600

References

PDFlib PDI 9.0.6 (C /Win64)

Related Documents

Preview Yaskawa HV600 Enclosed Bypass Installation & Startup Guide
This guide provides comprehensive installation and startup procedures for the Yaskawa HV600 AC Drive Bypass, designed for HVAC fan and pump applications. It details safety precautions, mechanical and electrical installation, startup procedures, and troubleshooting for reliable operation.
Preview Yaskawa VFDs: Comprehensive Guide to Variable Frequency Drive Technology & Applications
Explore Yaskawa Variable Frequency Drives (VFDs), their technology, key features, applications, and comparisons with leading manufacturers like ABB, Hitachi, Eaton, and Lenze. Learn about energy savings, motor control, and industrial automation benefits.
Preview Yaskawa CA-A1000 Inverter Quick Reference Manual
This manual provides essential information for the correct application, installation, and operation of the Yaskawa CA-A1000 Series Inverters. It covers quick setup, troubleshooting, maintenance, and specifications for these high-performance vector control inverters.
Preview YASKAWA AC Drive Option LCD Keypad Installation Manual
Comprehensive installation guide for the YASKAWA AC Drive Option LCD Keypad (models JVOP-KPLCA04Axx, JVOP-KPLCA04Mxx, JVOP-KPLCA04Kxx), covering installation, operation, safety, and specifications for YASKAWA AC drives.
Preview Yaskawa Variable Frequency Drives (VFDs): Overview, Comparisons, and Services
A comprehensive guide to Yaskawa Variable Frequency Drives (VFDs), detailing their benefits, features, comparisons with ABB, Eaton, Hitachi, and Lenze, and Precision Electric's expert services for selection, installation, and repair.
Preview Yaskawa AC Drive GA700 Technical Manual - High Performance
Comprehensive technical manual for the Yaskawa AC Drive GA700, covering installation, operation, maintenance, and troubleshooting for this high-performance drive.
Preview Yaskawa Variable Frequency Drives: An Overview and Comparison
Explore Yaskawa Variable Frequency Drives (VFDs), their features, benefits, and comparisons with other leading manufacturers. Learn about energy savings, improved control, and reduced mechanical stress with Yaskawa VFDs.
Preview Variador CA Yaskawa GA700: Guía de Primeros Pasos y Operación
Manual de primeros pasos y guía de operación para el Variador CA Yaskawa GA700. Cubre instalación, configuración, seguridad y procedimientos de puesta en marcha para controlar la velocidad y dirección de motores.