Vent-Axia Response Continuous Extract Fan

Installation and Wiring Instructions

Electrical: 220-240V~50Hz

Ingress Protection: IPX4

IMPORTANT: READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION

SAFETY AND GUIDANCE NOTES

  1. All wiring to be in accordance with the current I.E.E. Regulations, or the appropriate standards of your country and MUST be installed by a suitably qualified person.
  2. The Fan should be provided with a local isolator switch capable of disconnecting all poles, having a contact separation of at least 3mm.
  3. Ensure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label.
  4. The Fan should only be used in conjunction with the appropriate Vent-Axia products.
  5. The fan should only be used in conjunction with fixed wiring.
  6. When the Fan is used to remove air from a room containing a fuel-burning appliance, ensure that the air replacement is adequate for both the fan and the fuel-burning appliance.
  7. The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of time.
  8. Where ducted Fans are used to handle moisture-laden air, a condensation trap should be fitted. Horizontal ducts should be arranged to slope slightly downwards away from the Fan.
  9. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  10. Young children should be supervised to ensure that they do not play with the appliance.

DESCRIPTION

The Response fan is a continuously running extract fan for kitchens, utility rooms, bathrooms and toilets.

The product incorporates an airflow detection system that detects the installation duct resistance and maintains the correct fan speed to achieve the preset extract flow rate of either 6l/s, 8l/s or 13l/s, minimising energy use and noise (see Section C-Setup for more information).

The incorporated LED display allows the installer to verify the installed flow rate, and also provides feedback for system pressure and days installed (for landlords).

The fan can be wall or panel/ceiling mounted.

ACCESSORIES (not supplied)

WALL FITTING KIT

A range of white (stock ref. 254102) or brown (stock ref. 254100) 100mm wall kits are available for installing into most walls using telescopic liners supplied.

A. INSTALLATION

PANEL/CEILING MOUNTING

  1. Cut a 105mm diameter hole.
  2. Remove the front panel by carefully pulling away from the fan.
  3. Loosen the two self-retaining screws and remove the inner grille by carefully pulling away from the housing.
  4. Mark the screw centres through the holes in the fan back plate. Drill, plug and screw into position. Attach ducting as required for the installation.
  5. Wire the fan as described in Section B-Wiring. Adjust any settings as required (see Section C-Setup).
  6. After installation, ensure impeller rotates freely.
  7. Replace the inner grille and tighten the retaining screws. Replace the front panel.

WALL MOUNTING

  1. For wall mounting cut a 117mm diameter hole through the wall and insert the wall sleeve. Slope the sleeve slightly downwards away from the fan. Where necessary cut to length and cement both ends into position flush with the wall faces.
  2. Fix exterior grille into position with the louvres positioned downwards.
  3. Remove the front panel by carefully pulling away from the fan.
  4. Loosen the two self-retaining screws and remove the inner grille by carefully pulling away from the housing.
  5. Mark the screw centres through the holes in the fan back plate. Drill, plug and screw into position.
  6. Wire the fan as described in Section B-Wiring. Adjust any settings as required (see Section C-Setup).
  7. After installation, ensure impeller rotates freely.
  8. Replace the inner grille and tighten the retaining screws. Replace the front panel.

B. WIRING.

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.

IMPORTANT

  1. Select and follow the appropriate wiring diagram. (Fig. 1, 2 or 3)
  2. Check all connections have been made correctly and ensure all terminal connections and supply wires are securely fastened.
  3. Ensure the impeller rotates and is free from obstructions.

C. SETUP

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.

1) Trickle speed selection (6l/s or 8l/s) – (Fig. 5) (dMEV,TP & HTP models)

In normal running mode the fan can extract at either 6l/s (22m³/h) or 8l/s (29m³/h) flow rate. The fan will boost to 13l/s (46.8m³/h) when the LS connection is switched or humidity rises above the set point (see humidity setting below).

2) Airflow detection system – enable/disable (Fig. 5) (dMEV,TP & HTP models)

The airflow detection system will detect the installation duct resistance and also react to external wind conditions to ensure the fan maintains a constant extraction rate. This can cause the fan to ramp up and down and in most applications will not be required. To turn this feature on, complete the following:

IMPORTANT – On first power up, the fan will run through its initialisation routine. For the first 15 minutes, the flow rate, pressure and day logger will be displayed. The fan may not be fully functional until this is over. After the first 15 minutes, the fan will calibrate the installation which will involve the fan speeding up and down for a few minutes. Once this is complete the fan will operate normally with the display off.

3) LED Display with prism (Fig. 6) (dMEV,TP & HTP models)

For the first 15 minutes EVERY time the fan is powered off and on (via the isolator), the display will cycle between displaying the actual airflow rate (l/s) being achieved* and system pressure (Pa). They will cycle every 10-20 seconds, where the pressure will flash, and the airflow rate will be on constantly. The day logger feature will only be displayed once, after the first cycle of displaying the flow rate and system pressure.

*Airflow detection system must be enabled to display the calibrated flow rate.

4) Adjustable timer (TP model only)

The TP model incorporates an adjustable overrun timer. This adjusts the time the fan will continue to run on boost after the LS connection has been deactivated. The timer function is factory set at approx 15 minutes but can be adjusted between 1 & 30 minutes. This is also the run time period for the integral pullcord.

5) Fixed timer (HTP model only)

The HTP model incorporates an optional fixed timer – set at 15 minutes. This is the time the fan will continue to run on boost after the LS connection has been deactivated. The integral pullcord timer is fixed at 15 minutes and cannot be disabled.

6) Adjustable ambient response humidistat (HTP model only)

The HTP model incorporates an adjustable ambient response humidistat. The fan will increases the extract rate if the humidity rises above the set point – adjustable via the pot shown in fig. 5.

Note: The ambient response feature will automatically boost the fan to 13l/s if the humidity rises quickly irrespective of the set point and run on for the predetermined timeout period.

7) Pullcord (TP and HTP models only)

The integral pullcord activates the timer (see 4 and 5 above) and the fan will run at 13l/s for the set time period. If the integral pullcord is pulled for a second time (once activated), the timer will be cancelled and the fan will revert back to the trickle extract rate.

To remove the pullcord, cut the cord and leave the switch in place. There is no need to switch the fan on/off beforehand.

8) System pressure detection (dMEV,TP & HTP models)

The fan can detect the system pressure for fault finding. If the fan seems noisy or cannot achieve the desired flow rate, this could be due to a blocked duct or the ducting has not been suitably stretched during installation (if flexible ducting is used). This is displayed during the first 15 minutes EVERY time the fan is powered off and on (via the isolator). The number is displayed in Pascals (Pa) and the higher the number, the more torturous the system (and air path) – i.e. harder for the fan to move the air through the ducting. As a consequence the fan has to use more energy and it will increase the fans noise level.

The fan will maintain the correct airflow rate up to a maximum of 30Pa system pressure. The system pressure will be different for all speeds, but worst on the 13l/s setting.

9) Fan silent running boost mode

This feature delays the boost operation for a maximum of 20 minutes to reduce noise and cold drafts while bathing. After LS is disconnected, the fan will look at the amount of time since the LS was activated and then run the fan on boost for that same period or to a maximum of 20 minutes, whichever is shorter.

a. Dip switch 2 in the off position – Traditional mode (factory set) (fig. 5):

b. Dip switch 2 in the on position:

10) Calibration

The airflow sensor is calibrated at the factory using UKAS accredited equipment. Details of the equipment and certification can be found on the inside of the fan.

D. SERVICING AND MAINTENANCE.

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE.

  1. At intervals appropriate to the installation, the fan should be inspected and cleaned to ensure there is no build up of dirt or other deposits.
  2. Carefully pull the front panel off the inner grille. (Fig. 4)
  3. Wipe the inlets and front face with a damp cloth until clean. Be careful not to push dirt into the airflow sensor.

The fan has sealed for life bearings, which do not require lubrication.

E. TROUBLESHOOTING

1. Fan continuously speeds up and down:

a. Cause:

b. Solution:

2. The fan continuously runs in boost (HTP model only):

a. Cause:

b. Solution:

3. The fan does not turn to boost when the humidity is high:

a. Cause:

b. Solution:

4. Water is dripping out of the fan when installed in a ceiling:

a. Cause:

b. Solution:

Diagrams and Figures

Siting the fan

Illustration showing incorrect fan siting with a cross ❌ and correct fan siting with a checkmark ✔️.

Wiring Diagrams

Fig. 1: Continuous trickle (6l/s or 8l/s) with no boost facility. Depicts a 1-phase supply (220-240V 50Hz) connected to a fan via a switch. The fan is internally fused.

Fig. 2: Continuous boost (13l/s) with no trickle facility. Depicts a 1-phase supply (220-240V 50Hz) connected to a fan via a switched spur. The fan is internally fused.

Fig. 3: Continuous trickle with boost facility. Depicts a 1-phase supply (220-240 Volts 50 Hz) connected to a ceiling junction box, which then connects to a 3-pole isolator switch and the fan. Includes a pull cord and lamp connection.

Fig. 4. Removing the grille for wiring and setting the controls

Illustrates the process of removing the front panel by pulling it away, then loosening self-retaining screws to pull the inner grille away from the housing. A note advises ensuring the flow sensor aligns with the grille slot when reassembling.

Fig. 5. Controls

Note: Before changing any dipswitch positions, the fan must be isolated from the power supply.

Trickle speed (JP1) (All models):

Airflow detection system (All models):

Silent running boost mode (TP & HTP only):

Adjuster: Located for timer (TP) or humidistat (HTP).

JP1: Trickle speed.

JP2 (HTP ONLY): Fixed timer enable/disable jumper.

SW1: Airflow detection system and Silent running boost.

Fig. 6. Display and prism

The display is visible from the side to avoid affecting airflow through the sensor. Every 10-20 seconds, it cycles between airflow rate and system pressure. Pressure display flashes.

Example Airflow display: 13.2 (13.2l/s flow rate)

Example Pressure display: 17 (flashing - 17Pa system pressure)

The Vent-Axia Guarantee

Applicable only to products installed and used in the United Kingdom. For details of guarantee outside the United Kingdom contact your local supplier.

Vent-Axia guarantees its products for two years from date of purchase against faulty material or workmanship. In the event of any part being found to be defective, the product will be repaired, or at the Company's option replaced, without charge, provided that the product:

IF CLAIMING UNDER TERMS OF GUARANTEE

Please return the complete product, carriage paid to your original supplier or nearest Vent-Axia Centre, by post or personal visit. Please ensure that it is adequately packed and accompanied by a letter clearly marked "Guarantee Claim" stating the nature of the fault and providing evidence of date and source of purchase.

The guarantee is offered to you as an extra benefit, and does not affect your legal rights.

Vent-Axia Contact Information

Head Office:

Fleming Way, Crawley, West Sussex, RH10 9YX.

UK NATIONAL CALL CENTRE:

Newton Road, Crawley, West Sussex, RH10 9JA

SALES ENQUIRIES:

Tel: 0844 8560590 Fax: 01293 565169

TECHNICAL SUPPORT:

Tel: 0844 8560594 Fax: 01293 539209

For details of the warranty and returns procedure please refer to www.vent-axia.com or write to Vent-Axia Ltd, Fleming Way, Crawley, RH10 9YX.

Document Reference: 404302B

PDF preview unavailable. Download the PDF instead.

404302 b 0 Acrobat Distiller 10.1.5 (Windows)

Related Documents

Preview Vent-Axia Lo-Carbon Response/SELV dMEV Unit: Energy Efficient Ventilation
Discover the Vent-Axia Lo-Carbon Response/SELV dMEV Unit, a next-generation continuous running fan offering superior energy efficiency, improved comfort, and guaranteed installed performance for modern homes. Learn about its features, benefits, and technical specifications.
Preview Vent-Axia Response SELV Continuous Extract Fan Installation and Wiring Instructions
Comprehensive installation, wiring, setup, and troubleshooting guide for the Vent-Axia Response SELV continuous extract fan, including technical specifications and safety information.
Preview Vent-Axia Lo-Carbon Response Extractor Fan: Installation and Wiring Guide
Comprehensive installation and wiring instructions for the Vent-Axia Lo-Carbon Response continuous extract fan range, covering safety, setup, wiring diagrams, and maintenance. Includes product details, accessories, and energy comparison.
Preview Vent-Axia Lo-Carbon NBR dMEV C Installation and Wiring Guide
Detailed installation, wiring, setup, and maintenance guide for the Vent-Axia Lo-Carbon NBR dMEV C continuous extract filterless fan, including product specifications and safety information.
Preview Vent-Axia Lo-Carbon Response 7 Home Owner Guide: Reduce Condensation and Mould
A comprehensive guide for homeowners on the Vent-Axia Lo-Carbon Response 7 ventilation system, explaining how it prevents condensation and mould, improves air quality, and its low running costs.
Preview Vent-Axia Centra Lo-Carbon SELV Extractor Fan Installation and Wiring Instructions
Comprehensive installation and wiring guide for the Vent-Axia Centra Lo-Carbon SELV 100mm continuous extract fan, covering safety, mounting, wiring, and setup for models 443175A, 443176A, 443177A, and 447128A.
Preview Vent-Axia MultiVent Continuous Extract Ventilation FAN7200 Installation Guide
Comprehensive installation instructions, technical specifications, and feature descriptions for the Vent-Axia MultiVent Continuous Extract Ventilation System (FAN7200). Covers setup, wiring, operation, and troubleshooting for residential and commercial applications.
Preview Vent-Axia VA150 Window Extract Fan Installation and Wiring Instructions
Comprehensive installation, wiring, and maintenance guide for the Vent-Axia VA150A and VA150P window extract fans, including product specifications and guarantee information.