Systemair SysCoil Comfort
Floor and ceiling fan coil units
Key Specifications:
- Airflow: from 91 to 1548 m³/h
- Cooling capacity: from 0,5 to 9,6 kW
- Heating capacity: from 0,6 to 13,6 kW
Image description: Three different models of SysCoil Comfort fan coil units are shown: a floor-standing unit, a ceiling-mounted unit, and a unit with an open front panel revealing internal components.
Innovation for an optimum comfort
Features:
- ErP 2018 compliance logo
- Tertiary H logo
- Airflow from 91 to 1548 m³/h
- Cooling capacity from 0,5 to 9,6 kW
- Heating capacity from 0,6 to 13,6 kW
- Very low sound level
- Universal version for either vertical or horizontal installation
- Available with or without cabinet
Product Description
Lower sound levels, better performances, and integration of the new SysLogic electronic control system characterize the latest generation of SysCoil units. SysCoil Comfort fan coils are designed to meet customer needs, with a grille and refined cabinet for harmonious integration into any interior. They are ideal for air conditioning hotels, hospitals, offices, and other premises year-round.
Product advantages
- Very low sound level
- Robust units
- Ease of installation
- Very good performances and large working range
- Harmonious and aesthetic RAL 9003 painted cabinet
- Streamlined design enabling harmonious integration
- Large range of accessories and options
- Eurovent certified
Versions and configurations
- 8 sizes (from SCC10 to SCC80)
- With or without cabinet
- EC (low consumption) or AC 5-speed fan motors
- Standard or Low Noise versions
- 2-pipes, 2-pipes/2-wires, 4 pipes
- Left or right connection
- Universal installation units (vertical or horizontal)
Sustainability and Compliance
The preservation of the environment and energy savings are central to Systemair's philosophy. Our "Green Ventilation" label signifies products with high energy-saving potential. All Systemair terminal units are ERP 2018 compliant following COMMISSION REGULATION (EU) No2016/2281.
? 100% of the units are factory tested.
Better performances & Quieter than ever
With SysCoil Comfort, Systemair's R&D department has improved performance and reduced sound levels:
- +5% cooling capacity *
- -2 dB(A) for Standard versions *
- -3 dB(A) for "Low Noise" versions *
* Compared to the previous generation SysCoil 2.
"Low Noise" versions feature reinforced acoustic insulation around the fans.
A new casing design
The casing and component parts have been strengthened, creating a unique and universal product that can be installed either vertically or horizontally. Features an L-shaped drain pan for both horizontal and vertical installations.
A wide range of control systems for ultimate comfort
Systemair offers a wide range of electronic and electromechanical control systems to optimize water terminal unit operation.
- WRC remote control
- SysLogic controller
- BRC remote control
Many options and accessories to meet your needs
- SysLogic controller (other electromechanical or electronic control systems also available)
- WRC/BRC remote controls for SysLogic
- Modbus communication board for SysLogic
- 2-way or 3-way ON/OFF valves
- Modulating valves
- Auxiliary drain pan
- Condensate drain pump
- Electrical heater
- Additional 2-pipe coil
- Feet + grid between feet
- Front air intake
- Front/Back/Floor air intake with manual damper
- Discharge and return plenums (for circular duct connections)
- Fuse holder or Circuit breaker
- G3 filter
- Suspension kit
Sysoft AC: Online Selection Software
Use the online selection tool Sysoft AC to precisely and quickly select and dimension the required water terminal units. This is a EUROVENT certified software for the full range of water terminals.
Quick selection guide
SysCoil Comfort | Cooling and heating capacities* (kW) | Acoustic * | Airflow * LS/MS/HS (m³/h) | Pressure | Fan |
---|---|---|---|---|---|
10 | 2,1 / 2,4 | NR 33 at MS | 108/228/417 | 0-30 Pa | AC / EC |
20 | 2,4 / 2,8 | NR 33 at MS | 98/234/413 | 0-30 Pa | |
30 | 3,1 / 2,8 | NR 36 at MS | 145/380/585 | 0-30 Pa | |
40 | 4,2 / 4,5 | NR 30 at MS | 170/412/678 | 0-30 Pa | AC / EC |
50 | 5,0 / 5,2 | NR 37 at MS | 203/645/816 | 0-40 Pa | |
60 | 5,2 / 5,8 | NR 40 at MS | 245/737/912 | 0-40 Pa | |
70 | 6,9 / 7,6 | NR 40 at MS | 350/850/1050 | 0-40 Pa | AC / EC |
80 | 8,8 / 9,8 | NR 42 at MS | 685/927/1398 | 0-40 Pa |
* Data for EC versions - 2 pipes / According to Eurovent standard.
Technical Data
SysCoil Comfort | SCC10 / SCC20 / SCC30 / SCC40 / SCC50 / SCC60 / SCC70 / SCC80 | ||||||||
---|---|---|---|---|---|---|---|---|---|
S1 / S3 / S5 ** | S1 / S3 / S5 ** | S1 / S3 / S5 ** | S1 / S3 / S5 ** | S1 / S3 / S5 ** | S1 / S3 / S5 ** | S1 / S3 / S5 ** | S1 / S3 / S5 ** | ||
Capacities - 2 pipes | |||||||||
Total cooling capacity | kW | 0,72/1,00/1,45 | 0,74/1,24/1,68 | 1,00/1,98/2,50 | 1,20/2,40/3,18 | 1,72/3,16/4,63 | 2,71/4,55/5,82 | 3,41/6,14/7,27 | 4,63/6,08/8,13 |
Sensible capacity | kW | 0,53/0,77/1,05 | 0,55/0,93/1,30 | 0,82/1,52/1,90 | 0,87/1,75/2,34 | 1,24/2,23/3,27 | 1,90/3,30/4,47 | 2,37/4,32/5,10 | 3,41/4,57/6,29 |
Cooling (1) Water flow | l/h | 124/172/250 | 127/213/289 | 172/341/430 | 206/413/547 | 296/544/798 | 466/784/1003 | 587/1058/1252 | 798/1048/1400 |
Water pressure drop (5) | kPa | 10,7/19,5/39,2 | 1,8/3,9/6,3 | 6,3/19,3/28,8 | 5,4/17,1/28 | 7,5/22,8/46,9 | 13,9/37,4/60,2 | 4,8/15,4/21,5 | 11,9/19,3/32,5 |
Heating (2) Heating capacity | kW | 0,73/1,18/1,71 | 0,76/1,26/1,86 | 1,05/1,96/2,62 | 1,21/2,39/3,35 | 1,79/3,46/4,81 | 2,58/4,44/5,93 | 3,63/6,59/7,80 | 4,95/6,80/9,90 |
Capacities - 4 pipes | |||||||||
Total cooling capacity | kW | 0,66/0,92/1,30 | 0,63/1,12/1,56 | 0,96/1,90/2,40 | 1,13/2,25/3,00 | 1,65/3,03/4,34 | 2,60/4,39/5,61 | 3,34/5,92/6,93 | 4,50/5,92/8,01 |
Sensible capacity | kW | 0,48/0,70/0,96 | 0,47/0,84/1,20 | 0,79/1,46/1,83 | 0,82/1,65/2,21 | 1,19/2,15/3,07 | 1,82/3,18/4,28 | 2,33/4,16/4,87 | 3,30/4,44/6,19 |
Cooling (1) Water flow | l/h | 114/159/225 | 109/192/268 | 165/327/414 | 194/388/517 | 284/522/748 | 449/756/967 | 575/1019/1193 | 775/1020/1380 |
Water pressure drop (5) | kPa | 8,3/15,2/29 | 1,5/3,4/5,6 | 3/9,5/14,4 | 7,2/22,3/36,8 | 4,2/12,8/25,1 | 10,3/27,7/44,5 | 5,9/17,9/24,4 | 19,3/31,1/53,6 |
Heating capacity | kW | 0,66/1,05/1,49 | 0,78/1,24/1,60 | 1,34/1,91/2,24 | 1,36/2,32/3,00 | 2,11/3,36/4,30 | 2,71/4,24/5,33 | 3,84/5,26/6,21 | 5,66/8,06/10,30 |
Heating (3) Water flow | l/h | 57/90/128 | 37/106/137 | 116/165/193 | 117/200/259 | 182/290/370 | 234/365/459 | 331/453/535 | 487/685/888 |
Water pressure drop (5) | kPa | 1,2/2,2/3,5 | <1/1,7/2,8 | 3/5,2/6,6 | 6/15,1/24,1 | 6,2/13,8/21,3 | 11,7/24,7/37 | 38,6/66,3/89 | 18,7/35,1/54,8 |
Sound Levels - 2 pipes | |||||||||
Sound power level | dB(A) | 33/40/49 | 31/43/50 | 30/45/52 | 30/44/51 | 34/46/56 | 38/51/58 | 43/56/61 | 50/55/64 |
Sound pressure level (4) | dB(A) | 24/31/40 | 22/34/41 | 21/36/43 | 21/35/42 | 25/37/47 | 29/42/49 | 34/47/52 | 41/46/55 |
NR (4) | dB(A) | 19/26/35 | 17/29/36 | 16/31/38 | 16/30/37 | 20/32/42 | 24/37/44 | 29/42/47 | 36/41/50 |
Sound Levels - 4 pipes | |||||||||
Sound power level | dB(A) | 33/40/49 | 31/43/50 | 30/45/52 | 30/44/51 | 34/46/56 | 38/51/58 | 43/56/61 | 50/55/64 |
Sound pressure level (4) | dB(A) | 24/31/40 | 22/34/41 | 21/36/43 | 21/35/42 | 25/37/47 | 29/42/49 | 34/47/52 | 41/46/55 |
NR (4) | dB(A) | 19/26/35 | 17/29/36 | 16/31/38 | 16/30/37 | 20/32/42 | 24/37/44 | 29/42/47 | 36/41/50 |
Ventilation | |||||||||
Number of fan(s) | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 3 | |
Airflow - 2 pipes | m³/h | 111/190/283 | 105/179/265 | 138/274/390 | 173/357/499 | 253/486/716 | 350/640/933 | 480/893/1064 | 660/936/1397 |
Airflow - 4 pipes | m³/h | 95/168/253 | 89/161/241 | 132/263/369 | 162/335/467 | 242/466/671 | 334/614/885 | 470/859/1012 | 634/905/1370 |
Filter | |||||||||
G2 | |||||||||
Electrical Data | |||||||||
Power supply | V/Ph/Hz | 230V/1~/50Hz - 230V/1~/60Hz | |||||||
Consumption - 2 pipes | W | 13/24/36 | 10/18/29 | 16/37/45 | 15/37/56 | 28/55/72 | 37/75/105 | 53/100/147 | 90/112/188 |
Consumption - 4 pipes | W | 13/24/36 | 10/18/28 | 16/37/44 | 15/37/55 | 28/54/70 | 37/74/104 | 53/99/145 | 90/112/188 |
Electrical heater (max.) | W | 500 | 500 | 500/1000 | 1250/2500 | 1250/2500 | 1250/2500 | 1250/2500 | 1250/2500 |
Water Connections | |||||||||
Type | Female gas threaded | ||||||||
2 pipes or 4 pipes "cooling" | inch | 1/2" | 1/2" | 1/2" | 1/2" | 1/2" | 1/2" | 3/4" | 3/4" |
4 pipes "heating" | inch | 1/2" | 1/2" | 1/2" | 1/2" | 1/2" | 1/2" | 1/2" | 1/2" |
Dimensions | |||||||||
Without cabinet (LxWxH) | mm | 570 x 220 x 430 | 570 x 220 x 430 | 753 x 220 x 430 | 938 x 220 x 430 | 1122 x 220 x 430 | 1307 x 220 x 430 | 1121 x 220 x 530 | 1316 x 220 x 530 |
With cabinet (LxWxH) | mm | 766 x 225 x 477 | 766 x 225 x 477 | 951 x 225 x 477 | 1136 x 225 x 477 | 1321 x 225 x 477 | 1506 x 225 x 477 | 1319 x 225 x 575 | 1506 x 225 x 575 |
Weight | |||||||||
Without cabinet - 2 pipes | kg | 13 | 13 | 15 | 20 | 22 | 26 | 27 | 38 |
Without cabinet - 4 pipes | kg | 14 | 14 | 16 | 22 | 24 | 28 | 29 | 40 |
With cabinet - 2 pipes | kg | 19 | 19 | 22 | 27 | 30 | 35 | 35 | 47 |
With cabinet - 4 pipes | kg | 20 | 20 | 23 | 29 | 32 | 37 | 37 | 49 |
** Standard factory set speeds with SysLogic controller.
(1) According to Eurovent standard. Air: 27°C DB / 19°C WB (nominal HS airflow), Chilled water: 7°C/12°C.
(2) According to Eurovent standard. Air: 20°C (nominal HS airflow), Hot water: 45°C/40°C.
(3) According to Eurovent standard. Air: 20°C (nominal HS airflow), Hot Water: 65°C/55°C.
(4) The sound pressure levels Lp are based on (NR) characteristics of a room having volume of 100 m³ with reverberation of 0.5 seconds.
(5) Pressure loss by corresponding nominal flow.
Dimensions
SysCoil Comfort with cabinet
Diagram description: Shows external dimensions of the SysCoil Comfort unit with cabinet, with labels A through H indicating specific measurements.
A | B | C | D | E | F | G | H | |
---|---|---|---|---|---|---|---|---|
SCC10 | 240 | 428 | 360 | 189 | 415,5 | 61 | 766 | 477 |
SCC20 | 240 | 428 | 360 | 189 | 415,5 | 61 | 766 | 477 |
SCC30 | 240 | 613 | 360 | 374 | 415,5 | 61 | 951 | 477 |
SCC40 | 240 | 798 | 360 | 559 | 415,5 | 61 | 1136 | 477 |
SCC50 | 240 | 983 | 360 | 744 | 415,5 | 61 | 1321 | 477 |
SCC60 | 240 | 1168 | 360 | 929 | 415,5 | 61 | 1506 | 477 |
SCC70 | 240 | 983 | 360 | 744 | 517,5 | 61 | 1319 | 575 |
SCC80 | 240 | 1168 | 360 | 929 | 517,5 | 85 | 1506 | 575 |
Dimensions are in millimeters.
SysCoil Comfort without cabinet
Diagram description: Shows external dimensions of the SysCoil Comfort unit without cabinet, with labels A through I indicating specific measurements.
A | B | C | D | E | F | G | H | I | |
---|---|---|---|---|---|---|---|---|---|
SCC10 | 66,5 | 428 | 185,5 | 189 | 415,5 | 61 | 569,5 | 430 | 407 |
SCC20 | 66,5 | 428 | 185,5 | 189 | 415,5 | 61 | 569,5 | 430 | 407 |
SCC30 | 64 | 613 | 184 | 374 | 415,5 | 61 | 753 | 430 | 592 |
SCC40 | 64 | 798 | 184 | 559 | 415,5 | 61 | 938 | 430 | 777 |
SCC50 | 63 | 983 | 183 | 744 | 415,5 | 61 | 1122 | 430 | 962 |
SCC60 | 63 | 1168 | 183 | 929 | 415,5 | 61 | 1307 | 430 | 1147 |
SCC70 | 63 | 983 | 195 | 744 | 519 | 88 | 1121 | 530 | 962 |
SCC80 | 69 | 1168 | 195 | 929 | 519 | 85 | 1316 | 530 | 1147 |
Dimensions are in millimeters.
Types of installation & Mounting accessories
Standard version for wall mounting.
Diagram description: Shows a vertical fan coil unit with arrows indicating airflow in and out.
Front air intake grille.
Diagram description: Shows a fan coil unit with a front grille for air intake.
Support feet for floor mounting. Air intake grille between feet for version with cabinet.
Diagram description: Shows a fan coil unit mounted on support feet, with an air intake grille positioned between the feet.
Air intake arrangement with manual damper (floor or/and front intake).
Diagram description: Shows a fan coil unit with an air intake system that includes a manual damper, applicable for floor or front intake.
Air intake arrangement with manual damper (back or/and front intake).
Diagram description: Shows a fan coil unit with an air intake system that includes a manual damper, applicable for back or front intake.
Standard ceiling mounted version with rear air intake (no inlet grille).
Diagram description: Shows a ceiling-mounted fan coil unit with air intake from the rear, without a visible inlet grille.
Bottom air intake (grille for version with cabinet).
Diagram description: Shows a fan coil unit with an air intake grille located at the bottom, designed for versions with a cabinet.
Air intake arrangement with manual damper.
Diagram description: Shows a fan coil unit with a general air intake arrangement featuring a manual damper.
Support feet. Air intake grille between feet.
Diagram description: Shows a fan coil unit mounted on support feet, with an air intake grille positioned between the feet.
Contact Information
Systemair AC SAS (France)
Route de Verneuil
27570 Tillières-sur-Avre
France
Tel. +33 02 32 60 61 00
Fax +33 02 32 32 55 13
Systemair srl (Italy)
Via XXV Aprile, 29
20825 Barlassina (MB)
Italy
Tel. +39 0362 680 1
Fax +39 0362 680 693