Instruction Manual for SIEMENS models including: DS III Pressure Transmitter, DS III, Pressure Transmitter, Transmitter

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions

A5E00053276-08;, 02/2016

PD PI Siemens AG

Sitrans P DSIII with Profibus PA Manua

Siemens Sitrans P DSIII Pressure Transmitter | Applied Instruments

SITRANS P DS III/P410 with PROFIBUS PA


File Info : application/pdf, 266 Pages, 5.30MB

PDF preview unavailable. Download the PDF instead.

Sitrans-P-DSIII-with-Profibus-PA-Manual-Feb-2016
SITRANS P DS III/P410 with PROFIBUS PA SITRANS Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA
Operating Instructions
7MF4.34
02/2016
A5E00053276-08

_In_tro_d_uc_tio_n____________1_ _Sa_fe_ty_in_fo_rm_a_ti_on_________2_ _De_s_cr_ipt_io_n ____________3_ _In_sta_ll_ing_/_m_o_un_ti_ng________4_ _Co_n_ne_c_tin_g_up___________5_ _O_pe_ra_tio_n_____________6_ _Ovia_peP_raR_tOo_rFc_IBo_UntS_ro_l f_un_ct_io_ns_____7_ _Fu_n_cti_on_a_l s_af_et_y _________8_ _Ceno_gn_ifnige_ue_rrain_tigo_n/_pr_oj_ec_t _______9_ _Co_m_m_is_si_on_in_g_________1_0_ _Re_p_ai_r a_n_d _ma_in_te_n_an_ce_____1_1_ _Ianl_ater_mrrus_p_ts,_e_rro_r_an_d_s_ys_te_m___1_2_ _Te_c_hn_ic_al_da_ta__________1_3_ _Di_m_en_si_on_d_ra_w_in_gs_______1_4_ _Sp_a_re_p_ar_ts_/ a_c_ce_ss_o_rie_s____1_5_ _Ap_p_en_d_ix_____________A_ _Laib_sbt _roef_via_ti_on_s/_ac_ro_n_ym_s______B_

Legal information
Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
DANGER indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION indicates that minor personal injury can result if proper precautions are not taken.
NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products Note the following:
WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY

Document order number: A5E00053276  03/2016 Subject to change

Copyright © Siemens AG 2016. All rights reserved

Table of contents

1 Introduction ........................................................................................................................................... 11

1.1

Purpose of this documentation ...............................................................................................11

1.2

Product information.................................................................................................................11

1.3

History .....................................................................................................................................11

1.4

Scope of the instructions ........................................................................................................12

1.5

Checking the consignment .....................................................................................................12

1.6

Transportation and storage.....................................................................................................13

1.7

Notes on warranty...................................................................................................................13

2 Safety information ................................................................................................................................. 15

2.1 2.1.1 2.1.2

Precondition for use ................................................................................................................15 Laws and directives ................................................................................................................15 Conformity with European directives ......................................................................................15

2.2

Improper device modifications ................................................................................................16

2.3

Requirements for special applications ....................................................................................16

2.4 2.4.1 2.4.2

Use in hazardous areas ..........................................................................................................17 Use of incorrect device parts in potentially explosive environments ......................................18 Electrostatic-sensitive devices................................................................................................19

3 Description............................................................................................................................................ 21

3.1

System configuration ..............................................................................................................21

3.2

Application ..............................................................................................................................22

3.3

SITRANS P DS III and SITRANS P410..................................................................................24

3.4

Structure .................................................................................................................................24

3.5

Nameplate layout ....................................................................................................................26

3.6

Measuring point label layout ...................................................................................................27

3.7 3.7.1 3.7.2 3.7.3 3.7.3.1 3.7.3.2 3.7.3.3 3.7.3.4 3.7.3.5 3.7.3.6 3.7.3.7

Principle of operation ..............................................................................................................27 Overview of mode of operation...............................................................................................27 Operation of the electronics ....................................................................................................28 Principle of operation of the measuring cell............................................................................29 Measuring cell for gauge pressure .........................................................................................30 Measuring cell for differential pressure and flow rate .............................................................31 Measuring cell for level ...........................................................................................................32 Measuring cell for absolute pressure from the differential pressure series ............................33 Measuring cell for absolute pressure from the gauge pressure series...................................34 Measuring cell for gauge pressure, front-flush membrane .....................................................34 Measuring cell for absolute pressure, front-flush membrane .................................................35

3.8

Remote seal............................................................................................................................36

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

5

Table of contents

3.9

SIMATIC PDM........................................................................................................................ 36

3.10 3.10.1 3.10.2 3.10.3

PROFIBUS............................................................................................................................. 37 Transmission technology ....................................................................................................... 37 Bus topology .......................................................................................................................... 37 Properties ............................................................................................................................... 38

4 Installing / mounting .............................................................................................................................. 39

4.1 4.1.1 4.1.2

Basic safety instructions ........................................................................................................ 39 Installation location requirements .......................................................................................... 43 Proper mounting..................................................................................................................... 43

4.2 4.2.1

Disassembly........................................................................................................................... 44 Incorrect disassembly ............................................................................................................ 44

4.3 4.3.1 4.3.2 4.3.3

Installation (except level) ....................................................................................................... 45 Installation mounting (except for level) .................................................................................. 45 Installation (except level) ....................................................................................................... 46 Fastening ............................................................................................................................... 46

4.4 4.4.1 4.4.2 4.4.3

"Level" installation .................................................................................................................. 48 Instructions for level installation ............................................................................................. 48 Installation for level ................................................................................................................ 49 Connection of the negative pressure line .............................................................................. 50

4.5 4.5.1 4.5.2

"Remote seal" installation ...................................................................................................... 53 Remote seal installation ......................................................................................................... 53 Installation of the remote seal with the capillary line.............................................................. 54

4.6

Turing the measuring cell against housing ............................................................................ 60

4.7

Rotating the display ............................................................................................................... 61

5 Connecting up....................................................................................................................................... 63

5.1 5.1.1 5.1.2

Basic safety instructions ........................................................................................................ 63 Hazardous contact voltage in versions with 4-conductor extension ...................................... 63 Incorrect measured values with incorrect grounding ............................................................. 65

5.2 5.2.1

Connecting the device ........................................................................................................... 66 PROFIBUS assembly guidelines ........................................................................................... 66

5.3

Connecting the M12 connector .............................................................................................. 68

6 Operation.............................................................................................................................................. 71

6.1

Overview of operation ............................................................................................................ 71

6.2

Basic safety instructions ........................................................................................................ 72

6.3

Information on operation ........................................................................................................ 72

6.4 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5

Display ................................................................................................................................... 73 Display elements.................................................................................................................... 73 Units display........................................................................................................................... 74 Error display ........................................................................................................................... 74 Mode display .......................................................................................................................... 75 Status display......................................................................................................................... 76

6.5 6.5.1

Local operation....................................................................................................................... 76 Control elements for local operation ...................................................................................... 76

SITRANS P DS III/P410 with PROFIBUS PA

6

Operating Instructions, 02/2016, A5E00053276-08

Table of contents

6.5.2 6.5.3 6.5.4 6.5.5 6.5.6 6.5.7 6.5.8 6.5.9 6.5.10 6.5.11 6.5.12 6.5.13

Operation using buttons..........................................................................................................79 Setting/adjusting electrical damping .......................................................................................79 Calibrate zero point.................................................................................................................80 Locking of buttons and functions ............................................................................................81 Measured value display ..........................................................................................................82 Unit ..........................................................................................................................................84 Bus address ............................................................................................................................88 Device operation type .............................................................................................................88 Position of the decimal point...................................................................................................90 Display of the zero-point adjustment ......................................................................................90 LO calibration..........................................................................................................................91 HI calibration ...........................................................................................................................92

7 Operator control functions via PROFIBUS ............................................................................................. 95

7.1 7.1.1 7.1.2 7.1.3 7.1.3.1 7.1.3.2 7.1.3.3 7.1.4 7.1.5 7.1.6

Communications structure for PROFIBUS PA .......................................................................95 Overview .................................................................................................................................95 Block model for collection and processing of measured values .............................................95 Pressure transducer block ......................................................................................................98 Pressure transducer block (transducer block 1) .....................................................................98 Linearization type function group..........................................................................................100 Units of the pressure transducer block .................................................................................102 Electronics temperature transducer block ............................................................................103 Analog input function block ...................................................................................................104 Totalizer function block .........................................................................................................105

7.2

Overview of operating functions ...........................................................................................106

7.3

Measurement ........................................................................................................................106

7.4 7.4.1 7.4.2 7.4.3 7.4.4 7.4.5 7.4.6

Settings .................................................................................................................................107 Overview of settings..............................................................................................................107 Settings .................................................................................................................................107 Pressure measurement.........................................................................................................107 Level measurement ..............................................................................................................108 Flow measurement ...............................................................................................................111 Adjusting to a desired process value ....................................................................................114

7.5

Electrical damping (filter time constant)................................................................................116

7.6

Key lock and write protection................................................................................................116

7.7

Warning and alarm limits ......................................................................................................117

7.8 7.8.1 7.8.2 7.8.3

Failure behavior ....................................................................................................................119 Overview of failure behavior .................................................................................................119 Output ...................................................................................................................................119 Totalizer output .....................................................................................................................119

7.9 7.9.1 7.9.2 7.9.3 7.9.4 7.9.5

Diagnostics functions ............................................................................................................120 Operating hours counter .......................................................................................................120 Calibration interval and service interval ................................................................................120 Clearing warning ...................................................................................................................121 Clearing the alarm.................................................................................................................121 Min/max indicator..................................................................................................................122

7.10 7.10.1

Simulation .............................................................................................................................122 Overview of simulation..........................................................................................................122

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

7

Table of contents

7.10.2 7.10.3 7.10.4 7.10.5

Simulating output ................................................................................................................. 123 Simulating input.................................................................................................................... 123 Simulating the pressure sensor ........................................................................................... 124 Simulating sensor and electronics temperature................................................................... 125

7.11

Calibrating the sensor .......................................................................................................... 125

7.12

Correcting for positional error .............................................................................................. 126

7.13 7.13.1 7.13.2 7.13.3

Reset .................................................................................................................................... 127 Resetting to delivery state.................................................................................................... 127 Warm start/restart ................................................................................................................ 128 Resetting the PROFIBUS address....................................................................................... 128

8 Functional safety..................................................................................................................................129

8.1

Safety function ..................................................................................................................... 129

8.2

Safety Integrity Level (SIL)................................................................................................... 130

8.3

Settings ................................................................................................................................ 132

8.4

Safety-related characteristics............................................................................................... 132

8.5 8.5.1 8.5.2 8.5.2.1 8.5.2.2 8.5.2.3 8.5.2.4 8.5.2.5

Maintenance/check .............................................................................................................. 133 Overview .............................................................................................................................. 133 Checking safety function/proof test...................................................................................... 134 Checking temperature sensors ............................................................................................ 135 Check response time of pressure transmitter. ..................................................................... 135 Two-point measurement  10% of the maximum measuring range .................................... 135 Two-point measurement  50% of the maximum measuring range .................................... 138 Checking pressure transmitter for external damage............................................................ 140

8.6 8.6.1 8.6.2

Add-on parts......................................................................................................................... 140 Checking a device with add-on pneumatic block................................................................. 140 Checking a device with add-on remote seal ........................................................................ 141

8.7 8.7.1 8.7.2 8.7.3 8.7.4 8.7.5 8.7.5.1 8.7.5.2 8.7.5.3 8.7.5.4 8.7.6 8.7.6.1 8.7.6.2 8.7.7 8.7.7.1 8.7.7.2 8.7.7.3 8.7.7.4 8.7.7.5 8.7.8 8.7.8.1

PROFIsafe ........................................................................................................................... 141 Introduction .......................................................................................................................... 141 Technical advantages of PROFIsafe ................................................................................... 141 Further information............................................................................................................... 143 Preconditions ....................................................................................................................... 144 PROFIsafe Configuration ..................................................................................................... 144 Import EDD with SIMATIC PDM .......................................................................................... 145 Configure CPU with HW Config ........................................................................................... 145 Configure device with HW Config ........................................................................................ 145 Configure CFC ..................................................................................................................... 148 Write protection .................................................................................................................... 150 Overview .............................................................................................................................. 150 Activate write protection using PIN in SIMATIC PDM.......................................................... 151 PROFIsafe Commissioning.................................................................................................. 151 Activate and parameterize PROFIsafe with SIMATIC PDM ................................................ 152 Commission PROFIsafe with SIMATIC PDM ...................................................................... 153 Check write protection with SIMATIC PDM ......................................................................... 158 Speeding up the commissioning process ............................................................................ 159 Resetting the device ............................................................................................................ 159 Quit PROFIsafe commissioning........................................................................................... 160 Preparations for maintenance and service .......................................................................... 160

SITRANS P DS III/P410 with PROFIBUS PA

8

Operating Instructions, 02/2016, A5E00053276-08

Table of contents

8.7.8.2 8.7.8.3 8.7.9 8.7.9.1 8.7.9.2

Deactivating PROFIsafe commissioning in SIMATIC PDM..................................................160 Disable write protection using PIN in SIMATIC PDM ...........................................................160 Replacing a device................................................................................................................161 Making settings locally ..........................................................................................................161 Configuration with host system.............................................................................................162

9 Configuration/project engineering........................................................................................................ 165

9.1

Cyclical data transfer ............................................................................................................165

9.2 9.2.1 9.2.2 9.2.3 9.2.4 9.2.5

Configuring ............................................................................................................................ 165 Overview of configuration .....................................................................................................165 Configuration of user data ....................................................................................................165 Transmission of user data over PROFIBUS .........................................................................167 Status ....................................................................................................................................167 Diagnosis ..............................................................................................................................168

9.3

Acyclic data transfer..............................................................................................................170

10 Commissioning ................................................................................................................................... 171

10.1

Basic safety instructions .......................................................................................................171

10.2

Introduction to commissioning ..............................................................................................171

10.3
10.3.1 10.3.2

Gauge pressure, absolute pressure from differential pressure series, and absolute pressure from gauge pressure series ...................................................................................172 Commissioning for gases .....................................................................................................172 Commissioning with steam or liquid .....................................................................................174

10.4 10.4.1 10.4.2 10.4.3 10.4.4

Differential pressure and flow rate ........................................................................................175 Safety notes for commissioning with differential pressure and flow rate ..............................175 Commissioning in gaseous environments ............................................................................176 Commissioning for liquids .....................................................................................................177 Commissioning with vapor ....................................................................................................179

11 Repair and maintenance ..................................................................................................................... 181

11.1

Basic safety instructions .......................................................................................................181

11.2 11.2.1 11.2.2 11.2.3 11.2.4

Maintenance and repair work ...............................................................................................184 Defining the maintenance interval ........................................................................................184 Checking the gaskets............................................................................................................185 Display in case of a fault .......................................................................................................185 Changing the measuring cell and application electronics.....................................................186

11.3 11.3.1

Cleaning ................................................................................................................................186 Servicing the remote seal measuring system .......................................................................187

11.4

Return procedure ..................................................................................................................187

11.5

Disposal ................................................................................................................................188

12 Interrupts, error and system alarms ..................................................................................................... 189

12.1

Overview of status codes......................................................................................................189

12.2

Errors ....................................................................................................................................192

13 Technical data .................................................................................................................................... 193

13.1

Overview of technical data....................................................................................................193

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

9

Table of contents

13.2

SITRANS P DS III input ....................................................................................................... 194

13.3

SITRANS P410 input ........................................................................................................... 200

13.4

Output .................................................................................................................................. 202

13.5

Measuring accuracy of SITRANS P DS III........................................................................... 203

13.6

Measuring accuracy of SITRANS P410............................................................................... 211

13.7

Operating conditions ............................................................................................................ 214

13.8

Construction ......................................................................................................................... 218

13.9

Display, keyboard and auxiliary power ................................................................................ 224

13.10

Certificates and approvals ................................................................................................... 225

13.11

PROFIBUS communication ................................................................................................. 227

14 Dimension drawings.............................................................................................................................229

14.1

SITRANS P, DS III/P410 for gauge pressure and absolute pressure from the gauge

pressure series..................................................................................................................... 229

14.2

SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from

the differential pressure series............................................................................................. 231

14.3

SITRANS P DS III/P410 for level ......................................................................................... 234

14.4 14.4.1 14.4.2 14.4.3 14.4.4 14.4.5

SITRANS P DS III (flush-mounted)...................................................................................... 235 Note 3A and EHDG.............................................................................................................. 236 Connections as per EN and ASME...................................................................................... 237 F&B and pharma flange ....................................................................................................... 238 PMC Style ............................................................................................................................ 242 Special connections ............................................................................................................. 243

15 Spare parts / accessories.....................................................................................................................245

15.1

Order data ............................................................................................................................ 245

15.2

Spare parts/accessories for SITRANS P DS III ................................................................... 245

15.3

Order data for SIMATIC PDM .............................................................................................. 247

15.4

Ordering data for PROFIBUS accessories .......................................................................... 248

A Appendix .............................................................................................................................................249

A.1

Certificate ............................................................................................................................. 249

A.2

Certificates (China) .............................................................................................................. 249

A.3

Literature and standards ...................................................................................................... 253

A.4

Technical support................................................................................................................. 254

B List of abbreviations/acronyms .............................................................................................................255

B.1

Pressure transmitter............................................................................................................. 255

B.2

Functional safety .................................................................................................................. 257

Glossary ..............................................................................................................................................259

Index ...................................................................................................................................................263

SITRANS P DS III/P410 with PROFIBUS PA

10

Operating Instructions, 02/2016, A5E00053276-08

Introduction

1

1.1

Purpose of this documentation

These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation.

The instructions are aimed at persons mechanically installing the device, connecting it electronically, configuring the parameters and commissioning it, as well as service and maintenance engineers.

1.2

Product information

The programming manual is an integral part of the CD, which is either supplied or can be ordered. The programming manual is also available on the Siemens homepage.

On the CD, you will also find the catalog extract with the ordering data, the Software Device Install for SIMATIC PDM for additional installation, and the required software.

See also

Process instrumentation catalog (http://www.siemens.com/processinstrumentation/catalogs) Product information on SITRANS P in the Internet (http://www.siemens.com/sitransp)

1.3

History
This history establishes the correlation between the current documentation and the valid firmware of the device.
The documentation of this edition applies to the following firmware:

Edition 12/2015

Firmware identifier nameplate
FW:300.01.08 FW:301.01.10
PROFIsafe FW:301.02.03 FW:301.02.04

System integration SIMATIC PDM V8.x

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

11

Introduction 1.4 Scope of the instructions

The most important changes in the documentation when compared with the respective previous edition are given in the following table.

Edition 12/2015

Remark All safety information has been revised. The following chapters have also been changed: · "Functional safety" chapter · "Technical data" chapter

1.4

Scope of the instructions

Table 1- 1 "7MF4.34.." stands for:

Order number 7MF4034.. 7MF4134.. 7MF4234.. 7MF4334.. 7MF4434..
7MF4534.. 7MF4634..

SITRANS P DS III/P410 for Gauge pressure Gauge pressure, flush mounted diaphragm Absolute pressure from the gauge pressure series Absolute pressure from the differential pressure series Differential pressure and flow rate, PN 32/160 (MAWP 464/2320 psi) Differential pressure and flow rate, PN 420 (MAWP 6092 psi) Level

1.5

Checking the consignment

1. Check the packaging and the delivered items for visible damage.

2. Report any claims for damages immediately to the shipping company.

3. Retain damaged parts for clarification.

4. Check the scope of delivery by comparing your order to the shipping documents for correctness and completeness.

WARNING Using a damaged or incomplete device Danger of explosion in hazardous areas. · Do not use damaged or incomplete devices.

See also

Return procedure (Page 187)

SITRANS P DS III/P410 with PROFIBUS PA

12

Operating Instructions, 02/2016, A5E00053276-08

Introduction 1.6 Transportation and storage

1.6

Transportation and storage

To guarantee sufficient protection during transport and storage, observe the following:

 Keep the original packaging for subsequent transportation.
 Devices/replacement parts should be returned in their original packaging.
 If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.

CAUTION Insufficient protection during storage The packaging only provides limited protection against moisture and infiltration. · Provide additional packaging as necessary.
Special conditions for storage and transportation of the device are listed in "Technical data" (Page 193).

1.7

Notes on warranty

The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.

The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

13

Introduction 1.7 Notes on warranty

SITRANS P DS III/P410 with PROFIBUS PA

14

Operating Instructions, 02/2016, A5E00053276-08

Safety information

2

2.1

Precondition for use

This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety.

Observe the information and symbols on the device. Do not remove any information or symbols from the device. Always keep the information and symbols in a completely legible state.

Symbol Explanation Consult operating instructions

2.1.1

Laws and directives
Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation. These include, for example:  National Electrical Code (NEC - NFPA 70) (USA)  Canadian Electrical Code (CEC) (Canada) Further provisions for hazardous area applications are for example:  IEC 60079-14 (international)  EN 60079-14 (EC)

2.1.2

Conformity with European directives
The CE mark on the device is a sign of conformity with the following European directives:

Electromagnetic Compatibil- Directive of the European Parliament and of the Council on the

ity EMC

approximation of the laws of the Member States relating to elec-

2004/108/EC

tromagnetic compatibility and repealing Directive 89/336/EEC.

Atmosphère explosible ATEX 94/9/EC

Directive of the European Parliament and the Council on the approximation of the laws of the Member States concerning equipment and protective systems intended for use in potentially explosive atmospheres.

Pressure Equipment Directive PED 97/23/EC

Directive of the European Parliament and of the Council on the approximation of the laws of the Member States concerning pressure equipment.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

15

Safety information 2.2 Improper device modifications
The standards applied can be found in the EC declaration of conformity for the device.

2.2

Improper device modifications

WARNING
Improper device modifications
Danger to personnel, system and environment can result from modifications to the device, particularly in hazardous areas. · Only carry out modifications that are described in the instructions for the device. Failure
to observe this requirement cancels the manufacturer's warranty and the product approvals.

2.3

Requirements for special applications

Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative.

Note
Operation under special ambient conditions
We highly recommend that you contact your Siemens representative or our application department before you operate the device under special ambient conditions as can be encountered in nuclear power plants or when the device is used for research and development purposes.

SITRANS P DS III/P410 with PROFIBUS PA

16

Operating Instructions, 02/2016, A5E00053276-08

Safety information 2.4 Use in hazardous areas

2.4

Use in hazardous areas

Qualified personnel for hazardous area applications
Persons who install, connect, commission, operate, and service the device in a hazardous area must have the following specific qualifications:
 They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures, aggressive, and hazardous media.
 They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems.
 They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations.

WARNING
Unsuitable device for the hazardous area
Danger of explosion. · Only use equipment that is approved for use in the intended hazardous area and
labelled accordingly.

See also

Technical data (Page 193)
WARNING
Loss of safety of device with type of protection "Intrinsic safety Ex i"
If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been observed, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion. · Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe
circuit. · Observe the specifications for the electrical data on the certificate and/or in Chapter
"Technical data (Page 193)".

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

17

Safety information 2.4 Use in hazardous areas

2.4.1

Use of incorrect device parts in potentially explosive environments

WARNING
Use of incorrect device parts in potentially explosive environments
Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection. If you do not adhere to these guidelines, the test certificates and the manufacturer warranty will become null and void.
· Use only device parts that have been approved for the respective type of protection in the potentially explosive environment. Covers that are not suited for the "explosionproof" type of protection are identified as such by a notice label attached to the inside of the cover with "Not Ex d Not SIL".
· Do not swap device parts unless the manufacturer specifically ensures compatibility of these parts.

WARNING
Risk of explosion due to electrostatic charge
To prevent the build-up of an electrostatic charge in a hazardous area, the key cover must be closed during operation and the screws tightened.
The key cover may be opened temporarily at any time for the purposes of operating the pressure transmitter, even during plant operation; the screws should then be tightened again.

SITRANS P DS III/P410 with PROFIBUS PA

18

Operating Instructions, 02/2016, A5E00053276-08

2.4.2

Safety information 2.4 Use in hazardous areas
Electrostatic-sensitive devices
NOTICE Electrostatic-sensitive devices The device contains electrostatic-sensitive devices (ESD). ESD can be destroyed by voltages far too low to be detected by humans. These voltages can occur if you simply touch a component part or the electrical connections of a module without being electrostatically discharged. The damage to a module caused by overvoltage cannot normally be detected immediately; it only becomes apparent after a longer period of operating time has elapsed. Protective measures against the discharge of static electricity: · Make sure that no power is applied. · Before working with modules, make sure that you discharge static from your body, for
example by touching a grounded object. · Devices and tools used must be free of static charge. · Hold modules only by their edges. · Do not touch connector pins or conductor tracks on a module with the ESD notice.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

19

Safety information 2.4 Use in hazardous areas

SITRANS P DS III/P410 with PROFIBUS PA

20

Operating Instructions, 02/2016, A5E00053276-08

Description

3

3.1

System configuration

Overview

The pressure transmitter can be used in a number of system configurations. Use with the SIMATIC PCS 7 Automation System is described below.

System communication
The operator station of the SIMATIC PCS 7 process control system allows easy and safe control of the process by the operating personnel via OS clients.
The maintenance station assists the maintenance engineer in guaranteeing high plant availability, securing this long-term using optimization measures, and implementing the maintenance measures using a minimum of personnel, materials, energy, expenses, etc.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

21

Description 3.2 Application
The field devices are integrated over PROFIBUS PA with:  PA Link to the gateway between PROFIBUS PA and PROFIBUS DP  Control system, e.g. SIMATIC PCS 7 Automation System, which communicates over
PROFIBUS  Engineering station, SIMATIC PDM (Process Device Manager) which communicates over
Industrial Ethernet

Image 3-1 Possible system configuration

3.2

Application

Overview

Depending on the variant, the pressure transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids.
Depending on the device version, you can use the pressure transmitter for the following types of measurement:
 Gauge pressure  Absolute pressure  Differential pressure

SITRANS P DS III/P410 with PROFIBUS PA

22

Operating Instructions, 02/2016, A5E00053276-08

Description 3.2 Application
With appropriate parameter settings and the necessary add-on parts (e.g. flow limiters and remote seals), the pressure transmitter can also be used for the following measurements:  Level  Volume  Mass  Volume flow  Mass flow The output signal is a process-based, digital PROFIBUS PA/FOUNDATIONTM Fieldbus FF signal. You can install the "intrinsically-safe" or "flameproof enclosure" version of the pressure transmitter in hazardous areas. The devices have an EC-Type Examination Certificate, and comply with the corresponding harmonized European directives of the CENELEC. The pressure transmitter is available with various designs of the remote seal for special applications. A special application, for example, is the measurement of highly viscous materials.
Gauge pressure
This version measures the gauge pressure of corrosive, non-corrosive and toxic gases, vapors and liquids. The smallest nominal measuring range is 0.01 bar g/1kPa g/14.5 psi g, the largest is 700 bar g/70 MPa g/10153 psi g.
Absolute pressure
This version measures the absolute pressure of corrosive, non-corrosive and toxic gases, vapors and liquids. There are two series: A "Differential pressure" series and a "Gauge pressure" series. The "Differential pressure" series features a high overload capacity. The smallest nominal measuring range of the "Differential pressure" series is 8.3 mbar a/0.83kPa/3.63 psi a, the largest is 100 bar a/10 MPa a/1450 psi a. The smallest nominal measuring range of the "Gauge pressure" series is 8.3 mbar a/0.83kPa/3.63 psi a, the largest is 30 bar a/3 MPa/435 psi a.
Differential pressure and flow rate
This version measures corrosive, non-corrosive and toxic gases, vapors and liquids. You can use it for the following types of measurement:  Differential pressure  Gauge pressure, suitable for small positive or negative pressure value  In combination with a primary element: flow rate q ~

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

23

Description 3.3 SITRANS P DS III and SITRANS P410

The smallest nominal measuring range is 20 mbar (8.03 in H2O), the largest is 30 bar (435 psi).

Level

This version with mounting flange measures the level of non-corrosive, corrosive and toxic liquids in open and closed containers. The smallest nominal measuring range is 250 mbar (3.63 psi), the largest is 5 bar (72.5 psi). The nominal diameter of the mounting flange is DN 80 or DN 100, or 3" or 4".
For the level measurement on open containers, the low-pressure side of the measuring cell remains open. This measurement is referred to as "Measurement against atmospheric pressure". For the measurement on closed containers, the low-pressure side is usually connected to the container. This balances out the static pressure.
The parts wetted by the medium are made of various materials according to the corrosion resistance required.

3.3

SITRANS P DS III and SITRANS P410

SITRANS P DS III and SITRANS P410
These instructions describe the pressure transmitters SITRANS P DS III and SITRANS P410. The main difference of the SITRANS P410 is the higher measuring precision compared to the SITRANS P DS III. Refer to the information in the section Technical data (Page 193).
You order SITRANS P410 using the order option C41 for specific device versions.

3.4

Structure

Depending on a customer-specific order, the device comprises different parts.

SITRANS P DS III/P410 with PROFIBUS PA

24

Operating Instructions, 02/2016, A5E00053276-08

Description 3.4 Structure



Key cover



Cable inlet, optionally with cable gland



Cover (front), optionally with inspection window



Cover (rear) for electrical terminal compartment



Display (optional)



Electrical terminal compartment



Measuring point label



Protective conductor connector/equipotential bond-

ing terminal



Retaining screw; twist proofing of the measuring cell 

Nameplate (approval information)

in relation to the electronics enclosure



Process connection



Blanking plug



Nameplate (general information)

Image 3-2 View of the pressure transmitter: Left: Front right: Rear view

 The electronics enclosure is made of die cast aluminum or precision cast stainless steel.
 The housing has a removable circular cover at the front and the back.
 Depending on the device version, the front cover  may be designed as an inspection
window. You can read the measured values straight off the digital display through this inspection window.
 The cable inlet  to the electrical terminal compartment is at the side; either the left or right-hand one can be used. The unused opening is closed with a blanking plug .
 The protective conductor terminal/equipotential bonding terminal  is located at the back
of the enclosure.
 The electrical terminal compartment  for the auxiliary power and shield is accessible when you remove the back cover .
 The measuring cell with a process connection  is located in the lower section of the enclosure. This measuring cell is secured against twisting by a retaining screw .
Thanks to the modular design of the pressure transmitter, the measuring cell and application electronics or connection board can be replaced if required.
 On the upper face of the enclosure you can see crosshead screws which secure the key
cover , under which there are 3 keys for local operation.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

25

Description 3.5 Nameplate layout

3.5

Nameplate layout

Nameplate with general information
The label which bears the Order No. and other important information such as design details or technical data is present on the side of the housing.

 Order number (machine-readable product  Serial number
code)
Nameplate with approval information
On the opposite side is the nameplate with approval information. This nameplate shows the firmware and hardware versions, for example. You must also observe the information in the relevant certificate for a pressure transmitter version for use in hazardous areas.

SITRANS P DS III/P410 with PROFIBUS PA

26

Operating Instructions, 02/2016, A5E00053276-08

Description 3.6 Measuring point label layout

3.6

 Characteristics of the hazardous area

 Maximum surface temperature (tempera-

ture class)

 Category of the operating range

 Device protection level

 Type of protection

 Firmware identifier

 Group (gas, dust)

 Hardware identifier

 QR code to the mobile website with de- A
vice-specific information on the product

More detailed information on the charac-
teristics 

Measuring point label layout

Image 3-3 Example of measuring point label

3.7

Principle of operation

3.7.1

Overview of mode of operation
This chapter describes how the pressure transmitter works.
First the electronics are described, and then the physical principle of the sensors which are used with the various device versions for the individual measurement types.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

27

Description 3.7 Principle of operation

3.7.2

Operation of the electronics

Description

 Measuring cell sensor  Measuring amplifier  Analog-to-digital converter  Microcontroller  Electrical isolation  Each with an EEPROM in the measuring cell
and in the electronics
 PROFIBUS PA interface

 Buttons (local operation)  Display  Power supply  DP/PA coupler or DP/PA link  Bus master
pe Input variable

Image 3-4 Principle of operation of the electronics with PA communication

Function
 The inlet pressure is converted into an electrical signal by the sensor .  This signal is amplified by the measuring amplifier  and digitized in an analog-to-digital
converter .  The digital signal is analyzed in a microcontroller  and corrected with regard to linearity
and thermal characteristics.
 The signal is available at an electrically isolated PA interface  on the PROFIBUS PA.

SITRANS P DS III/P410 with PROFIBUS PA

28

Operating Instructions, 02/2016, A5E00053276-08

Description 3.7 Principle of operation
 The data specific to the measuring cell, the electronics data, and the parameterization
data are stored in two EEPROMs . The first memory is linked with the measuring cell,
the second with the electronics.  The results with the status values and diagnostics data are transmitted cyclically over the
PROFIBUS PA. Parameterization data and error messages are transmitted acyclically by SIMATIC PDM. Operation
 The buttons  can be used to call up individual functions, so-called modes.  If you have a display , you can track the mode settings and other messages on it.

3.7.3

Principle of operation of the measuring cell

WARNING
Destruction of the seal diaphragm
Danger of injury or damage to device
If the seal membrane is destroyed, the sensor may also be destroyed. If the seal membrane is destroyed, no reliable measured values can be output.
Hot, toxic and corrosive process media can be released. · Ensure that the material of the device parts wetted by the process medium is suitable for
the medium. Refer to the information in Technical data (Page 193). · Make sure that the device is suitable for the maximum operating pressure of your
system. Refer to the information on the nameplate and/or in Technical data (Page 193). · Define maintenance intervals for regular inspections in line with device use and
empirical values. The maintenance intervals will vary from site to site depending on corrosion resistance.
In the following sections, the process variable to be measured is called general inlet pressure.

Overview

The following modes of operation are described:  Gauge pressure  Absolute pressure  Differential pressure and flow rate  Level The following process connections are available, for example:  G1/2 B, 1/2-14 NPT  Male thread: M20

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

29

Description 3.7 Principle of operation

 Flange connection in accordance with EN 61518  Flush-mounted process connections

3.7.3.1

Measuring cell for gauge pressure

 Reference pressure opening  Measuring cell  Process connection  Seal diaphragm

 Filling liquid  Gauge pressure sensor
pe Inlet pressure

Image 3-5 Function chart of measuring cell for gauge pressure

The inlet pressure (pe) is transferred to the gauge pressure sensor  via the seal diaphragm  and the fill fluid , displacing its measuring diaphragm. The displacement changes the
resistance of the four piezoresistors (bridge circuit) of the gauge pressure sensor. The change in the resistance causes a bridge output voltage proportional to the inlet pressure.
Pressure transmitters with spans  6.3 MPa measure the inlet pressure against atmosphere, those with spans  16 MPa the inlet pressure against vacuum.

SITRANS P DS III/P410 with PROFIBUS PA

30

Operating Instructions, 02/2016, A5E00053276-08

3.7.3.2

Measuring cell for differential pressure and flow rate

Description 3.7 Principle of operation

 Inlet pressure P+  Pressure cap  O-ring  Measuring cell body  Differential pressure sensor

 Overload diaphragm  Filling liquid  Seal diaphragm  Inlet pressure P-

Image 3-6 Function chart of the measuring cell for differential pressure and flow rate

 Differential pressure is transmitted to the differential pressure sensor  through the seal diaphragms  and the filling liquid .
 When measuring limits are exceeded, the seal diaphragm  is displaced until the seal diaphragm rests on the measuring cell body . The differential pressure sensor  is
thus protected against overloading since no further deflection of the overload diaphragm
 is possible.
 The seal diaphragm  is displaced by the differential pressure. The displacement
changes the resistance of the four piezoresistors (bridge circuit) of the differential pressure sensor.
 The change in the resistance causes a bridge output voltage proportional to the differential pressure.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

31

Description 3.7 Principle of operation

3.7.3.3

Measuring cell for level

 Pressure cap  O-ring  Measuring cell body
 Overload diaphragm  Differential pressure sensor

 Seal diaphragm on the measuring cell  Filling liquid of the measuring cell  Capillary tube with the fill fluid of the mounting
flange
 Flange with a tube  Seal diaphragm on the mounting flange

Image 3-7 Function chart of the measuring cell for level

 The inlet pressure (hydrostatic pressure) works hydraulically on the measuring cell
through the seal diaphragm  on the mounting flange .
 Differential pressure at the measuring cell is transmitted to the differential pressure
sensor  through the seal diaphragms  and the filling liquid .  When measuring limits are exceeded, the overload diaphragm  is displaced until one of
the seal diaphragms  or  rests on the measuring cell body . The seal diaphragms  thus protect the differential pressure sensor  from overload.  The seal diaphragm  is displaced by the differential pressure. The displacement
changes the resistance of the four doped piezoresistors in the bridge circuit.
 The change in the resistance causes a bridge output voltage proportional to the differential pressure.

SITRANS P DS III/P410 with PROFIBUS PA

32

Operating Instructions, 02/2016, A5E00053276-08

3.7.3.4

Description 3.7 Principle of operation
Measuring cell for absolute pressure from the differential pressure series

 Pressure cap  Seal diaphragm on the measuring cell  O-ring  Measuring cell body  Absolute pressure sensor

 Overload diaphragm  Measuring cell filling liquid  Reference pressure
pe Pressure input variable

Image 3-8 Function chart of measuring cell for absolute pressure

 Absolute pressure is transmitted to the absolute pressure sensor  through the seal diaphragm  and the filling liquid .
 When measuring limits are exceeded, the overload diaphragm  is displaced until the seal diaphragm  rests on the measuring cell body . The seal diaphragm thus protects the absolute pressure sensor  from overload.
 The difference between the inlet pressure (pe) and the reference pressure  on the negative side of the measuring cell displaces the seal diaphragm . The displacement
changes the resistance of the four piezoresistors (bridge circuit) of the absolute pressure sensor.
 The change in the resistance causes a bridge output voltage proportional to the absolute pressure.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

33

Description 3.7 Principle of operation

3.7.3.5

Measuring cell for absolute pressure from the gauge pressure series

3.7.3.6

 Measuring cell  Process connection  Seal diaphragm

 Filling liquid  Absolute pressure sensor
Pe Inlet pressure

Image 3-9 Function chart of measuring cell for absolute pressure

The inlet pressure (pe) is transferred to the absolute pressure sensor  via the seal diaphragm  and the fill fluid , displacing its measuring diaphragm. The displacement
changes the resistance of the four piezoresistors (bridge circuit) of the absolute pressure
sensor. The change in the resistance causes a bridge output voltage proportional to the inlet
pressure.

Measuring cell for gauge pressure, front-flush membrane

 Reference pressure opening  Measuring cell  Process connection  Seal diaphragm

 Filling liquid  Gauge pressure sensor
pe Inlet pressure

Image 3-10 Function chart of the measuring cell for gauge pressure, flush mounted diaphragm

The inlet pressure (pe) is transferred to the gauge pressure sensor  via the seal diaphragm  and the filling liquid , displacing its measuring diaphragm. The displacement changes

SITRANS P DS III/P410 with PROFIBUS PA

34

Operating Instructions, 02/2016, A5E00053276-08

3.7.3.7

Description 3.7 Principle of operation
the resistance of the four piezoresistors (bridge circuit) of the gauge pressure sensor. The change in the resistance causes a bridge output voltage proportional to the inlet pressure. Pressure transmitters with measuring span  63 bar measure the inlet pressure against atmosphere, those with measuring spans  160 bar the inlet pressure against vacuum.
Measuring cell for absolute pressure, front-flush membrane

 Measuring cell  Process connection  Seal diaphragm

 Filling liquid  Absolute pressure sensor
pe Inlet pressure

Image 3-11 Function chart of the measuring cell for absolute pressure, flush mounted diaphragm

The inlet pressure (pe) is transferred to the absolute pressure sensor  via the seal diaphragm  and the filling liquid , and displaces its measuring diaphragm. The
displacement changes the resistance of the four piezoresistors (bridge circuit) of the
absolute pressure sensor. The change in the resistance causes a bridge output voltage
proportional to the inlet pressure.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

35

Description 3.8 Remote seal

3.8

Remote seal

Product description
 A remote seal measuring system comprises the following elements: ­ Remote seal ­ Transmission line, e.g. capillary line ­ Pressure transmitter.
Note Malfunction of the remote seal measuring system If you separate the components of the remote seal measuring system, this results in malfunctioning of the system.
Do not separate the components under any circumstances.
 The measuring system based on a hydraulic principle is used to transfer pressure.  The capillary line and the remote seal diaphragm are the most sensitive components in
the remote seal measuring system. The material thickness of the remote seal diaphragm is only  0.1 mm.  The smallest of leakages in the transmission system leads to the loss of transmission fluid.  The loss of transmission fluid results in inaccuracies in the measurement and failure of the measuring system.  In order to avoid leaks and measuring errors, please observe the installation and maintenance instructions in addition to the safety notes.

3.9

SIMATIC PDM

SIMATIC PDM is a software package for configuring, parameter assignment, commissioning, diagnostics and maintenance of this device and other process devices.

SIMATIC PDM offers simple monitoring of process values, alarms, and device status information.

SIMATIC PDM allows the process device data to be:

 displayed  set  modified  saved  diagnosed

 checked for plausibility

SITRANS P DS III/P410 with PROFIBUS PA

36

Operating Instructions, 02/2016, A5E00053276-08

 managed  simulated

Description 3.10 PROFIBUS

3.10

PROFIBUS
The Process Fieldbus (PROFIBUS) is an open communications system for automation technology and is specified in the international standard IEC 61158.
PROFIBUS Process Automation (PROFIBUS PA) is a variant of PROFIBUS Decentral Peripherals (PROFIBUS DP), which is widely used in process technology.

3.10.1

Transmission technology
The PROFBUS PA has the special transmission technique MBP (Manchester coded Bus Powered) and therefore satisfies the requirements of process automation and process engineering requirements.
This transmission technology is defined in the international standard IEC 61158-2.
The PROFIBUS PA is based on the FISCO model (Fieldbus Intrinsically safe Concept) and can therefore be used in hazardous areas.

3.10.2

Bus topology
The bus topology is mainly able to be selected as desired. Therefore, line, star and tree structures, and mixed forms are possible. All types of field devices such as transmitters, actors, analysis devices, etc. can be connected to the PROFIBUS PA.
Advantages include:
 Savings on installation costs  More extensive diagnostics, leading to increased availability of installation sections  Automatic management of installation documentation  Installation optimization on the fly during operation In an automation system, there are generally multiple PROFIBUS PA lines connected to fast PROFIBUS DP via coupler units. This is also connected to the process control system.
Both bus systems use the same protocol layer. This makes PROFIBUS PA a "communications-compatible" extension of the PROFIBUS DP into the field.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

37

Description 3.10 PROFIBUS

Image 3-12 Functional principle of the PROFIBUS automation system
The figure shows a section of a typical PROFIBUS automation system. The control system consists of two masters with distributed tasks.
The class-1 master recognizes the control and regulation tasks. The class-2 master enables the operating and monitoring functions. Between the class-1 master and the field devices there is a periodic exchange of measurement and settings data. The status information from the field devices is transmitted parallel to this data, and evaluated in the class-1 master. Assignment of parameters for the field devices or the reading of additional device information is not performed during periodic operation.
Besides periodic operation, one or more class-2 masters can access the field devices asynchronously. Using this type of communication, additional information can be retrieved from the devices or settings sent to them.

3.10.3

Properties
PROFIBUS PA allows bidirectional communication between a bus master and field devices. At the same time, the shielded two-strand wiring provides auxiliary power to the two-wire field devices.

SITRANS P DS III/P410 with PROFIBUS PA

38

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting

4

4.1

Basic safety instructions

WARNING
Wetted parts unsuitable for the process media
Danger of injury or damage to device.
Hot, toxic and corrosive media could be released if the process medium is unsuitable for the wetted parts. · Ensure that the material of the device parts wetted by the process medium is suitable for
the medium. Refer to the information in "Technical data" (Page 193).

WARNING
Incorrect material for the diaphragm in Zone 0
Danger of explosion in the hazardous area. If operated with intrinsically safe supply devices of category "ib" or devices of the flameproof enclosure version "Ex d" and simultaneous use in Zone 0, pressure transmitter explosion protection depends on the tightness of the diaphragm. · Ensure that the material used for the diaphragm is suitable for the process medium.
Refer to the information in the section "Technical data (Page 193)".

WARNING Unsuitable connecting parts Danger of injury or poisoning. In case of improper mounting hot, toxic and corrosive process media could be released at the connections. · Ensure that connecting parts (such as flange gaskets and bolts) are suitable for
connection and process media.
Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

39

Installing / mounting 4.1 Basic safety instructions

WARNING Exceeded maximum permissible operating pressure Danger of injury or poisoning. The maximum permissible operating pressure depends on the device version. The device can be damaged if the operating pressure is exceeded. Hot, toxic and corrosive process media could be released. · Make sure that the device is suitable for the maximum permissible operating pressure of
your system. Refer to the information on the nameplate and/or in "Technical data (Page 193)".
WARNING Exceeded maximum ambient or process media temperature Danger of explosion in hazardous areas. Device damage. · Make sure that the maximum permissible ambient and process media temperatures of
the device are not exceeded. Refer to the information in Chapter "Technical data (Page 193)".
WARNING Open cable inlet or incorrect cable gland Danger of explosion in hazardous areas. · Close the cable inlets for the electrical connections. Only use cable glands or plugs
which are approved for the relevant type of protection.
WARNING Incorrect conduit system Danger of explosion in hazardous areas as result of open cable inlet or incorrect conduit system. · In the case of a conduit system, mount a spark barrier at a defined distance from the
device input. Observe national regulations and the requirements stated in the relevant approvals.

See also

Technical data (Page 193)

SITRANS P DS III/P410 with PROFIBUS PA

40

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting 4.1 Basic safety instructions
WARNING Incorrect mounting at Zone 0 Danger of explosion in hazardous areas. · Ensure sufficient tightness at the process connection. · Observe the standard IEC/EN 60079-14.
WARNING Danger with "flameproof enclosure" protection Danger of explosion in hazardous areas. An explosion may be caused by hot gas escaping from the flameproof enclosure if there is too little space between it and the fixed parts. · Ensure that there is a space of at least 40 mm between the flameproof joint and the
fixed parts.
 Flameproof joint
WARNING Loss of explosion protection Danger of explosion in hazardous areas if the device is open or not properly closed. · Close the device as described in Chapter "PROFIBUS assembly guidelines (Page 66)".

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

41

Installing / mounting 4.1 Basic safety instructions
WARNING Use of incorrect device parts in potentially explosive environments Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection. If you do not adhere to these guidelines, the test certificates and the manufacturer warranty will become null and void. · Use only device parts that have been approved for the respective type of protection in
the potentially explosive environment. Covers that are not suited for the "explosionproof" type of protection are identified as such by a notice label attached to the inside of the cover with "Not Ex d Not SIL". · Do not swap device parts unless the manufacturer specifically ensures compatibility of these parts.
CAUTION Hot surfaces resulting from hot process media Danger of burns resulting from surface temperatures above 70 °C (155 °F). · Take appropriate protective measures, for example contact protection. · Make sure that protective measures do not cause the maximum permissible ambient
temperature to be exceeded. Refer to the information in Chapter "Technical data (Page 193)".
CAUTION External stresses and loads Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released. · Prevent severe external stresses and loads from acting on the device.

SITRANS P DS III/P410 with PROFIBUS PA

42

Operating Instructions, 02/2016, A5E00053276-08

4.1.1

Installing / mounting 4.1 Basic safety instructions
Installation location requirements
WARNING Insufficient air supply The device may overheat if there is an insufficient supply of air. · Install the device so that there is sufficient air supply in the room. · Observe the maximum permissible ambient temperature. Refer to the information in the
section "Technical data (Page 193)".
CAUTION Aggressive atmospheres Damage to device through penetration of aggressive vapors. · Ensure that the device is suitable for the application.
NOTICE Direct sunlight Increased measuring errors. · Protect the device from direct sunlight. Make sure that the maximum ambient temperature is not exceeded. Refer to the information in the section Technical data (Page 193).

4.1.2

Proper mounting
NOTICE Incorrect mounting The device can be damaged, destroyed, or its functionality impaired through improper mounting. · Before installing ensure there is no visible damage to the device. · Make sure that process connectors are clean, and suitable gaskets and glands are
used. · Mount the device using suitable tools. Refer to the information in Technical data
(Page 193) for installation torque requirements.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

43

Installing / mounting 4.2 Disassembly

CAUTION
Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate or in Chapter "Technical data (Page 193)" is no longer guaranteed. · Make sure that the device is securely closed.

See also

PROFIBUS assembly guidelines (Page 66)

4.2

Disassembly

4.2.1

Incorrect disassembly
WARNING Incorrect disassembly The following dangers may result through incorrect disassembly: - Injury through electric shock - Danger through emerging media when connected to the process - Danger of explosion in hazardous area In order to disassemble correctly, observe the following: · Before starting work, make sure that you have switched off all physical variables such
as pressure, temperature, electricity etc. or that they have a harmless value. · If the device contains dangerous media, it must be emptied prior to disassembly. Make
sure that no environmentally hazardous media are released. · Secure the remaining connections so that no damage can result if the process is started
unintentionally.

SITRANS P DS III/P410 with PROFIBUS PA

44

Operating Instructions, 02/2016, A5E00053276-08

4.3

Installation (except level)

Installing / mounting 4.3 Installation (except level)

4.3.1

Installation mounting (except for level)

Requirements
Note Compare the desired operating data with the data on the nameplate. Please also refer to the information on the remote seal if this is fitted.
Note Protect the pressure transmitter from: · Direct heat radiation · Rapid temperature fluctuations · Heavy contamination · Mechanical damage · Direct sunlight
Note The housing may only be opened for maintenance, local operation or to make electrical connections.
The installation location is to be as follows:  Easily accessible  As close as possible to the measuring point  Vibration-free  Within the permitted ambient temperature values

Installation configuration
The pressure transmitter may in principle be configured above or below the pressure tapping point. The recommended configuration depends on the medium.
Installation configuration for gases
Install the pressure transmitter above the pressure tapping point.
Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensate produced can drain in the main line and thereby avoid corruption of the measured values.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

45

Installing / mounting 4.3 Installation (except level)
Installation configuration for vapor and liquid Install the pressure transmitter below the pressure tapping point. Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the main line.

4.3.2

Installation (except level)
Note Damage to measuring cell When installing the process connection of the pressure transmitter, do not rotate the housing. Rotating the housing may damage the measuring cell. To avoid damage to the device, tighten the threaded nuts of the measuring cell using a wrench.

Procedure

Attach the pressure transmitter to the process connection with an appropriate tool.

4.3.3

Fastening

Fastening without the mounting bracket
You can fasten the pressure transmitter directly to the process connection.

Fastening with the mounting bracket
You can fasten the mounting bracket as follows:  On a wall or a mounting frame using two screws  On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket Fasten the pressure transmitter mounting bracket using the two screws provided.

SITRANS P DS III/P410 with PROFIBUS PA

46

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting 4.3 Installation (except level)

Image 4-1 Fastening the pressure transmitter on the mounting bracket

Image 4-2 An example of fastening the pressure transmitter on the mounting bracket in the case of differential pressure and horizontal differential pressure lines

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

47

Installing / mounting 4.4 "Level" installation

Image 4-3 An example of fastening on the mounting bracket in the case of differential pressure and vertical differential pressure lines

4.4

"Level" installation

4.4.1

Instructions for level installation

Requirements
Note Compare the desired operating data with the data on the nameplate. Please also refer to the information on the remote seal if this is fitted.

SITRANS P DS III/P410 with PROFIBUS PA

48

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting 4.4 "Level" installation
Note Protect the pressure transmitter from: · Direct thermal radiation · Rapid temperature fluctuations · Severe soiling · Mechanical damage · Direct sunlight
Note Select the height of the mounting flange such that the pressure transmitter is always mounted below the lowest fill height to be measured.
The installation location is to be as follows:  Easily accessible  The measuring point must be as close as possible  Vibration-free  Within the permitted ambient temperature values

4.4.2

Installation for level
Note Seals are required for the installation. The seals must be compatible with the medium to be measured. Seals are not included in the delivery.

Procedure

To install the pressure transmitter for level, proceed as follows:
1. Attach the seal to the container's mating flange.
Ensure that the seal is centrically positioned and that it does not restrict the movement of the flange's seal diaphragm in any way as otherwise the tightness of the process connection is not guaranteed.
2. Screw on the pressure transmitter's flange.
3. Observe the installation position.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

49

Installing / mounting 4.4 "Level" installation

4.4.3

Connection of the negative pressure line

Assembly on an open container
A line is not required when taking measurements in an open container since the negative chamber is connected with the atmosphere. Ensure that no dirt enters the open connection ports, for example by using connection screws with a 7MF4997-1CP bleed valve.
Formula: Start of scale value: pMA =  · g · hU Full-scale value: pME =  · g · hO

Measurement assembly on an open container

hU Lower filling level hO Upper filling level p Pressure

pMA pME 
g

Start of scale value Full-scale value Density of the measured medium in the container Acceleration due to gravity

SITRANS P DS III/P410 with PROFIBUS PA

50

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting 4.4 "Level" installation
Assembly on a closed container
When taking measurements in a closed container without or with little condensate formation, the negative pressure line is not filled. Lay the line in such a way that pockets of condensate do not form. Install a condensation container if required.
Formula: Start-of-scale value: pMA =  · g · hU Full-scale value: pME =  · g · hO

Measurement assembly on a closed container (no or little condensate separation)

hU Lower filling level hO Upper filling level p Pressure

pMA pME 
g

Start of scale value Full-scale value Density of the measured medium in the container Acceleration due to gravity

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

51

Installing / mounting 4.4 "Level" installation
When taking measurements in a closed container with strong condensate formation, you must fill the negative pressure line (mostly with the condensate of the measured medium) and install a condensate pot. You can cut off the device using the dual pneumatic block 7MF9001-2.
Formula: Start-of-scale value: pMA = g · (hU · - hV · ') Full-scale value: pMA = g · (hO · - hV · ')

Measurement assembly on a closed container (strong condensate formation)

hU Lower filling level hO Upper filling level hV Gland distance
p Pressure

pMA pME   '
g

Start of scale value
Full-scale value
Density of the measured medium in the container
Density of fluid in the negative pressure line corresponds to the prevailing temperature there
Acceleration due to gravity

The process connection on the negative side is a female thread 1/4-18 NPT or an oval flange. Lay the line for the negative pressure using a seamless steel tube 12 mm x 1.5 mm.

SITRANS P DS III/P410 with PROFIBUS PA

52

Operating Instructions, 02/2016, A5E00053276-08

4.5

"Remote seal" installation

Installing / mounting 4.5 "Remote seal" installation

4.5.1

Remote seal installation

General installation instructions
 Keep the measuring system in the factory packing until it is installed in order to protect it from mechanical damage.
 When removing from the factory packing and installing: ensure that damage to and mechanical deformations in the membrane are prevented.
 Never loosen the sealed filling screws on the remote seal and the measuring instrument.
 Do not cause damage to the remote separating membrane; scratches on the remote separating membrane, e.g. due to sharp-edged objects, are the main starting points for corrosion.
 Select suitable gaskets for sealing.
 Use a gasket having an adequately large inner diameter for flanging. Insert the gasket concentrically; contact with the membrane leads to deviations in measurements.
 When using gaskets made of soft materials or PTFE: follow the guidelines of the gasket manufacturer, especially regarding the tightening torque and setting cycles.
 At the time of installation, use suitable fastening components such as screws and nuts that are compliant with fitting and flange standards.
 Excessive tightening of screwed joints on the process connection may displace the zero point on the pressure transmitter.
Note Commissioning
If a shut-off valve exists, open the shut-off valve slowly when commissioning in order to avoid pressure surges.
Note Permissible ambient and operating temperatures
Install the pressure measuring device such that the permissible limits of ambient and measured medium temperatures are not overshot or undershot even with the consideration of the effect of convection and heat radiation. · Note the effect of temperature on the measuring accuracy. · When selecting the remote seals, ensure that fittings and flange components have
adequate pressure-temperature resistance by selecting suitable materials and pressure ratings. The pressure rating specified on the remote seal applies to reference conditions according to IEC 60770. · For the maximum permissible pressure at higher temperatures, please refer to the standard specified on the remote seal.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

53

Installing / mounting 4.5 "Remote seal" installation
Using remote seals with pressure measuring device for hazardous areas:
 When using remote seals with pressure measuring device for hazardous areas, the permissible limits of ambient temperatures for the pressure transmitter must not be exceeded. Hot surfaces on the cooling section (capillaries or cooling elements) are a possible source of ignition. Initiate suitable measures.
 When remote seals with a flame arrestor are used, the pressure measuring instrument determines the permissible ambient temperature. In the case of potentially explosive gaseous atmosphere, the temperature around the flame arrestor must not exceed +60 °C.

4.5.2 Notes

Installation of the remote seal with the capillary line
 Do not transport the measuring assembly (pressure transmitters, flange and capillary) using the capillary line.
 Do not bend capillary lines; risk of leakages and/or risk of considerable increase in the setting time of the measuring system.
 Owing to the risk of bending and breakages, pay attention to mechanical overloads at the joints such as capillary line-remote seal and capillary line-measuring device.
 Unwinding the excess capillary lines with a radius of at least 150 mm.  Fasten the capillary line such that there are no vibrations.  Permissible height differences:
­ When installing the pressure measuring device above the measuring point, keep the following in mind: In the case of remote seal measuring systems with silicon, glycerin or paraffin oil filling, the height difference of H1max. = 7 m must not be exceeded.
­ If halocarbon oil is used as a fill fluid, this maximum height difference is only H1max. = 4 m; see installation type A and installation type B.
If negative overpressure is observed during measurements, reduce the permissible height difference accordingly.

SITRANS P DS III/P410 with PROFIBUS PA

54

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting 4.5 "Remote seal" installation

Installation type for gauge pressure and level measurements (open containers)

Installation type A

Start of scale value: pMA = FL * g * HU + oil * g * H1
Full-scale value: pME = FL * g * HO + oil * g * H1

Pressure transmitter above the measuring point
Installation type B

Start of scale value: pMA = FL * g * HU - oil * g * H1
Full-scale value: pME = FL * g * HO - oil * g * H1

Pressure transmitter below the measuring point
H1  7 m (23 ft); with halocarbon oil as the filling liquid, only H1  4 m(13.1 ft)

Key

pMA

Start of scale value

pME

Full-scale value

FL

Density of the process medium in the container

oil

Density of the filling oil in the capillary line of the remote seal

g

Acceleration due to gravity

HU

Lower filling level

HO

Upper filling level

H1

Distance between the container flange and the pressure transmitter

For absolute pressure measurements (vacuum), install the measuring device at least at the height of the remote seal or below it (see installation types C).

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

55

Installing / mounting 4.5 "Remote seal" installation

Installation types for absolute pressure measurements (closed containers)

Installation type C1

Start of scale value: pMA = pstart + oil * g * H1
Full-scale value: pME = pend + oil * g * H1

Installation type C2

Pressure transmitter for absolute pressure always below the measuring point: H1  200 mm (7.9 inch)

Key

pMA

Start of scale value

pME

Full-scale value

pstart

Start of scale pressure

pend

Full scale pressure

oil

Density of the filling oil in the capillary line of the remote seal

g

Acceleration due to gravity

H1

Distance between the container flange and the pressure transmitter

SITRANS P DS III/P410 with PROFIBUS PA

56

Operating Instructions, 02/2016, A5E00053276-08

Installing / mounting 4.5 "Remote seal" installation

Note Effects of temperature
Keep the following instructions in mind in order to minimize keep the effects of temperature in remote seal measuring systems with the differential pressure measuring device:
Install the device such that the positive and negative sides are symmetrical as far as ambient effects, especially ambient temperatures, are concerned.

Installation type for differential pressure and flow rate measurements

Installation type D

Start of scale value: pMA = pstart - oil * g * HV
Full-scale value: pME = pend - oil * g * HV

Key

pMA

Start of scale value

pME

Full-scale value

pstart

Start of scale pressure

pend

Full scale pressure

oil

Density of the filling oil in the capillary line of the remote seal

g

Acceleration due to gravity

HV

Gland distance

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

57

Installing / mounting 4.5 "Remote seal" installation

Installation types for level measurements (closed containers)

Installation type E

Start of scale value: pMA = FL * g * HU - oil * g * HV
Full-scale value: pME = FL * g * HU - oil * g * HV

Key

pMA

Start of scale value

pME

Full-scale value

FL

Density of the process medium in the container

oil

Density of the filling oil in the capillary line of the remote seal

g

Acceleration due to gravity

HU

Lower filling level

HO

Upper filling level

HV

Gland distance

SITRANS P DS III/P410 with PROFIBUS PA

58

Operating Instructions, 02/2016, A5E00053276-08

Installation type G

Installing / mounting 4.5 "Remote seal" installation
H1  7 m (23 ft), for halocarbon oil, however only H1  4 m (13.1 ft) Start of scale value: pMA = FL * g * HU - oil * g * HV Full-scale value: pME = FL * g * HO - oil * g * HV

Pressure transmitter for differential pressure above the upper measuring point, no vacuum
Installation type H
Start of scale value: pMA = FL * g * HU - oil * g * HV Full-scale value: pME = FL * g * HO - oil * g * HV

Below the lower measuring point Installation type J

H2  7 m (23 ft); with halocarbon oil as the filling liquid, only H2  4 m(13.1 ft)
Start of scale value: pMA = FL * g * HU - oil * g * HV
Full-scale value: pME = FL * g * HO - oil * g * HV

Between the measuring points, no vacuum

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

59

Installing / mounting 4.6 Turing the measuring cell against housing

Key

pMA

Start of scale value

pME

Full-scale value

FL

Density of the process medium in the container

oil

Density of the filling oil in the capillary line of the remote seal

g

Acceleration due to gravity

HU

Lower filling level

HO

Upper filling level

HV

Gland distance

4.6

Turing the measuring cell against housing

Description

You can turn the measuring cell against the housing. Rotating the pressure transmitter facilitates its operation when it is installed at an angle, for example. The buttons and the current connection can thus also be operated for an external measuring device. The display also remains visible in enclosure covers with an inspection window.
Only limited turning is permissible! The turning range  is marked at the foot of the electronic housing. An orientation mark  is provided at the throat of the measuring cell.
This mark must remain in the marked section when turning.

 Turning range  Retaining screw  Orientation mark
Image 4-4 Example: Turning range of pressure transmitters for pressure and absolute pressure from the gauge pressure series
The turning range for pressure transmitters for differential pressure and flow rate, absolute pressure from the differential pressure series and level is identified in a similar manner.

SITRANS P DS III/P410 with PROFIBUS PA

60

Operating Instructions, 02/2016, A5E00053276-08

Procedure

Installing / mounting 4.7 Rotating the display
NOTICE Damage to the ribbon cable If the pressure transmitter enclosure is rotated against the measuring cell, this can damage the ribbon cable (sensor connection to the electronics).
· Comply with the specified range of rotation  as detailed.
1. Loosen the retaining screw  (Allen screw 2.5 mm).
2. Turn the electronic housing against the measuring cell. Follow the marked turning range
 while doing so.
3. Tighten the retaining screw (torque: 3.4 to 3.6 Nm).

4.7

Rotating the display

You can rotate the display in the electronics enclosure. This makes it easier to read the display if the device is not being operated in a vertical position.

Procedure

1. Unscrew the cover of the electrical cable compartment. See section Structure (Page 24). An identification text "FIELD TERMINAL" is provided at the side of the housing.
2. Unscrew the display. Depending on the application position of the pressure transmitter, you can reinstall it at four different positions. You can turn it by ±90° or ±180°.
3. Screw the covers back on as far as they will go.
4. Secure the covers with the cover catch.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

61

Installing / mounting 4.7 Rotating the display

SITRANS P DS III/P410 with PROFIBUS PA

62

Operating Instructions, 02/2016, A5E00053276-08

Connecting up

5

5.1

Basic safety instructions

WARNING
Unsuitable cables and/or cable glands
Danger of explosion in hazardous areas. · Only use suitable cables and cable glands complying with the requirements specified in
Chapter "Technical data (Page 193)". · Tighten the cable glands in accordance with the torques specified in Chapter "Technical
data (Page 193)". · When replacing cable glands use only cable glands of the same type. · After installation check that the cables are seated firmly.

5.1.1

Hazardous contact voltage in versions with 4-conductor extension
WARNING Hazardous contact voltage in versions with 4-conductor extension Danger of electrocution in case of incorrect connection. · Observe the instructions in the 4-conductor extension operating manual for the electrical
connection.
WARNING Improper power supply Danger of explosion in hazardous areas as result of incorrect power supply, e.g. using direct current instead of alternating current. · Connect the device in accordance with the specified power supply and signal circuits.
The relevant specifications can be found in the certificates, in Chapter "Technical data (Page 193)" or on the nameplate.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

63

Connecting up 5.1 Basic safety instructions
WARNING Unsafe extra-low voltage Danger of explosion in hazardous areas due to voltage flashover. · Connect the device to an extra-low voltage with safe isolation (SELV).
WARNING Lack of equipotential bonding Danger of explosion through compensating currents or ignition currents through lack of equipotential bonding. · Ensure that the device is potentially equalized. Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection "Intrinsic safety Ex i".
WARNING Unprotected cable ends Danger of explosion through unprotected cable ends in hazardous areas. · Protect unused cable ends in accordance with IEC/EN 60079-14.
WARNING Improper laying of shielded cables Danger of explosion through compensating currents between hazardous area and the nonhazardous area. · Only ground shielded cables that run into the hazardous area at one end. · If grounding is required at both ends, use an equipotential bonding conductor.
WARNING Connecting device in energized state Danger of explosion in hazardous areas. · Connect devices in hazardous areas only in a de-energized state. Exceptions: · Circuits of limited energy may also be connected in the energized state in hazardous
areas. · Exceptions for type of protection "Non-sparking nA" (Zone 2) are regulated in the
relevant certificate

SITRANS P DS III/P410 with PROFIBUS PA

64

Operating Instructions, 02/2016, A5E00053276-08

Connecting up 5.1 Basic safety instructions
WARNING Incorrect selection of type of protection Danger of explosion in areas subject to explosion hazard. This device is approved for several types of protection. 1. Decide in favor of one type of protection. 2. Connect the device in accordance with the selected type of protection. 3. In order to avoid incorrect use at a later point, make the types of protection that are not
used permanently unrecognizable on the nameplate.
NOTICE Ambient temperature too high Damage to cable sheath. · At an ambient temperature  60 °C (140 °F), use heat-resistant cables suitable for an
ambient temperature at least 20 °C (36 °F) higher.

5.1.2

Incorrect measured values with incorrect grounding
NOTICE Incorrect measured values with incorrect grounding The device must not be grounded via the "+" connection. It may otherwise malfunction and be permanently damaged. · If necessary, ground the device using the "-" connection.
Note Electromagnetic compatibility (EMC) You can use this device in industrial environments, households and small businesses. For metal housings there is an increased electromagnetic compatibility compared to highfrequency radiation. This protection can be increased by grounding the housing, see Chapter "PROFIBUS assembly guidelines (Page 66)".

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

65

Connecting up 5.2 Connecting the device

5.2

Connecting the device

5.2.1

PROFIBUS assembly guidelines
Further information on PROFIBUS and PROFINET can be found on the Internet "PI PROFIBUS - PROFINET (http://www.profibus.com/home/)" > DOWNLOADS under "Installation guidelines".

Opening the device
1. Use a 3 mm Allen key to loosen the cover (if present).
2. Unscrew the cover of the electrical cable compartment. An identification text "FIELD TERMINALS" is provided at the side of the housing.

Procedure

1. Insert the connecting cable through the cable gland . 2. Connect the device to the plant with the protective conductor connection .

SITRANS P DS III/P410 with PROFIBUS PA

66

Operating Instructions, 02/2016, A5E00053276-08

Connecting up 5.2 Connecting the device
3. Connect the wires to the terminals "+" and "-" .
The device is not polarity sensitive.
4. If necessary, ground the shield to the screw of the ground terminal . The ground
terminal is electrically connected to the external protective conductor connection.

 PROFIBUS PA/FOUNDATIONTM Fieldbus FF  Cable entry  Connecting terminals  Safety catch  Protective conductor connector/equipotential bonding terminal  Process connection  Grounding terminal
Image 5-1 Electrical connection, power supply

Closing the device 1. Screw the covers  back on as far as they will go. 2. Secure each cover with the cover catch . 3. Close the key cover .

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

67

Connecting up 5.3 Connecting the M12 connector
4. Tighten the screws in the key cover.
5. Check the tightness of the blanking plugs  and cable gland  in accordance with the
degree of protection.



Key cover



Cable gland



Safety catch (back)



Cover (rear) for electrical terminal compartment



Blanking plug



Safety catch (front)



Cover (front), optionally with inspection window



Safety catch for stainless steel enclosure

Image 5-2 View of the pressure transmitter: Left: Back right: Front view

See also

Structure (Page 24)

5.3

Connecting the M12 connector

Procedure

CAUTION A conductive connection must not exist between the shield and the connector housing.
WARNING The connector may only be used for Ex ia devices and non-Ex devices; otherwise the safety required for the approval is not guaranteed.

SITRANS P DS III/P410 with PROFIBUS PA

68

Operating Instructions, 02/2016, A5E00053276-08

Connecting up 5.3 Connecting the M12 connector
Note Observe the protection class of the M12 connector when defining the protection class.
For devices in which a connector is already available on the housing, the connection is established using a cable jack. 1. Thread the parts of the cable jack as described by the connector manufacturer.
2. Strip approximately 18 mm of the bus cable .
3. Twist the shield. 4. Thread the shield in the insulating sleeve.
5. Draw 8 mm of shrink sleeve over the cable, wires and shield up to the reference edge .
6. Screw the cable ends and the shield in the pin insert. 7. Fix the parts of the cable jack as described by the connector manufacturer.

Image 5-3 Preparing the connecting cable

 Reference edge for stripping

 Insulating sleeve over the shield

 Reference edge for the dimension  Shrink sleeve
specifications for cable assembly

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

69

Connecting up 5.3 Connecting the M12 connector
Pin assignment

Layout for M12 connector



M12 x 1 thread



Positioning catch

1

+

2

Not connected

3

-

4

Shield

Layout for M12 jack



Positioning slot

1

+

2

Not connected

3

-

4

Shield

Middle jack contact not connected

SITRANS P DS III/P410 with PROFIBUS PA

70

Operating Instructions, 02/2016, A5E00053276-08

Operation

6

6.1

Overview of operation

Introduction

The following description provides an overview of the operating functions which can be executed with the pressure transmitter and the safety information which is to be observed when doing so. You can operate the pressure transmitter locally and over PROFIBUS. Local operation will be described first, and then the operating functions over PROFIBUS.

Chapter contents:
 Basic safety instructions (Page 72)  Information on operation (Page 72)  Display (Page 73)  Local operation (Page 76)

Overview of operating functions
You can operate the basic settings of the pressure transmitter using the buttons on the device. The entire range of settings can be operated via PROFIBUS.
The following table describes the basic operating functions offered by a device with display.

Table 6- 1 Operating functions
Function Electrical damping Zero point calibration (position correction) Key lock and write protection Measured value display Unit Bus address Device mode Decimal point Zero point drift LO calibration HI calibration Customized characteristic curve Diagnostics function Measurement type

With buttons Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No

Over PROFIBUS Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

71

Operation 6.2 Basic safety instructions
Further operating functions are accessible via PROFIBUS for special applications.

6.2

Basic safety instructions

Note Incorrect reproduction of the process pressure
If you have changed the basic functions of the pressure transmitter, the display and the measurement output could be set such that the actual process pressure is not reproduced.
Therefore, check the basic parameters before commissioning.

6.3

Information on operation

The following rules apply to operation of the pressure transmitter:
 The device always increments numerical values in steps from the displayed digit of least significance.
If you press the button longer, it increments the next displayed digit of higher significance. This procedure can be used for fast coarse setting over a wide numerical range. For the fine adjustment, release the [] or [] button again. Then press the button again.

Violations of the measured value limits are output on the display by or .

 If you wish to operate the device using the buttons, the lock must be canceled.
 If you are operating the pressure transmitter locally, write operations over PROFIBUS are rejected during this time.
It is possible to read data at any time, e.g. measured values.

Note
If you allow more than 2 minutes to pass following the pressing of a button, the setting is saved and the measured-value display is returned to automatically.
The operating instructions in the section "Local operation (Page 76)" apply if the device has been delivered with a dummy cover.

SITRANS P DS III/P410 with PROFIBUS PA

72

Operating Instructions, 02/2016, A5E00053276-08

6.4

Display

6.4.1

Display elements

Structure

Operation 6.4 Display

Description

 Measured value  Unit/bar graph  Root display  Mode/button lock
Image 6-1 Display layout

 Violation of lower limit  Symbol for measured value  Violation of higher limit  Communication display

The display is used for the local display of the measured value  with:  Unit   Mode   Sign   Statuses  and  The display  outputs the measured value in a physical unit  which can be selected by
the customer.
The Violation of lower limit  and Violation of upper limit  displays are also referred to as
status since they have meanings dependent on the settings.
If the communication display  blinks, this indicates an active communication.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

73

Operation 6.4 Display

6.4.2

Units display

Description

The unit display comprises five 14-segment fields for representing the unit as a percentage value or physical unit. A bar graph showing the percentage measured value range from 0 to 100% can be displayed as an alternative to the unit. The bar graph function is disabled by default.

Display

Image 6-2 Examples of measured-value display and bar graph The following messages may appear as a ticker in the bottom line of the display.

Table 6- 2 Message as ticker Ticker "DIAGNOSTIC WARNING"
"SIMULATION"

Meaning Is always displayed if:
· An event configured by the user is to be signaled with a warning. For example: ­ Limit reached ­ Event counter for limit values exceeded ­ Calibration time expired
· The status of one of the device variables is "UNCERTAIN".
Is always displayed when the simulation of a pressure value or temperature value is active.

6.4.3

Error display

Description

If hardware faults, software errors or diagnostic interrupts occur in the pressure transmitter, the message "Error" appears in the measured value display.
A status code indicating the type of error appears in the bottom line of the display. This diagnostic information is also available via PROFIBUS.

SITRANS P DS III/P410 with PROFIBUS PA

74

Operating Instructions, 02/2016, A5E00053276-08

Display

Operation 6.4 Display
Error messages are displayed for about 10 seconds after the occurrence of the error.

See also

Image 6-3 Example of error message Overview of status codes (Page 189)

6.4.4

Mode display

Description

The selected active mode is shown in the mode display.

Display

Image 6-4 Example for mode display In the example, a damping of 0.2 seconds was set in mode 4.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

75

Operation 6.5 Local operation

6.4.5

Status display

Description

The arrows of the status display have a different meaning depending on the mode setting. The table below shows the meanings of the arrows in the respective functions.

Meaning

Table 6- 3 Meaning of the arrow displays

Function Measured value display
Adjusting damping
LO calibration HI calibration Alarm Warning

Mode
4 19 20

Display Pressure exceeds the upper sensor limit. Exceeds the upper damping value ­ Calibration span too high Upper alarm limit reached Upper warning limit reached

Display Pressure falls below the lower sensor limit. Falls below the lower damping value Calibration span too low ­ Lower alarm limit reached Lower warning limit reached

See also

Overview of status codes (Page 189)

6.5

Local operation

6.5.1

Control elements for local operation

Introduction

The pressure transmitter can be operated on-site using the keys. You can select and execute the functions described in the table using adjustable modes. Operation by buttons is not available for devices without display.

SITRANS P DS III/P410 with PROFIBUS PA

76

Operating Instructions, 02/2016, A5E00053276-08

Control elements

Operation 6.5 Local operation



Display



Connecting plug for the display



Button symbols (see cap)

Image 6-5 Position of keys and display

 Mode key  Increment button  Decrement button

Operating functions
Note Zero point calibration For absolute pressure transmitters, the start of scale value is at vacuum. A zero-point calibration with pressure transmitters which do not measure absolute pressure leads to faulty settings.
Note Locking of buttons and functions Local operation is possible if you are in measuring mode and neither "L", "LA" nor "LL" is output in the mode display. If operations are disabled, parameters can still be read. An error message is output if you try to change parameters.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

77

Operation 6.5 Local operation

Table 6- 4 Operating functions using buttons

Function

Mode

Button function

Display, explanations

Measured value
Error display Electrical damping Zero point calibration (position correction)
Locking of buttons and functions
Measured value display Unit
Bus address Operating mode of device, see also Device operation type (Page 88)

[M] Here you can select the modes. 4 71)
10
13 14
15 16

[]

[]

[] and []

The current measured value is displayed as you have set it in the function "Measuredvalue display, mode 13".

Error A fault exists.

Increase De-

Set to 0

damping creased

damping

Time constant T63 in seconds Range of adjustment: 0.0 s to 100.0 s

Increase Decrease Apply

correction correc-

value

tion value

Pressurize the pressure transmitter for gauge pressure, differential pressure, flow rate or level.
Evacuate pressure transmitter for absolute pressure (< 0.1  of the measuring span).
Measured value in pressure unit

Change

Cancel 5 s *) L

Locking of buttons and functions (hardware write protection); local operation disabled

LC

Write blocking; local operation pos-

sible

LA

Enabling of local operation

LL

Combination of write blocking and

no enabling of local operation

*) Does not apply to "Safe (PROFIsafe) mode". In this case, refer to the information in section "PROFIsafe (Page 141)".

Select from various ­ possibilities.

Selection of various variables

Select from table for measured value display.

First value in each case from the physical unit table

Physical unit

Increase Decrease

Node address on the PROFIBUS Value between 0 and 126

Change

Selection of operating mode of device

· Profile-compatible 1 AI

· Profile-compatible with extensions

· Old SITRANS P/PA device

· Profile-compatible 1 AI, 1 TOT

Decimal point

17

Zero point adjustment 18

LO calibration

19

HI calibration

20

To left To right

Increase value
Increase value

Decrease Apply value
Decrease Apply value

Position of decimal point in display Display of current measuring range Calibrate bottom point of characteristic
Calibrate top point of characteristic

SITRANS P DS III/P410 with PROFIBUS PA

78

Operating Instructions, 02/2016, A5E00053276-08

Operation 6.5 Local operation
1) Mode 7 is not available with transmitter for absolute pressure. Please note the information in the sections "" and "".LO calibration (Page 91)HI calibration (Page 92)

6.5.2

Operation using buttons

Introduction

This overview informs you about the most important safety notes to be observed when operating the pressure transmitter. Furthermore, the overview guides you in adjusting the operating functions on site.

Requirement

The keyboard must have been unlocked in order to operate the device using the buttons.

Procedure

In the default setting, the device is in the measured value display. To adjust the operating functions, proceed as follows: 1. Loosen both the screws of the keyboard cover and lift it upwards. 2. Press the [M] button until the desired mode is displayed. 3. Keep pressing the [] or [] button until the desired value is displayed. 4. Press the [M] button.
Now you have saved the values and the device goes to the next mode. 5. Close the keyboard cover using the two screws.
Note If you allow more than 2 minutes to pass after pressing a button, the setting is saved and the measured value display is returned to automatically.

6.5.3

Setting/adjusting electrical damping

Difference between setting and adjusting
You can set or adjust the time constant of electrical damping using the buttons. Setting means that the time constant is automatically set to 0 seconds. Adjusting means that the time constant is adjusted between 0 and 100 seconds using the increments of 0.1 seconds. This electrical damping also has an effect on the built-in basic damping of the device.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

79

Operation 6.5 Local operation

Condition for "setting"
You are familiar with the correct operation of the pressure transmitter and the associated safety information.

Setting electrical damping
To set electrical damping to 0 seconds, proceed as follows: 1. Set mode 4. 2. Press the [] and [] buttons simultaneously. 3. Save with the [M] button.

Result

Electrical damping has been set to 0 seconds.

Condition for "adjusting"
The default adjusting of steps is an interval of 0.1 seconds. If you press the [] or [] button for a long time, the steps are increased.

Adjusting electrical damping
To adjust electrical damping, proceed as follows: 1. Set mode 4. 2. Adjust the desired damping. 3. Save with the [M] button.

Result

Electrical damping has been set to the desired time constant.

See also

Operation using buttons (Page 79) Electrical damping (filter time constant) (Page 116)

6.5.4

Calibrate zero point

Introduction

A zero point calibration is used to correct zero errors resulting from the mounting position of the transmitter. You must proceed differently depending on the device version.

SITRANS P DS III/P410 with PROFIBUS PA

80

Operating Instructions, 02/2016, A5E00053276-08

Operation 6.5 Local operation

Requirement

You are familiar with the correct operation of the pressure transmitter and the associated safety information.

Zero point calibration for gauge pressure transmitter
To calibrate the zero point, proceed as follows: 1. Pressurize the pressure transmitter. 2. Set mode 7. 3. Press the [] und [] buttons simultaneously for 2 seconds. 4. Save with the [M] button.
Note Zero point calibration for absolute pressure transmitter Mode 7 is not available with transmitter for absolute pressure. Please note the information in the sections "Balance LO (Page 91)" and "HI calibration (Page 92)".

6.5.5

Locking of buttons and functions

Introduction

In mode 10 you can lock the functions which are always possible using the buttons. An example of locking is the saving of stored parameter settings.

Requirement

Note Check the measured value display to establish that this indicates the desired setting.

Activation of locking of buttons and functions
To lock the buttons, proceed as follows: 1. Set mode 10. 2. Activate the locking of buttons and functions. 3. Save with the [M] button. "L" is output in the mode display.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

81

Operation 6.5 Local operation

Deactivate the locking of buttons and functions
To unlock the buttons, proceed as follows: 1. Set mode 10. 2. Press the [] und [] buttons simultaneously for 5 seconds. Locking of the buttons and functions is now deactivated. "- -" is output in the mode display.

See also

Key lock and write protection (Page 116)

6.5.6

Measured value display

Introduction

In mode 13, select a variable which represents the source of the measured value display. The variable is based on the measurement type set at the factory or over the bus. The measurement type cannot be set locally.
The measurement type options available can be set in SIMATIC PDM using the "transmitter type" parameter. Find the following values under this parameter:
 Pressure
 Flow, not relevant for relative and absolute pressure
 Level
 Volume

Procedure

To select the source for the measured value display, proceed as follows: 1. Set mode 13. 2. Select the variable. 3. Save with the [M] button.

SITRANS P DS III/P410 with PROFIBUS PA

82

Operating Instructions, 02/2016, A5E00053276-08

Parameter

Operation 6.5 Local operation

The following tables give the meaning of the variables, depending on the value of the "transmitter type" parameter. This allows you to select the units available in mode 14.

Table 6- 5 Measurement type "Absolute pressure", "Differential pressure" and "Pressure"

Source of measured value display From analog input function block: [0] : Output :
From pressure transducer block: [1] : Secondary variable 1 [2] : Measurement value (primary variable) [3] : Sensor temperature [4] : Electronics temperature [7] : Raw pressure value

Variable Available unit

OUT

(P)

Pressure

(U)

User specific

SEC 1 PRIM

(P)

Pressure

(P)

Pressure

TMP S

(T)

Temperature

TMP E

(T)

Temperature

SENS

(P)

Pressure

Table 6- 6 Measurement type "Flow"

Source of measured value display Variable Available unit

From analog input function block:

[0] : Output

OUT

(L)

Level

(U)

User specific

From pressure transducer block:

[1] : Secondary variable 1

SEC 1

(P)

Pressure

[2] : Measurement value (primary variable)

PRIM

(L)

Level

[3] : Sensor temperature

TMP S

(T)

Temperature

[4] : Electronics temperature

TMP E

(T)

Temperature

[5] : Secondary variable 3:

SEC 3

(M)

Mass flow

[7] : Raw pressure value

SENS

(P)

Pressure

From totalizer function block:

[6] : Totalizer output

TOTAL

(V)

Volume

(M) *) Total mass flow

Flow not relevant for relative and absolute pressure

*) The option of selecting the physical unit is additionally determined by the channel setting (mass or volume) of the analog input and totalizer function blocks.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

83

Operation 6.5 Local operation

Table 6- 7 Measurement type "Level (height)"

Source of measured value display From analog input function block: [0] : Output

Variable OUT

From pressure transducer block: [1] : Secondary variable 1 [2] : Measurement value (primary variable) [3] : Sensor temperature [4] : Electronics temperature

SEC 1 PRIM
TMP S TMP E

Available units

(L)

Level

(U)

User specific

(P)

Pressure

(L)

Level

(T)

Temperature

(T)

Temperature

See also

Table 6- 8 Measurement type "Level (volume)"

Source of measured value display From analog input function block: [0] : Output
From pressure transducer block: [1] : Secondary variable 1 [2] : Measurement value (primary variable) [3] : Sensor temperature [4] : Electronics temperature

Variable Available units

OUT

(V)

Volume

(U)

User specific

SEC 1 PRIM

(P)

Pressure

(V)

Volume

TMP S

(T)

Temperature

TMP E

(T)

Temperature

Block model for collection and processing of measured values (Page 95) Pressure transducer block (transducer block 1) (Page 98)

6.5.7

Unit

Introduction

In mode 14, set the physical unit in which the device's measured value display should be represented.

Requirement

You have already selected the desired source for the measured value display in mode 13.

SITRANS P DS III/P410 with PROFIBUS PA

84

Operating Instructions, 02/2016, A5E00053276-08

Procedure Units

Operation 6.5 Local operation
To adjust the physical unit, proceed as follows: 1. Set mode 14.
The physical unit used appears in the bottom line of the display. 2. Select a unit. 3. Save with the [M] button. The following tables show the physical units available in each measurement type.

Table 6- 9 Unit for pressure (P)

Unit Pa MPa kPa hPa bar mbar torr atm psi

Display Pa MPa KPa hPa bar mbar Torr ATM PSI

Unit g/cm² kg/cm² inH2O inH2O(4°C) mmH2O mmH2O(4°C) ftH2O inHg mmHg

Display G/cm2 KGcm2 INH2O INH2O mmH2O mmH2O FTH2O IN HG mm HG

Table 6- 10 Unit for volume (V)

Unit m3 dm3 cm3 mm3 l cl ml hl in3

Display m3 dm3 cm3 mm3 L cL mL hL IN3

Unit ft3 yd3 pint (US) quart (US) US gallon imp. gallon bushel barrel barrel liquid

Display FT3 Yd3 Pint Quart GAL ImGAL BUSHL bbl bblli

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

85

Operation 6.5 Local operation

Table 6- 11 Unit for volume flow (F)

Unit m3 / second m3 / minute m3 / hour m3 / day Liters / second Liters / minute Liters / hour

Display m3/S m3/M m3/H m3/D L/S L/M L/H

Liters / day

L/D

Millions of liters / day ml/D

ft3 / second

FT3/S

ft3 / minute

FT3/M

Table 6- 12 Unit for mass flow (M)

Unit g / s g / min g / h g / d Kg / s Kg / min Kg / h Kg / d T / s T / min T / h T / d

Display G/S G/MIN G/H G/D KG/S KG/M KG/H KG/D T/S T/M T/H T/D

Table 6- 13 Unit for level (L)

Unit

Display

m

m

cm

cm

mm

mm

Unit ft3 / hour ft3 / day Gallons / second Gallons / minute Gallons / hour Gallons / day British barrel liquid / second British barrel liquid / minute British barrel liquid / hour British barrel liquid / day

Display FT3/H FT3/D Gal/S Gal/M Gal/H Gal/D bbl/S
bbl/M
bbl/H
bbl/D

Unit Pound / s Pound / min Pound / h Pound / d Short tons / s Short tons / min Short tons / h Short tons / d Long tons / s Long tons / m Long tons / h Long tons / d

Display P/S lb/M lb/H lb/D ST/S ST/m ST/h ST/d LT/s LT/m LT/h LT/d

Unit

Display

ft

FT

in

IN

yd

Yd

SITRANS P DS III/P410 with PROFIBUS PA

86

Operating Instructions, 02/2016, A5E00053276-08

Table 6- 14 Unit for mass (M)

Unit

Display

kg

KG

g

G

t

T

oz

oz

Unit lb STon LTon

Operation 6.5 Local operation
Display lb STon LTon

Table 6- 15 Unit for temperature (T)

Unit

Display

Unit

K

K

°F

°C

°C

°R

Display °F °R

Table 6- 16 Unit for user-specific (U)

Unit arbitrary
%

Display Max. 16 characters, If more than 5 characters, the display shows the unit as a ticker. The input of the characters to be displayed can only be performed through the PROFIBUS. %

Note
The profile allows a much larger number of possible units. There is no limitation on some physical values special to the output of the analog input function block. For instance, if you have selected a unit with SIMATIC PDM which does not appear in the corresponding valid list, the current measurement value will be shown without a unit in the measured value display.

See also

Units of the pressure transducer block (Page 102)

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

87

Operation 6.5 Local operation

6.5.8

Bus address

Introduction

The node address of the device on the PROFIBUS, the so-called bus address, is set in mode 15. The permissible range runs from 0 to 126.
Note Do not change the bus address of the device while your system is running. The device will then no longer be visible from the application program.

Procedure

To change the bus address, proceed as follows: 1. Set mode 15.
The currently set bus address of the device appears in the measured value display. 2. Select the bus address within the permissible range. 3. Save with the [M] button.

6.5.9

Device operation type

Introduction

Set the device mode to mode 16.
The device mode [1] is preset on the pressure transmitter. Other device modes are only suitable if you have set another operation type through PROFIBUS.

Table 6- 17 Device mode

Display [0]
[1]

Meaning Profile-compliant: Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0, with analog input function block, without totalizer Delivery state Profile-compatible with extensions: Full functionality of the SITRANS P with:
· Analog input function block · Totalizer

SITRANS P DS III/P410 with PROFIBUS PA

88

Operating Instructions, 02/2016, A5E00053276-08

Operation 6.5 Local operation

Display [2] [128]

Meaning Exchangeable for previous SITRANS P/PA device Profile-compliant: Exchangeable for pressure transmitter with PROFIBUS PA Profile 3.0 with: · Analog input function block · Totalizer.

Procedure

To change the device mode, proceed as follows: 1. Set mode 16.
The current operation type "0", "1", "2" or "128" appears in the measured value display. 2. Select the device mode.
The local operation type must match the operation type in PROFIBUS. 3. Save with the [M] button.
Note Each device operation type is assigned a particular device master data file (GSD file). If the configuration of your PROFIBUS-PA strand does not correspond to the device mode selected, the device will not start periodic data exchange. Successful establishment of communication is identified by the indicator "o" at the top left of the display.
Note If the device is exchanging period data, no change is possible to the device operating type.

See also

Table 6- 18 Device master data file

Display [0] [1] [2] [128]

File name pa_29700.gsd or pa_39700.gsd siem80A6.gsd sip1804B.gsd pa_29740.gsd or pa_39740.gsd

Errors (Page 192)

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

89

Operation 6.5 Local operation

6.5.10

Position of the decimal point

Introduction

Set the position of the decimal point in mode 17. The device can display measured values with up to four decimal places.

Procedure

To move the decimal point, proceed as follows: 1. Set mode 17.
A mask appears in the display showing the current position of the decimal point. 2. Select the desired display format.
8.8888 88.888 888.88 8888.8 88888 3. Save with the [M] button.
Note If you set the decimal point too far to the right, the resolution of the display may be too low. The display may show e.g. "0" instead of "0.43". If you set the decimal point too far to the left, it can overflow. The display will then show the character sequence 9.9.9.9.9 and error code F_004 instead of the measured value.

See also

Errors (Page 192)

6.5.11

Display of the zero-point adjustment

Introduction

The zero-point adjustment is shown in mode 18. The zero point adjustment is carried out by the zero point calibration in mode 7 or by the calibration procedure in modes 19 and 20.

SITRANS P DS III/P410 with PROFIBUS PA

90

Operating Instructions, 02/2016, A5E00053276-08

Procedure

To display the current zero-point adjustment, proceed as follows: 1. Set mode 18.
The current zero offset appears in the display. 2. Close with the [M] button.

Operation 6.5 Local operation

6.5.12

LO calibration

Introduction

The slope of the characteristic is changed in mode 19. This rotates the characteristic around setting point HI.
This function replaces the zero-point calibration (mode 7) which is not permitted for absolute pressure transmitters.
The unit in which you want to calibrate is set using the following functions:
 In mode 13, set the source of the measured value display[7] : Raw pressure value, variable SENS.
 In mode 14, select the desired pressure unit.
Note
If you change this setting, the measurement range can be restricted to the point that the permissible sensor limits are violated even with small pressure changes.

Procedure

To calibrate LO, proceed as follows: 1. Set mode 19.
The display shows the value of the last calibration procedure, with the appropriate unit. 2. Create the reference pressure. 3. Press the [] or [] button.
The measured value display switches to the current pressure value. Using the [] and [] keys, you can enter the reference value starting from there. 4. Press the [] und [] buttons simultaneously for 2 seconds. 5. Save with the [M] button.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

91

Operation 6.5 Local operation

Note
In the case of transmitters for absolute pressure, note the following information: · You need a thruster to apply the reference pressure. · The value of the reference pressure can be changed by only about 10%.

Result

If the calibration was successful, the current measurement value of the device will be displayed, and will correspond to the calibration value as long as the reference pressure is still applied.
If you switch to the measured value display without taking a sufficiently large calibration span into account, the pressure status "Bad" B_004 will be displayed.
The failure logic of the function block is activated. The output has the status "Unsure" U_0xx, depending on the setting.
If the two trim points are too close together, status F_006 is displayed. The smallest calibration span depends on the nominal measurement range. Select either the higher reference pressure in mode 20, or the lower reference pressure in mode 19.
As long as mode 19 is active, you can repeat this procedure as often as necessary.

View LO calibration
To view the LO calibration, proceed as follows: 1. Set mode 19.
The display shows the value of the last calibration procedure, with the appropriate unit. 2. Leave the mode by pressing [M].

See also

Errors (Page 192) Calibrating the sensor (Page 125)

6.5.13

HI calibration

Introduction

The slope of the characteristic is changed in mode 20. This rotates the characteristic around setting point LO.

SITRANS P DS III/P410 with PROFIBUS PA

92

Operating Instructions, 02/2016, A5E00053276-08

Operation 6.5 Local operation
The unit in which you want to calibrate is set using the following functions:  In mode 13, set the source of the measured value display[7] : Raw pressure value,
variable SENS.  In mode 14, select the desired pressure unit.
Note If you change this setting, the measurement range can be restricted to the point that the permissible sensor limits are violated even with small pressure changes.

Procedure

To calibrate HI, proceed as follows: 1. Set mode 20.
The display shows the value of the last calibration procedure, with the appropriate unit. 2. Create the reference pressure. 3. Press the [] or [] button.
The measured value display switches to the current pressure value. Using the [] and [] keys, you can enter the reference value starting from there. 4. Press the [] und [] buttons simultaneously for 2 seconds. 5. Save with the [M] button.
Note In the case of transmitters for absolute pressure, note the following information: · You need a thruster to apply the reference pressure. · The value of the reference pressure can be changed by only about 10%.

Result

If the calibration was successful, the current measurement value of the device will be displayed, and will correspond to the calibration value as long as the reference pressure is still applied.
If you switch to the measured value display without taking a sufficiently large calibration span into account, the pressure status "Bad" B_004 will be displayed.
The failure logic of the function block is activated. The output has the status "Unsure" U_0xx, depending on the setting.
If the two trim points are too close together, status F_006 is displayed. The smallest calibration span depends on the nominal measurement range. Select either the higher reference pressure in mode 20, or the lower reference pressure in mode 19.
As long as mode 20 is active, you can repeat this procedure as often as necessary.

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

93

Operation 6.5 Local operation

Viewing the HI calibration
To view the HI calibration, proceed as follows: 1. Set mode 20.
The display shows the value of the last calibration procedure, with the appropriate unit. 2. Leave the mode by pressing [M].

See also

Errors (Page 192) Calibrating the sensor (Page 125)

SITRANS P DS III/P410 with PROFIBUS PA

94

Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS

7

7.1

Communications structure for PROFIBUS PA

7.1.1

Overview
This chapter describes the processing method of the device-specific function blocks using a graphical block model which is resolved into its individual layers step by step. Knowledge of the physical block is assumed: This block is therefore not explained in this chapter.

7.1.2

Block model for collection and processing of measured values
The device functions are subdivided into blocks of different task areas. They can be parameterized during asynchronous data transmission.

p

Pressure

T

Temperature

S

Sensor

Image 7-1 Block circuit diagram of collection and processing of measured values

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

95

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

Pressure transducer block
The transducer block for pressure handles the adaptation to the pressure sensor. Its output value is the linearized and temperature-compensated measurement result. When measuring levels and flow, the necessary recalculation of the measurement value is performed in the pressure transducer block. The output value is the linearized and temperature-compensated measurement result.
The pressure transducer block also processes the temperature measurement of the pressure sensor and monitors the pressure and temperature limits.

Example

In hydrostatic level measurement, the pressure transducer block converts the incoming pressure value into height or volume.

Electronics temperature transducer block
The electronics temperature transducer block executes the required temperature measurement functions and monitors the permissible temperature limits.

Analog input function block
The analog input function block further processes the selected measurement value and passes it on to the automation task.

Example

For a container full of water, you measure the volume. The analog input function block calculates the container volume [m3] in a user-specific volume unit [bottles]. The output of this block gives the measured value and the corresponding status on the PROFIBUS.

Totalizer function block
The totalizer function block totals the volumes or mass that flowed during flow measurement. Its function is very similar to that of a water meter.
The output of this block forwards the totalized values and the corresponding status information via PROFIBUS.

Local operation and display
The display shows the desired measured value with its physical unit. You can select different functions for local operation.

SITRANS P DS III/P410 with PROFIBUS PA

96

Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

Connection between blocks via parameters
The output values of the transducer blocks for pressure and electronics temperature can be fed to the analog input and totalizer function blocks as input values for further processing. To do this, the parameter "Channel" must be correctly set in each function block.

Table 7- 1 Connection between blocks

Transducer block Pressure
Electronics temperature

Output value (Parameters) Temperature Secondary variable 1 Secondary variable 2 Measurement value (primary variable) Secondary variable 3 Electronics temperature

Usable in the analog input function block X X X X
X X

Usable in the totalizer function block
X X

Parameters for measured value display
The values of the following parameters from the measurement and function blocks can be shown on the display. The parameter "Source for display" must be set appropriately.

Table 7- 2 Visualization on the display

Block

Parameter

Pressure transducer block

Temperature

Secondary variable 1

Secondary variable 2

Measurement value (primary variable)

Secondary variable 3

Raw pressure value

Electronics temperature transducer block Electronics temperature

Analog input function block

Output

Totalizer function block

Totalizer output

Can be shown on the display X X
X
X X X X X

See also

Measured value display (Page 82) Cyclical data transfer (Page 165) Acyclic data transfer (Page 170)

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

97

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

7.1.3

Pressure transducer block

7.1.3.1

Pressure transducer block (transducer block 1)
The following figure shows the signal flow of measurement values from the sensor cell through the pressure transducer block into the appropriate output values, e.g. temperature, measurement value (primary variable), etc. The parameters of the individual functions, e.g. measurement range, output range, etc. can be changed using acyclic access.

p

Pressure

S

Sensor

T

Temperature

SEC 1 SEC 2 PRIM SEC 3

Image 7-2 Function groups of the pressure transducer block

Secondary variable 1 Secondary variable 2 Primary variable Secondary variable 3

SITRANS P DS III/P410 with PROFIBUS PA

98

Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

Functional principle
The raw pressure value first passes through a calibration. The resulting cleaned-up pressure value is checked for sensor limits. Any violation of the limits results in status "Bad" and a diagnostic error of "error collecting measured value". The cleaned-up pressure value is stored in SEC 1.
Then, it is subjected to a normalization, where the input signal is expressed in the range 0 to 10 (percentage/100). The normalized pressure value is stored in SEC 2.
Afterwards, depending on the measurement task, it is fed through one of four different linearization types. Scaling uses the preset working range (minimum and maximum values) to determine the normalized and linearized measured value (pressure, height, or volume) of the actual process variable. This is stored in PRIM.
By means of a multiplication with the density the volume is used to compute the mass. This is stored in SEC 3.
The temperature value of the pressure sensor is available in the "temperature" parameter.

See also

Acyclic data transfer (Page 170)

SITRANS P DS III/P410 with PROFIBUS PA

Operating Instructions, 02/2016, A5E00053276-08

99

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

7.1.3.2

Linearization type function group
The normalized pressure is fed through the linearization algorithms for adjustment to the various process requirements, as shown in the following figure. The algorithm is switched using the "Characteristic curve type" parameter.

0

Linear

10 Root

1

User-defined "table"

240 Root/table

Image 7-3 Linearization type function group

Table 7- 3 Available linearization functions

Measurement task Linearization symbol

Pressure meas- urement

Level: Height

-

Level: Volume

Characteristic curve type
Linear

Description No linearization

Linear

No linearization

User de- Linearization of container characterisfined (table) tics.

The relationship between level and volume is described using a maximum of 31 nodes at arbitrary intervals.

100

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

Measurement task Linearization symbol
Flow: Mass/volume flow without correction

Characteristic curve type
Root extracted

Description
Square root extraction of the input value for measurement using the orifice plate method. Additional parameters for the root function: Application point of the root function and creep quantity suppression.

Flow: Mass/volume flow with correction

Root extracted and table

Square root extraction of the input value for measurement using the orifice plate method.
With the orifice plate method, the accuracy is greatest when the operating point is at the design point. If there are deviations, the measurement deviation is also greater. For this reason, the measurement accuracy is corrected using a characteristic curve with 31 nodes.

To input a characteristic curve, select the characteristic curve type "user-defined (table)". Enter the "New number of nodes" which you will later want to enter.
The nodes must always be entered in pairs. For each point x[n] in the working range, a point y[n] is required.
The device checks which pair of nodes bracket the pressure (secondary variable 1) relative to the measurement range. To convert the pressure to the measured value (primary variable), the device interpolates on a line between the interpolation nodes.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

101

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

7.1.3.3

x

Measurement range, here e.g. pressure (secondary variable 1)

y

Working range, here e.g. volume, measured value (primary variable)

Image 7-4 Entry of a user-defined characteristic using nodes x(i), y(i)

The following table describes the vendor-specific parameters used with the flow measurement type and that supplement the root function.

Table 7- 4 Vendor-specific parameters for flow measurement

Parameter Application point of the root function
Creep volume suppression

Description
This parameter specifies the flow point as a % at which the differential pressure is set in a linear relationship to the flow.
This parameter specifies the flow point as a % below which the flow becomes 0.

Units of the pressure transducer block
In the pressure transducer block you have the option of setting units in four different places. Depending on the measurement type, units are allowed from the following measurement functions:

Table 7- 5 Overview of available units

Variable
Raw pressure value Secondary variable 1

Measurement type

Pressure Level

P

P

P

P

Volume P P

Volume flow P P

Mass flow P P

102

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

See also

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

Variable
Measurement value (primary variable) Secondary variable 3

Measurement type

Pressure P

Level L

---

---

Volume V
---

Volume flow F

Mass flow F

---

M

P

Pressure

L

Level

V

Volume

F

Volume flow

M

Mass flow

For the measurement values (primary variables) you can also set the unit "%" for all measurement types.

Secondary variable 2 is a value normalized to one in all measurement types. The unit is fixed at "none".

Unit (Page 84)

7.1.4

Electronics temperature transducer block
The electronics temperature transducer block is manufacturer-specific and not described in the profile. The transducer block is responsible for monitoring the internal temperature of the device electronics. The transducer block cannot change the pressure value, only its status.
The permissible limits correspond to those of the permissible ambient temperature. If a limit is violated, the status changes to "GOOD ­ Active Critical Alarm ­ High/Low-limit". The status of the cleaned-up pressure value in the pressure transducer block receives the status "UNCERTAIN ­ Value not accurate ­ high/low-limit". This procedure is accompanied by a PROFIBUS diagnostic message "Electronics temperature too high".
There are also peak indicators for maximum and minimum values available.

See also

Min/max indicator (Page 122) Status (Page 167)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

103

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA

7.1.5

Analog input function block
The analog input function block is part of the standard functions of pressure transmitters. The following figure shows the processing of the measured values up to the output.

Image 7-5 Function groups of the analog input function block

Mi Incoming measured value from the transducer for pressure
OUT Output (value, status)

MAN Manual O/S Out of Service AUTO Automatically

Operating principle
The incoming measurement value from the pressure transducer block - or a simulated value prescribed through the simulation switch - is subject to another normalization (measured value scaling) and a projection onto the output range through output scaling (applicationspecific measured value).
Afterwards, the signal is filtered (damping) and check for being within preset limit values. An upper and lower warning and alarm limit is always available.
If the measured value has the status "Bad", the shutdown logic can output a safety preset value: This may be the last usable measured value or a preset substitute value.

104

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

See also

Operator control functions via PROFIBUS 7.1 Communications structure for PROFIBUS PA
Using the target mode selected in Mode and status processing, you can choose between output of the automatically acquired measured value (AUTO setting) or a manually set simulation value (MAN setting). If the function block is out of order (O/S setting) then the safety preset value is always output. The analog input function block handles the numerical value separately from the physical unit. This allows you to set 1000 predefined units.
Unit (Page 84)

7.1.6

Totalizer function block
The totalizer function block belongs to the standard functions of pressure transmitters. The function block is used in flow measurement. The following figure shows the processing of the measured values through to the output values.

Image 7-6 Function groups of the totalizer function block

Mi Incoming measured value from the trans- MAN Manual

ducer for pressure

O/S Out of Service

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

105

Operator control functions via PROFIBUS 7.2 Overview of operating functions

OUT Output (value, status)

AUTO Automatically

Operating principle
The function block processes the measured values from the transducer for pressure. If the status of the measured values is "bad", the setting of the failure behavior decides whether this value or the last "good" value is forwarded for totalizing.
The measured value now pass through the specified summation direction. The measured values are fed to a forward flow, reverse flow or net counting function.
The measured values are then integrated over time so that the flow can be calculated for a specified time segment. Adherence to the limit values is also checked. Here, it is also possible to reset the counted total to a preload value.
You can reset or initialize the totalizer function block not only with acyclic services. You can configure the totalizer function block so that you can reset or initialize it from the user program in cyclic data traffic.
In the Mode and status processing, select Target mode. Using the target mode, you can choose between output of the automatically acquired measured value (AUTO setting) or a manually set simulation value (MAN setting).
The possible units correspond to the volume and mass values of the transducer for pressure.

See also

Configuration of user data (Page 165) Units of the pressure transducer block (Page 102)

7.2

Overview of operating functions

A PC software program like SIMATIC PDM is necessary for operation over PROFIBUS PA. How to do this is explained in the corresponding user manual and the online help. The full functionality of the pressure transmitter is available via PROFIBUS PA communication.

7.3

Measurement

In measurement mode, measurement values such as pressure, fill level or flow are available on the PROFIBUS-PA interface. PROFIBUS PA communication is signaled by the communication symbol "o" on the display.

See also

Display elements (Page 73)

106

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

7.4

Settings

Operator control functions via PROFIBUS 7.4 Settings

7.4.1

Overview of settings
The pressure transducer can handle numerous measurement tasks. You only have to make the following settings:
 Settings with a configuration tool, for example STEP 7 or HW Config: Here, you choose the desired configuration with which the cyclically transmitted user data will be structured.
 Settings with SIMATIC PDM: Here you set the parameters that also influence the cyclic user data.

See also

Configuration of user data (Page 165)

7.4.2

Settings
If you set a new device, select the measurement type, for example pressure or fill level. As a result, you will see the appropriate default parameter settings in the SIMATIC PDM user interface. The following sections will introduce only those which you will still have to set.

Procedure

To read out the settings, proceed as follows: 1. Start the "Download to PG/PC" function.
The current settings are downloaded to the device. 2. Check the current settings. 3. Change the necessary settings. 4. Load the parameter settings into the device. 5. Save the parameter settings offline.

7.4.3

Pressure measurement

Procedure

To select pressure measurement, proceed as follows: 1. Start SIMATIC Manager. 2. Create a device with the desired measurement type. 3. To open SIMATIC PDM, double-click on the device you have created.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

107

Operator control functions via PROFIBUS 7.4 Settings

7.4.4

Level measurement

Procedure

To set fill level measurement, proceed as follows: 1. Start SIMATIC Manager. 2. Create a device with measurement type "Fill level". 3. To open SIMATIC PDM, double-click on the device you have created. Depending on whether you want to measure a height, a volume, or a mass, set the following values.

Height measurement
To select height measurement, proceed as follows:
 Start SIMATIC PDM. Create an assignment between the pressure to be measured (measurement range) and the fill level to be recorded (working range), by setting these parameters:

> Input

> > Transducer block 1

Transmitter type: Level

> > > Measuring range

Start of scale value

Full scale value

> > > Working range

Unit:

Unit of length [m, cm, mm, ft, in, yd]

Start of scale value

Full scale value

 Create an assignment between the measured level value and the output value by setting these parameters:

> Output

> > Function block 1 - analog input

Channel:

Measured value (primary variable)

> > > Measured value scaling

Start of scale value: as in "working range"

Full scale value: as in "working range"

> > > Output scaling

Unit:

as in "working range"

Start of scale value: as in "working range"

Full scale value: as in "working range"

108

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.4 Settings

You can also adjust the output to another process value. Assign the required unit to the parameters under the rubric output scaling. Assign the start of scale and full scale values according to the measured value scaling.

Volume measurement
 Start SIMATIC PDM. Create an assignment between the pressure to be measured (measurement range) and the volume to be recorded (working range), by setting these parameters:

> Input

> > Transducer block 1

Transmitter type: Volume

> > > Measuring range

Start of scale value

Full scale value

> > > Working range

Unit:

Unit of volume [m3, dm3, cm3, mm3, l ...]

Start of scale value

Full scale value

 If there is no linear relationship between level and volume in your container, you can also define a characteristic curve:

> Input

> > Transducer block 1

Transmitter type: Volume

> > > Characteristic curve

Characteristic curve User-defined table type:

> > > Nodes

New number of nodes:

max. 31

x[n] measurement Pressure value range:

y[n] working range: Corresponding volume value

 Create an assignment between the measured volume value and the output value by setting these parameters:

> Output

> > Function block 1 - analog input

Channel:

Measured value (primary variable)

> > > Measured value scaling

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

109

Operator control functions via PROFIBUS 7.4 Settings

Start of scale value: as in "working range"

Full scale value: as in "working range"

> > > Output scaling

Unit:

as in "working range"

Start of scale value: as in "working range"

Full scale value: as in "working range"

You can also adjust the output to another process value. Assign the required unit to the parameters under the rubric output scaling. Assign the start of scale and full scale values according to the measured value scaling.

Mass measurement
 Start SIMATIC PDM. The measurement of mass is calculated from the volume and density. Therefore create an assignment between the pressure to be measured (measuring range) and the volume to be recorded (working range) by setting the following parameters:

> Input

> > Transducer block 1

Transmitter type: Volume

> > > Measuring range

Start of scale value

Full scale value

> > > Working range

Unit:

Unit of volume [m3, dm3, cm3, mm3, l ...]

Start of scale value

Full scale value

 If there is no linear relationship between level and volume in your container, you can also define a characteristic curve:

> Input

> > Transducer block 1

Transmitter type: Volume

> > > Characteristic curve

Characteristic curve User-defined table type:

> > > Nodes

New number of nodes:

max. 31

x[n] measurement Pressure value range:

y[n] working range: Corresponding volume value

110

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

See also

Operator control functions via PROFIBUS 7.4 Settings

 Create an assignment between the measured mass value and the output value by setting these parameters:

> Output

> > Function block 1 - analog input

Channel:

Measured value (primary variable)

> > > Measured value scaling

Start of scale value: as in "working range"

Full scale value: as in "working range"

> > > Output scaling

Unit:

Unit of mass [kg, g, t ...]

Start of scale value: as "measured value scaling" * density

Full scale value: as "measured value scaling" * density

You can also adjust the output to another process value. Assign the required unit to the parameters under the rubric output scaling. Assign the start of scale and full scale values according to the measured value scaling.

Adjusting to a desired process value (Page 114)

7.4.5

Flow measurement
 Select the required configuration with the configuration tool:

Table 7- 6 Desired configuration for flow measurement

Desired configuration Output Totalizer output Output, totalizer output
Output, totalizer output, reset totalizer output

Measurement type Current flow/time
Volume or mass that has flowed over a time segment
Current flow/time, volume or mass that has flowed over a time segment, reset totalizer output (with SIMATIC PDM)
Current flow/time, volume or mass that has flowed over a time segment, Dosing

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

111

Operator control functions via PROFIBUS 7.4 Settings

Desired configuration Output, reset totalizer output, mode
Totalizer output, reset totalizer output Totalizer output, reset totalizer output, mode

Measurement type
Current flow/time,
volume or mass that has flowed over a time segment,
Dosing,
Controlling the mode of the totalizer from the user program: Net, forward flow, reverse flow, hold totalizer count
Volume or mass that has flowed over a time segment,
Dosing
Volume or mass that has flowed over a time segment,
Dosing,
Controlling the mode of the totalizer from the user program: Net, forward flow, reverse flow, hold totalizer count

 Create a device with measurement type "Flow".
 Start SIMATIC PDM. Create an assignment between the pressure to be measured (measurement range) and the volume or mass flow to be recorded (working range), by setting these parameters:

> Input

> > Transducer Block 1

Transmitter type: Flow

> > > Measuring range

Start-of-scale value: 0

Final value

> > > Working area

Unit:

Volume unit/time unit [m3/s, m3/h, l/s, ...]

Mass unit/time unit [kg/s, t/min, ...]

Start-of-scale value 0

Final value

> > > Characteristic curve

Characteristic curve Root extracted type:

 To acquire the current flow, use "Function Block 1 ­ Analog Input". Create an assignment between the measured flow value and the output value by setting these parameters:
> Output > > Function Block 1 - Analog Input

112

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.4 Settings

Channel:

Measurement value (primary variable)

> > > Measured value scaling

Start-of-scale value: as in "working range"

Final value:

as in "working range"

> > > Output scaling

Unit:

as in "working range"

Start value:

as in "working range"

Final value:

as in "working range"

 To acquire an amount that has flowed (mass or volume), use the totalizer function block.

> Output

> > Totalizer function block

Channel:

Measurement value (primary variable)

Unit (totalizer)

 If your desired configuration does not include the mode settings (reset totalizer or mode), set the following parameters as well with SIMATIC PDM:

> Output > > Totalizer function block > > > Operating mode
Operating mode: [Pos. and neg. values | only positive values] Totalizer output: Count

Application point of the root function, creep quantity suppression
If you want to suppress the error that occurs at low flow quantities, you have two options that you can also combine:
 The application point of the root function determines the point below which the root function becomes linear.
 Creep quantity suppression sets the measured flow quantity to 0, when the value falls below the preset limit.
Enter the application point as a % of the operating range (volume flow).

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

113

Operator control functions via PROFIBUS 7.4 Settings

Image 7-7 Application point of the root function and creep quantity suppression

Flow measurement correction
If you want to carry out a correction in your application (for example to take account of the flow coefficient  and the expansion coefficient ), select:
 Characteristic curve type: Root extracted and characteristic curve
 Nodes: For a maximum of 31 nodes, enter an input value (measured volume flow) and an output value (corrected volume flow).

See also

Configuration of user data (Page 165)

7.4.6

Adjusting to a desired process value
The analog input function block has the purpose of mapping the measured value to the process value. In general, you want to direct the measured value straight to the bus: Then the input and output range is taken from the working range.
If the measured pressure or the fill level has an indirect but linear relation to the process value, however, assign the start and final values of the input range to start and final values for the output range. The following examples illustrate this:

Procedure

The procedure is shown by means of two concrete application examples.

114

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Example 1

Operator control functions via PROFIBUS 7.4 Settings

You want to assign the input range 1 to 4 Pa to the output range 0 to 100%. 1. Set measurement type "Pressure". 2. Set the following parameters:

> Pressure transducer block

Unit for measured value Pa (primary variable):

> Analog input function block

Input starting value:

1.0

Input final value:

4.0

Output starting value: 0.0

Output final value:

100.0

Unit (output):

%

Note
The display can only show a part of the ASCII character set in both upper and lower case. If you enter lower-case letters f, g, j, p, q, t, x, y, z in SIMATIC PDM in the parameter "Unit text (output)", they will only be shown in upper case. The German letters ä, ö, ü, and ß, as well as any ASCII characters with codes higher than 125, are displayed with a block symbol with all segments on. Thus try to avoid language-specific characters.

Example 2

You want to convert the input range 0 to 400 m3 to 200 l barrels. The output range, for instance, is 0 to 2000 barrels.
1. Set measurement type "Volume".
2. Set the following parameters:

> Pressure transducer block

Unit for measured value m3 (primary variable):

> Analog input function block

Input for start-of-scale 0.0 value:

Input for final value:

400.0

Output for start-of-scale 0.0 value:

Output for final value: 2000.0

Unit (output):

Text

Unit text (output):

Barrels

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

115

Operator control functions via PROFIBUS 7.5 Electrical damping (filter time constant)

See also

Level measurement (Page 108) Pressure measurement (Page 107)

7.5

Electrical damping (filter time constant)

You can set the time constant of electrical damping (filter time constant) to a point within a range of 0 to 100 seconds. It always applies to the "Pressure" device variable (DV0) and thus to the measured values derived from it.

See also

Setting/adjusting electrical damping (Page 79)

7.6

Key lock and write protection
You can set operation blocks according to the following table.

Table 7- 7 Keypad locks

Lock

Effect

Switching on/off

Keypad and function Parameter changes with SIMATIC PDM and

block (hardware

setting changes made locally are blocked.

write protection)

Independent of other operating locks.

Local Mode 10

Write block

Write block for parameterization using SIMATIC PDM. Local operation is possible.

SIMATIC PDM

With PROFIsafe devices, password protection can be set for parameter modifications via bus. Refer to Write protection (Page 150).

Local operation

If local operation is not enabled, no access is possible using the keypad. Regardless of the setting of this parameter, local operation is automatically enabled 30 seconds after loss of communication. After communication is restored, the "Local operation permitted" parameter is restored to its original setting in the device.

SIMATIC PDM

Combination of write blocking and no enabling of local operation

Acts like an active keypad block. Changes to parameters (except for keypad block) are not possible either with local operation or using SIMATIC PDM.

SIMATIC PDM

Display L LC
LA
LL

116

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

See also

Operator control functions via PROFIBUS 7.7 Warning and alarm limits

Blocks can also be combined:

Table 7- 8 Combined blocks

Lock
On Off Off Off Off

Write block for parameter changes over the bus On or off Off Off On On

Release of local operation over SIMATIC PDM Released or blocked Blocked Released Blocked Released

Display
L LA - LL LC

Locking of buttons and functions (Page 81)

7.7
Status

Warning and alarm limits
The analog input function blocks each have high and low warning and alarm limits for the output. In order to avoid unstable display of warnings and alarms, specify a hysteresis.
In the analog input function blocks, set the following parameters according to process requirements:
 Limit value hysteresis  High warning limit  High alarm limit  Low warning limit  Low alarm limit

If limits are violated, the output is accompanied by a status which you can evaluate in your application program:

Table 7- 9 Limits and status displays

Status Display G_137 G_138 G_141 G_142

Status Hex 89 8A 8D 8E

Violation
Low warning limit High warning limit Low alarm limit High alarm limit

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

117

Operator control functions via PROFIBUS 7.7 Warning and alarm limits
Example

G_137 G_138 G_141 G_142

Low warning limit High warning limit Low alarm limit High alarm limit

t

Time

Image 7-8 Warning and alarm limits

A1

High alarm

A2

Low alarm

W1

High warning limit

W2

Low warning limit

Hys Hysteresis

w

Measured value

118

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

7.8

Failure behavior

Operator control functions via PROFIBUS 7.8 Failure behavior

7.8.1

Overview of failure behavior
If the transducer block fails, the analog input and totalizer function blocks can adopt a value preset by the user. If the output variables of the transducer block have the status "Bad" due to an error, activate the failure behavior for the function blocks. The status "Unsure" then accompanies the output or the totalizer output.

7.8.2

Output
Set the failure behavior in the analog input function block:

Table 7- 10 Failure behavior of the analog input function block

Failure behavior
The output value is set to the replacement value.
Saving of the last valid output value.
The incorrectly calculated measured value is on the output (shutdown logic turned off).

Description

Status code

The predefined safety preset value is output.

U_075

The last valid output value is output.

U_071

The bad output value is accompanied by B_0xx the status assigned to it by the transducer block.

To narrow down the cause of failure after the shutdown logic engages, read the measured value (primary variables) or secondary variables including the status from SIMATIC PDM.

7.8.3

Totalizer output
Set the failure behavior in the totalizer function block:

Table 7- 11 Failure behavior of the totalizer function block

Failure behavior Stop
Safe operation
Operation

Description
Counting is stopped if there are input values with the "Bad" status.
Counting continues with the last input value that had the "Good" status prior to the failure.
The bad measured value is accompanied by the status assigned to it by the transducer block.

Status code U_075
U_072
B_0xx

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

119

Operator control functions via PROFIBUS 7.9 Diagnostics functions

7.9

Diagnostics functions

7.9.1

Operating hours counter
You can read out one operating hours counter for the electronics and one for the sensor. They are activated upon first commissioning of the pressure transmitter.

7.9.2

Calibration interval and service interval
There are two timers in the pressure transmitter:
 A timer for the calibration interval, which ensures regular calibration of the electronics.  A timer for the service interval, which draws attention to any necessary service for the
sensor cell and its connections.
The interval is selectable. The timers can monitor on two levels, first giving a warning, then an alarm.

Image 7-9 Calibration and service intervals

v

Timer value

A Interrupt

t

Time

W Warning

120

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Procedure

Operator control functions via PROFIBUS 7.9 Diagnostics functions
To adjust the calibration and service interval, proceed as follows: 1. Set the parameter for warning/alarm. 2. Give the time interval after which a warning is output. 3. Give the additional time interval after which an alarm is output.

7.9.3

Clearing warning
As soon as the warning interval is past, the first monitoring level emits a warning. Measured values have the status "Good, Maintenance request". The "Maintenance request" diagnostics alarm is also displayed. SIMATIC PDM can also display the status for calibration or service and the value of the timer.

Procedure

To clear a warning, proceed as follows: 1. Clear the warning.
The diagnostic message is deleted and the status set back to "Good". 2. Perform the calibration or service. 3. Reset the timer.

7.9.4

Clearing the alarm
If you don't perform calibration or service on time, the second monitoring level emits an alarm which again draws attention to the urgent need for service. Measured values are accompanied by the status "Unsure, value inexact" and the diagnostic message "Service required" is displayed.

Procedure

To clear an alarm, proceed as follows: 1. Clear the alarm.
The diagnostic message is deleted and the status set back to "Good". 2. Perform the calibration or service. 3. Reset the timer.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

121

Operator control functions via PROFIBUS 7.10 Simulation

7.9.5

Min/max indicator

Description

The pressure transmitter has three pairs of min/max pointers which you can use to monitor the three measured variables pressure, sensor temperature, and electronics temperature for negative and positive peak values. For each measured value, a resettable min/max pointer saves the maximum and minimum peak values in long-term storage in the two non-volatile memories. Consequently, the values are available even after the device is restarted. The min/max pointers are also updated during a simulation.

See also

p

Pressure

Image 7-10 Basic representation of min/max pointers

Simulating the pressure sensor (Page 124) Simulating sensor and electronics temperature (Page 125)

7.10

Simulation

7.10.1
122

Overview of simulation
Simulation functions help you when commissioning parts of the system and the pressure transmitter. You can generate process values without recording real measured values. The value range of simulated process values can be tested fully: This makes the simulation of errors possible.
SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.10 Simulation
From the output of the pressure transmitter, you can get ever closer to the sensor and check the measurement and function blocks. The display indicates active simulation with an "Si" in the mode display.

7.10.2

Simulating output
By simulating the output, you can make process values available at the output of the pressure transmitter for cyclic data transmissions using acyclic write access. This allows you to test the process value processing in the automation program.

Procedure

To simulate the output, make the following settings: 1. Select output simulation. 2. Set the target mode to manual (MAN). 3. Enter the desired output value, the quality, and the status. 4. Transmit the settings from the program into the pressure transmitter. The behavior of the output can be observed, e.g. in SIMATIC PDM or using a variable table (VAT component). To return to normal operation afterwards, set the target mode to AUTO.

7.10.3

Simulating input
By simulating the input, you can check the following functions:  Adaptation of the measured value to the required process variable  Monitoring of the process limits you have set  Electrical damping  Response to failure

Procedure

To simulate the input, make the following settings: 1. Select input simulation. 2. Set the target mode to AUTO. 3. Select the simulation mode "Released". 4. Enter the desired input value, the quality, and the status. 5. Transmit the settings from the program into the pressure transmitter. You can observe the behavior of the input in e.g. SIMATIC PDM. To return to normal operation afterwards, you must switch off the simulation.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

123

Operator control functions via PROFIBUS 7.10 Simulation

7.10.4

Simulating the pressure sensor
By simulating the pressure sensor as a fixed value or a parameterizable ramp, you can check the following functions:
 Trim  Check the zero-point adjustment  Reaction to violation of sensor limits  Linearization  Projection onto the working range You can make the simulation value dynamic with a parameterizable ramp. The simulation value then goes from a start value (v1) in a step function to a full-scale value (v2), staying at each level for the given step interval (tv). At the full-scale value, the direction reverses.

Procedure

Image 7-11 Parameterizable ramp

v

Value

v1 Start value

v2 Full-scale value

t

Time

tv

Step interval

vn

Number of steps

To simulate the pressure sensor, make the following settings: 1. Select pressure sensor simulation. 2. Set the simulation mode and the parameters:
­ Simulation mode "Fixed" and parameter pressure value ­ Simulation mode "Ramp" and ramp parameters 3. Transmit the settings from the program into the pressure transmitter.

124

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Operator control functions via PROFIBUS 7.11 Calibrating the sensor
The behavior of the measured value (primary variable), the secondary variables 1, 2, and 3, and of the output, can be observed in SIMATIC PDM. To return to normal operation afterwards, you must switch off the simulation.

7.10.5

Simulating sensor and electronics temperature
By simulating the sensor and electronics temperature you can, for instance, check the influence of excessive temperature on the measurement results:

Procedure

To simulate the sensor and electronics temperature, make the following settings: 1. Select the simulation of sensor or of the electronics temperature. 2. Set the simulation mode and the parameters:
­ Simulation mode "Fixed" and parameter pressure value ­ Simulation mode "Ramp" and ramp parameters 3. Transmit the settings from the program into the pressure transmitter. The behavior of the measured value (primary variable), the secondary variables 1, 2, and 3, and of the output, can be observed in SIMATIC PDM. To return to normal operation afterwards, you must switch off the simulation.

7.11

Calibrating the sensor
Sensor calibration enables you to calibrate the pressure transmitter. Analogous to modes 19 and 20 for local operation, you can change the slope of the characteristic curve of the pressure transmitter.
Using a lower and an upper trim point, you can determine the course of the characteristic curve.
Change the slope of the characteristic to a minimum of 0.9 and a maximum of 1.1. Any larger variation from a slope of 1.0 will prevent the respective trim point from being stored.
The lower trim point must be far enough from the upper trim point so that the smallest calibration span is included.
The smallest calibration span is displayed in the sensor calibration dialog and depends on the measurement range. If the calibration is smaller than the smallest span, the following status code accompanies the measured value:
"Bad, configuration error"
In this case, recalibration the lower or the upper sensor trim point with a sufficiently large calibration span.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

125

Operator control functions via PROFIBUS 7.12 Correcting for positional error

Calibrating the lower point
To calibrate the lower point, proceed as follows: 1. Call up the dialog "Sensor Trim". 2. Apply the reference pressure for the lower sensor trim point. 3. Enter the value of the reference pressure in the field "Lower Sensor Trim Point". 4. Click on "Transfer". In the field "Pressure cleaned raw value", observe the effect of the calibration. In the "Lower Sensor Trim Point" box, you can see whether the new trim point was applied.

Calibrating the upper point
To calibrate the upper point, proceed as follows:
1. Call up the dialog "Sensor Trim".
2. Switch to the "Upper Sensor Trim" tab.
3. Apply the reference pressure for the upper sensor trim point.
4. Enter the value of the reference pressure in the field "upper sensor trim point".
5. Click on "Transfer".
In the field "Pressure cleaned raw value", observe the effect of the calibration. In the "Upper Sensor Trim Point" box, you can see whether the new calibration point was applied.
After both points have been calibrated, the status of the measured value must be "Good". If the status "Bad, configuration error" is displayed, the calibration was smaller than the smallest calibration span. You must move the trim points away from one another by moving one of the two trim points.

See also

LO calibration (Page 91) HI calibration (Page 92)

7.12

Correcting for positional error
External influences can affect the original zero point. External influences include:
 Mounting position  Ambient temperature  Installation-caused preset pressures, for instance fluid columns in the pressure line to the
pressure transmitter
 The screw-mounting on the process plant, e.g. measuring ranges from 1 to 20 mbar (differential pressure), can respond more sensitively to the screw-mounting.

126

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Procedure

Operator control functions via PROFIBUS 7.13 Reset

You can correct for these influences within the following limits.

Differential pressure -100% to +100% of the rated measuring range

Pressure

-100%, but not more than -1 bar

up to +100% of the nominal measurement range

Absolute pressure Correction for positional error not possible

To correct for positional error, proceed as follows: 1. Call up the dialog "Position correction". 2. Create a pressure calibration. 3. Click on "Transfer".

7.13

Reset

7.13.1

Resetting to delivery state
If the pressure transmitter is so maladjusted that it can no longer fulfill its measurement tasks, you can use this function to reset it to the factory settings. It resets all parameters to the factory settings, with a few exceptions.
The exceptions are:
 PROFIBUS address  Device operation type  Static version number
­ In Transducer Block 1
­ In the analog input function block
The reset is indicated by the diagnostic message "New start executed". The automation or control system reads the status "Unsure, initial value, value constant" until a measured value result is available.

See also

Resetting the PROFIBUS address (Page 128) Device operation type (Page 88)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

127

Operator control functions via PROFIBUS 7.13 Reset

7.13.2

Warm start/restart
With a warm start, you cause the pressure transmitter to switch itself off and restart. This interrupts and then reestablishes communication.
You need this function, for example, if the PROFIBUS address is changed during running communication with a cyclical master.
This restart is indicated by the diagnostic message "Restart executed". The automation or control system reads the status "Unsure, initial value, value constant" until a measured value result is available.

7.13.3

Resetting the PROFIBUS address
If no other pressure sensor in your system has the preset address 126, you can add your pressure transmitter to the PROFIBUS strand during running operation of the automation or control system. You must subsequently change the address of the newly connected device to a different value.
If you remove the pressure transmitter from the PROFIBUS chain, reset its address to 126. This allows you to include the pressure transmitter in this or another system if necessary.

128

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety

8

8.1

Safety function
The safety function of SITRANS P DS III with PROFIsafe protocol (ordering option -Z C21) is based on the measurement of pressure.
The pressure is converted to a digital measured value and transmitted via PROFIsafe communication. Fault tolerance allowances must be made, because the measured value transferred to the automation system by the pressure transmitter can deviate from the physical value. This fault tolerance is calculated as follows:
Total tolerance (safety function) = ± [application-specific measurement error + 2 % safety accuracy].
Pressure transmitter safety accuracy: the maximum effect of a non-critical individual error on the measured value.
The measured value is transferred along with the "Validity" and "Quality" status information.
The diagnostics function will respond within 60 seconds in the worst-case scenario.
The safety accuracy together with the application-specific measurement error allows the system operator to include a backup for process monitoring. Even if a random individual error occurs that is within the safety accuracy, the system can still be safely shut down.
As there is also always a possibility of dangerous faults occurring, these are categorized and listed in the manufacturer declaration for the device (SIL declaration of conformity, functional safety pursuant to IEC 61508 and IEC 61511).
Example:
A silo is to be securely monitored to check that the level does not exceed 10 meters.
Application-specific measurement error: 0.1% Safety accuracy: 2.0% Total tolerance: 2.1% 2.1% of 10 meters is 21 centimeters. If process monitoring is set to 9.79 meters, safe shutdown is guaranteed even in the event of a random individual error within the safety accuracy.
Note Use of remote seals
If remote seals are used, the application-specific measurement error is the product of the pressure transmitter and remote seal measurement errors.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

129

Functional safety 8.2 Safety Integrity Level (SIL)
WARNING Disregarding conditions for fulfilling the safety function Disregard can result in a malfunction of the process plant or application, e.g. process pressure too high, maximum level exceeded. The mandatory settings and conditions are listed in chapters "Settings (Page 132)" and "Safety-related characteristics (Page 132)". Please observe the applicable conditions to ensure the safety function.
Safety-instrumented system in single-channel operation (SIL 2)

Image 8-1 Safety-related system for pressure transmitters in single-channel operation
The combination of pressure transmitter, automation system and final controlling element forms a safety-instrumented system that performs a safety function. The emphasis of this description is on the pressure transmitter. For information on requirements for the automation system or final controlling element, please refer to the corresponding standards.
The pressure transmitter generates a process-related measured value that is transferred to the automation system. The automation system monitors this measured value. If the measured value violates the high or low limit, the automation system generates a shutdown signal for the connected final controlling element, which switches the corresponding valve to the specified safety position.
Only one SITRANS P DS III device is required for single-channel operation for SIL 2.

8.2

Safety Integrity Level (SIL)

The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4. Every level corresponds to a probability range for the failure of a safety function.

130

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Description

Functional safety 8.2 Safety Integrity Level (SIL)

The following table shows the dependency of the SIL on the "average probability of dangerous failures of a safety function of the entire safety-instrumented system" (PFDAVG). The table deals with "Low demand mode", i.e. the safety function is required a maximum of once per year on average.

Table 8- 1 Safety Integrity Level

SIL

Interval

4

10-5  PFDAVG < 10-4

3

10-4  PFDAVG < 10-3

2

10-3  PFDAVG < 10-2

1

10-2  PFDAVG < 10-1

The "average probability of dangerous failures of the entire safety-instrumented system" (PFDAVG) is normally split between the following three components:

Image 8-2 PFD distribution
The following table shows the achievable Safety Integrity Level (SIL) for the entire safetyinstrumented system for type B devices depending on the safe failure fraction (SFF) and the hardware fault tolerance (HFT).
 Type B devices include analog transmitters and shut-off valves with complex components, e.g. microprocessors (also see IEC 61508, Section 2).
 For detailed information on values and hardware/firmware versions for your device, refer to the manufacturer declaration for the device (Declaration of Conformity, Functional Safety according to IEC 61508 and IEC 61511): Certificates (http://www.siemens.com/processinstrumentation/certificates).

SFF
< 60 % 60 to 90 % 90 to 99 % > 99 %

HFT for type B devices 0
Not permitted SIL 1 SIL 2 SIL 3

1 (0) 1) SIL 1 SIL 2 SIL 3 SIL 4

1) Operational reliability in accordance with IEC 61511-1, Section 11.4.4

2 (1) 1) SIL 2 SIL 3 SIL 4 SIL 4

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

131

Functional safety 8.3 Settings

Operational reliability
According to IEC 61511-1, Section 11.4.4, the hardware fault tolerance (HFT) can be reduced by one (values in brackets) for transmitters and final controlling elements with complex components if the following conditions apply to the device:
 The device is proven in operation.
 The user can configure only the process-related parameters, e.g. control range, signal direction in case of a fault, limiting values, etc.
 The configuration level of the firmware is blocked against unauthorized operation.
 The function requires SIL of less than 4.

See also

General functional safety (http://www.siemens.com/safety) Functional safety in process instrumentation (http://www.siemens.com/SIL)

8.3

Settings

Introduction

When using the device for functional safety, follow these steps:

Procedure

1. Setting safety-relevant parameters (Page 144) 2. Checking the safety function (Page 134) 3. Enabling write protection (Page 150)

8.4

Safety-related characteristics

The safety characteristics necessary for using the system are listed in the "SIL Declaration of Conformity". These values apply under the following conditions:

 SITRANS P DS III pressure transmitters are only used in applications with a low demand rate for the safety function (low demand mode).

 The safety-relevant parameters/settings were entered before the safety-instrumented operation via PROFIBUS communication. Check the safety-relevant parameters/settings
by means of PDM; refer to chapter "PROFIsafe Configuration (Page 144)".

 The safety function test has been concluded successfully.
 The pressure transmitters are protected from accidental and unauthorized changes/operation.

132

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.5 Maintenance/check
 Fault rates are calculated on the basis of a mean time to repair (MTTR) of eight hours (order option C21).
 Only one SITRANS P DS III device is required for single-channel operation in accordance with SIL 2.
 Secure data transmission is only guaranteed when using a PROFIsafe master.

8.5

Maintenance/check

8.5.1

Overview

Checking safety
Check the safety function of the entire safety circuit on a regular basis in accordance with IEC 61508/61511. The test intervals are determined in the course of calculations for each safety circuit of a system (PFDAVG).
Checking safety function/proof test
Runs this test to detect hidden serious faults of the pressure transmitter. Hidden faults result in incorrect measurements and dangerous failures in your safety-related system. If necessary, replace the pressure transmitter.

Enabling write protection
After parameter assignment/commissioning as well as after a proof test, perform the following steps:
1. Disable the write protection. For this purpose you have various options, which are described in the section "Write protection (Page 150)".
2. Protect the keys from unintended change in the parameters, e.g. by selecting the key lock or function lock (Mode 10).

Electronics and measuring cell
The safety function of the pressure transmitter is ensured only if you use the electronics, measuring cell, display and connection board delivered by the factory. These components cannot be replaced.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

133

Functional safety 8.5 Maintenance/check

8.5.2

Checking safety function/proof test

Requirement

 You should preferably check the safety function while the device is installed. If this is not possible, you can also check the safety function when the device is not installed. Make sure that the pressure transmitter is mounted in the same position for testing as it is in the system.
 Observe the information in the section Write protection (Page 150).
 If you are using add-on parts, also see the tests in section Add-on parts (Page 140).

Procedure

1. Make sure that the test does not inadvertently result in an emergency shutdown of the system.
2. Make sure that there are no active warnings or error messages. 3. Check temperature sensors (Page 135). 4. Check response time of pressure transmitter (Page 135). 5. Conduct a two-point measurement:
Two-point measurement  10% of the maximum measuring range. (Page 135) - or Two-point measurement  50% of the maximum measuring range. (Page 138) 6. Make sure that the pressure transmitter is in measuring mode. 7. After the test, make sure that the emergency shutdown of the system is working again. 8. Disable the write protection.

Result

If you are conducting the test as described, you will detect dangerous faults to a certain degree that are not detected by runtime diagnostics:
 With two-point measurement  10% of the maximum measuring range: 89% of the faults are detected.
 With two-point measurement  50% of the maximum measuring range: 98% of the faults are detected.

Interval
134

 Check the pressure transmitter regularly for proper function (proof test) to detect influences which could reduce the functionality of the pressure transmitter in time.
 Select the interval according to the process and ambient conditions of the installation location of the pressure transmitter.
SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.5 Maintenance/check

Note
For a safety-instrumented system, we recommend checking the device at regular intervals of one year.

8.5.2.1

Checking temperature sensors

Procedure

 Read the sensor temperature and the electronics temperature via communication.  Check whether the measured sensor temperature is within the range of -50 °C to 120 °C.  Check whether the measured electronics temperature is within the range of -50 °C to
90 °C.
If the measured temperatures are not within this range, the temperature sensor is defective.

8.5.2.2

Check response time of pressure transmitter.

Procedure

To check whether the response time of the pressure transmitter meets the requirements of the process plant, follow these steps:
 Change the pressure at the input abruptly from a base value by  10% of the maximum measuring range and check the measured values that result from this.
Note that the set damping can affect the damping of the response time of the pressure transmitter.

8.5.2.3

Two-point measurement  10% of the maximum measuring range

General procedure

Requirement

The difference between the first input pressure and the second input pressure is  10% of the maximum measuring range.

Checking the measuring range
1. Apply an initial input pressure. 2. Check the transferred value.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

135

Functional safety 8.5 Maintenance/check
3. Apply a second input pressure. 4. Check the transferred value.
Image 8-3 Example of two-point measurement 10%
Procedure for monitoring a minimum pressure Checking monitoring of a minimum pressure
1. Check the monitoring of the minimum pressure with the threshold defined in the system. 2. Apply an input pressure value that is above the threshold. 3. Apply an input pressure value that is  1% of the maximum measuring range below the
threshold.
 Threshold
Image 8-4 Example of monitoring of a minimum pressure

136

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.5 Maintenance/check
Procedure for monitoring a maximum pressure
Checking monitoring of the maximum pressure
1. Check the monitoring of the maximum pressure with the threshold defined in the system. 2. Apply an input pressure value that is below the threshold. 3. Apply an input pressure value that is  10% of the maximum measuring range above the
threshold.
Note Step 3 can only be performed if the maximum limit value is  10% below the maximum full scale value. Otherwise, check only up to full scale value. However, the test range must be  10% of the maximum measuring range.

 Threshold
Image 8-5 Example of monitoring of a maximum pressure

Result

The two-point measurements are successful when the deviation between input pressure and transferred value is  0.2%.

Negative measurement result
If the two-point measurements of the pressure transmitter were not successful, the SIL level is no longer guaranteed.
 Replace the pressure transmitter.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

137

Functional safety 8.5 Maintenance/check

8.5.2.4

Two-point measurement  50% of the maximum measuring range

General procedure

Requirement

The difference between the first input pressure and the second input pressure is  50% of the maximum measuring range.

Checking monitoring of the maximum measuring range
1. Apply an initial input pressure. 2. Measure the transferred value. 3. Apply a second input pressure. 4. Measure the transferred value.

Image 8-6 Example of two-point measurement 50%
Procedure for monitoring a minimum pressure
Checking monitoring of a minimum pressure
1. Check the monitoring of the maximum pressure with the threshold defined in the system. 2. Apply an input pressure value that is above the threshold. 3. Apply an input pressure value that is  1% of the maximum measuring range below the
threshold.

138

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.5 Maintenance/check

 Threshold
Image 8-7 Example of monitoring of a minimum pressure
Procedure for monitoring a maximum pressure
Checking monitoring of the maximum pressure
1. Check the monitoring of the maximum pressure with the threshold defined in the system. 2. Apply an input pressure value that is below the threshold. 3. Apply an input pressure value that is  10% of the maximum measuring range above the
threshold.
Note Step 3 can only be performed if the maximum limit value is  10% below the maximum full scale value. Otherwise, check only up to full scale value. However, the test range must be 50% of the maximum measuring range.

Result

 Threshold
Image 8-8 Example of monitoring of a maximum pressure
The two-point measurements are successful when the deviation between input pressure and transferred value is  0.2%.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

139

Functional safety 8.6 Add-on parts

Negative measurement result
If the two-point measurements of the pressure transmitter were not successful, the SIL level is no longer guaranteed.
 Replace the pressure transmitter.

8.5.2.5

Checking pressure transmitter for external damage
 Make sure that the terminal compartment is dry.  Make sure that the enclosure and the process connections do not have any leaks through
which the filling oil or the process medium could escape.
 Check the enclosure for critical damages.  Make sure that the connecting cable is plugged in correctly and that it is not damaged.

8.6

Add-on parts

This chapter contains safety information for add-on parts.

WARNING
Add-on parts unsuitable for process medium
Danger of injury or damage to device.
If the process medium is not suitable for the parts which come into contact with it, hot and/or toxic or corrosive substances could be released. · Refer to the information in the chapter "Technical data (Page 193)". · Make sure that the add-on parts are suitable for the corresponding application with
regard to materials, temperature of process medium, and pressure.

8.6.1

Checking a device with add-on pneumatic block

Procedure

1. Check the connection between the pressure transmitter and pneumatic block and between the pneumatic block and pipelines in the plant for leaks.
2. Observe the safety information and specifications in chapter Installing / mounting (Page 39).

140

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe
3. Check the following valves for correct positioning and absence of leaks: ­ Process valves ­ Stabilizing valve ­ Vent valves ­ Blowout valves or plugs
4. Observe the safety information and specifications in chapter Commissioning (Page 171).

8.6.2

Checking a device with add-on remote seal

Procedure

1. Check the connection between the pressure transmitter and remote seal and between the remote seal and the plant for leaks.
2. Observe the safety information and specifications in chapter Installing / mounting (Page 39).

8.7

PROFIsafe

8.7.1

Introduction
PROFIsafe enables safe communication by detecting and reporting all communication errors. Data security is continuously monitored on the PROFIBUS in the process.

8.7.2

Technical advantages of PROFIsafe
The main advantage of PROFIsafe is that the PROFIBUS communication channel becomes secured by a protocol in a transparent way. Thus incorrect values cannot be transferred to the master without being discovered. The user does not need any special network components. All the user needs is the standard network components of PROFIBUS. However, the CPU must be suitable for safety applications.
In the following example, you see that PROFIsafe and PROFIBUS devices can be operated simultaneously on a PROFIBUS network.
Note
PROFIsafe devices can only be operated with the S7 F Systems V6.1 configuration software in combination with S7-400H.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

141

Functional safety 8.7 PROFIsafe

See also

Image 8-9 Example of PROFIsafe communication PI PROFIBUS - PROFINET (http://www.profibus.com/home/)

142

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe

8.7.3

Further information

Standards

The PROFIsafe protocol was developed while taking the international standard IEC 61508 into account. The IEC 61508 governs the requirements for the functional safety of products and systems. The use of the IEC 61508 in the process industry is described in the application-specific standard IEC 61511.

Safety levels

The device meets the requirements of Safety Integrity Level 2 (SIL).
Note You will find more information on safety engineering and installing PROFIsafe in the document "Safety Engineering in SIMATIC S7".

See also

General functional safety (http://www.siemens.com/safety) Functional safety in process instrumentation (http://www.siemens.com/SIL) Product information on SITRANS P in the Internet (http://www.siemens.com/sitransp)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

143

Functional safety 8.7 PROFIsafe

8.7.4

Preconditions

CPU

The CPU must be capable of operating in fail-safe mode to be able to communicate with PROFIsafe devices.
These F-CPUs are contained in the catalog ST 70, SIMATIC S7.

Electronic Device Description (EDD):
Operate your application in conjunction with the EDD and GSD of SITRANS P, series DSIII PA PROFIsafe in the following system environment:  with EDD version 01.02.01-53 with GSD "SI0180A6.GSD revision 1.03"
­ PCS 7 V7.0 and F systems V5.2SP4 with library Failsafe Blocks (V1_2) or ­ PCS 7 V7.0 and F systems V6.0 with library Failsafe Blocks (V1_2) or  EDD version 01.02.02 or higher with GSD "SI0180A6.GSD revision 1.04" with PCS 7 V7.0 SP1 and F systems V6.0 with library S7 F Systems Lib V1_3  EDD version 01.02.03 or higher with GSD "SIEM8170.GSD revision 1.0" with PCS7 V7.1 SP3 and F systems V6.1 with libraryS7 F Systems Lib V1_4
Note With this EDD, the "PROFIBUS Ident number" parameter can be set to manufacturerspecific (3.01), PROFIsafe V1/V2

PROFIsafe device
For safety reasons, the PROFIsafe device ships with default settings. This means PROFIsafe is deactivated. You activate PROFIsafe with the PROFIsafe commissioning. Technical requirements for PROFIsafe:  SIMATIC PDM HF1  EDD from 01.02.01  Firmware from 301.02.01

8.7.5

PROFIsafe Configuration
For safety reasons, the PROFIsafe device ships with default settings.

Requirement

Before you commission the PROFIsafe device, configure it, for example in STEP 7.

144

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe

Process

Import EDD with SIMATIC PDM (Page 145) Configure CPU with HW Config (Page 145) Configure device with HW Config (Page 145) Configure CFC (Page 148)

8.7.5.1

Import EDD with SIMATIC PDM
To import the EDD, click on "SIMATIC PDM" > "Manage Device Catalog".

8.7.5.2

Configure CPU with HW Config
The relevant settings for fail-safe of the CPU are located in the CPU-specific documentation.

Procedure

If your CPU is a SIMATIC CPU, proceed as follows: 1. Double click on the CPU. 2. You are now in the "Properties" dialog box on the "Protection" tab. Activate the following
checkboxes: ­ Protection level "1" ­ "Removable with password" ­ "CPU contains safety program"

8.7.5.3

Configure device with HW Config

Procedure

1. You are in the "Catalog" view with the "standard" profile. Go to the device in the catalog: ­ "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe" valid for firmware 0301.02.01 and 0301.02.02 ­ "PROFIBUS-PA > Sensors > Pressure > SIEMENS > SITRANS P DSIII PROFIsafe V2" valid as of firmware 0301.02.03
Note You will find the valid firmware version on the label and can then select the correct GSD file for your version.
2. Pull the following device onto "PA Master System" with Drag & Drop. The "Properties" dialog then opens.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

145

Functional safety 8.7 PROFIsafe
3. Set the PROFIBUS address. The device is displayed in HW Config with the default configurations.
4. Delete the default module of the device at Slot 1. 5. You are now in the "Catalog" view. For the PROFIsafe device, select the fail-safe-
compliant configuration "F:Pressure\Level\Flow\Temp". 6. Drag the F-module to slot 1. 7. Open the "PROFIsafe" tab in the "Properties - DP slave" dialog of the catalog. 8. Check the PROFIsafe address, parameter "F_Dest_ADD".
Note: You must set the PROFIsafe address, parameter "F_Dest_ADD" to the same value later using the PDM table in the device. 9. Valid as of firmware 0301.02.03: Select the PROFIsafe protocol version V1 or V2 with which the device will work. ­ crc length = 3, F-Par-Version = 1  V2 PROFIsafe protocol ­ crc length = 2, F-Par-Version = 0  V1 PROFIsafe protocol

10.Adapt the value of the "F_WD_Time" parameter to the number of PROFIBUS devices connected to the PROFIBUS-PA bus. The default value for this parameter is 1 second.

146

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe
11.Close the "Properties - DP slave" dialog of the catalog. 12.Click the "Save and compile" button. 13.Press the "Download to module" button.
Note F-CPUs for PROFIsafe V2 communication With F-CPUs, if you set "F_Par_Version" to "1" for a device, a communications error occurs in the case of safety-oriented communication with the device because PROFIsafe V2 communication does not support this setting. One of the following diagnostic events will then be entered in the diagnostic buffer of the F-CPU: · "F-I/O passivated": Cyclic redundancy check error/sequence number error. · "F-I/O passivated": F-monitoring time for safety frame exceeded.
To make sure that PROFIsafe V2 communication works correctly, use only F-CPUs approved for this purpose.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

147

Functional safety 8.7 PROFIsafe

8.7.5.4

Configure CFC

Procedure

1. You are in the "Catalog" window, "Libraries" tab. 2. Locate the block "F_PA_AI [FB356] in the "Failsafe Blocks" library. 3. Pull the block into the plan with Drag & Drop. 4. Set the parameter "Value", value type "Real" in the block "F_PA_AI" as follows:
­ Click this parameter with the right mouse button. ­ Select "Connect to Operand..." in the context menu.
A selection list of transfer rates is displayed. ­ Connect the parameter value of the block "F_PA_AI" with the real value of the
configured device. 5. Click the "Compile program" button.

148

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

6. Select the "Generate module drivers" check box.

Functional safety 8.7 PROFIsafe

7. Click the "OK" button.
The parameters are connected.
Note
Until PROFIsafe commissioning is completed, the device displays the error "B_60: Bad function check". This has no effect on the operation of the device. The error message lets you know that the device is not yet in "S4".

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

149

Functional safety 8.7 PROFIsafe

8.7.6

Write protection

8.7.6.1

Overview

Write protection
The following write-protection options are available:
 Lock or unlock device The dialog box shows the current write protection. If you have activated write protection with PIN, you can lock or unlock the device with the PIN here.
Default PIN: 2457
 Change stored PIN The dialog box shows the current write protection. In addition, you enter your desired PIN here.
 Enter Super PIN If you have forgotten your PIN, it is possible to deactivate the write protection by entering the super PIN. The device resets the PIN to the default value.
Super PIN: G73KMQ2W

See also

Activate write protection using PIN in SIMATIC PDM (Page 151) Activate and parameterize PROFIsafe with SIMATIC PDM (Page 152) Disable write protection using PIN in SIMATIC PDM (Page 160)

150

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

8.7.6.2

Activate write protection using PIN in SIMATIC PDM

Requirement

The device is in the PROFIsafe commissioning status "S1".

Procedure for creating user-defined PIN
1. In the "Device" menu, select the "Write protection" command. 2. Click the "Change PIN" button.
An additional dialog opens. 3. Enter the desired PIN. 4. Click "OK".
The dialog closes. 5. Click the "ON" button. 6. Click the "Close" button.
Create default PIN 1. In the "Device" menu, select the "Write protection" command. 2. Click the "ON" button.

Result

The "Write protection" dialog is closed. A user-defined PIN has been created for the write protection.

Functional safety 8.7 PROFIsafe

8.7.7

PROFIsafe Commissioning

Requirement

Before you commission the PROFIsafe device, configure it, for example in STEP 7.

Process

Activate and parameterize PROFIsafe with SIMATIC PDM (Page 152) Commission PROFIsafe with SIMATIC PDM (Page 153) Check write protection with SIMATIC PDM (Page 158)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

151

Functional safety 8.7 PROFIsafe

8.7.7.1

Activate and parameterize PROFIsafe with SIMATIC PDM

Procedure

1. Click the "Upload to PC" button. SIMATIC PDM reads in the parameters from the device.
2. Under ">> PROFIsafe", set the "PROFIsafe activation" parameter to "Yes". 3. Set the "F_Dest_ADD" parameter so that it has the same value as in HW Config. 4. If you must change other parameters, then parameterize them. 5. Press the "Download to device" button.

Result

The device has activated the PROFIsafe functionality. The relevant menus for PROFIsafe commissioning are active in SIMATIC PDM.
Note If you want to change the "F_Dest_ADD" parameter later, reset the device. Resetting the device (Page 159)

152

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe

8.7.7.2

Commission PROFIsafe with SIMATIC PDM

Start PROFIsafe commissioning
1. In the "Device" menu, select the "Wizard - PROFIsafe commissioning" command.

The "Wizard - PROFIsafe commissioning" dialog box is opened.

2. Click "Next".
SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

153

Functional safety 8.7 PROFIsafe

3. If the checksums are the same, select the checkbox. You obtain further information.

4. Click "Next". 5. Click "OK" to confirm the message that follows.

154

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe
6. In the "Device" menu, select the "Wizard - continue PROFIsafe commissioning" command.

The "Wizard - PROFIsafe commissioning" dialog box is opened again.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

155

Functional safety 8.7 PROFIsafe

The PROFIsafe commissioning status shows the following: "S2 = application not inspected".

7. If the checksums are still the same, select the checkboxes. The PROFIsafe commissioning status shows the following: "S3 = inspection completed".

156

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

8. Click "Next".

Functional safety 8.7 PROFIsafe

Result

The PROFIsafe commissioning status shows the following: "S4 = PROFIsafe operation mode" 9. Click the "Close" button.
The "Wizard - PROFIsafe commissioning" dialog box is closed. The PROFIsafe device is in "S4" and is write protected accordingly.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

157

Functional safety 8.7 PROFIsafe

8.7.7.3

Check write protection with SIMATIC PDM

Procedure

To check the write protection in the PROFIsafe Commissioning State, e.g. "S4", proceed as follows:
1. In the "Device" menu, select the "Write protection" command.
2. Make sure that the second option checkbox is active.

Note Local operation The write protection in the PROFIsafe Commissioning State "S4" restricts local operation. The parameters that affect the local appearance of the display can be adjusted.
Note SIMATIC PDM operation The write protection in the PROFIsafe commissioning status "S4" allows the maintenance timer to be changed, for example for the calibrating interval of the electronics and for the servicing interval of the sensor.
Note Additional write protection by HOST The additional write protection by HOST is set in Continuous Function Chart (CFC) in the F_PA_AI function block, I_PAR_EN parameter.
Note If you need a user-defined PIN write protection, you will find it in the appropriate chapter.

158

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Functional safety 8.7 PROFIsafe

See also

Overview (Page 150) Activate write protection using PIN in SIMATIC PDM (Page 151)

8.7.7.4

Speeding up the commissioning process

Parameter setting
During PROFIsafe commissioning you only have 60 seconds for confirmation between steps S3 and S4.
Proceed as follows to speed up commissioning of the device:
1. Insert the blocks from the library into the CFC and interconnect them. Show the properties of the "F_PA_AI" block.
2. Go to the folder "Connections" and change the preselection of the "IPAR_EN" connection from hidden to visible.
3. Close the "Properties" menu. The input "IPAR_EN" is now visible at the "F_PA_AI" block.
4. Assign this input with "1." Write protection of the host is now cancelled.
5. Now go to the PDM table of SITRANS P DSIII PA PROFIsafe
6. Set the "Service Diagnostics" parameter to locked under "Performance > Status/Diagnostics add-on."
7. Save this setting before commissioning.
8. Once you have concluded commissioning, unlock the "Service Diagnostics" parameter once again to receive all diagnostics information of the device.

8.7.7.5

Resetting the device
The following procedure no longer belongs to standard commissioning. Take the following steps only when necessary.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

159

Functional safety 8.7 PROFIsafe

Procedure

1. Select the "Master Reset" command in the "Device" menu. The "Master Reset - ..." dialog opens.
2. Click the "Warm restart" button.
Note Procedure when subsequently changing the F parameter 1. Carry out a change to an F parameter using HW Config or PDM. 2. Select the "Reset" command in the "Device" menu.
The "Reset - ..." dialog opens. 3. Click the "Warm restart" button.
As a result of the warm restart, the change to the F parameter is included in the cyclic communication procedure.

8.7.8

Quit PROFIsafe commissioning

8.7.8.1

Preparations for maintenance and service

Procedure

Before you perform maintenance on a PROFIsafe device, proceed as follows: 1. Deactivate "PROFIsafe Commissioning". 2. Disable the write protection.

8.7.8.2

Deactivating PROFIsafe commissioning in SIMATIC PDM

Procedure

1. In the "Device" menu, select the "Wizard - PROFIsafe commissioning" command. 2. Click the "Change to unsafe mode" button. 3. Click the "Close" button.

8.7.8.3

Disable write protection using PIN in SIMATIC PDM

Procedure

1. In the "Device" menu, select the "Write protection" command. 2. Click on the "OFF" button. 3. Enter the user-defined PIN, the default PIN, or the super PIN.

160

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

See also

Overview (Page 150)

Functional safety 8.7 PROFIsafe

8.7.9

Replacing a device
Replacing a PROFIsafe device with firmware <= 0301.02.02 or a PROFIBUS device with a PROFIsafe device with firmware 0301.02.03 or higher
When shipped, PROFIsafe is disabled on the replacement device.

Requirement

Import the PROFIsafe EDD as of version 01.02.03 to the device catalog of SIMATIC PDM.

Process

1. Replace the device. 2. Configure the device. You have two options:
­ Making settings locally ­ Host system The EDD of the new device must be reassigned to that of the replaced PDM object. Making the reassignment in the "Process Devices - Network View" of the SIMATIC Manager.

8.7.9.1

Making settings locally

Procedure

1. Set mode 16. 2. Set the device mode [129] with the [] and [] keys. 3. Save with the [M] key.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

161

Functional safety 8.7 PROFIsafe
Device modes
Display Meaning [0]: Profile-compliant: Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0, with analog input function block (without totalizer) (as standard device only) [1]: State as shipped Profile-compliant with expansions: Full range of functions of the SITRANS P, series DS III PROFIsafe with: · Analog input function block · Safe analog input · Totalizer PROFIsafe communication in mode V1 or V2 possible [2]: Can be replaced by the predecessor device SITRANS P, series DS III PA (only as standard device)
[128]: Profile-compliant: Exchangeable for pressure transmitters with PROFIBUS PA Profile 3.0 (as standard device only) · Analog input function block · Totalizer
[129]: · Can be replaced by SITRANS P, series DS III PROFIsafe with PROFIsafe communication only possible in V1 mode.
· In this device operating mode a SITRANS P, DS III PA series (standard device with Profibus Profile 3.00 or 3.01) can be replaced by a SITRANS P, DS III PROFIsafe series (firmware version 0301.02.03 or higher).

8.7.9.2

A specific Generic Station Description (GSD) file is assigned to each device mode:
Display File name [0]: pa_29700.gsd or pa_39700.gsd [1]: siem8170.gsd [2]: sip1804B.gsd
[128]: pa_29740.gsd or pa_39740.gsd [129]: SI0180A6.gsd or SIEM80A6.gsd or SI0280A6.gsd
Configuration with host system
Note Generic Station Description (GSD) The generic station description file in HW Config remains the same: SI0180A6.gsd.

162

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Procedure

Functional safety 8.7 PROFIsafe
1. Using the EDD, change the "PROFIBUS Ident Number" parameter from manufacturer specific (3.01), PROFIsafe V1/V2 to manufacturer specific (3.01), PROFIsafe V1, if you want to operate your devices with PROFIsafe V1.

Result See also

Note Write protection Check whether or not write protection is disabled. If write protection is enabled, no further configuration is possible, If write protection is enabled, disable it.
2. Commission PROFIsafe as described in section PROFIsafe Commissioning (Page 151) .
After downloading the data to the device, cyclic communication with the device is once again possible.
Activate and parameterize PROFIsafe with SIMATIC PDM (Page 152) Commission PROFIsafe with SIMATIC PDM (Page 153)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

163

Functional safety 8.7 PROFIsafe

164

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Configuration/project engineering

9

9.1

Cyclical data transfer

Cyclical data transmission is used to transfer user data relevant for process automation between the control or automation system (class 1 master) and the pressure transmitter.

Setting the PROFIBUS address
The PROFIBUS is set to 126 at the factory. You set it at the device or using a parameterization tool through the bus, e.g.:
 SIMATIC PDM  HW Config The new address will take effect either after the first warm start or when the device is disconnected temporarily from the bus.

9.2

Configuring

9.2.1

Overview of configuration

General

Information on the input and output range as well as the consistency of cyclically transmitted data is defined in the device master data file (GSD file). Using the configuration packet, it is checked by the device and declared valid. During projection it must be determined which data will be transmitted in cyclical operation. This allows the optimization of the data quantity to be transmitted. In the Siemens control system, the GSD files of all the usual devices are already available, and they are also available on the Internet and can be imported later.

Reference

http://www.ad.siemens.de/csi_e/gsd

9.2.2

Configuration of user data
The user data which are provided through the PROFIBUS to the control system are based on the selected target configuration. User data is generated by the function blocks and assembled in the following order:

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

165

Configuration/project engineering 9.2 Configuring
Analog input function block The Analog input function block provides the content of the "Output" parameter. The Totalizer function block provides the content of the "Totalizer output" parameter. You can
select in the configuration which function block is used to generate the output data:  Output  Totalizer output In the "Totalizer output" parameter you can insert the following additional functions:  Reset totalizer output  Operating mode Using "Reset totalizer output" you can reset the integrator from the application program, and with "Operating mode" you can determine its function.
Note For STEP 7, the configuration tool is HW Config. For STEP 5, the configuration tool is COM_PROFIBUS.

User data

Table 9- 1 User data dependent on the selected function block

Function block / parameter
Analog input/output

Byte
1-4 5.

User data, sent to master Measured value Status

User data, sent from master ---

Totalizer / totalizer 6-9 Measured value ---

output

5 Status

Meaning,
depending on parameter
Pressure, height, volume, mass flow, volume flow, sensor temperature, electronics temperature
Mass or volume

Table 9- 2 User data, dependent on selected additional function in the totalizer output function block

Additional function Byte

Reset totalizer

1

output

User data, sent to master ---

User data,
sent from master Reset totalizer output

Meaning
Totalizer reset function 0 Normal operation of totalizer
Integration running. 1 Step integration and reset
integrator back to 0. 2 Stop integration and load
integrator with preset value.

166

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

See also

Configuration/project engineering 9.2 Configuring

Additional function Byte Operating mode 2

User data, sent to master ---

User data, sent from master Operating mode

Meaning
Operating mode of totalizer 0 Net counter - count up and
down. 1 Ascending counter 2 Descending counter 3 Hold count.

Analog input function block (Page 104) Flow measurement (Page 111)

9.2.3

Transmission of user data over PROFIBUS
User data is continually updated via PROFIBUS cyclical data transmission.

Table 9- 3 IEEE standard floating point representation of the measured value

Bits

7

6

5

4

3

2

1

0

Byte

VZ

E

E

E

E

E

E

E

1

27

26

25

24

23

22

21

Byte

E

E

M

M

M

M

M

M

2

20

2-1

2-2

2-3

2-4

2-5

2-6

2-7

Byte

M

M

M

M

M

M

M

M

3

2-8

2-9

2-10

2-11

2-12

2-13

2-14

2-15

Byte

M

M

M

M

M

M

M

M

4

2-16

2-17

2-18

2-19

2-20

2-21

2-22

2-23

VZ Sign

0

positive

1

negative

M mantissa

E exponent

9.2.4

Status
The status provides information on:  Usability of the measured value in the application program  Device status, e.g. self-diagnosis or system diagnostic  Additional process information, for instance process alarms

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

167

Configuration/project engineering 9.2 Configuring

The status code consists of one letter and a three-digit number. The letter stands for:

G

Good

U

Unsure

B

Bad

Table 9- 4 Example status code

Digital display G_141
U_071
B_011

Hex Configured measured value source
8D Electronics temperature, output
47 Output
0B Secondary variable 3

PDM display

Cause

Measure

Good, lower alarm limit violated
Unsure, last usable value, value constant
Bad, not connected, value constant

Lower configured alarm limit Correct error through

violated.

user program.

Input condition "fail safe" is fulfilled, the parameterized safety setting is set to "keep last valid value".

Check the data measurement.

Variable is not calculated, Correct the "transmitter type" setting.

See also

Overview of status codes (Page 189)

9.2.5

Diagnosis
Besides status information, the device can also actively send information about its own state. Diagnostics are important information which an automation system can use to initiate corrective measures.
To transmit diagnostic information, the standard mechanisms of the PROFIBUS DP are used and messages are actively sent to the class 1 master. PROFIBUS DP provides a protocol to transmit information to the class 1 master with a higher priority than the user data.

Messages

The content of the "Device state" parameter from the physical block is sent, along with information about whether a state change (event incoming/event sent) has occurred.
The diagnostic object consists of four bytes. For the pressure transmitter, only the first two bytes are relevant.

Table 9- 5 Diagnostics messages

Byte

Bit

Byte 0 0

1

Meaning of "1"

Cause

Measure

168

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Configuration/project engineering 9.2 Configuring

Byte

Bit

2

3

4

5
6 7 Byte 0 0 1 2 3
4
5
6 7

Meaning of "1"

Cause

Measure

Electronics temperature too high
Memory errors
Error recording measured value

The transmitter monitors the temperature of the transmitter electronics. If this exceeds 85 °C, this message is generated.
During operation, the memory of the cells and the electronics is continually checked for checksum errors and read/write errors. In case of error, this message is generated.
In case of a sensor failure or the violation of control limits (< -20 % or > +20 % of the nominal measurement range)

Reduce the ambient temperature to the permitted range.
Replace the electronics and, if necessary, the sensor.
Have a service technician check the sensor.

Restart executed (goes to "0" after 10 seconds)

Power was applied to the device, or a warm start was performed using SIMATIC PDM, or the internal watchdog triggered.

Restart
Goes to "0" after 10 seconds

The device was reset to the factory settings.

Service necessary

A calibration or service interval has run out.

Check the wiring and the supply voltage.
Perform the calibration or service and clear the message and reset the messages using SIMATIC PDM.

Ident number changed

You changed the parameter "PROFIBUS Ident Number" during cyclical operation. The device signals the change to the ident number and shows a shutdown warning. In case of a restart, the device will no longer participate in cyclic user data exchange unless the system configuration is changed.

Make a change to the configuration data (change the GSD file) so that it matches the ident number configured in the device.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

169

Configuration/project engineering 9.3 Acyclic data transfer

Note
The device state can be simulated using SIMATIC PDM. This allows you to check the reaction of the automation system to an error.

9.3

Acyclic data transfer

Acyclic data transmission is used primarily for the transmission of parameters:

 During commissioning
 During service
 In batch processes
 To display additional measurement data which is not sent during cyclic user data transmission, e.g. raw pressure value

The data traffic between a class 2 master and the field device occurs over a so-called C2 connection. So that multiple class 2 masters can access the same pressure transmitter at the same time, the device supports up to four C2 connections. However, you must ensure that the same data is not being written.

170

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Commissioning

10

10.1

Basic safety instructions
DANGER Toxic gases and liquids Danger of poisoning when venting the device: if toxic process media are measured, toxic gases and liquids can be released. · Before venting ensure that there are no toxic gases or liquids in the device, or take the
appropriate safety measures.
WARNING Improper commissioning in hazardous areas Device failure or danger of explosion in hazardous areas. · Do not commission the device until it has been mounted completely and connected in
accordance with the information in Chapter "Technical data (Page 193)". · Before commissioning take the effect on other devices in the system into account.
WARNING Opening device in energized state Danger of explosion in areas subject to explosion hazard. · Only open the device in a de-energized state. · Check prior to commissioning that the cover, cover locks, and cable inlets are
assembled in accordance with the directives. Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in energized state in hazardous areas.

10.2

Introduction to commissioning
Following commissioning, the pressure transmitter is immediately ready for use.
To obtain stable measured values, the pressure transmitter needs to be allowed to warm up for around 5 minutes after the power supply is switched on. When it starts up, the pressure transmitter goes through an initialization routine (display at the end: "Init done"). If the pressure transmitter does not complete the initialization routine, check the auxiliary power.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

171

Commissioning 10.3 Gauge pressure, absolute pressure from differential pressure series, and absolute pressure from gauge pressure series
The operating data must correspond to the values specified on the nameplate. If you switch on the auxiliary power, the pressure transmitter is in operation. The following commissioning cases are typical examples. Configurations different from those listed here may be meaningful depending on the system configuration.

10.3

Gauge pressure, absolute pressure from differential pressure series,

and absolute pressure from gauge pressure series

10.3.1

Commissioning for gases
Usual arrangement

Special arrangement

Measuring gases above the pressure tapping Measuring gases below the pressure tapping

point

point

172

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Commissioning 10.3 Gauge pressure, absolute pressure from differential pressure series, and absolute pressure from gauge pressure ser

 Pressure transmitter

 Pressure line

 Shut-off valve

 Shut-off valve

 Shut-off valve to process

 Shut-off valve (optional)

 Shut-off valve for test connection or for  Condensate vessel (optional)

bleed screw

 Drain valve

Requirement

All valves are closed.

Procedure

To commission the pressure transmitter for gases, proceed as follows:
1. Open the shut-off valve for the test connection . 2. Via the test connection of the shut-off valve , apply the pressure corresponding to the
start of scale value to the pressure transmitter .
3. Check the start of scale value.
4. If the start of scale value differs from the value desired, correct it.
5. Close the shut-off valve for the test connection . 6. Open the shut-off valve  at the pressure tapping point. 7. Open the shut-off valve for the process .

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

173

Commissioning
10.3 Gauge pressure, absolute pressure from differential pressure series, and absolute pressure from gauge pressure series

10.3.2

Commissioning with steam or liquid

 Pressure transmitter  Shut-off valve  Shut-off valve to process  Shut-off valve for test connection or for bleed screw  Pressure line  Shut-off valve  Blow-out valve  Compensation vessel (steam only)
Image 10-1 Measuring steam

Requirement

All valves are closed.

Procedure

To commission the pressure transmitter for steam or liquid, proceed as follows:
1. Open the shut-off valve for the test connection . 2. Via the test connection of the shut-off valve , apply the pressure corresponding to the
start of scale value to the pressure transmitter .
3. Check the start of scale value. 4. If the start of scale value differs from the value desired, correct it.
5. Close the shut-off valve for the test connection .

174

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Commissioning 10.4 Differential pressure and flow rate
6. Open the shut-off valve  at the pressure tapping point. 7. Open the shut-off valve for the process .

10.4

Differential pressure and flow rate

10.4.1

Safety notes for commissioning with differential pressure and flow rate
WARNING Incorrect or improper operation If the lock screws are missing or are not sufficiently tight, and/or if the valves are operated incorrectly or improperly, it could lead to serious physical injuries or considerable damage to property. Measure · Make sure the locking screw and/or the vent valve are screwed in and tightened. · Ensure that the valves are operated correctly and properly.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

175

Commissioning 10.4 Differential pressure and flow rate

10.4.2

Commissioning in gaseous environments

Usual arrangement

Special arrangement

Pressure transmitter above the differ- Pressure transmitter below the

ential pressure transducer

differential pressure transducer

 Pressure transmitter  Stabilizing valve ,  Differential pressure valves  Differential pressure lines

Requirement

All shut-off valves are closed.

 Shut-off valves  Blow-out valve  Condensation vessels (optional)  Differential pressure transducer

176

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Procedure

Commissioning 10.4 Differential pressure and flow rate
To commission the pressure transmitter for gases, proceed as follows:
1. Open both the shut-off valves  at the pressure tapping point. 2. Open the stabilizing valve . 3. Open the differential pressure valve ( or ).
4. Check and, if necessary, correct the zero point when the start of scale value is 0 kPa.
5. Close the stabilizing valve . 6. Open the other differential pressure valve ( or ).

10.4.3

Commissioning for liquids
Usual arrangement

Special arrangement

Pressure transmitter below the differential Pressure transmitter above the

pressure transducer

differential pressure transducer

 Pressure transmitter  Stabilizing valve ,  Differential pressure valves

 Drain valve  Gas collector vessels (optional)  Differential pressure transducer

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

177

Commissioning 10.4 Differential pressure and flow rate

 Differential pressure lines  Shut-off valves

 Vent valves

Requirement

All valves are closed.

Procedure

DANGER
Toxic liquids
Danger of poisoning when the device is vented.
If toxic process media are measured with this device, toxic liquids can escape when the device is vented. · Before venting, make sure there is no liquid in the device or take the necessary safety
precautions.
To commission the pressure transmitter for liquids, proceed as follows:
1. Open both the shut-off valves  at the pressure tapping point. 2. Open the stabilizing valve .
3. With pressure transmitters below the differential pressure transducer, open both drain
valves one after the other  until the liquid emerges without bubbles.
In the case of a pressure transmitter above the differential pressure transducer, open
both vent valves one after the other  until the liquid emerges without bubbles. 4. Close both drain valves  or vent valves . 5. Open the differential pressure valve  and the vent valve on the positive side of the
pressure transmitter  slightly, until fluid escapes without bubbles.
6. Close the vent valve.
7. Open the vent valve on the negative side of the pressure transmitter  slightly, until fluid
escapes without bubbles.
8. Close the differential pressure valve . 9. Open the differential pressure valve  until the liquid emerges and then close it. 10.Close the vent valve on the negative side of the pressure transmitter . 11.Open the differential pressure valve  by rotating it in half a turn.
12.Check and if required correct the zero point when the start of scale value is 0 kPa.
13.Close the stabilizing valve . 14.Open the differential pressure valves ( and ) completely.

178

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

10.4.4

Commissioning with vapor

Commissioning 10.4 Differential pressure and flow rate



Pressure transmitter



Stabilizing valve

, Differential pressure valves





Differential pressure lines



Shut-off valves

Image 10-2 Measuring steam

 Drain valve  Condensate pots  Differential pressure transducer
 Insulation

Requirement

All valves are closed.

Procedure

WARNING
Hot vapor
Danger of injury or damage to device.
If the shutoff valves  and the differential pressure valve  are both open and the stabilizing valve  is then opened, the pressure transmitter  can be damaged by the
flow of vapor. · Follow the specified procedure for commissioning.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

179

Commissioning 10.4 Differential pressure and flow rate
WARNING Hot vapor Danger of injury.
You can briefly open the drain valves  to clean the line. Hot vapor can escape in the
process.
· Only open the drain valves  briefly, and close them again before vapor escapes.
Note Incorrect measurement results
The measurement result is only free of errors if the differential pressure lines  have
equally high condensate columns with the same temperature. The zero calibration must be repeated, if required, if these conditions are fulfilled.
To commission the pressure transmitter for vapor, proceed as follows:
1. Open both the shut-off valves  at the pressure tapping point. 2. Open the stabilizing valve . 3. Wait till the vapor in the differential pressure lines  and in the condensate pots 
condenses.
4. Open the differential pressure valve  and the vent valve on the positive side of the pressure transmitter  slightly, until condensate escapes without bubbles.
5. Close the vent valve.
6. Open the vent valve on the negative side of the pressure transmitter  slightly, until
condensate escapes without bubbles.
7. Close the differential pressure valve . 8. Open the differential pressure valve  till the air-free condensate goes out and then
close it.
9. Close the vent valve on the negative side . 10.Open the differential pressure valve  by rotating it in half a turn.
11.Check and if required correct the zero point when the start of scale value is 0 kPa.
12.Close the stabilizing valve . 13.Open the differential pressure valve  and  completely. 14.You can briefly open the blow-out valves  to clean the line. Close before steam starts
to leak.

180

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Repair and maintenance

11

11.1

Basic safety instructions
WARNING Impermissible repair of explosion protected devices Danger of explosion in areas subject to explosion hazard. · Repair must be carried out by Siemens authorized personnel only.
WARNING Impermissible accessories and spare parts Danger of explosion in areas subject to explosion hazard. · Only use original accessories or original spare parts. · Observe all relevant installation and safety instructions described in the instructions for
the device or enclosed with the accessory or spare part.
WARNING Use of incorrect device parts in potentially explosive environments Devices and their associated device parts are either approved for different types of protection or they do not have explosion protection. There is a danger of explosion if device parts (such as covers) are used for devices with explosion protection that are not expressly suited for this type of protection. If you do not adhere to these guidelines, the test certificates and the manufacturer warranty will become null and void. · Use only device parts that have been approved for the respective type of protection in
the potentially explosive environment. Covers that are not suited for the "explosionproof" type of protection are identified as such by a notice label attached to the inside of the cover with "Not Ex d Not SIL". · Do not swap device parts unless the manufacturer specifically ensures compatibility of these parts.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

181

Repair and maintenance 11.1 Basic safety instructions

WARNING Maintenance during continued operation in a hazardous area There is a danger of explosion when carrying out repairs and maintenance on the device in a hazardous area. · Isolate the device from power. - or · Ensure that the atmosphere is explosion-free (hot work permit).
WARNING Commissioning and operation with pending error If an error message appears, correct operation in the process is no longer guaranteed. · Check the gravity of the error. · Correct the error. · If the error still exists:
­ Take the device out of operation. ­ Prevent renewed commissioning.

See also

Display in case of a fault (Page 185)
WARNING Hot, toxic or corrosive process media Danger of injury during maintenance work. When working on the process connection, hot, toxic or corrosive process media could be released. · As long as the device is under pressure, do not loosen process connections and do not
remove any parts that are pressurized. · Before opening or removing the device ensure that process media cannot be released.
WARNING Improper connection after maintenance Danger of explosion in areas subject to explosion hazard. · Connect the device correctly after maintenance. · Close the device after maintenance work. Refer to Chapter "Connecting up (Page 63)".

182

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Repair and maintenance 11.1 Basic safety instructions
WARNING Use of a computer in a hazardous area If the interface to the computer is used in the hazardous area, there is a danger of explosion. · Ensure that the atmosphere is explosion-free (hot work permit).
CAUTION Releasing key lock Improper modification of parameters could influence process safety. · Make sure that only authorized personnel may cancel the key locking of devices for
safety-related applications.
CAUTION Hot surfaces Danger of burns during maintenance work on parts having surface temperatures exceeding 70 °C (158 °F). · Take corresponding protective measures, for example by wearing protective gloves. · After carrying out maintenance, remount touch protection measures.
WARNING Hazardous voltage with open device in versions with 4-conductor extension Danger of electrocution when the enclosure is opened or enclosure parts are removed. · Disconnect the device before you open the enclosure or remove enclosure parts. · Observe the special precautionary measures if maintenance is required while the device
is live. Have maintenance work carried out by qualified personnel.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

183

Repair and maintenance 11.2 Maintenance and repair work
NOTICE Electrostatic-sensitive devices The device contains electrostatic-sensitive devices (ESD). ESD can be destroyed by voltages far too low to be detected by humans. These voltages can occur if you simply touch a component part or the electrical connections of a module without being electrostatically discharged. The damage to a module caused by overvoltage cannot normally be detected immediately; it only becomes apparent after a longer period of operating time has elapsed. Protective measures against the discharge of static electricity: · Make sure that no power is applied. · Before working with modules, make sure that you discharge static from your body, for
example by touching a grounded object. · Devices and tools used must be free of static charge. · Hold modules only by their edges. · Do not touch connector pins or conductor tracks on a module with the ESD notice.

11.2

Maintenance and repair work

11.2.1

Defining the maintenance interval
WARNING No maintenance interval has been defined Device failure, device damage, and risk of injury. · Define a maintenance interval for recurring tests depending on the use of the device and
your own experience. · The maintenance interval will vary from site to site depending on corrosion resistance.

184

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Repair and maintenance 11.2 Maintenance and repair work

11.2.2

Checking the gaskets

Inspect the seals at regular intervals
Note Incorrect seal changes Incorrect measured values will be displayed. Changing the seals in a process flange of a differential pressure measuring cell can alter the start-of-scale value. · Changing seals in devices with differential pressure measuring cells may only be carried
out by personnel authorized by Siemens.
Note Using the wrong seals Using the wrong seals with flush-mounted process connections can cause measuring errors and/or damage the diaphragm. · Always use seals which comply with the process connection standards or are
recommended by Siemens.
1. Clean the enclosure and seals. 2. Check the enclosure and seals for cracks and damage. 3. Grease the seals if necessary.
- or 4. Replace the seals.

11.2.3

Display in case of a fault
Check the start of scale value of the device from time to time. Differentiate between the following in case of a fault:  The internal self test has detected a fault, e.g. sensor break, hardware fault/Firmware
fault. Displays: ­ Display: display "ERROR" ­ PROFIBUS: B_016: sensor error
diagnostics in measured-value recording  Grave hardware faults, the processor is not functioning.
Displays: ­ Display: no defined display ­ PROFIBUS: slave not available

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

185

Repair and maintenance 11.3 Cleaning

In case of defect, you can replace the electronic unit by following the warning notes and the provided instruction manual.

See also

Error display (Page 74)

11.2.4 Related

Changing the measuring cell and application electronics
Each of the individual components "Measuring cell" and "Electronics" has a non-volatile memory (EEPROM).
Measuring cell data (e.g.: measuring range, measuring cell material, oil filling) and application-specific electronics data (e.g.: downscaling, additional electrical damping) are located in the measuring cell EEPROM. Application-specific data is lost when the measuring cell is changed. Application-specific data is not lost when the application electronics is changed.
You can backup application-specific data before changing the measuring cell and reload it afterwards. Use an input device which supports the PROFIBUS protocol (e.g. PROFIBUS communicator, PC with PROFIBUS modem and PROFIBUS software or PC with PROFIBUS modem and PDM software). Factory settings will be used if application-specific data is not backed up before the measuring cell is changed.
Technical developments enable advanced functions to be implemented in the firmware of the measuring cell or application electronics. Further technical developments are indicated by modified firmware statuses (FW). The firmware status does not affect whether the modules can be replaced. However, the scope of functions is limited to the function of existing components.
If a combination of certain firmware versions of measuring cell and application electronics is not possible for technical reasons, the device will identify this problem and go into "Fault current" mode. This information is also provided over the PROFIBUS interface.

11.3

Cleaning
WARNING Dust layers above 5 mm Danger of explosion in hazardous areas. Device may overheat due to dust build up. · Remove dust layers in excess of 5 mm.

186

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Repair and maintenance 11.4 Return procedure
NOTICE Penetration of moisture into the device Device damage. · Make sure when carrying out cleaning and maintenance work that no moisture
penetrates the inside of the device.
Cleaning the enclosure
 Clean the outside of the enclosure and the display window using a cloth moistened with water or a mild detergent.
 Do not use aggressive cleaning agents or solvents. Plastic components or painted surfaces could be damaged.
WARNING Electrostatic charge Danger of explosion in hazardous areas if electrostatic charges develop, for example, when cleaning plastic surfaces with a dry cloth. · Prevent electrostatic charging in hazardous areas.

11.3.1

Servicing the remote seal measuring system
The remote seal measuring system usually does not need servicing. If the mediums are contaminated, viscous or crystallized, it could be necessary to clean the diaphragm from time to time. Use only a suitable solvent to remove the deposits from the diaphragm. Do not use corrosive cleaning agents. Prevent the diaphragm from getting damaged due to sharp-edged tools.
NOTICE Improper cleaning of diaphragm Device damage. The diaphragm can be damaged. · Do not use sharp or hard objects to clean the diaphragm.

11.4

Return procedure
Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

187

Repair and maintenance 11.5 Disposal
Required forms
 Delivery note  Return goods delivery note
(http://www.siemens.com/processinstrumentation/returngoodsnote)
with the following information:
­ Product (item description)
­ Number of returned devices/replacement parts
­ Reason for returning the item(s)
 Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."
If the returned device/replacement part has come into contact with poisonous, corrosive, flammable or water-contaminating substances, you must thoroughly clean and decontaminate the device/replacement part before returning it in order to ensure that all hollow areas are free from hazardous substances. Check the item after it has been cleaned.
Any devices/replacement parts returned without a decontamination declaration will be cleaned at your expense before further processing.
The forms can be found on the Internet as well as in the documentation which comes with the device.

11.5

Disposal
Devices identified by this symbol may not be disposed of in the municipal waste disposal services under observance of the Directive 2002/96/EC on waste electronic and electrical equipment (WEEE). They can be returned to the supplier within the EC or to a locally approved disposal service. Observe the specific regulations valid in your country.
Note Special disposal required The device includes components that require special disposal. · Dispose of the device properly and environmentally through a local waste disposal
contractor.

188

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Interrupts, error and system alarms

12

12.1

Overview of status codes

Table 12- 1 Status code

Display
G_132
G_137 G_138 G_141 G_142 G_164 U_071

Hex configured measured value PDM display source

80 Electronics temperature, ---

sensor temperature, raw pressure value, secondary variable 1, secondary variable 2, measured value (primary variable), secondary variable 3, output, totalizer output

84 Electronics temperature, Good,

sensor temperature, raw pressure value, secondary variable 1, secondary variable 2, measured value (primary variable), secondary variable 3, output, totalizer output

update.event

89 Output, totalizer output

Good,

warning limit exceeded

8A Output, totalizer output

Good,

warning limit exceeded

8D Electronics temperature, output, totalizer output

Good, alarm limit violated

8E Electronics temperature, output, totalizer output

Good, alarm limit violated

A4 Raw pressure value, sec- Good, ondary variable 1, second- Service required ary variable 2, measured value (primary variable), secondary variable 3, output, totalizer output

47 Output

Unsure,

Last usable value, value constant

Cause Normal operation

Measure ---

A parameter relevant to the behavior of the slave was changed.
The display goes off after 10 sec.

Note to the control system.

Configured low warn- Correct error through

ing limit violated.

user program.

High configured warn- Correct error through

ing limit violated.

user program.

Configured low alarm limit violated.
High configured alarm limit violated.
Service interval expired: Calibrate or service.

Correct error through user program.
Correct error through user program.
Service, calibration of the electronics, or service of the sensor cell is necessary.

Input condition "fail safe" is fulfilled, the parameterized safety setting is set to "keep last valid value".

Check the data measurement.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

189

Interrupts, error and system alarms 12.1 Overview of status codes

Display U_072
U_075 U_079 U_080 U_081 U_082 B_000 B_004 B_011

Hex configured measured value PDM display source

Cause

Measure

48 Totalizer output

Unsure, Replacement value

Use of the totalizer block if the measured value status is "Bad" and the parameterized safety setting is "Safe operation". The summed value changes. Failure behavior = safe operation.

Check the data measurement.

4B Output, totalizer output

Unsure,
Replacement value, value constant

Value is not an automatic measurement value. A parameterizable, static replacement value or preset value is marked in this manner.

Check the data measurement.

4F Output, totalizer output

Unsure,
Initial value, value constant

An initial value is written to the device memory after startup.

Throw away the value in the application program.

50 Raw pressure value, sec- Unsure, ondary variable 1, second- Value inexact ary variable 2, measured value (primary variable), secondary variable 3, output, totalizer output

Impermissible operating parameter or service alarm.

Check the operating parameters, e.g. the permissible ambient temperature. Immediate service required.

51 Raw pressure value, sec- Unsure,

Low nominal range

ondary variable 1, secondary variable 2, measured value (primary variable),

Value inexact, limit value violated

measurement limit violated (<0%).

secondary variable 3, out-

put, totalizer output

Increase the pressure in the positive direction.

52 Raw pressure value, sec- Unsure,

High nominal range

ondary variable 1, secondary variable 2, measured value (primary variable),

Value inexact, limit value violated

measurement limit violated (>100%).

secondary variable 3, out-

put, totalizer output

Reduce the pressure.

00 Output (cyclical data only), Bad totalizer output (cyclical data only)

Used if no other infor- mation is available.
Device does not exist or cyclical connection is interrupted.

04 Raw pressure value, sec- Bad,

Calibration span too

ondary variable 1, second- Configuration error small. ary variable 2, measured

value (primary variable),

secondary variable 3, out-

put 1), totalizer output 2)

Repeat the calibration procedure with pressure values which are farther apart.

0B Secondary variable 3

Bad,

Variable is not calcu-

not connected, value lated

constant

Correct the "transmitter type" setting.

190

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Interrupts, error and system alarms 12.1 Overview of status codes

Display B_012 B_015 B_016 B_017 B_018 B_031 B_060

Hex configured measured value PDM display source

Cause

Measure

0C Raw pressure value, sec- Bad, ondary variable 1, second- Device error ary variable 2, measured value (primary variable), secondary variable 3, output 1), totalizer output 2)

Device has an irrepa- Replace the electronics. rable error

0F Raw pressure value, sec- Bad,

Device has an irrepa- Replace the electronics.

ondary variable 1, secondary variable 2, measured value (primary variable),

Device error, value constant

rable error

secondary variable 3, out-

put 1), totalizer output 2)

10 Raw pressure value, sec- Bad, ondary variable 1, second- Sensor error ary variable 2, measured value (primary variable), secondary variable 3, output 1), totalizer output 2)

Sensor indicates an error.

Have a service technician check the sensor.

11 Raw pressure value, sec- Bad,

ondary variable 1, secondary variable 2, measured value (primary variable),

Sensor error, limit value violated

secondary variable 3, out-

put 1), totalizer output 2)

Negative pressure too high. Low control limit violated (<-20% of nominal measurement range).

Increase the pressure in the positive direction.

12 Raw pressure value, sec- Bad,

ondary variable 1, secondary variable 2, measured value (primary variable),

Sensor error, limit value violated

secondary variable 3, out-

put 1), totalizer output 2)

Positive pressure too high. High control limit violated (>120% of nominal measurement range).

Reduce the pressure.

1F Output, totalizer output

Bad,
Out of service, value constant

Function block was placed out of service with a target mode command. A parameterized safety value is output.

For normal operation, reset the target mode to AUTO.

3C Output

Bad; configuration error

Device is not yet in safe state.

Complete PROFIsafe commissioning.

1) Only if the failure behavior of the analog input function block is set to "The incorrectly calculated measured value is on output".

2) Only if the failure behavior of the totalizer function block has been set to "Operation".

See also

Error display (Page 74) Status display (Page 76) Status (Page 167)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

191

Interrupts, error and system alarms 12.2 Errors

12.2

Errors

Errors and error correction

Errors
Measured value
Measured value shows up on the display but is not displayed in the control system.

Cause · Mode 15

· Mode 16

Measure
· Check whether the bus address on the device matches the bus address in the control system. If it does not match, correct the bus address.
· Set "ident" in mode 16.

See also

Table 12- 2 Error message

Display F_001 F_003

PDM display -

F_004

-

F_005

-

F_006

-

F_007

-

F_008

-

Cause

Measure

Local operation blocked.

Remove write protection.

Changes to the bus address and device operating type are not possible, since the device is in communication with a class 1 master.

End communication with class 1 master.

Display overflow.

Check settings of physical unit and position of decimal point, and adjust to the current measured value.

Value is read-only.

-

Correction not successful.

Check calibration span and repeat procedure.

After zero-point calibration,

Check measurement range,

measurements no longer possi- decrease correction if neces-

ble in entire measurement range. sary.

Local operation blocked by SIMATIC PDM.

Use SIMATIC PDM to set the "Local operation" parameter to "released".

Status (Page 167)

192

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data

13

13.1

Overview of technical data

Introduction

The following overview of technical data provides you with a quick and easy access to relevant data and characteristic numbers.
Remember that tables in part contain the data of the three communication types HART, PROFIBUS and FOUNDATIONTM Fieldbus. This data deviates in many cases. Therefore, adhere to the communication type used by you when using the technical data.

Contents of the chapter
 SITRANS P DS III input (Page 194)  SITRANS P410 input (Page 200)  Output (Page 202)  Measuring accuracy of SITRANS P DS III (Page 203)  Measuring accuracy of SITRANS P410 (Page 211)  Operating conditions (Page 214)  Construction (Page 218)  Display, keyboard and auxiliary power (Page 224)  Certificates and approvals (Page 225)  PROFIBUS communication (Page 227)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

193

Technical data 13.2 SITRANS P DS III input

13.2

SITRANS P DS III input

Gauge pressure input

Measured variable

Gauge pressure

Span continuously adjustable) or measuring range, max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive) and max. test pressure (in accordance with DIN 16086) (for oxygen measurement, max. 100 bar and 60 °C ambient temperature/process temperature )

Span 1)
8.3 ... 250 mbar 0.83 ... 25 kPa 0.12 ... 3.6 psi 0.01 ... 1 bar 1 ... 100 kPa

Maximum operating pressure MAWP (PS) 4 bar 400 kPa 58 psi 4 bar 400 kPa

0.15 ... 14.5 psi

58 psi

0.04 ... 4 bar

7 bar

4 ... 400 kPa

0.7 MPa

0.58 ... 58 psi

102 psi

0.16 ... 16 bar

21 bar

16 ... 1600 kPa

2.1 MPa

2.3 ... 232 psi

305 psi

0.63 ... 63 bar

67 bar

63 ... 6300 kPa

6.7 MPa

9.1 ... 914 psi

972 psi

1.6 ... 160 bar

167 bar

0.16 ... 16 MPa

16.7 MPa

23 ... 2321 psi

2422 psi

4 ... 400 bar

400 bar

0.4 ... 40 MPa

40 MPa

58 ... 5802 psi

5802 psi

7 ... 700 bar

800 bar

0.7 ... 70 MPa

80 MPa

102 ... 10153 psi

11603 psi

Low measuring limit2)

· Measuring cell with silicone oil filling

30 mbar a/3 kPa a/0.44 psi a

Maximum test pressure
6 bar 0.6 MPa 87 psi 6 bar 0.6 MPa 87 psi 10 bar 1 MPa 145 psi 32 bar 3.2 MPa 464 psi 100 bar 10 MPa 1450 psi 250 bar 2.5 MPa 3626 psi 600 bar 60 MPa 8702 psi 800 bar 80 MPa 11603 psi

· Measuring cell with inert liquid

30 mbar a/3 kPa a/0.44 psi a

Upper measuring limit Start of scale value

100 % of max. span (for oxygen measurement: max. 100 bar/10 MPa/1450 psi and 60 °C ambient temperature/process temperature)
Between the measuring limits (fully adjustable)

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.
2) With 250mbar/25 kPa/3.6 psi measuring cells, the lower measuring limit is 750 mbar a/75 kPa a/10.8 psi a. The measuring cell is vacuum-tight down to 30 mbar a/3 kPa a/0.44 psi a.

194

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.2 SITRANS P DS III input

gauge pressure input, with flush mounted diaphragm

Measured variable

Gauge pressure

Span (continuously adjustable) or measuring range, max. operating pressure and max. test pressure

Span 1) 0.01 ... 1 bar

Maximum operating pressure MAWP (PS)
4 bar

1 ... 100 kPa

400 kPa

0.15 ... 14.5 psi

58 psi

0.04 ... 4 bar

7 bar

4 ... 400 kPa

0.7 MPa

0.58 ... 58 psi

102 psi

0.16 ... 16 bar

21 bar

0.06 ... 1600 kPa

2.1 MPa

2.3 ... 232 psi

305 psi

0.6 ... 63 bar

67 bar

0.06 ... 6.3 MPa

6.7 MPa

9.1 ... 914 psi

972 psi

Lower measuring limit

· Measuring cell with silicone oil filling

100 mbar a/10 kPa a/1.45 psi a

Maximum test pressure
6 bar 0.6 MPa 87 psi 10 bar 1 MPa 145 psi 32 bar 3.2 MPa 464 psi 100 bar 10 MPa 1450 psi

· Measuring cell with inert liquid

100 mbar a/10 kPa a/1.45 psi a

· Measuring cell with neobee

100 mbar a/10 kPa a/1.45 psi a

Upper measuring limit

100% of maximum span

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

Absolute pressure input, with flush-mounted diaphragm

Measured variable

Absolute pressure

Span (continuously adjustable) or measuring range, max. operating pressure and max. test pressure

Span 1) 43 ... 1300 mbar a

Maximum operating pressure MAWP (PS)
2.6 bar a

Maximum test pressure 10 bar a

4.3 ... 130 kPa a

260 kPa a

1 MPa a

17 ... 525 inH2O a

37.7 psi a

145 psi a

160 ... 5000 mbar a

10 bar a

30 bar a

16 ... 500 kPa a

1 MPa a

3 MPa a

2.32 ... 72.5 psi a

145 psi a

435 psi a

1 ... 30 bar a

45 bar a

100 bar a

0.1 ... 3 MPa a

4.5 MPa

10 MPa a

14.5 ... 435 psi a

653 psi a

1450 psi a

Depending on the process connection, the span may differ from these values

Lower measuring limit

0 mbar a/kPa a/psi a

Upper measuring limit

100% of maximum span

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

195

Technical data 13.2 SITRANS P DS III input

Input pressure transmitter with PMC connection

Measured variable

Gauge pressure

Span (continuously adjustable) or measuring range, max. operating pressure and max. test pressure

Span1) 2) 0.01 ... 1 bar

Maximum operating pressure MAWP (PS)
4 bar

1 ... 100 kPa

400 kPa

0.15 ... 14.5 psi

58 psi

0.04 ... 4 bar

7 bar

4 ... 400 kPa

700 kPa

0.58 ... 58 psi

102 psi

0.16 ... 16 bar

21 bar

0.016... 1.6 MPa

2.1 MPa

2.3 ... 232 psi

305 psi

Lower measuring limit

· Measuring cell with silicone oil filling 2) 100 mbar a/10 kPa a/1.45 psi a

Maximum test pressure
6 bar 600 kPa 87 psi 10 bar 1 MPa 145 psi 32 bar 3.2 MPa 464 psi

· Measuring cell with inert liquid 2)

100 mbar a/10 kPa a/1.45 psi a

· Measuring cell with neobee 2)

100 mbar a/10 kPa a/1.45 psi a

Upper measuring limit

100% of maximum span

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus. 2) For PMC-Style Minibolt, the span should not be less than 500 mbar

Absolute pressure input (from the gauge pressure series)

Measured variable

Absolute pressure

Span (continuously adjustable) or measuring range, maximum operating pressure (as per 97/23/EC pressure device guideline) and maximum test pressure (as per DIN 16086)

Span 1)
8.3 ... 250 mbar a 0.83 ... 25 kPa a 3 ... 100 inH2O a

43 ... 1300 mbar a

4.3 ... 130 kPa a

17 ... 525 inH2O a

160 ... 5000 mbar a

16 ... 500 kPa a

2.32 ... 72.5 psi a

1 ... 30 bar a

0.1 ... 3 MPa a

14.5 ... 435 psi a

Lower measuring limit

· Measuring cell with silicone oil filling

0 mbar a/kPa a/psi a

· Measuring cell with inert liquid

Maximum operating pressure MAWP (PS) 1.5 bar a 150 kPa a 21.8 psi a 2.6 bar a 260 kPa a 37.7 psi a 10 bar a 1 MPa a 145 psi a 45 bar a 4.5 MPa a 653 psi a

Maximum test pressure
6 bar a 600 kPa a 87 psi a 10 bar a 1 MPa a 145 psi a 30 bar a 3 MPa a 435 psi a 100 bar a 10 MPa a 1450 psi a

196

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.2 SITRANS P DS III input

Absolute pressure input (from the gauge pressure series)

for process temperature -20°C <  30 mbar a/3 kPa a/0.44 psi a  60°C (-4°F <   +140°F)

for process temperature 60°C <   100°C (max. 85°C for measuring cell 30 bar) (140°F <   212°F (max. 185°F for measuring cell
435 psi))

30 mbar a + 20 mbar a · ( - 60 °C)/°C 3 kPa a + 2 kPa a · ( - 60 °C)/°C 0.44 psi a + 0.29 psi a · ( - 108 °F)/°F

Upper measuring limit

100 % of max. span (for oxygen measurement: max. 100 bar/10 MPa/1450 psi and 60 °C ambient temperature/process tempera-
ture)

Start of scale value

Between the measuring limits (fully adjustable)

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

Absolute pressure input (from the differential pressure series)

Measured variable

Absolute pressure

Span (continuously adjustable) or measuring range and max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive)

Span 1)
8.3 ... 250 mbar a 0.83 ... 25 kPa a

3 ... 100 inH2O a

43 ... 1300 mbar a

4.3 ... 130 kPa a

17 ... 525 inH2O a

160 ... 5000 mbar a

16 ... 500 kPa a

2.32 ... 72.5 psi a

1 ... 30 bar a

0.1 ... 3 MPa a

14.5 ... 435 psi a

5.3 ... 100 bar a

0.5 ... 10 MPa a

76.9 ... 1450 psi a

Lower measuring limit

· Measuring cell with silicone oil filling

0 mbar a /kPa a /psi a

Maximum operating pressure MAWP (PS) 32 bar a 3.2 MPa a 464 psi a 32 bar a 3.2 MPa a 464 psi a 32 bar a 3.2 MPa a 464 psi a 160 bar a 16 MPa a 2320 psi a 160 bar a 16 MPa a 2320 psi a

· Measuring cell with inert liquid

for process temperature -20°C <   60°C (-4°F <   +140°F)
for process temperature 60°C <   100°C (max. 85°C for measuring cell 30 bar) (140°F <   212°F (max. 185°F for measuring cell 435 psi))

30 mbar a /3 kPa a /0.44 psi a
30 mbar a + 20 mbar a · ( - 60 °C)/°C 3 kPa a + 2 kPa a · ( - 60 °C)/°C 0.44 psi a + 0.29 psi a · ( - 108 °F)/°F

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

197

Technical data 13.2 SITRANS P DS III input

Absolute pressure input (from the differential pressure series)

Upper measuring limit

100 % of max. span (for oxygen measurement: max. 100 bar/10 MPa/1450 psi and 60 °C ambient temperature/process tempera-
ture)

Start of scale value

Between the measuring limits (fully adjustable)

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

Differential pressure and flow rate input
Measured variable
Span (continuously adjustable) or measuring range and max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive)

Differential pressure and flow rate Span 1)
1 ... 20 mbar 0.1 ... 2 kPa 0.4015 ... 8.031 inH2O 1 ... 60 mbar 0.1 ... 6 kPa 0.4015 ... 24.09 inH2O 2.5 ... 250 mbar 0.2 ... 25 kPa 1.004 ... 100.4 inH2O 6 ... 600 mbar 0.6 ... 60 kPa 2.409 ... 240.9 inH2O 16 ... 1600 mbar 1.6 ... 160 kPa 6.424 ... 642.4 inH2O 50 ... 5000 mbar 5 ... 500 kPa 20.08 ... 2008 inH2O 0.3 ... 30 bar 0.03 ... 3 MPa 4.35 ... 435 psi 2.5 ... 250 mbar 0.25 ... 25 kPa 1.004 ... 100.4 inH2O 6 ... 600 mbar 0.6 ... 60 kPa 2.409 ... 240.9 inH2O 16 ... 1600 mbar 1.6 ... 160 kPa 6.424 ... 642.4 inH2O

Maximum operating pressure MAWP (PS) 32 bar 3.2 MPa 464 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 420 bar 42 MPa 6091 psi 420 bar 42 MPa 6091 psi 420 bar 42 MPa 6091 psi

198

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.2 SITRANS P DS III input

Differential pressure and flow rate input
Lower measuring limit · Measuring cell with silicone oil filling

50 ... 5000 mbar 5 ... 500 kPa 20.08 ... 2008 inH2O 0.3 ... 30 bar 0.03 ... 3 MPa 4.35 ... 435 psi

420 bar 42 MPa 6091 psi 420 bar 42 MPa 6091 psi

-100% of max. measuring range (-33 % for 30 bar /3 MPa /435 psi measuring cell) or 30 mbar a /3 kPa a /0.44 psi a

· Measuring cell with inert liquid

for process temperature -20°C <   60°C (-4°F <   +140°F)
for process temperature 60°C <   100°C (max. 85°C for measuring cell 30 bar) (140°F <   212°F (max. 185°F for measuring cell 435 psi))

-100 % of max. measuring range (-33 % for 30 bar/3 MPa/435 psi measuring cell) or 30 mbar a/3 kPa a/0.44 psi a
· -100% of max. measuring range (-33% for 30 bar/3 kPa/435 psi measuring cell)
· 30 mbar a + 20 mbar a · ( - 60 °C)/°C 3 kPa a + 2 kPa a · ( - 60 °C)/°C 0.44 psi a + 0.29 psi a · ( - 108 °F)/°F

Upper measuring limit Start of scale value

100 % of max. span (for oxygen measurement: max. 100 bar/10 MPa/1450 psi and 60 °C ambient temperature/process temperature)
Between the measuring limits (fully adjustable)

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

Level input
Measured variable
Span (continuously adjustable) or measuring range and max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive)

Level Span 1)
25 ... 250 mbar 2.5 ... 25 kPa 10 ... 100 inH2O 25 ... 600 mbar 2.5 ... 60 kPa 10 ... 240 inH2O 53 ... 1600 mbar 5.3 ... 160 kPa 021 ... 640 inH2O 160 ... 5000 mbar 16 ... 500 kPa 2.32 ... 72.5 psi

Maximum operating pressure MAWP (PS)
see the mounting flange

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

199

Technical data 13.3 SITRANS P410 input

Level input Lower measuring limit · Measuring cell with silicone oil filling
· Measuring cell with inert liquid
Upper measuring limit Start of scale value

-100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending on the mounting flange
-100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending on the mounting flange
100% of maximum span
between the measuring limits continuously adjustable

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

13.3

SITRANS P410 input

Gauge pressure input Measured variable Span (continuously adjustable) or measuring range, max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive) and max. test pressure (in accordance with DIN 16086).
Lower measuring limit · Measuring cell with silicone oil filling

Gauge pressure Span 1)
0.01 ... 1 bar 1 ... 100 kPa 0.15 ... 14.5 psi 0.04 ... 4 bar 4 ... 400 kPa 0.58 ... 58 psi 0.16 ... 16 bar 16 ... 1600 kPa 2.3 ... 232 psi 0.63 ... 63 bar 63 ... 6300 kPa 9.1 ... 914 psi 1.6 ... 160 bar 0.16 ... 16 MPa 23 ... 2321 psi

Maximum operating pressure MAWP (PS) 4 bar 400 kPa 58 psi 7 bar 0.7 MPa 102 psi 21 bar 2.1 MPa 305 psi 67 bar 6.7 MPa 972 psi 167 bar 16.7 MPa 2422 psi

30 mbar a/3 kPa a/0.44 psi a

Maximum test pressure
6 bar 0.6 MPa 87 psi 10 bar 1 MPa 145 psi 32 bar 3.2 MPa 464 psi 100 bar 10 MPa 1450 psi 250 bar 2.5 MPa 3626 psi

Upper measuring limit Start of scale value

100% of maximum span Between the measuring limits (fully adjustable)

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

200

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.3 SITRANS P410 input

Differential pressure and flow rate input Measured variable Span (continuously adjustable) or measuring range and max. operating pressure (in accordance with 97/23/EC Pressure Equipment Directive)
Lower measuring limit · Measuring cell with silicone oil filling Upper measuring limit Start of scale value

Differential pressure and flow rate Span 1)
2.5 ... 250 mbar 0.2 ... 25 kPa 1.004 ... 100.4 inH2O 6 ... 600 mbar 0.6 ... 60 kPa 2.409 ... 240.9 inH2O 16 ... 1600 mbar 1.6 ... 160 kPa 6.424 ... 642.4 inH2O 50 ... 5000 mbar 5 ... 500 kPa 20.08 ... 2008 inH2O 0.3 ... 30 bar 0.03 ... 3 MPa 4.35 ... 435 psi 6 ... 600 mbar 0.6 ... 60 kPa 2.409 ... 240.9 inH2O 16 ... 1600 mbar 1.6 ... 160 kPa 6.424 ... 642.4 inH2O 50 ... 5000 mbar 5 ... 500 kPa 20.08 ... 2008 inH2O 0.3 ... 30 bar 0.03 ... 3 MPa 4.35 ... 435 psi

Maximum operating pressure MAWP (PS) 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 160 bar 16 MPa 2320 psi 420 bar 42 MPa 6091 psi 420 bar 42 MPa 6091 psi 420 bar 42 MPa 6091 psi 420 bar 42 MPa 6091 psi

-100 % of max. measuring range (-33 % for 30 bar/3 MPa/435 psi measuring cell) or 30 mbar a/3 kPa a/0.44 psi a
100% of maximum span
Between the measuring limits (fully adjustable)

1) Order the nominal measuring range with the order option Y01 for PROFIBUS PA or FOUNDATION Fieldbus.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

201

Technical data 13.4 Output

13.4

Output

Output

Output signal
· Low saturation limit (fully adjustable)

HART 4 ... 20 mA 3.55 mA, set to 3.84 mA in the factory

PROFIBUS PA and FOUNDATION Fieldbus
Digital PROFIBUS PA or FOUNDATIONTM Fieldbus signal
­

· High saturation limit (fully adjusta- 23 mA, set to 20.5 mA or optionally ­

ble)

22.0 mA in the factory

· Ripple (without HART communica- ISS  0.5 % of the max. output current ­ tion)

adjustable time constants damping coefficient
Adjustable time constants (T63) with local operation
· Current transmitter

0 ... 100 s, continuously adjustable
0 ... 100 s, in steps of 0.1 s Factory-set to 2 s 3.55 ... 23 mA

0 ... 100 s, continuously adjustable
0 ... 100 s, in steps of 0.1 s Factory-set to 2 s ­

· Failure signal

3.55 ... 23 mA

­

Load

Resistor R []

­

· Without HART communication

­

· With HART communication HART communicator (Handheld) SIMATIC PDM
Characteristic curve
Bus physics Polarity-independent

UH Power supply in V ­

R =230 ... 1100 

­

R =230 ... 500 

­

· Linearly increasing or linearly decreasing
· Linear increase or decrease or root extraction increase (only for differential pressure and flow rate)

­

IEC 61158-2

­

Yes

202

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.5 Measuring accuracy of SITRANS P DS III

13.5

Measuring accuracy of SITRANS P DS III

Measuring accuracy (as per EN 60770-1) gauge pressure

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, Turn-Down)
Conformity error at limit point setting, including hysteresis and repeatability
· Linear characteristic curve

r = max. measuring span/set measuring span and nominal measuring range

r  1.25

1.25 < r  30

250 mbar/25 kPa/3.6 psi · Linear characteristic curve

 0.065% r  5

 (0.008 · r + 0.055) % 5 < r  100

1 bar/100 kPa/14.5 psi 4 bar/400 kPa/58 psi 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/12321 psi
· Linear characteristic curve

 0.065% r  3

 (0.004 · r + 0.045) %

3 < r  10

10 < r  100

400 bar/40 MPa/5802 psi 700 bar/70 MPa/10152 psi Effect of ambient temperature · 250 mbar/25 kPa/3.6 psi

 0.075%

 (0.0029 · r + 0.071) %  (0.005 · r + 0.05) %

In percent per 28 °C (50 °F)  (0.16 · r + 0.1) %

· 1 bar/100 kPa/14.5 psi

 (0.05 · r + 0.1) %

· 4 bar/400 kPa/58 psi 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi 400 bar/40 MPa/5802 psi

 (0.025 · r + 0.125) %

· 700 bar/70 MPa/10152 psi

 (0.08 · r + 0.16) %

Long-term stability at ±30 °C (±54 °F)
· 250 mbar/25 kPa/3.6 psi

Per year  (0.25 · r) %

· 1 bar/100 kPa/14.5 psi

In 5 years  (0.25 · r) %

4 bar/400 kPa/58 psi

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

203

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Measuring accuracy (as per EN 60770-1) gauge pressure

· 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi 400 bar/40 MPa/5802 psi

In 5 years  (0.125 · r) %

· 700 bar/70 MPa/10152 psi

In 5 years  (0.25 · r) %

Step response time T63 (without electrical damping) Effect of mounting position
Effect of auxiliary power supply
Measured value resolution for PROFIBUS PA or FOUNDATION Fieldbus

Approx. 0.15 s
 0.05 mbar/0.005 kPa/0.000725 psi per 10° incline (zero-point correction is possible with position error compensation) In percent per change in voltage 0.005 % per 1 V 3 · 10-5 of the nominal measuring range

Gauge pressure measuring accuracy, with flush mounted diaphragm

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, TurnDown)
Conformity error at limit point setting, including hysteresis and repeatability

r = max. measuring span/set measuring span and nominal measuring range

· Linear characteristic curve

r  5 5 < r  100 Effect of ambient temperature In percent per 28 °C (50 °F) Effect of process temperature
· Temperature difference between medium temperature and ambient temperature
Long-term stability at ±30 °C (±54 °F) Step response time T63 without electrical damping Effect of mounting position

 0.075 %  (0.005 · r + 0.05) %
 (0.08 · r + 0.16) In pressure per temperature change 3 mbar per 10 K 0.3 kPa per 10 K 0.04 psi per 10 K In 5 years  (0.25 · r) % Approx. 0.2 s
In pressure per change of angle 0.4 mbar/0.04 kPa/0.006 psi per 10° incline (zero-point correction is possible with position error compensation)

204

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Gauge pressure measuring accuracy, with flush mounted diaphragm

Effect of auxiliary power supply

In percent per change in voltage 0.005 % per 1 V

Measured value resolution for PROFIBUS PA or FOUNDATION Fieldbus

3 · 10-5 of the nominal measuring range

Absolute pressure measuring accuracy with flush diaphragm

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, TurnDown)
Conformity error at limit point setting, including hysteresis and repeatability

r = max. measuring span/set measuring span and nominal measuring range

· Linear characteristic curve

r  10 10 < r  30 Effect of ambient temperature In percent per 28 °C (50 °F) Effect of process temperature · Temperature difference between medium temperature and ambient temperature Long-term stability at ±30 °C (±54 °F) Step response time T63 without electrical damping Effect of mounting position
Effect of auxiliary power supply
Measured-value resolution for PROFIBUS PA or FOUNDATION Fieldbus

 0.2%  0.4%
 (0.16 · r + 0.24) In pressure per temperature change 3 mbar per 10 K 0.3 kPa per 10 K 0.04 psi per 10 K In 5 years  (0.25 · r) % Approx. 0.2 s
In pressure per change of angle 0.04 kPa/0.4 mbar/0.006 psi per 10° incline (zero-point correction is possible with position error compensation) In percent per change in voltage 0.005 % per 1 V 3 · 10-5 of the nominal measuring range

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

205

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Measuring accuracy (according to EN 60770-1) of pressure transmitter with PMC connection

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, TurnDown)
Conformity error at limit point setting, including hysteresis and repeatability

r = max. measuring span/set measuring span and nominal measuring range

· Linear characteristic curve

r  5 5 < r  100 Effect of ambient temperature In percent per 28 °C (50 °F) Effect of process temperature · Temperature difference between medium temperature and ambient temperature Long-term stability at ±30 °C (±54 °F) Step response time T63 without electrical damping Effect of mounting position
Effect of auxiliary power supply
Measured-value resolution for PROFIBUS PA or FOUNDATION Fieldbus

 0.075 %  (0.005 · r + 0.05) %
 (0.08 · r + 0.16) In pressure per temperature change 3 mbar per 10 K 0.3 kPa per 10 K 0.04 psi per 10 K In 5 years  (0.25 · r) % Approx. 0.2 s
In pressure per change of angle  0.1 mbar/0.01 kPa/0.00145 psi per 10° incline (zero point correction is possible with position error compensation) In percent per change in voltage 0.005 % per 1 V 3 · 10-5 of the nominal measuring range

Absolute pressure measuring accuracy (from gauge and differential pressure series)

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, TurnDown)
Conformity error at limit point setting, including hysteresis and repeatability

r = max. measuring span/set measuring span and nominal measuring range

206

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Absolute pressure measuring accuracy (from gauge and differential pressure series) · Linear characteristic curve

r  10 10 < r  30 · Effect of ambient temperature

 0.1%  0.2% In percent per 28 °C (50 °F)

· 250 mbar/25 kPa/3.6 psi

 (0.15 · r + 0.1)

· 1300 mbar a/130 kPa a/18.8 psi a

 (0.08 · r + 0.16)

5 bar a/500 kPa a/72.5 psi a

30 bar a/3000 kPa a/435 psi a

100 bar a/10 MPa a/1450.3 psi a

160 bar a/16 MPa a/2321 psi a

400 bar a/40 MPa a/5802 psi a

700 bar a/70 MPa a/10152.6 psi a

Long-term stability at ±30 °C (±54 °F) In 5 years  (0.25 · r) %

Step response time T63 without electrical Approx. 0.2 s damping

Effect of mounting position

In pressure per change of angle

· for absolute pressure (from the gauge pressure series):  0.05 mbar/0.005 kPa/0.000725 psi per 10° incline

· for absolute pressure (from the differential pressure series): 0.7 mbar/0.07 kPa/0.001015 psi per 10° incline
(zero-point correction is possible with position error compensation)

Effect of auxiliary power supply
Measured value resolution for PROFIBUS PA or FOUNDATION Fieldbus

In percent per change in voltage 0.005 % per 1 V
3 · 10-5 of the nominal measuring range

Differential pressure and flow rate measuring accuracy

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, Turn-Down)
Conformity error at limit point setting, including hysteresis and repeatability

r = max. measuring span/set measuring span and nominal measuring range

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

207

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Differential pressure and flow rate measuring accuracy

· Linear characteristic curve

r  5

5 < r  10

20 mbar/2 kPa/0.29 psi · Linear characteristic curve

 0.075 % r  5

 (0.0029 · r + 0.071) %

60 mbar/6 kPa/0.87 psi · Linear characteristic curve

 0.075 % r  5

250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

 0.065%

· Root extraction characteristic

10 < r  20  (0.0045 · r + 0.071) % 5 < r  60  (0.005 · r + 0.05) % 5 < r  100  (0.004 · r + 0.045) %

Flow > 50 % · 20 mbar/2 kPa/0.29 psi

r  5  0.075 %

5 < r  10

10 < r  20

 (0.0029 · r + 0.071) %  (0.0045 · r + 0.071) %

· Root extraction characteristic Flow > 50 % · 60 mbar/6 kPa/0.87 psi

r  5  0.075 %

5 < r  60  (0.005 · r + 0.05) %

· Root extraction characteristic

Flow > 50 %
· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 p si 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

r  5  0.065%

5 < r  100  (0.004 · r + 0.045) %

· Root extraction characteristic Flow 25 ... 50% · 20 mbar/2 kPa/0.29 psi

r  5  0.15 %

5 < r 10

10 < r  20

 (0.0058 · r + 0.142) %  (0.009 · r + 0.142) %

· Root extraction characteristic

Flow 25 ... 50% · 60 mbar/6 kPa/0.87 psi

r  5  0.15 %

· Root extraction characteristic r  5

· 250 mbar/25 kPa/3.63 psi  0.13% 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 p si 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

Effect of ambient temperature

In percent per 28 °C (50 °F)

5 < r  60  (0.01 · r + 0.1) % 5 < r  100  (0.008 · r + 0.9) %

208

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Differential pressure and flow rate measuring accuracy

· 20 mbar/2 kPa/0.29 psi

 (0.15 · r + 0.1) %

· 60 mbar/6 kPa/0.87 psi

 (0.075 · r + 0.1) %

· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

 (0.025 · r + 0.125) %

Effect of static pressure

· At the start of scale value

20 mbar/2 kPa/0.29 psi
60 mbar/6 kPa/0.87 psi 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

 (0.15 · r) % per 32 bar (zero-point correction is possible with position error compensation)  (0.1 · r) % per 70 bar (zero-point correction is possible with position error compensation)
 (0.2 · r) % per 70 bar (zero-point correction is possible with position error compensation)

· On the measuring span

20 mbar/2 kPa/0.29 psi
60 mbar/6 kPa/0.87 psi 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi
Long-term stability at ±30 °C (±54 °F)
· 20 mbar/2 kPa/0.29 psi

 0.2% per 32 bar  0.14 % per 70 bar
Static pressure max. 70 bar/7 MPa/1015 psi Per year  (0.2 · r) %

· 60 mbar/6 kPa/0.87 psi 30 bar/3 MPa/435.11 psi

In 5 years  (0.25 · r) %

· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi

In 5 years  (0.125 · r) %

Step response time T63 without electrical damping
· 20 mbar/2 kPa/0.29 psi

Approx. 0.3 s

60 mbar/6 kPa/0.87 psi
· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

Approx. 0.2 s

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

209

Technical data 13.5 Measuring accuracy of SITRANS P DS III

Differential pressure and flow rate measuring accuracy

Effect of mounting position

In pressure per change of angle

 0.7 mbar/0.07 kPa/0.028 inH2O per 10° incline (zero-point correction is possible with position error compensation)

Effect of auxiliary power supply

In percent per change in voltage 0.005 % per 1 V

Measured-value resolution for PROFIBUS PA or

3 · 10-5 of the nominal measuring range

FOUNDATION Fieldbus

Level measuring accuracy Reference conditions
Measuring span ratio r (spread, TurnDown) Conformity error at limit point setting, including hysteresis and repeatability · Linear characteristic curve
250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.70 psi
1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
Effect of ambient temperature · 250 mbar/25 kPa/3.63 psi · 600 mbar/60 kPa/8.70 psi · 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi
Effect of static pressure · At the start of scale value
Measuring cell 250 mbar/25 kPa/3.63 psi Measuring cell 600 mbar/60 kPa/8.70 psi

· Rising characteristic curve · Start of scale value 0 bar/kPa/psi · Seal diaphragm stainless steel · Measuring cell with silicone oil filling · Room temperature 25 °C (77 °F)
r = max. measuring span/set measuring span and nominal measuring range

r  5  0.125%
 0.125%  0.125%

5 < r  10

5 < r  25

 (0.007 · r + 0.09) %

 (0.007 · r + 0.09) %

 0.125%

In percent per 28 °C (50 °F)  (0.4 · r + 0.16) %  (0.24 · r + 0.16) %  (0.2 · r + 0.16) %

5 < r  30
 (0.007 · r + 0.09) %  (0.007 · r + 0.09) %

 (0.3 · r) % per nominal pressure  (0.15 · r) % per nominal pressure

210

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.6 Measuring accuracy of SITRANS P410

Level measuring accuracy Measuring cell 1600 mbar/160 kPa/23.21 psi Measuring cell 5 bar/500 kPa/72.52 psi
· On the measuring span

 (0.1 · r) % per nominal pressure  (0.1 · r) % per nominal pressure

Long-term stability at ±30 °C (±54 °F)
Step response time T63 without electrical damping Effect of mounting position Effect of auxiliary power supply
Measured value resolution for PROFIBUS PA or FOUNDATION Fieldbus

in 5 years  (0.25 · r) % static pressure max. 70 bar/7 MPa/1015 psi Approx. 0.2 s
depending on the fill fluid in the mounting flange In percent per change in voltage 0.005 % per 1 V 3 · 10-5 of the nominal measuring range

13.6

Measuring accuracy of SITRANS P410

Measuring accuracy (as per EN 60770-1) gauge pressure

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, TurnDown)
Conformity error at limit point setting, including hysteresis and repeatability
· Linear characteristic curve

r = max. measuring span/set measuring span and nominal measuring range

r  5

5 < r  100

1 bar/100 kPa/14.5 psi 4 bar400 kPa/58 psi 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi Effect of ambient temperature
· 1 bar/100 kPa/14.5 psi

 0.04%
In percent per 28 °C (50 °F)  (0.05 · r + 0.1) %

 (0.004 · r + 0.045) %

· 4 bar/400 kPa/58 psi

 (0.025 · r + 0.125) %

16 bar/1.6 MPa/232 psi

63 bar/6.3 MPa/914 psi

160 bar/16 MPa/2321 psi

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

211

Technical data 13.6 Measuring accuracy of SITRANS P410

Measuring accuracy (as per EN 60770-1) gauge pressure

Long-term stability at ±30 °C (±54 °F)

· 1 bar/100 kPa/14.5 psi

In 5 years  (0.25 · r) %

4 bar/400 kPa/58 psi
· 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi

In 5 years  (0.125 · r) %

Step response time T63 (without electrical damping) Effect of mounting position
Effect of auxiliary power supply
Measured value resolution for PROFIBUS PA or FOUNDATION Fieldbus

Approx. 0.15 s
 0.05 mbar/0.005 kPa/0.02 inH2O per 10° incline (zero point correction is possible with position error compensation) In percent per change in voltage 0.005 % per 1 V 3 · 10-5 of the nominal measuring range

Differential pressure and flow rate measuring accuracy

Reference conditions

· Rising characteristic curve

· Start of scale value 0 bar/kPa/psi

· Seal diaphragm stainless steel

· Measuring cell with silicone oil filling

· Room temperature 25 °C (77 °F)

Measuring span ratio r (spread, Turn-Down)
Conformity error at limit point setting, including hysteresis and repeatability
· Linear characteristic curve

r = max. measuring span/set measuring span and nominal measuring range

r  5

5 < r  100

250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

 0.04%

 (0.004 · r + 0.045) %

· Root extraction characteristic

Flow > 50 %

r  5

· 250 mbar/25 kPa/3.63 psi  0.04% 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 ps i 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

5 < r  30  (0.004 · r + 0.045) %

Flow 25 ... 50%

r  5

5 < r  30

212

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.6 Measuring accuracy of SITRANS P410

Differential pressure and flow rate measuring accuracy
· 250 mbar/25 kPa/3.63 psi  0.08% 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 ps i 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

 (0.008 · r + 0.09) %

Effect of ambient temperature
· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

In percent per 28 °C (50 °F)  (0.025 · r + 0.125) %

Effect of static pressure

· At the start of scale value

250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi
5 bar/500 kPa/72.52 psi
30 bar/3 MPa/435.11 psi

 (0.1 · r) % per 70 bar (zero-point correction is possible with position error compensation)
 (0.2 · r) % per 70 bar (zero-point correction is possible with position error compensation)

· On the measuring span

250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi
Long-term stability at ±30 °C (±54 °F)
· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi

 0.14 % per 70 bar
Static pressure max. 70 bar/7 MPa/1015 psi In 5 years  (0.125 · r) %

· 30 bar/3 MPa/435.11 psi

In 5 years  (0.25 · r) %

Step response time T63 without electrical damping
· 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi

Approx. 0.2 s

Effect of mounting position

In pressure per change of angle  0.7 mbar/0.07 kPa/0.001015 psi per 10° incline (zero-point correction is possible with position error compensation)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

213

Technical data 13.7 Operating conditions

Differential pressure and flow rate measuring accuracy

Effect of auxiliary power supply

In percent per change in voltage 0.005 % per 1 V

Measured value resolution for PROFIBUS PA or FOUNDATION Fieldbus

3 · 10-5 of the nominal measuring range

13.7

Operating conditions

Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series) Installation conditions Ambient conditions · Ambient temperature

Note

Observe the temperature class in hazardous areas.

Measuring cell with sili- -40 ... +100 °C (-40 ... +212 °F) cone oil filling

Measuring cell with inert -20 ... +85 °C (-4 ... +185 °F) liquid

Measuring cell with inert filling liquid for gauge pressure measuring cells 1, 4, 16 and 63 bar

-40 ... +85°C (-40...+185°F)

Display

-30 ... +85 °C (-22 ... +185 °F)

Storage temperature

-50 ... +85 °C (-58 ... +185 °F)

· Climate class

Condensation
· Degree of protection in accordance with EN 60529

Permitted IP66, IP68

· Degree of protection in accordance with NEMA 250

NEMA 4X

· Electromagnetic compatibility

Interference emission

In accordance with EN 61326 and

and interference immuni- NAMUR NE 21

ty

Process medium conditions

· Process temperature

Cell

Pressure

Measuring cell with silicone oil filling

Temperature range -40 ... +100 °C (-40 ... +212 °F)

214

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.7 Operating conditions

Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)

Measuring cell with inert 1 bar/100 kPa/3.6 psi liquid

-40 ... +100 °C (-40 ... +212 °F)

4 bar/400 kPa/58 psi

-40 ... +100 °C (-40 ... +212 °F)

16 bar/1.6 MPa/232 psi

-40 ... +100 °C (-40 ... +212 °F)

63 bar/6.3 MPa/914 psi

-40 ... +100 °C (-40 ... +212 °F)

160 bar/16 MPa/2321 psi

-20 ... +100 °C (-4 ... +212 °F)

400 bar/40 MPa/5802 psi

-20 ... +100 °C (-4 ... +212 °F)

700 bar/70 MPa/10152 psi

-20 ... +100 °C (-4 ... +212 °F)

With extension to Zone 0

-20 ... +60 °C (-4 ... +140 °F)

Conditions of use for gauge pressure and absolute pressure with flush-mounted diaphragm

Installation conditions

Ambient temperature

Note

Observe the temperature class in hazardous areas.

· Measuring cell with silicone oil filling

-40 ... +85 °C (-40 ... +185 °F)

· Measuring cell with inert liquid (various pressure classes)
· Measuring cell with Neobee (FDA-compliant)

1 bar/100 kPa/3.6 psi 4 bar/400 kPa/58 psi 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi 400 bar/40 MPa/5802 psi 700 bar/70 MPa/10152 psi -10 ... +85 °C (14 ... 185 °F)

-40 ... +100 °C (-40 ... +212 °F) -40 ... +100 °C (-40 ... +212 °F) -40 ... +100 °C (-40 ... +212 °F) -40 ... +100 °C (-40 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F) -20 ... +100 °C (-4 ... +212 °F)

· Display

-30 ... +85 °C (-22 ... +185 °F)

· Storage temperature
Climate class Condensation
· Degree of protection in accordance with EN 60 529

-50 ... +85 °C (-58 ... +185 °F) (with Neobee: -20 ... + 85 °C (-4 ... +185 °F)) (with high-temperature oil: -10 ... + 85 °C (14 ... 185 °F))
Permitted IP66, IP68

· Degree of protection in accordance with NEMA 250

NEMA 4X

Electromagnetic compatibility

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

215

Technical data 13.7 Operating conditions

Conditions of use for gauge pressure and absolute pressure with flush-mounted diaphragm

· Interference emission and In accordance with EN 61326 and

interference immunity

NAMUR NE 21

Process medium conditions Process temperature1) · Measuring cell with sili-
cone oil filling
· Measuring cell with inert liquid
· Measuring cell with Neobee (FDA-compliant)
· Measuring cell with hightemperature oil filling

-40 ... +150°C (-40 ... +302 °F) -40 ... +200°C (-40 ... +392 °F) with cooling extension
-20 ... +100 °C (-4 ... +212 °F) -20 ... +200°C (-4 ... +392 °F) with cooling extension
-10 ... +150°C (14 ... 302 °F) -10 ... +200°C (14 ... 392 °F) with cooling extension
-10 ... +250 °C (14 ... 482 °F) with cooling extension

1) Observe the temperature limits in the process connection standards (e.g. DIN 32676 and DIN 11851) for the maximum process temperature for flush-mounted process connections.

Conditions of use for pressure transmitter with PMC connection

Installation conditions

Ambient temperature

Note

Observe the temperature class in hazardous areas.

· Measuring cell with silicone oil filling

-40 ... +85 °C (-40 ... +185 °F)

· Display

-30 ... +85 °C (-22 ... +185 °F)

· Storage temperature

-50 ... +85 °C (-58 ... +185 °F)

Climate class Condensation
· Degree of protection in accordance with EN 60529

Permitted IP66, IP68

· Degree of protection in accordance with NEMA 250

NEMA 4X

Electromagnetic compatibility
· Interference emission and interference immunity

In accordance with EN 61326 and NAMUR NE 21

Process medium conditions · Process temperature

-40 ... +100 °C (-40 ... +212 °F)

216

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.7 Operating conditions

Rated conditions for absolute pressure (from the differential pressure series), differential pressure and flow rate

Installation conditions

· Installation instruction

any

Ambient conditions

· Ambient temperature

Note
Measuring cell with silicone oil filling

Observe the temperature class in hazardous areas. -40 ... +85 °C (-40 ... +185 °F)

· Measuring cell 30 bar (435 psi)

· -20 ... +85 °C (-4 ... +185 °F) · For flow: -20 ... +85 °C (-4 ... +185 °F)

Measuring cell with inert liquid Display Storage temperature

-20 ... +85 °C (-4 ... +185 °F) -30 ... +85 °C (-22 ... +185 °F) -50 ... +85 °C (-58 ... +185 °F)

· Climate class

Condensation
· Degree of protection in accordance with EN 60529

Permitted IP66, IP68

· Degree of protection in accordance with NEMA 250

NEMA 4X

· Electromagnetic compatibility
Interference emission and interference immunity Process medium conditions
· Process temperature
Measuring cell with silicone oil filling
· Measuring cell 30 bar (435 psi)
Measuring cell with inert liquid
· Measuring cell 30 bar (435 psi)
In conjunction with dust explosion protection

In accordance with EN 61326 and NAMUR NE 21
-40 ... +100 °C (-40 ... +212 °F) -20 ... +85 °C (-4 ... +185 °F) -20 ... +100 °C (-4 ... +212 °F) -20 ... +85 °C (-4 ... +185 °F) -20 ... +60°C (-4 ... +140°F)

Rated conditions for level Installation conditions · Installation instruction Ambient conditions · Ambient temperature

specified through the flange

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

217

Technical data 13.8 Construction

Rated conditions for level Note
Measuring cell with silicone oil filling Display Storage temperature · Climate class

Observe the allocation of the max. permissible operating temperature to the max. permissible operating pressure of the relevant flange connection. -40 ... +85 °C (-40 ... +185 °F)
-30 ... +85 °C (-22 ... +185 °F) -50 ... +85 °C (-58 ... +185 °F)

Condensation
· Degree of protection in accordance with EN 60529

Permitted IP66

· Degree of protection in accordance with NEMA 250

NEMA 4X

· Electromagnetic compatibility

Interference emission and interference immunity
Process medium conditions

In accordance with EN 61326 and NAMUR NE 21

· Process temperature

Measuring cell with silicone oil filling

· Plus side: See mounting flange · Low-pressure side: -40 ... +100 °C (-40 ... +212 °F)

13.8

Construction

Construction for gauge pressure and absolute pressure (from the gauge pressure series)

Weight

Approx. 1.5 kg (3.3 lb) for aluminum enclosure

Material

· Wetted parts materials

Process connection Oval flange Seal diaphragm

Stainless steel, mat. no. 1.4404/316L or Hastelloy C4, mat. no. 2.4610 Stainless steel, mat. no. 1.4404/316L Stainless steel, material no. 1.4404/316L or Hastelloy C276, material no. 2.4819

· Non-wetted parts materials

Electronics housing

· Copper-free die cast aluminum GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408
· Standard: Powder coating with polyurethane Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane
· Stainless steel nameplate

Mounting bracket

Steel or stainless steel

218

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.8 Construction

Construction for gauge pressure and absolute pressure (from the gauge pressure series)

Measuring cell filling

· Silicone oil

· Neobee M20

· Inert liquid (max. 120 bar g (2320 psi g) for oxygen measurement)

Process connection

G1/2B connection pin in accordance with DIN EN 837-1; female thread 1/2-14 NPT or oval flange (PN 160 (MAWP 2320 psi g)) with M10 fastening screw thread in accordance with DIN 19213 or 7/16-20 UNF in accordance with EN 61518. Male thread M20 x 1.5 and 1/2-14 NPT

Electrical connection

Cable inlet using the following cable glands:

· Pg 13.5

· M20 x 1.5 and ½-14 NPT or Han 7D/Han 8D connector1)
­ Cable diameter: 6 to 12 mm; types of protection "nA" and "ic" (Zone 2): 8 to 12 mm or a suitable cable gland for smaller diameters

· M12 connector

Degree of protection for Han and M12 connectors

IP65

1) Han 8D is identical to Han 8U.

Construction for gauge pressure, with flush mounted diaphragm

Weight

Approx 1.5 ... 13.5 kg (3.3 ... 30 lb) with aluminum enclosure

Material

· Wetted parts materials

Process connection Seal diaphragm

Stainless steel, mat. no. 1.4404/316L Stainless steel, mat. no. 1.4404/316L

· Non-wetted parts materials

Electronics housing

· Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408
· Standard: Powder coating with polyurethane Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane
· Stainless steel nameplate

Mounting bracket Measuring cell filling

Steel or stainless steel · Silicone oil · Neobee M20 · Inert liquid

Process connection

· Flanges as per EN and ASME · F&B and Pharma flange, clamp and threaded connectors · NEUMO BioConnect/BioControl · PMC connections for the paper industry

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

219

Technical data 13.8 Construction

Construction for gauge pressure, with flush mounted diaphragm

Electrical connection

Cable inlet using the following cable glands:

· Pg 13.5

· M20x1.5

· ½-14 NPT

· Han 7D/Han 8D plug1)

· M12 connector

Degree of protection for Han and M12 connectors

IP65

1) Han 8D is identical to Han 8U.

Construction of pressure transmitter with PMC connection

Weight

Approx. 1.5 kg (3.3 lb) for aluminum enclosure

Material

· Wetted parts materials

Gasket (standard) O-ring (minibolt)

PTFE flat gasket · FPM (Viton) · FFPM or NBR (optional)

Seal diaphragm · Non-wetted parts materials

Hastelloy C276, mat. No. 2.4819

Electronics housing

· Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408
· Standard: Powder coating with polyurethane Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane
· Stainless steel nameplate

Mounting bracket Measuring cell filling

Steel or stainless steel · Silicone oil · Inert liquid

Process connection · Standard

· Flush mounted · 11/2'' · PMC Standard design

· Minibolt

· Flush mounted · 1'' · PMC Minibolt design

220

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.8 Construction

Construction of pressure transmitter with PMC connection

Electrical connection

Cable inlet using the following cable glands:

· Pg 13.5

· M20 x 1.5

· ½-14 NPT

· Han 7D/Han 8D plug1)

· M12 connector

Degree of protection for Han and M12 connectors

IP65

1) Han 8D is identical to Han 8U.

Design for absolute pressure (from the differential pressure series), differential pressure and flow rate

Weight

Approx. 4.5 kg (9.9 lb) for aluminum enclosure

Material

· Wetted parts materials

Seal diaphragm

Stainless steel, mat. no. 1.4404/316L, Hastelloy C276, mat. no. 2.4819, Monel, mat. no. 2.4360, tantalum or gold

Pressure caps and locking screw Stainless steel, mat. no. 1.4408 to PN 160, mat. no. 1.4571/316Ti for PN 420, Hastelloy C4, 2.4610 or Monel, mat. no. 2.4360

O-ring

FPM (Viton) or optionally: PTFE, FEP, FEPM and NBR

· Non-wetted parts materials

Electronics housing

· Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408
· Standard: Powder coating with polyurethane Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane
· Stainless steel nameplate

Pressure cap screws Mounting bracket Measuring cell filling
Process connection

Stainless steel Steel or stainless steel
· Silicone oil · Neobee M20 · Inert liquid (max. 120 bar g (2320 psi g) for oxygen measurement) 1/4-18 NPT female thread and flat connection with 7/16-20 UNF fastening screw thread in accordance with EN 61518 or M10 fastening screw thread in accordance with DIN 19213 (M12 for PN 420 (MAWP 6092 psi))

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

221

Technical data 13.8 Construction

Design for absolute pressure (from the differential pressure series), differential pressure and flow rate

Electrical connection

Screw terminals

Cable inlet using the following cable glands:

· Pg 13.5

· M20 x 1.5

· ½-14 NPT or Han 7D/Han 8D connector1)

· M12 connector

Degree of protection for Han and M12 connectors

IP65

1) Han 8D is identical to Han 8U.

Construction for level Weight
· as per EN (pressure transmitter with mounting flange, without tube)

approx 11 ... 13 kg (24.2 ... 28.7 lb)

· as per ASME (pressure transmitter with mounting flange, without tube)

approx 11 ... 18 kg (24.2 ... 39.7 lb)

Material

· Wetted parts materials

Plus side · Seal diaphragm on the
mounting flange
· Sealing surface
Sealing material in the pressure caps · for standard applications

Stainless steel, mat. no. 1.4404/316L, Monel 400, mat. no. 2.4360, Hastelloy B2, mat. no. 2.4617, Hastelloy C276, mat. no. 2.4819, Hastelloy C4, mat. no. 2.4610, tantalum, PTFE, ECTFE smooth as per EN 1092-1, form B1 or ASME B16.5 RF 125 ... 250 AA for stainless steel 316L, EN 2092-1 form B2 or ASME B16.5 RFSF for the remaining materials
Viton

· for underpressure applica- Copper tions on the mounting flange

Minus side · Seal diaphragm

Stainless steel, mat. no. 1.4404/316L

· Pressure caps and locking screws

Stainless steel, mat. no. 1.4408

· O-ring

FPM (Viton)

· Non-wetted parts materials

222

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.8 Construction

Construction for level Electronics housing
Pressure cap screws Measuring cell filling · Mounting flange fill fluid Process connection · Plus side · Minus side Electrical connection
Degree of protection for Han and M12 connectors 1) Han 8D is identical to Han 8U.

· Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408
· Standard: Powder coating with polyurethane Option: 2 coats: Coat 1: epoxy-based; coat 2: polyurethane
· Stainless steel nameplate Stainless steel Silicone oil Silicon oil or a different design
Flange as per EN and ASME
1/4-18 NPT female thread and flat connection with M10 fastening screw thread in accordance with DIN 19213 (M12 for PN 420 (MAWP 6092 psi)) or 7/16-20 UNF in accordance with EN 61518 Screw terminals Cable inlet using the following cable glands: · Pg 13.5 · M20 x 1.5 · ½-14 NPT or Han 7D/Han 8D connector1) · M12 connector IP65

Torques Cable glands/blanking plugs
· Screw-in torque for plastic gland in all enclosures

4 Nm (3 ft lb)

· Screw-in torque for metal/stainless steel glands in aluminum/stainless steel enclosure

6 Nm (4.4 ft lb)

· Screw-in torque for NPT adapter made of metal/stainless steel in aluminum/stainless steel enclosure

15 Nm (11.1 ft lb)

· Screw-in torque for NPT gland in the 68 Nm (50 ft lb) NPT adapter

NOTE: To avoid damage to the device, the NPT adapter must be held in place while the NPT gland is screwed into the NPT adapter.
· Tightening torque for union nut made 2.5 Nm (1.8 ft lb) of plastic

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

223

Technical data 13.9 Display, keyboard and auxiliary power

Torques
· Tightening torque for union nut made of metal/stainless steel

4 Nm (3 ft lb)

13.9

Display, keyboard and auxiliary power

Display and user interface Keys Display

3 for on-site programming directly at the device · With or without integrated display (optional) · Cover with inspection window (optional)

Auxiliary power UH

HART

Terminal voltage on pressure transmit- ·

ter

·

DC 10.5 V ... 45 V
In the case of intrinsically safe operation 10.5 V ... 30 V DC

Ripple Noise Auxiliary power Separate supply voltage Bus voltage
· Not

USS  0.2 V (47 ... 125 Hz) Ueff  1.2 mV (0.5 ... 10 kHz) ­ ­
­

· For intrinsically safe operation

­

Current consumption

· Max. basic current

­

· Starting current  basic current

­

· Max. current in event of fault

­

Error shut-down electronics (FDE)

­

present

PROFIBUS PA or Foundation Fieldbus ­
­ ­ Bus-powered Not necessary
9 ... 32 V 9 ... 24 V
12.5 mA Yes 15.5 mA Yes

224

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Technical data 13.10 Certificates and approvals

13.10 Certificates and approvals

Certificates and approvals

Classification according to Pressure Equipment Directive (PED 97/23/EC)

HART

PROFIBUS PA and FOUNDATION Fieldbus

· for gases of Fluid Group 1 and liquids of Fluid Group 1; meets requirements of Article 3 Para. 3 (good engineering practice)

· only for flow rate: for gases of Fluid Group 1 and liquids of Fluid Group 1; fulfills the basic safety requirements as per article 3, Para 1 (appendix 1); classified as category III, module H conformity evaluation by TÜV Nord

Drinking water Explosion protection

In preparation

· Intrinsic safety "i"

Designation Permissible ambient temperature
Connection
Effective inner capacitance Effective inner inductance · Flameproof enclosure encapsulation "d"

II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb

-40 ... +85 °C (-40 ... +185 °F) temperature class T4 -40 ... +70 °C (-40 ... +158 °F) temperature class T5 -40 ... +60 °C (-40 ... +140 °F) temperature class T6

To a certified intrinsically safe circuit with the max. values:
Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 

FISCO supply unit U0 = 17.5 V, I0 = 380 mA, P0 = 5.32 W
Linear barrier U0 = 24 V, I0 = 174 mA, P0 = 1 W

Ci = 6 nF

Ci = 1.1 nF

Li = 0.4 mH

Li = 7 µH

Designation

II 1/2 G Ex d IIC T4, T6 Ga/Gb

Permissible ambient temperature -40 ... +85 °C (-40 ... +185 °F) temperature class T4 -40 ... +60 °C (-40 ... +140 °F) temperature class T6

Connection

To a circuit with the operating values: To a circuit with the operating values:

UH = 10.5 ... 45 V DC

UH = 9 ... 32 V DC

· Dust explosion protection for Zone 20 and 20/21

Designation

II 1 D Ex ta IIIC IP65 T120°C Da,

Permissible ambient temperature max. surface temperature Connection
Effective inner capacitance Effective inner inductance

II 1/2 D Ex ta/tb IIIC IP65 T120°C Da/Db

-40 ... +85 °C (-40 ... +185 °F)

120°C (248°F)

To a certified intrinsically safe circuit with the max. values:
Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 

FISCO supply unit U0 = 17.5 V, I0 = 380 mA, P0 = 5.32 W
Linear barrier U0 = 24 V, I0 = 250 mA, P0 = 1.2 W

Ci = 6 nF

Ci = 1.1 nF

Li = 0.4 mH

Li = 7 µH

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

225

Technical data 13.10 Certificates and approvals

Certificates and approvals

HART

PROFIBUS PA and FOUNDATION Fieldbus

· Dust explosion protection for Zone 22

Designation Connection

II 2 D Ex tb IIIC IP65 T120°C Db
To a circuit with the operating values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W

To a circuit with the operating values: UH = DC 9 ... 32 V; Pmax = 1.2 W

· Type of protection "n" (Zone 2)

Designation

II 2/3 G Ex nA II T4/T5/T6 Gc

Connection "nA" Connection "ic"

II 2/3 G Ex ic IIC T4/T5/T6 Gc Un = 45 V To a circuit with the operating values: Ui = 45 V

Effective inner capacitance

Ci = 6 nF

Effective inner inductance

Li = 0.4 mH

· Explosion protection in accordance Certificate of Compliance 3008490 with FM

Um = 32 V
FISCO supply unit UO =17.5 V, IO = 570 mA Linear barrier U0 = 32 V, I0 = 132 mA, P0 = 1 W
Ci = 1.1 nF
Li = 7 µH

Designation (XP/DIP) or IS; NI; S CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4 ... T6; CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III

Permissible ambient temperature Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T5: -40 ... +70 °C (-40 ... +158 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F)

Entity parameters

As per "control drawing" A5E00072770A: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 , Ci = 6 nF, Li = 0.4 mH

As per "control drawing" A5E00072770A: Umax = 17.5 V, Imax = 380 mA, Pmax = 5.32 W, Cmax = 6 nF, Lmax = 0.4 mH

· Explosion protection as per CSA Certificate of Compliance 1153651

Designation (XP/DIP) or (IS) Permissible ambient temperature Entity parameters

CL I, DIV 1, GP ABCD T4 ... T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4 ... T6: CL I, DIV 2, GP ABCD T4 ... T6; CL II, DIV 2, GP FG; CL III
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T5: -40 ... +70 °C (-40 ... +158 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
As per "control drawing" A5E00072770A: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 , Li = 0.4 mH, Ci = 6 nF

226

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

13.11

Technical data 13.11 PROFIBUS communication

PROFIBUS communication

PROFIBUS PA communication Simultaneous communication with master Class 2 Setting of address possible using
Cyclic user data · Output byte
· Input byte
Internal preprocessing Device profile Function blocks · Analog input
Adaptation to user-specific process variable Adjustable electrical damping Simulation function Failure response
Limit monitoring · Totalizer
Failure response
Limit monitoring · Physical block Transducer blocks · Transducer block "Pressure"
Calibration by applying two pressures

Max. 4
· Configuration tool · Local operation (standard setting is address 126)
· One measured value: 5 bytes · Two measured values: 10 bytes · Totalizer mode: 0, 1 or 2 bytes · Reset function because of injection: 1 byte (totalizer mode and reset function because of injection)
PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B 2
Yes, linearly rising or falling characteristic 0 ... 100 s Output/input Can be parameterized: · Last good value · Substitute value · Faulty value Upper and lower warning and alarm limits · Can be reset and preset · Selectable counting direction · Simulation function of totalizer output Can be parameterized: · Addition with last good value · Stop addition · Addition with faulty value Upper and lower warning and alarm limits 1 2
Yes

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

227

Technical data 13.11 PROFIBUS communication

PROFIBUS PA communication Monitoring of sensor limits Input of a container characteristic Characteristic curve

Yes With max. 30 interpolation points · Linear · Square-root

Low-flow cut-off and starting point of squarerooting Not for gauge and absolute pressures Simulation function
· Pressure measurement

Not for gauge and absolute pressures Parameterizable
· Constant value · Parameterizable ramp function

· Sensor temperature

· Constant value · Parameterizable ramp function

· Transducer block "Electronics temperature" Simulation function · Pressure measurement

· Constant value · Parameterizable ramp function

· Electronics temperature

· Constant value · Parameterizable ramp function

228

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings

14

14.1

SITRANS P, DS III/P410 for gauge pressure and absolute pressure

from the gauge pressure series



Electronics side, display

(longer for cover with inspection window)1)



Connection side1)



Electrical connection:

· Pg 13.5 gland (adapter)2)3)

· M20 x 1.5 gland3)

· ½-14 NPT gland

· Han 7D/Han 8D plug2) 3)



Harting adapter



Protective cap of the operating buttons



Blanking plug



Safety catch

(only for flameproof encapsulation, not shown in the drawing)



Process connection: G½B connection pin or oval flange



Mounting bracket (optional)

1)

Take an additional 20 mm (0.79 inches) thread length into account

2)

Not with "flameproof enclosure" type of protection

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

229

Dimension drawings 14.1 SITRANS P, DS III/P410 for gauge pressure and absolute pressure from the gauge pressure series

3)

Not for "FM + CSA [is + XP]" type of protection

4)

For Pg 13.5 with adapter, approx 45 mm (1.77 inches)

5)

Minimum distance for rotating

6)

SITRANS P410 is only available as gauge pressure and differential pressure version.

Image 14-1 Pressure transmitter SITRANS P DS III/P410 for absolute pressure, from the gauge pressure series, dimensions in mm (inches)

230

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series

14.2

SITRANS P DS III/P410 for differential pressure, flow rate and

absolute pressure from the differential pressure series



Electronics side, display

(longer for cover with inspection window)1)



Connection side1)



Electrical connection:

· Pg 13.5 gland (adapter)2)3)

· M20 x 1.5 gland

· ½-14 NPT gland

· Han 7D/Han 8D plug2)3



Harting adapter



Protective cap of the operating buttons



Blanking plug



Safety catch

(only for "flameproof enclosure" type of protection, not shown in the drawing)



Lateral ventilation for liquid measurement (standard)



Lateral ventilation for gas measurement (addition H02)



Mounting bracket (optional)



Sealing plug, with valve (optional)



Process connection: 1/4-18 NPT (EN 61518)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

231

Dimension drawings
14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series

1)

Take an additional 20 mm (0.79 inches) thread length into account

2)

Not with "flameproof enclosure" type of protection

3)

Not for "FM + CSA [IS + XP]" type of protection

4)

For Pg 13.5 with adapter, approx 45 mm (1.77 inches)

5)

92 mm (3.62 inch) minimum distance for rotating the pointer

6)

SITRANS P410 is only available as gauge pressure and differential pressure version.

Image 14-2 Pressure transmitter SITRANS P DS III/P410 for differential pressure and flow rate, dimensions in mm (inches)

232

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings 14.2 SITRANS P DS III/P410 for differential pressure, flow rate and absolute pressure from the differential pressure series



Electronics side, display

(longer for cover with inspection window)1)



Connection end



Electrical connection:

· Pg 13.5 gland (adapter)2)3)

· M20 x 1.5 gland

· ½-14 NPT gland

· Han 7D/Han 8D plug2)3



Harting adapter



Protective cap of the operating buttons



Blanking plug



Safety catch

(only for "flameproof enclosure" type of protection, not shown in the drawing)



Sealing plug, with valve (optional)



Process connection: ¼-18 NPT (IEC 61518)



Clearance for rotating the enclosure

1)

Take an additional 20 mm (0.79 inches) thread length into account

2)

Not with "flameproof enclosure" type of protection

3)

Not for "FM + CSA [is + XP]" type of protection

4)

92 mm (3.6 inch) minimum distance for rotating the pointer

5)

74 mm (2.9 inch) for PN  420 (MAWP  6092 psi)

6)

91 mm (3.6 inch) for PN  420 (MAWP  6092 psi)

7)

219 mm (8.62 inch) for PN  420 (MAWP  6092 psi)

8)

For Pg 13.5 with adapter approx. 45 mm (1.77 inches)

9)

SITRANS P410 is only available as gauge pressure and differential pressure version.

Image 14-3 Pressure transmitter SITRANS P DS III/P410 for differential pressure and flow rate with caps for vertical differential pressure lines, dimensions in mm (inches)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

233

Dimension drawings 14.3 SITRANS P DS III/P410 for level

14.3

SITRANS P DS III/P410 for level



Electrical connection:

· Pg 13.5 gland (adapter)2)3)

· M20 x 1.5 gland

· ½-14 NPT gland

· Han 7D/Han 8D plug2) 3)



Protective cap of the operating buttons



Blanking plug



Safety catch

(only for "flameproof enclosure" type of protection, not shown in the drawing)



Connection side1)



Electronics side, display

(longer for cover with inspection window)1)

234

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)



Locking screw with valve (option)



Harting adapter



Process connection: Minus side ¼-18 NPT (IEC 61518)

1)

Take an additional 20 mm (0.79 inches) thread length into account

2)

Not with "flameproof enclosure" type of protection

3)

Not for "FM + CSA [is + XP]" type of protection

4)

92 mm (3.62 inches) minimum distance for rotating the enclosure with pointer

5)

For Pg 13.5 with adapter, approx 45 mm (1.77 inches)

6)

SITRANS P410 is only available as gauge pressure and differential pressure version.

Image 14-4 Pressure transmitter SITRANS P DS III/P410 for level, including mounting flange, dimensions in mm (inches)

14.4

SITRANS P DS III (flush-mounted)



Electronics side, display

(longer for cover with inspection window)1)



Connection side1)



Electrical connection:

· M20 x 1.5 gland

· ½-14 NPT gland

· M12 connector



Protective cap of the operating buttons



Blanking plug



Safety catch

(only for "flameproof enclosure" type of protection, not shown in the drawing)



Process connection: see Flange table

1)

In addition, allow approx. 20 mm (0.79 inch) for the thread length

2)

92 mm (3.6 inches) minimum distance for rotating the enclosure with display

3)

SITRANS P410 is only available as gauge pressure and differential pressure version.

Image 14-5 SITRANS P DS III/P410 (flush mounted)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

235

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

14.4.1

Note 3A and EHDG
Note Approvals The references to the approvals for "EHEDG" and "3A" refer to the respective process connections and are not device-specific. Please refer to the technical specifications of the respective pressure transmitter to see whether the desired certificate is available for your device/flange combination.

236

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

14.4.2

Connections as per EN and ASME

Flange as per EN
EN 1092-1

DN

PN

D

H2

25

40

115 mm (4.5'')

Approx. 52 mm (2'')

25

100

140 mm (5.5'')

40

40

150 mm (5.9'')

40

100

170 mm (6.7'')

50

16

165 mm (6.5'')

50

40

165 mm (6.5'')

80

16

200 mm (7.9'')

80

40

200 mm (7.9'')

Threaded connections

G3/4", G1" and G2" In accordance with DIN 3852

DN

PN

D

¾"

63

37 mm (1.5'')

1"

63

48 mm (1.9'')

2''

63

78 mm (3.1'')

H2 Approx. 45 mm (1.8'') Approx. 47 mm (1.9'') Approx. 52 mm (2'')

Flanges as per ASME
ASME B 16.5 DN 1'' 1'' 1½'' 1½'' 2'' 2'' 3'' 3'' 4'' 4''
SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

CLASS 150 300 150 300 150 300 150 300 150 300

D 110 mm (4.3'') 125 mm (4.9'') 130 mm (5.1'') 155 mm (6.1'') 150 mm (5.9'') 165 mm (6.5'') 190 mm (7.5'') 210 mm (8.1'') 230 mm (9.1'') 255 mm (10.0'')

H2 Approx. 52 mm (2'')
237

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

14.4.3

F&B and pharma flange

Connections as per DIN
DIN 11851 DN 50 80

PN

D

25

92 mm (3.6'')

25

127 mm (5.0'')

H2 Approx. 52 mm (2'')

DIN 11864-1 Form A - sterile threaded sockets

DN

PN

25

40

40

40

50

40

100

40

D 52 mm (2'') 65 mm (2.6'') 78 mm (3.1'') 130 mm (5.1'')

H2 Approx. 52 mm (2'')

Approvals

EHEDG

DIN 11864-2 Form A - sterile collar flange

DN

PN

50

16

65

16

80

16

100

16

D 94 mm (3.7'') 113 mm (4.4'') 133 mm (5.2'') 159 mm (6.3'')

Approvals

EHEDG

H2 Approx. 52 mm (2'')

238

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

DIN 11864-2 Form A - sterile groove flange

DN

PN

50

16

65

16

80

16

100

16

Approvals

EHEDG

D 94 mm (3.7'') 113 mm (4.4'') 133 mm (5.2'') 159 mm (6.3'')

DIN 11864-3 Form A - sterile collar sockets

DN

PN

50

25

65

25

80

16

100

16

D 77.5 mm (3.1'') 91 mm (3.6'') 106 mm (4.2'') 130 mm (5.1'')

H2 Approx. 52 mm (2'')
H2 Approx. 52 mm (2'')

Approvals

EHEDG

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

239

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

Tri-Clamp as per DIN 32676 DN 50 65

PN

D

16

64 mm (2.5'')

16

91 mm (3.6'')

H2 Approx. 52 mm (2'')

Other connections

Varivent® connector

DN

PN

40-125

40

D 84 mm (3.3'')

H2 Approx. 52 mm (2'')

Approvals

EHEDG

Connection in accordance with DRD

DN

PN

65

40

D 105 mm (4.1'')

H2 Approx. 52 mm (2'')

240

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

BioConnectTM connectors

BioConnectTM screwed joint

DN

PN

50

16

65

16

80

16

100

16

2"

16

2½"

16

3"

16

4"

16

Approvals

EHEDG

BioConnectTM flange connector

DN

PN

50

16

65

16

80

16

100

16

2"

16

2½"

16

3"

16

4"

16

Approvals

EHEDG

BioConnectTM clamp connector

DN

PN

50

16

65

10

80

10

100

10

2"

16

2½"

16

3"

10

4"

10

Approvals

EHEDG

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

D 82 mm (3.2'') 105 mm (4.1'') 115 mm (4.5'') 145 mm (5.7'') 82 mm (3.2'') 105 mm (4.1'') 105 mm (4.1'') 145 mm (5.7'')

H2 Approx. 52 mm (2'')

D 110 mm (4.3'') 140 mm (5.5'') 150 mm (5.9'') 175 mm (6.9'') 100 mm (3.9'') 110 mm (4.3'') 140 mm (5.5'') 175 mm (6.9'')

H2 Approx. 52 mm (2'')

D 77.4 mm (3.0") 90.9 mm (3.6'') 106 mm (4.2'') 119 mm (4.7'') 64 mm (2.5") 77.4 mm (3.0'') 90.9 mm (3.6'') 119 mm (4.7'')

H2 Approx. 52 mm (2'')

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

241

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

Connect STM flanged joint

DN

PN

50

16

65

10

80

10

100

10

2"

16

2½"

10

3"

10

4"

10

Approvals

EHEDG

Other connections

BioControlTM connector

DN

PN

50

16

65

16

D 125 mm (4.9'') 145 mm (5.7'') 155 mm (6.1'') 180 mm (7.1'') 125 mm (4.9'') 135 mm (5.3'') 145 mm (5.7'') 180 mm (7.1'')

H2 Approx. 52 mm (2'')

D 90 mm (3.5'') 120 mm (4.7'')

H2 Approx. 52 mm (2'')

Approvals

EHEDG

14.4.4

PMC Style

Connections for the paper industry

PMC Style Standard

DN

PN

­

­

M44x1.25 cap nut

D 40.9 mm (1.6'')

H2 Approx. 36.8 mm (1.4'')

242

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

PMC-Style Minibolt DN ­

PN

D

­

26.3 mm (1.0'')

H2 Approx. 33.1 mm (1.3'')

14.4.5

Special connections

Tank connection

TG52/50 and TG52/150

DN

PN

TG52/50

43.5 mm 10

TG52/150

43.5 mm 10

D 63 mm (2.5'') 63 mm (2.5'')

H2 Approx. 63 mm (2.5'') Approx. 170 mm (6.7'')

SMS connectors

SMS sockets with union nut

DN

PN

D

2"

25

84 mm (3.3'')

2½"

25

100 mm (3.9'')

3"

25

114 mm (4.5'')

H2 Approx. 52 mm (2.1'')

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

243

Dimension drawings 14.4 SITRANS P DS III (flush-mounted)

SMS threaded sockets

DN

PN

D

H2

2"

25

70 x 1/6 mm (2.8")

Approx. 52 mm (2.1'')

2½"

25

85 x 1/6 mm (3.3")

3"

25

98 x 1/6 mm (3.9")

IDF connectors

IDF sockets with union nut

DN

PN

D

2"

25

77 mm (3.0'')

2½"

25

91 mm (3.6'')

3"

25

106 mm (4.2'')

H2 Approx. 52 mm (2.1'')

IDF threaded sockets DN 2" 2½" 3"

PN

D

25

64 mm (2.5'')

25

77.5 mm (3.1'')

25

91 mm (3.6'')

H2 Approx. 52 mm (2.1'')

244

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Spare parts / accessories

15

15.1

Order data
In order to ensure that the ordering data you are using is not outdated, the latest ordering data is always available on the Internet:
Catalog process instrumentation (http://www.siemens.com/processinstrumentation/catalogs)

Selection and order data CD "sitrans p - pressure transmitters" with documentation in German/English/French/Spanish/Italian, etc. HART modem · With USB interface Weld-in support for PMC connection For Series SITRANS P DS III and SITRANS P300 · PMC Style Standard: Thread 1½"
· PMC-Style Minibolt: flush mounted 1" Gaskets for PMC connection, (1 set = 5 pieces) · PTFE gasket for PMC Style Standard: Thread 1½"
· Viton gasket for PMC Style Minibolt: flush mounted 1" Weld-in adapter for PMC connection For connection of weld-in support delay during welding for: · PMC Style Standard: Thread 1½"
· PMC-Style Minibolt: flush mounted 1"

Order no. A5E00090345
7MF4997-1DB1) D)
7MF4997-2HA 7MF4997-2HB 7MF4997-2HC 7MF4997-2HD
7MF4997-2HE 7MF4997-2HF

1) Available from stock D) Subject to export regulations AL: N, ECCN, EAR99H

15.2

Spare parts/accessories for SITRANS P DS III

Selection and order data Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF For gauge pressure transmitter (7MF403.-.....-..C.) For absolute pressure transmitter (7MF423.-.....-..C.) · Made of steel

Order no. 7MF4997-1AB

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

245

Spare parts / accessories 15.2 Spare parts/accessories for SITRANS P DS III

Selection and order data · Made of stainless steel Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF For gauge pressure transmitter (7MF403.-.....-..A., -..B. and -..D.) For absolute pressure transmitter (7MF423.-.....-..A., -..B. and -..D.) · Made of steel
· Made of stainless steel Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF Differential pressure transmitter with flange thread · Made of steel
For thread M10 (7MF433.-... and 7MF443.-...) For thread M12 (7MF453.-...) · Made of stainless steel For thread M10 (7MF433.-... and 7MF443.-...) For thread M12 (7MF453.-...) Mounting bracket and fastening parts For SITRANS P DS III, DS III PA and DS III FF Differential and absolute pressure transmitter with flange thread 7/16-20 UNF (7MF433.-..., 7MF443.-... and 7MF453.-...) · Made of steel
· Made of stainless steel Cover For SITRANS P DS III, DS III PA and DS III FF · Made of aluminum die casting, including gasket
Without inspection window With inspection window · Made of stainless steel, including gasket Without inspection window With inspection window Digital display For SITRANS P DS III, DS III PA and DS III FF Including the fastening material Measuring point label · not labeled (five pieces)
· labeled (1 unit) Specifications as per Y01 or Y02, Y15 and Y16 (refer to SITRANS P pressure transmitter)

Order no. 7MF4997-1AH
7MF4997-1AC 7MF4997-1AJ
7MF4997-1AD 7MF4997-1AE 7MF4997-1AK 7MF4997-1AL
7MF4997-1AF 7MF4997-1AM
7MF4997-1BB 7MF4997-1BE 7MF4997-1BC 7MF4997-1BF
7MF4997-1BR 7MF4997-1CA 7MF4997-1CB-Z Y..: ................

246

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Selection and order data Fastening screws, 50 pieces for: · Measuring point label · Earthing and connecting terminals · Digital display Locking screws, (1 set = 2 pieces) for pressure cap · Made of stainless steel · Made of Hastelloy Vent valves, complete (1 set = 2 pieces) · Made of stainless steel · Made of Hastelloy Electronics · For SITRANS P DS III · For SITRANS P DS III PA · For SITRANS P DS III FF Network card · For SITRANS P DS III · For SITRANS P DS III PA and DS III FF Sealing rings for pressure caps made of · FPM (Viton) · PTFE (Teflon) · FEP (with silicon core, suitable for food) · FFPM (Kalrez, Compound 4079) · NBR (Buna N)

Spare parts / accessories 15.3 Order data for SIMATIC PDM
Order no. 7MF4997-1CD
7MF4997-1CG 7MF4997-1CH
7MF4997-1CP 7MF4997-1CQ
7MF4997-1DK 7MF4997-1DL 7MF4997-1DM
7MF4997-1DN 7MF4997-1DP
7MF4997-2DA 7MF4997-2DB 7MF4997-2DC 7MF4997-2DD 7MF4997-2DE

15.3

Order data for SIMATIC PDM
You can find ordering data in the Catalog FI 01 "Field devices for process automation in the Chapter "Communication and software > Software > SIMATIC PDM - Process Device Manager".

See also

Catalog process instrumentation (http://www.siemens.com/processinstrumentation/catalogs)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

247

Spare parts / accessories 15.4 Ordering data for PROFIBUS accessories

15.4

Ordering data for PROFIBUS accessories
In the Industrial Communication catalog (IK PI) you can find additional accessories that are required for communication with our devices and PROFIBUS.
For the latest updates to this catalog, please visit the Industry Mall (https://mall.industry.siemens.com/).

248

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Appendix

A

A.1

Certificate
The certificates can be found on the enclosed CD and on the Internet under: Certificates (http://www.siemens.com/processinstrumentation/certificates)

A.2

Certificates (China)

Additional information for China
The product is based on the standards QDSSC 001-2013, QDSSC 002-2013, QDSSC 0032013 and meets the requirements of CMC and CPA.

CMC

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

249

Appendix A.2 Certificates (China)
CPA

250

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Appendix A.2 Certificates (China)

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

251

Appendix A.2 Certificates (China)

252

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Appendix A.3 Literature and standards

A.3

Literature and standards

No. Standard /1/ IEC 61508
Section 1-7
/2/ IEC 61511 Section 1-3

Description Functional safety of following systems: · Safety-instrumented · Electrical · Electronic · Programmable Target group: Manufacturers and suppliers of equipment Functional safety - Safety systems for the process industry Target group: Planners, constructors and users

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

253

Appendix A.4 Technical support

A.4

Technical support

Technical Support
If this documentation does not provide complete answers to any technical questions you may have, contact Technical Support at:
 Support request (http://www.siemens.com/automation/support-request)
 More information about our Technical Support is available at Technical support (http://www.siemens.com/automation/csi/service)

Internet Service & Support
In addition to our documentation, Siemens provides a comprehensive support solution at:
 Service&Support (http://www.siemens.com/automation/service&support) where you will find support news, support documents including EDDs and software, and also support from experts.

Additional Support
If you have additional questions about the device, please contact your local Siemens representative.
Find your local contact partner at:
 Partner (http://www.automation.siemens.com/partner) Documentation for various products and systems is available at:
 Instructions and manuals (http://www.siemens.com/processinstrumentation/documentation)

See also

Product information on SITRANS P in the Internet (http://www.siemens.com/sitransp) Process instrumentation catalog (http://www.siemens.com/processinstrumentation/catalogs) E-mail (mailto:support.automation@siemens.com)

254

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

List of abbreviations/acronyms

B.1

Pressure transmitter

List of abbreviations
Table B- 1 Tags
Abbreviation OUT PRIM SEC SENS TMP E TMP S TOTAL

In full Output Primary variable Secondary variable Raw pressure value Electronics temperature Sensor temperature Totalizer output

Meaning

Table B- 2 Units
Abbreviation bar a bar g lb psi a psi g mbar Pa hPa psi g/cm² kg/cm² mmH2O inH2O ftH2O mmHg inHg l norml m3 normm3 Hl inch3

In full Bar absolute Bar gauge Pound psi absolute psi gauge Millibar Pascal Hectopascal Pound per square inch Gram per square centimeter Kilogram per square centimeter Millimeter water column Inch water column Foot water column Millimeter mercury [column] Inch mercury [column] Liter Standard liter Cubic meter Standard cubic meter Hectoliter Cubic inch

Meaning Pressure unit for absolute pressure Pressure unit for gauge pressure Unit of weight Pressure unit for absolute pressure Pressure unit for gauge pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for pressure Unit for volume Unit for volume Unit for volume Unit for volume Unit for volume Unit for volume

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

B
255

List of abbreviations/acronyms B.1 Pressure transmitter

Abbreviation stdft3 ft3 yd3 gal Imp. gallon Bushel bl Barrel liquid s min h d K °C °F °R

In full Standard cubic foot Cubic foot Cubic yard Gallon (USA) Imperial gallon
Bushel Barrel Barrel liquid Second Minute Hour Day Kelvin degrees Celsius degrees Fahrenheit degrees Rankine

Meaning Unit for volume Unit for volume Unit for volume Unit for volume Unit for volume
Unit for volume Unit for volume Unit for volume
Unit for time Unit for time Unit for time Unit for time Temperature unit Temperature unit Temperature unit Temperature unit

Table B- 3 Other abbreviations

Abbreviation CLASS PED DN DP

In full
Pressure Equipment Directive Diameter Nominal Distributed I/O

FDE FISCO
GSD HART
F&B PA

Fault disconnection electronics Fieldbus Intrinsically Safety Concept Device master data Highway Addressable Remote Transducer Food and beverage industry Process automation

PDM PN PNO PROFIBUS

Process Device Manager Pressure Nominal PROFIBUS User Organization Process Field Bus

SELV

Safety extra-low voltage Safety extra-low-voltage

Meaning Term for nominal pressure measured in psi
Nominal diameter measured in mm Protocol for the transmission of information between field device and automation system over PROFIBUS.
Standard protocol for the transmission of information between field device and automation system.
Protocol for the transmission of information between field device and automation system over PROFIBUS.
Nominal pressure measured in bar
Manufacturer-independent standard for the networking of field devices, e.g. PLC, drives, or sensors. PROFIBUS can be used with the DP and PA protocols.

256

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

List of abbreviations/acronyms B.2 Functional safety

B.2

Functional safety

Abbreviation CFC FIT HFT MooN
MTBF MTTR PFD PFDAVG SFF
SIL
SIS

Full term in English Continuous Function Chart Failure in Time Hardware Fault Tolerance "M out of N" voting
Mean Time Between Failures Mean Time To Restoration Probability of Dangerous Failure on Demand Average Probability of Dangerous Failure on Demand Safe Failure Fraction
Safety Integrity Level
Safety Instrumented System

Meaning
Software package for graphical, technology-oriented configuration of automation tasks
Frequency of failure Number of faults withing 109 hours
Hardware fault tolerance:
Capability of a function unit to continue executing a required function in the presence of faults or deviations.
Classification and description of the safety-instrumented system in terms of redundancy and the selection procedures used.
A safety-instrumented system or part that consists of "N" independent channels. The channels are connected to each other in such a way that "M" channels are in each case sufficient for the device to perform the safety instrumented function.
Example: Pressure measurement: 1oo2 architecture. A safetyinstrumented system decides that a specified pressure limit has been exceeded if one out of two pressure sensors reaches this limit. In a 1oo1 architecture, there is only one pressure sensor.
Average period between two failures
Average period between the occurrence of a fault in a device or system and restoration of functionality
Probability of dangerous failures of a safety function on demand
Average probability of dangerous failures of a safety function on demand
Proportion of safe failures:
Proportion of failures without the potential to bring the safetyinstrumented system into a dangerous or non-permissible functional status.
The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL 1 to SIL 4). Each level corresponds to a range of probability for failure of a safety function. The higher the Safety Integrity Level of the safety-instrumented system, the lower the probability that it will not execute the required safety functions.
A safety-instrumented system (SIS) executes the safety functions that are required to achieve or maintain a safe status in a system. It consists of a sensor, logic unit/control system and final controlling element.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

257

List of abbreviations/acronyms B.2 Functional safety

258

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Glossary

Coupler

connects the DP and PA segments in PROFIBUS. It has a fixed transmission speed. The transmission speed is 45.45 kbps (DP) to 31.25 kbps (PA).

Dangerous failure
Failure with the potential to switch a safety-instrumented system to a hazardous or nonfunctioning safety status.

Diameter nominal
The diameter nominal is specified according to DIN EN ISO 6708 by the term DN followed by a dimensionless number approximating the inner diameter in millimeters. According to DIN 2440 (medium-weight threaded pipe), a DN 50 pipe, for example, identifies a pipe with an outer diameter of 60.3 mm and a wall thickness of 3.65 mm (inner diameter therefore 53 mm).

EEPROM

EEPROM (Electrically Erasable Programmable Read-Only Memory) is a non-volatile, electronic memory chip.
EEPROM are often used when individual data bytes change over long intervals and need to be stored and retained if there is a network failure, for example configuration data or operating hours counters.

Failure/Fault

Failure: A resource is no longer capable of executing a required function.
Fault: Undesired state of a resource indicated by the incapability of executing a required function.

Fault

 Failure/Fault

Fault tolerance
Fault tolerance N means that a device can execute the intended task even when N faults exist. The device fails to execute the intended function in the case of N+1 faults.

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

259

Glossary

Final controlling element
Converter that converts electric signals into mechanical or other non-electric variables.

Firmware

Firmware is a type of software that is embedded in a chip in electronic devices in contrast to software proper that is stored on hard disks or other media. Today, firmware is usually stored in a flash memory or EEPROM.
The firmware usually contains elementary functions for controlling the device or input and output routines.

Frequency shift keying
Frequency shift keying is a simple modulation method in which the digital values 0 and 1 are represented by two different frequencies.

Frequency shift keying (FSK)  Frequency shift keying

Function block

A named block consisting of one or more inputs, outputs, and included parameters.
Function blocks represent the basic automation functions executed by an application in a way as independent as possible from the details of I/O devices and the network. Each function block processes input parameters using a specified algorithm and a set of internally stored parameters. They produce output parameters which are available for use inside the same function block application or by other function block applications.

Generic Station Description
The generic station description (GSD) contains the information necessary for the control system to establish communication.

GSD

 Generic Station Description

Link

is a coupler with a variable transmission speed. The transmission speed is a maximum of 12 Mbps (DP) to 31.25 kbps (PA).

Non-volatile memory  EEPROM

260

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Glossary

Risk

Combination of the probability of damage occurring and the extent of the damage.

Safety function
Defined function executed by a safety-instrumented system with the objective of attaining or maintaining a safe status of the system by taking a defined hazardous incident into account.
Example: Limit pressure monitoring

Safety Integrity Level  SIL

Safety-instrumented system
A safety-instrumented system (SIS) executes the safety functions that are required to achieve or maintain a safe status in a system. It consists of a sensor, logic unit/control system and final controlling element.
Example: A safety-instrumented system is made up of a pressure transmitter, a limit signal sensor and a control valve.

Sensor

Converter that converts mechanical or other non-electric variables into electric signals.

SIL
The international standard IEC 61508 defines four discrete safety integrity levels (SIL) from SIL 1 to SIL 4. Every level corresponds to a probability range for the failure of a safety function. The higher the SIL of the safety-instrumented system, the higher the probability that the required safety function works.
The achievable SIL is determined by the following safety-instrumented characteristics:
 Average probability of failure on demand (PFDAVG)  Hardware fault tolerance (HFT)  Safe failure fraction (SFF)

srli2  srlin2

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

261

Glossary

srlin2

"srli2" or "srlin2" is a type of square root extracting characteristic curve for the output current. This characteristic curve type is proportional to the flow rate, linear in two levels up to the application point and has a pre-defined application point of 10%.
"srli2" or "srlin2" are synonymous and technically there is no difference between them. The abbreviation "srli2" is used in sections that refer to the on-site operation of the pressure transmitter. The reason for the abbreviation is that the pressure transmitter display is restricted to five characters. The abbreviation "srlin2" is used for HART operation.

Zero point adjustment
After the following functions, the measuring range will have changed:  Zero point calibration  LO calibration  HI calibration If you have used one of these functions, the measuring range will have changed. This changed, remaining measuring range is called the zero point offset. Refer to the Operation section for the corresponding modes of these functions.

262

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Index

3

D

3A, 236
A
Additional Support, 254 Address
PROFIBUS, 88 Ambient temperature, 214, 215, 216, 217, 217
Effect, 203, 204, 205, 206, 207, 208, 210, 211, 213 Approval
3A, 236 EHEDG, 236 Approval plate, (Nameplate with approval information) Arrow display, 76 AUTO, 105
B
Bridge output voltage, 30, 31, 32 Bus address, 88 button and function lock
Activate, 133 Buttons, 71

Damping, 104 Data consistency, 165 Data transmission
acyclic, 170 cyclic, 165 Floating point representation, 167 Decimal point, 90 Device Electrostatic-sensitive, 19, 184 Device mode, 88 Device operating mode, 161 Diagnostic information Transmission, 168 Diagnostic information, 74 Diagnostics messages, 168 Differential pressure, 23, 23 Digital display, 97 Direct sunlight, 43 Display Error message, 192 Status code, 189 Display of unit, 74
E

C
C2 connection, 170 Calibration
HI, 93 LO, 91 Certificate, 249 Certificates, 15 Certification, 249 Characteristics Safety, 132 Checksum, 154 Configuration, 165 Connector M12, 69 Correct usage, (See improper device modifications) CPU, 144 Customer Support Hotline, 254

EDD, 145 EHEDG, 236 Electromagnetic compatibility, 214, 215, 216, 217, 218 Electronics, 133 Electrostatic-sensitive device (ESD), 19, 184 EMC, 214, 215, 216, 217, 218 Error message, 192
F
Filling liquid, 30, 32, 33 Firmware, 11 Flange, 32, 49 Flow, 23, 82 Function block
Analog input, 104, 114 Function chart, 34

SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

263

Index
G
Generic Station Description, (See GSD) GMD file, 89 GSD, 162 GSD file
Internet address, 165
H
Hazardous area Laws and directives, 15
History, 11 Hotline, 254
I
Improper device modifications, 16 Install
Remote seal, 53 Installation, 45, 45, 46 Internet, 254
K
Keypad lock, 116
L
Label, 26 Level, 24 Limits
Alarm, 117 Warning, 117 Load, 202 Locking of buttons, 81
M
M12 connector, 69 Master
Class 2 master, 170 Class-1 master, 38, 165 Class-2 master, 38 Measured value display, 74, 79 Measured value display, 74, 79 Measuring cell Absolute pressure, 34 Differential pressure and flow rate, 31
264

Gauge pressure, 30 Level, 32 Mode 13, 82 14, 84 15, 88 16, 88 17, 90 18, 90 19, 91 20, 92 Mounting bracket, 46 Mounting flange, 32 MTTR, 133
N
Nameplate with general information, 26
O
Operation Local, 79
Output scaling, 104, 108, 113
P
Pairs of min/max pointer, 122 Parameter
Transmitter type, 82 PDM display
Error message, 192 Status code, 189 Position correction, 80, 80 Process connection, 25 PROFIBUS, 37, 95 Automation system, 38 Communication structure, 95 DP, 37 Eigenschaft, 38 Functions, 106 Operation, 106 PA, 37 Setting the address, 165 Topology, 37 PROFIsafe, 141 Proof test, 133
SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Q
Qualified personnel, 17
R
Remote seal Description, 36 Install, 53 Maintenance, 187
Resetting Delivery state, 127 Factory settings, 127
Restart, 128
S
Safety Checking, 133
Safety function, 129 Safety Integrity Level, 143 Scaling
Measured value, 104, 108, 113 Scope of delivery, 12 Service, 254 Setting
Height measurement, 108 Level measurement, 108 Mass measurement, 110 Volume measurement, 109 Shut-off valve, 174, 176, 178, 179, 180 SIL, 143 Simulation, 104, 122, 122 Software package S7-F, 144 Stabilizing valve, 176, 177, 178, 180 Status, 167, 189 Status, 167, 189 Status code, 168, 189 Status code, 168, 189 Status display, 76 Structure, 24 Support, 254
T
Tank connection, 243 Test certificates, 15 Transducer block
for electronics temperature, 96, 103 for pressure, 96
SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions, 02/2016, A5E00053276-08

Trim Sensor, 125
Turning range, 60
U
Unit for level, 86 for mass, 87 for pressure, 85 for temperature, 87 for user-specific, 87 for volume, 85
V
Variable, 82 Vent valve, 178, 180
W
Warm start, 128 Watchdog, 169 Write protection, 81, 133
Z
Zero point adjustment, 90 Zero point calibration, 80, 80, 91

Index 265



References

PD PI Adobe PDF Library 11.0