VLT Micro Drive FC 51 Operating Guide

Brand: Danfoss

1 Introduction

This Operating Guide provides necessary information for qualified personnel to install and commission the AC drive. Read and follow the instructions to use the drive safely and professionally. VLT® is a registered trademark for Danfoss A/S.

Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.

2 Safety

WARNING HIGH VOLTAGE AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing.

UNINTENDED START The motor may start from LCP, I/O inputs, fieldbus, or MCT 10 Set-up software at any time, when the drive is connected to the AC mains, DC supply, or load sharing.

DISCHARGE TIME The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off. - Stop the motor, and disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other drives. - Wait for the capacitors to discharge fully and measure it before performing any service or repair work. - The minimum waiting time is 4 minutes for M1, M2, and M3 drives, and 15 minutes for M4 and M5 drives.

LEAKAGE CURRENT Leakage currents of the drive exceed 3.5 mA. Make sure that the drive is properly grounded with at least 10 mm² (8 AWG) grounding wire and use RCDs of type B with an inrush delay.

3 Installation

3.1 Mechanical Dimensions

Enclosure sizeHeight [mm (in)]Width [mm (in)]Depth [mm (in)]Mounting holes [mm (in)](2)Maximum weight [kg (lb)]
M1150 (5.9)205 (8.1)140.4 (5.5)70 (2.8)1.1 (2.4)
M2176 (6.9)230 (9.1)166.4 (6.6)75 (3.0)1.6 (3.5)
M3239 (9.4)294 (11.6)226 (8.9)90 (3.5)3.0 (6.6)
M4292 (11.5)347.5 (13.7)272.4 (10.7)125 (4.9)6.0 (13.2)
M5335 (13.2)387.5 (15.3)315 (12.4)165 (6.5)9.5 (20.9)

(1) Including decoupling plate. (2) For LCP with potentiometer, add 7.6 mm (0.3 in).

3.2 Connecting to Mains and Motor

3.3 Load Sharing/Brake

Use 6.3 mm (0.25 in) insulated Faston plugs designed for high voltage for DC (load sharing and brake). Contact Danfoss or see Load sharing instruction VLT® 5000 for load sharing and VLT® 2800/5000/5000 FLUX/FCD 300 Brake for brake.

Load sharing: Connect terminals -UDC and +UDC/+BR. Brake: Connect terminals -BR and +UDC/+BR (not applicable to enclosure size M1).

NOTICE: Voltage levels of up to 850 V DC may occur between terminals +UDC/+BR and -UDC. Not short-circuit protected.

3.4 Control Terminals

All control cable terminals are located underneath the terminal cover in front of the drive. Remove the terminal cover using a screwdriver.

NOTICE: - See the back of the terminal cover for outlines of control terminals and switches. - Do not operate switches with power on the drive. - Set parameter 6-19 Terminal 53 Mode according to Switch 4 position.

S200 Switches Configuration

Switch 1: Controls PNP/NPN terminal configuration for terminal 29. Off = PNP, On = NPN.

Switch 2: Controls PNP/NPN terminal configuration for terminals 18, 19, 27, and 33. Off = PNP, On = NPN.

Switch 3: No function.

Switch 4: Selects analog input mode for terminal 53. Off = 0-10 V, On = 0/4-20 mA. (Default setting is Off).

Control Terminal Overview

The following illustration shows all control terminals of the drive. Applying start (terminal 18) and an analog reference (terminal 53 or 60) make the drive run. The overview shows terminal numbers (61, 68, 69, 12, 18, 19, 20, 27, 29, 33, 42, 50, 53, 55, 60) and their functions, such as +24V, GND, Analog Inputs (A IN), Analog Outputs (A OUT), Digital Inputs (D IN), and RS485 communication. The diagram shows factory settings for PNP configuration.

4 Programming

4.1 Local Control Panel (LCP)

The Local Control Panel (LCP) features a numeric display, indicator lights for status (On, Warn, Alarm), and control keys. Navigation keys include [Menu], [Back], and directional arrows. Confirmation is done with [OK]. Operation keys are [Hand On] for manual start, [Off/Reset] for stopping or resetting alarms, and [Auto On] for automatic control. An LCP12 model includes a potentiometer for manual control.

4.2 Programming on Automatic Motor Tuning (AMT)

Run AMT to optimize compatibility between the drive and the motor in VVC+ mode. The drive builds a mathematical model of the motor for regulating output motor current thus enhancing motor performance. 1. Enter the main menu. 2. Set parameter group 1-** Load and Motor, parameter group 1-2* Motor Data, and parameter 1-29 Automatic Motor Tuning (AMT). 3. Press [OK]. The test runs automatically and indicates when it is complete.

5 Parameter Overview

This section lists the parameter groups and individual parameters available for configuring the VLT Micro Drive FC 51. Parameters are organized into logical groups such as Operation/Display, Set-up Operations, Load and Motor, References/Ramps, Limits/Warnings, Digital In/Out, Brakes, Comm. and Options, Smart Logic, Data Readouts, and Drive Information.

6 Troubleshooting

This table lists common warnings, alarms, and triplock errors, along with their potential causes and recommended actions.

NumberDescriptionWarningAlarmTriplockErrorCause of problem
2Live zero errorXXSignal on terminal 53 or 54 is less than 50% of the value set in: Parameter 6-10 Terminal 53 Low Voltage, Parameter 6-12 Terminal 53 Low Current, or Parameter 6-22 Terminal 54 Low Current.
4Mains phase loss(1)XXXMissing phase on the supply side or too high voltage imbalance. Check the supply voltage.
7DC overvoltage(1)XXXDC-link voltage exceeds the limit.
8DC undervoltage(1)XXXDC-link voltage drops below voltage warning low limit.
9Inverter overloadXXXMore than 100% load for a long time.
10Motor ETR overtemperatureXXXMotor is too hot due to more than 100% load for a long time.
11Motor thermistor overtemperatureXXXThermistor or thermistor connection is disconnected.
12Torque limitXXTorque exceeds value set in either parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode.
13OvercurrentXXXInverter peak current limit is exceeded.
14Ground faultXXXDischarge from output phases to ground.
16Short circuitXXXShort circuit in motor or on motor terminals.
17Control word timeoutXXXNo communication to drive.
25Brake resistor short-circuitedXXXBrake resistor is short-circuited, thus the brake function is disconnected.
27Brake chopper short-circuitedXXXBrake transistor is short-circuited, thus the brake function is disconnected.
28Brake checkXXBrake resistor is not connected/working.
29Power board over tempXXXHeat sink cutout temperature has been reached.
30Motor phase U missingXXXMotor phase U is missing. Check the phase.
31Motor phase V missingXXXMotor phase V is missing. Check the phase.
32Motor phase W missingXXXMotor phase W is missing. Check the phase.
38Internal faultXXXContact the local Danfoss supplier.
47Control voltage faultXXX24 V DC supply is overloaded.
51AMA check Unom and InomXXWrong setting for motor voltage and/or motor current.
52AMA low InomXXThe motor current is too low. Check the settings.
59Current limitXXThe drive is overloaded.
63Mechanical brake lowXXActual motor current has not exceeded the release brake current within the start delay time window.
80Drive initialized to default valueXXAll parameter settings are initialized to default settings.
84The connection between drive and LCP is lostXNo communication between LCP and drive.
85Key disabledXSee parameter group 0-4* LCP.
86Copy failXAn error occurred while copying from drive to LCP, or from LCP to drive.
87LCP data invalidXOccurs when copying from LCP if the LCP contains erroneous data - or if no data was uploaded to the LCP.
88LCP data not compatibleXOccurs when copying from LCP if data is moved between drives with major differences in software versions.
89Parameter read onlyXOccurs when trying to write to a read-only parameter.
90Parameter database busyXLCP and RS485 connections are trying to update parameters simultaneously.
91Parameter value is not valid in this modeXOccurs when trying to write an illegal value to a parameter.
92Parameter value exceeds the min/max limitsXOccurs when trying to set a value outside the range.
nw runNot while runningXParameters can only be changed when the motor is stopped.
Err.A wrong password was enteredXOccurs when using a wrong password for changing a password-protected parameter.

(1) These faults are caused by mains distortions. Install a Danfoss line filter to rectify this problem.

7 Specifications

Table 2: Mains Supply 1x200 240 V AC

DriveTypical shaft output [kW (hp)]Enclosure protection rating IP20Output current Continuous (3x200 240 V) [A]Intermittent (3x200 240 V) [A]Maximum cable size (Mains, motor) [mm/AWG]Maximum input current Continuous (1x200 240 V) [A]Intermittent (1x200 240 V) [A]Environment Estimated power loss [W], Best case/typical(1)
PK180.18 (0.25)M11.21.83.34.512.5/15.5
PK370.37 (0.5)M12.23.36.18.320/25
PK750.75 (1)M14.26.311.615.636.5/44
P1K51.5 (2)M26.810.218.726.461/67
P2K22.2 (3)M39.614.426.43781/85.1

Normal overload 150% for 1 minute

Table 3: Mains Supply 3x200 240 V AC

DriveTypical shaft output [kW (hp)]Enclosure protection rating IP20Output current Continuous (3x200 240 V) [A]Intermittent (3x200 240 V) [A]Maximum cable size (Mains, motor) [mm/AWG]Maximum input current Continuous (3x200 240 V) [A]Intermittent (3x200 240 V) [A]Environment Estimated power loss [W], Best case/typical(1)
PK250.25 (0.33)M11.52.32.43.214/20
PK370.37 (0.5)M12.23.33.54.619/24
PK750.75 (1)M14.26.36.710.94/10
P1K51.5 (2)M26.810.210.914.431.5/39.5
P2K22.2 (3)M39.614.415.424.351/57
P3K73.7 (5)M315.222.823.435.372/77.1

Normal overload 150% for 1 minute

Table 4: Mains Supply 3x380 480 V AC

DriveTypical shaft output [kW (hp)]Enclosure protection rating IP20Output current Continuous (3x380 440 V) [A]Intermittent (3x380 440 V) [A]Continuous (3x440 480 V) [A]Intermittent (3x440 480 V) [A]Maximum cable size (Mains, motor) [mm/AWG]Maximum input current Continuous (3x380 440 V) [A]Intermittent (3x380 440 V) [A]Continuous (3x440 480 V) [A]Intermittent (3x440 480 V) [A]Environment Estimated power loss [W], Best case/typical(1)
PK370.37 (0.5)M11.21.81.11.74/101.92.61.72.318.5/25.5
PK750.75 (1)M12.23.32.13.23.54.73.04.028.5/43.5
P1K51.5 (2)M23.75.63.45.15.98.75.17.541.5/56.5
P2K22.2 (3)M25.38.04.87.28.512.67.310.857.5/81.5
P3K03.0 (4)M37.210.86.39.511.516.89.914.475/101.6
P4K04.0 (5.5)M39.013.78.212.314.420.212.417.598.5/133.5
P5K55.5 (7.5)M312181116.516/619.227.416.623.6131/166.8
P7K57.5 (10)M315.523.51421.324.836.321.430.1175/217.5
P11K11 (15)M42334.52131.53347.52941290/342
P15K15 (20)M43146.52740.542603652387/454
P18K18.5 (25)M53755.5345134.74931.544395/428
P22K22 (30)M54364.5406041.257.637.553467/520

Normal overload 150% for 1 minute

(1) Applies to dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmartTM website.

8 Special Conditions

8.1 Derating for Ambient Temperature

The ambient temperature measured over 24 hours should be at least 5 °C (9 °F) lower than the maximum ambient temperature. If the drive is operated at high ambient temperature, decrease the continuous output current. The drive has been designed for operation at maximum 50 °C (122 °F) ambient temperature with 1 motor size smaller than nominal. Continuous operation at full load at 50 °C (122 °F) ambient temperature reduces the lifetime of the drive.

8.2 Derating for Low Air Pressure

The cooling capability of air is decreased at low air pressure. Below 1000 m (3280 ft) altitude, no derating is necessary, but above 1000 m (3280 ft), decrease the ambient temperature or the maximum output current. For altitudes above 2000 m (6560 ft), contact Danfoss regarding PELV. Decrease the output by 1% per 100 m (328 ft) altitude above 1000 m (3280 ft), or reduce the maximum ambient temperature by 1 °C (1.8 °F) per 200 m (656 ft).

8.3 Derating for Running at Low Speeds

When a motor is connected to a drive, check that the cooling of the motor is adequate. A problem may occur at low speeds in constant torque applications. Running continuously at low speeds - less than half the nominal motor speed - may require extra air cooling. Alternatively, select a larger motor (1 size up).

9 Technical Documentation

Scan the QR code to access more technical literatures for FC 51. Or, after scanning the QR code, click Global English on the website to select your local region's website, search FC 51 to find the documents with your own languages.

Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com

Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 2021.08 AQ383124996793en-000101 / 130R1226 | 2

PDF preview unavailable. Download the PDF instead.

AQ383124996793en-000101 Danfoss A/S

Related Documents

Preview Danfoss VLT Micro Drive FC 51 Operating Guide: Installation, Programming, and Specifications
Comprehensive operating guide for the Danfoss VLT Micro Drive FC 51, covering installation, safety, programming, parameter overview, troubleshooting, and technical specifications for AC drives.
Preview VLT® Midi Drive FC 280: Flexible, Communicative, Easy to Use AC Drive | Danfoss
Explore the Danfoss VLT® Midi Drive FC 280, an advanced AC drive engineered for flexibility, communication, and user-friendliness. Ideal for machine builders in food & beverage, material handling, and processing industries, it offers high efficiency, integrated functional safety, and a compact design for simplified installation and operation.
Preview VLT® HVAC Basic Drive FC 101 Operating Guide - Danfoss
Comprehensive operating guide for the Danfoss VLT® HVAC Basic Drive FC 101, covering installation, safety, programming, troubleshooting, and specifications for HVAC applications. Includes details on enclosure sizes, electrical specifications, and mounting.
Preview Danfoss VLT AutomationDrive FC 301/FC 302 Operating Guide
Comprehensive operating guide for Danfoss VLT AutomationDrive FC 301 and FC 302 AC drives, covering installation, commissioning, configuration, maintenance, diagnostics, troubleshooting, and detailed specifications for industrial automation applications.
Preview Danfoss VLT® Micro Drive FC 51 Programming Guide
Comprehensive programming guide for the Danfoss VLT® Micro Drive FC 51 series frequency converters. Covers safety, setup, parameter configuration, and troubleshooting for optimal motor control.
Preview VLT® Micro Drive FC 51 LCP Mounting Instructions | Danfoss
Step-by-step guide for mounting the Local Control Panel (LCP) onto the Danfoss VLT® Micro Drive FC 51. Features clear instructions and textual descriptions of diagrams for installation.
Preview Danfoss VLT Micro Drive FC 51 Operating Instructions Manual
Comprehensive operating instructions for the Danfoss VLT Micro Drive FC 51, covering safety, mechanical and electrical installation, programming, Modbus RTU communication, parameter overview, troubleshooting, and specifications.
Preview Danfoss VLT® HVAC Drive FC 102 Operating Guide - Installation, Operation, and Safety
Official operating guide for the Danfoss VLT® HVAC Drive FC 102 (1.1-90 kW). Covers safe installation, commissioning, operation, maintenance, specifications, and troubleshooting for HVAC applications.