Daikin Packaged Water-Cooled Heat Pumps

Installation, Operation and Maintenance Manual

Model Numbers: EWWQ014KCW1N, EWWQ025KCW1N, EWWQ033KCW1N, EWWQ049KCW1N, EWWQ064KCW1N

Introduction

The Daikin EWWQ-KC packaged water-cooled water chillers are designed for indoor installation and are used for cooling and/or heating applications. These units are available in 7 standard sizes with nominal cooling capacities ranging from 14 to 64 kW. The EWWQ units can be combined with Daikin fan coil units or air handling units for air conditioning purposes. They can also be used for supplying chilled water for process cooling.

This manual describes the procedures for unpacking, installing, and connecting the EWWQ units. It is intended for use by expert or trained users in shops, light industry, farms, or for commercial use by lay persons.

Sound pressure level is less than 70 dB(A).

Options and Features

Options

Standard Features

Operation Range

The operating limits for EWWQ014-033 and EWWQ049-064 models are illustrated in the figures below. These figures show the Evaporator Leaving Water Temperature (ELWT) and Condenser Leaving Water Temperature (CLWT).

Figure 1: Operating limits on EWWQ014-033

This graph displays the operational range for EWWQ014-033 models, indicating zones for operation with water and with glycol.

Figure 2: Operating limits EWWQ049-064

This graph displays the operational range for EWWQ049-064 models, indicating zones for operation with water and with glycol.

Key:

Main Components

The main components of the unit include:

Selection of Location

Units are designed for indoor installation and require a location that meets the following criteria:

Inspecting and Handling the Unit

Upon delivery, the unit should be checked for any damage, which should be reported to the carrier immediately.

Unpacking and Placing the Unit

  1. Cut straps and remove the cardboard box from the unit.
  2. Cut straps and remove the cardboard box with water piping from the pallet.
  3. Remove the four screws fixing the unit to the pallet.
  4. Level the unit in both directions.
  5. Use four anchor bolts with M8 thread to fix the unit in concrete (directly or using floor standing supports).
  6. Remove the service front plate.

Important Information Regarding the Refrigerant Used

This product contains fluorinated greenhouse gases (R410A) covered by the Kyoto Protocol. Do not vent gases into the atmosphere. The Global Warming Potential (GWP) value is 2090. The refrigerant quantity is indicated on the unit's name plate.

Checking the Water Circuit

The units are equipped with water inlets and outlets for connection to chilled and hot water circuits. These must be provided by a licensed technician and comply with all relevant regulations.

WARNING: The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.

Before installation, check the following points:

Additional components not delivered with the unit

  1. A circulation pump must discharge water directly into the heat exchanger.
  2. Drain taps must be provided at all low points for complete drainage during maintenance or shutdown.
  3. Anti-vibration systems in water piping are recommended to avoid straining and transmitting vibration and noise.

Additional water piping delivered with the unit

All additional water piping must be installed according to the piping diagram. The flowswitch must be connected as described on the wiring diagram. See also chapter "Before starting".

Plastic bag 1 (water piping evaporator) includes: 2x Ball valve, 1x Water filter, 1x Air purge, 1x T-joint for air purge, 2x Flowswitch pipe, 1x Flowswitch + 1x T-joint.

Plastic bag 2 (water piping condenser) includes: 2x Ball valve, 1x Water filter, 1x Air purge, 1x T-joint for air purge.

The flowswitch must be installed in the water outlet pipe of the evaporator to prevent operation at too low a water flow.

WARNING: It is crucial to install the flowswitch correctly in relation to the water flow direction to ensure proper protection against freezing.

A specific terminal is provided in the switch box for the electrical connection of the flowswitch. Refer to the wiring diagram.

Shut-off valves must be installed at the unit for normal servicing of the water filter without draining the complete system.

Air purge valves must be provided at all high points of the system for easy servicing.

The water filter must be installed in front of the unit to remove dirt and prevent damage to the unit or evaporator/condenser. The water filter must be cleaned regularly.

Table 3: Water quality specifications

DAE Water quality requirementsBPHE
pH (25 °C)7.5-9.0
Electrical conductivity [µS/cm] (25°C)< 500
Chloride ion [mg Cl- / l]< 70
Sulphate ion [mg SO42- / l]< 100
Alkalinity [mg CaCO3 / l]< 200
Total Hardness [mg CaCO3 / l]75 ÷ 150
Iron [mg Fe / l]< 0.2
Ammonium ion [mg NH4+ / l]< 0.5
Silica [mg SiO2 / l]
Chlorine molecular (mg Cl2/l)< 0.5

Connecting the Water Circuit

Evaporator and condenser have GAS male pipe threads for water inlet and outlet. Connections must be made respecting the water in- and outlet as shown in the outlook diagram.

Avoid air, moisture, or dust in the water circuit. Always consider the following when connecting:

  1. Use clean pipes only.
  2. Hold the pipe end downwards when removing burrs.
  3. Cover the pipe end when inserting through a wall to prevent dust and dirt entry.

WARNING: Use a good thread sealant for connections. The sealant must withstand system pressures and temperatures and be resistant to glycol. External surfaces of water pipes must be protected against corrosion.

Water Charge, Flow and Quality

A minimum water volume and flow rate are required for proper operation. Refer to the table below for water flow operation ranges.

Table 4: Water flow operation range

General EWWQMinimum water volume (l)Minimum water flowMaximum water flow
EWWQ0146231 l/min75 l/min
EWWQ02513453 l/min123 l/min
EWWQ03315576 l/min186 l/min
EWWQ049205101 l/min247 l/min
EWWQ064311152 l/min373 l/min

WARNING: The water pressure should not exceed the maximum working pressure of 10 bar.

WARNING: Provide adequate safeguards in the water circuit to ensure water pressure does not exceed the maximum allowable working pressure.

Piping Insulation

The complete water circuit, including all piping, must be insulated to prevent condensation and reduce cooling capacity loss.

11.1 Antifreeze protection for BPHE and recovery exchangers

If heat exchangers are completely empty and cleaned with antifreeze solution, additional methods can be used against freezing.

Consider the following protection methods:

  1. Continuous water flow circulation inside piping and exchangers.
  2. Addition of an appropriate amount of glycol to the water circuit, or alternative, additional heat insulation and heating of exposed piping.
  3. If the unit is not used during winter, empty and clean the heat exchanger.

The installer or local maintenance personnel are responsible for ensuring that antifreeze methods are used. Failure to follow these instructions may result in unit damage. Damage caused by freezing is excluded from the warranty.

Field Wiring

WARNING: All field wiring and components must be installed by a licensed electrician and comply with relevant European and national regulations.

Field wiring must be carried out according to the wiring diagram supplied with the unit and the instructions below. Use a dedicated power circuit; never use a power supply shared by another appliance.

WARNING: During the removal of the control cabinet door, disconnect the display cable before removing the panel completely.

12.1 Power circuit and cable requirements

  1. The electrical power supply to the unit must be switchable on/off independently of other plant equipment.
  2. A dedicated power circuit with safety devices (circuit breaker, slow blow fuse on each phase, earth leak detector) must be provided. Recommended fuses are mentioned on the wiring diagram.

WARNING: Switch off the main isolator switch before making any connections.

12.2 Connection of the water-cooled water chiller power supply

  1. Install cable gland to proper tight main power supply cable.
  2. Using the appropriate cable, connect the power circuit to the N, L1, L2 and L3 terminals of the unit (cable section 2.5~16mm²).
  3. Connect the earth conductor (yellow/green) to the earthing terminal PE.

12.3 Point for attention regarding quality of the public electric power supply

This equipment complies with EN/IEC 61000-3-11 provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user's supply and the public system. The installer or user must ensure, by consultation with the distribution network operator, that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax.

Table 5: Impedance Z

ModelZmax (Ω)
EWWQ0140.28
EWWQ0250.23
EWWQ0330.21
EWWQ0490.22
EWWQ0640.20

Only for EWWQ014~064: Equipment complying with EN/IEC 61000-3-12.

12.4 Interconnection cables

Operator's Responsibilities

The operator must be appropriately trained and familiar with the system before operating the unit. This includes studying the microprocessor operating manual and wiring diagram to understand start-up, operation, shutdown sequences, and safety devices.

A technician authorized by the manufacturer is available during the initial start-up phase to answer questions and provide instructions.

The operator must keep a record of operating data and maintenance activities for each installed unit.

If abnormal operating conditions are noted, consult the authorized technical service.

WARNING: If the unit is switched off, the compressor oil heater cannot be used. Once reconnected to the mains, allow the compressor oil heater to charge for at least 6 hours before restarting the unit. Failure to do so may cause compressor damage due to liquid accumulation.

This unit represents a substantial investment and requires careful attention to maintain good working order. Observe the following during operation and maintenance:

In case of sudden unit stop, follow instructions in the Control Panel Operating Manual.

It is strongly recommended to perform installation and maintenance with others.

WARNING: Avoid installing the unit in areas that could be dangerous during maintenance operations, such as platforms without parapets or railings.

Maintenance

This unit must be maintained by qualified technicians. Ensure all security precautions are taken before starting any work.

Neglecting maintenance can degrade unit performance and functionality.

Two maintenance levels are available, based on application type (critical/noncritical) and installation environment (highly aggressive).

Critical applications include process cooling and data centers.

Highly Aggressive Environments include:

Units in highly aggressive environments may experience faster corrosion. Periodic washing of frame surfaces with water and detergents is recommended. Repaint any exposed parts to prevent progressive deterioration. For salt deposits, rinse with fresh water.

WARNING: All electrical maintenance must be performed by qualified personnel. Ensure the system is switched off and the main switch is open. Failure to observe this rule could result in serious personal injury.

Electrical maintenance includes:

  1. Comparing the absorbed current by the compressor to the rated value.
  2. Performing security checks at least every three months to verify functionality. Monitor operation points and adjust or replace components as needed. Check pump interlocks and flow switches to ensure they interrupt the control circuit if they intervene.

Table 7: Standard Routine Maintenance Plan

List of ActivitiesWeeklyMonthly (Note 1)Yearly/Seasonal (Note 2)
General:
Reading of operating dataX
Verification of thermal insulation integrityX
Visual inspection of unit for any damage and/or looseningX
CleaningX
Paint where necessaryX
Analysis of waterX
Check of flow switch operationX
Electrical Installation:
Verification of start-up sequenceX
Verify contactor wear - Replace if necessaryX
Verify that all electrical terminals are tight - Tighten if necessaryX (Quarterly)
Clean inside the electrical panelX
Visual inspection of components for any signs of overheatingX
Verify operation of compressor and electrical resistanceX
Refrigeration circuit:
Check for any refrigerant leakage (leak test)X
Analyse compressor vibrationsX
Hydraulic circuit:
Check for any water leakageX
Check hydraulic connectionsX
Check the pressure at the exchangers water inletX
Clean the water filterX
Check the glycol concentrationX
Check the water flow rateX
BPHE:
Check the cleaning of the BPHEX

Notes:

Table 8: Routine Maintenance Plan for Critical Application and/or Highly Aggressive Environment

List of ActivitiesWeeklyMonthly (Note 1)Yearly/Seasonal (Note 2)
General:
Reading of operating dataX
Visual inspection of unit for any damage and/or looseningX
Verification of thermal insulation integrityX
CleaningX
Paint where necessaryX
Analysis of waterX
Check of flow switch operationX
Electrical Installation:
Verification of start-up sequenceX
Verify contactor wear - Replace if necessaryX
Verify that all electrical terminals are tight - Tighten if necessaryX (Quarterly)
Clean inside the electrical panelX
Visual inspection of components for any signs of overheatingX
Verify operation of compressor and electrical resistanceX
Measure with the Megger the compressor motor insulationX
Refrigeration circuit:
Check for any refrigerant leakage (leak test)X
Analyse compressor vibrationsX
Hydraulic circuit:
Check for any water leakageX
Check hydraulic connectionsX
Check the pressure at the exchangers water inletX
Clean the water filterX
Check the glycol concentrationX
Check the water flow rateX
BPHE:
Check the cleaning of the BPHEX

Notes:

Service and Limited Warranty

All units are factory tested and guaranteed for 12 months from the first start-up or 18 months from delivery. These units are developed and constructed to high quality standards ensuring years of failure-free operation. Maintenance is required even during the warranty period, from installation until commissioning.

Daikin strongly advises stipulating a maintenance contract with a manufacturer-authorized service provider for efficient and problem-free service.

Operating the unit inappropriately, beyond its limits, or not performing proper maintenance as per this manual can void the warranty. Observe the following points to conform to warranty limits:

  1. The unit cannot function beyond specified limits.
  2. Electrical power supply must be within voltage limits and without voltage harmonics or sudden changes.
  3. Three-phase power supply must not have an unbalance between phases exceeding 3%. The unit must remain off until the electrical problem is solved.
  4. No safety device (mechanical, electrical, or electronic) must be disabled or overridden.
  5. Water used for filling the water circuit must be clean and suitably treated. A mechanical filter must be installed at the point closest to the BPHE inlet.
  6. The BPHE water flow value must be included in the declared range for the unit, as per CSS selection software.

Before Starting

WARNING: The unit should not be started, even for a short period, before the following pre-commissioning checklist is filled out completely.

Table 9: Standards steps to go through before starting the unit

Tick when checkedStep
1. Check for external damage.
2. Install main fuses, earth leak detector and main switch. Recommended fuses: aM according to IEC standard 269-2. Refer to the wiring diagram for size.
3. Supply the main voltage and check if it is within the allowable ±10% limits of the nameplate rating. The electrical main power supply must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipment in general. Refer to the wiring diagram, terminals N, L1, L2, L3 and PE.
4. Supply water to the evaporator and condenser and verify if waterflow is within the limits as given in the table under "Water charge, flow and quality".
5. The piping must be completely purged. See also chapter "Checking the water circuit".
6. Connect flowswitch and pump contacts, so that the unit can only come in operation when the water pumps are running and the waterflow is sufficient. Make sure a water filter is installed.
7. Connect the field wiring pumps start-stop.
8. Connect the fiels wiring for remote control.

I do confirm having executed and checked all the above-mentioned items.

Date: _________________________ Signature: _________________________

Keep for future reference

Models: EWWQ014KCW1N, EWWQ025KCW1N, EWWQ033KCW1N, EWWQ049KCW1N, EWWQ064KCW1N, Packaged Water-Cooled Heat Pumps, EWWQ064KCW1N Packaged Water-Cooled Heat Pumps

File Info : application/pdf, 20 Pages, 645.10KB

PDF preview unavailable. Download the PDF instead.

EWWQ-KC Installation, Operation and Maintenance Manual D-EIMHP01501-22 00 English

References

Microsoft Word per Microsoft 365

Related Documents

Preview Εγχειρίδιο Εγκατάστασης, Λειτουργίας και Συντήρησης Daikin EWWQ-KC Series
Αναλυτικός οδηγός για την εγκατάσταση, λειτουργία και συντήρηση των συσκευασμένων αντλιών θερμότητας Daikin EWWQ-KC, καλύπτοντας προδιαγραφές, διαδικασίες και αντιμετώπιση προβλημάτων.
Preview Daikin EWWQ-AJYNN Water-cooled Screw Chillers Service Manual
Comprehensive service manual for Daikin EWWQ-AJYNN water-cooled screw chillers, covering installation, maintenance, troubleshooting, and operational details for qualified personnel.
Preview Daikin Trailblazer™ AGZ-E Series Air-Cooled Scroll Chillers: Installation, Operation, and Maintenance Manual
Comprehensive installation, operation, and maintenance manual for Daikin Trailblazer™ AGZ-E series air-cooled scroll chillers (30-240 Tons). Details unit specifications, electrical data, controller functions, operational sequences, and troubleshooting for HVAC professionals.
Preview Daikin MicroTech Controller Operating Manual for Water Cooled Chillers and Heat Pumps
Comprehensive operating manual for Daikin's water-cooled chillers and heat pumps featuring inverter-driven screw compressors and the MicroTech controller. This guide covers safety considerations, general descriptions, controller usage, menu structures, unit setup, alarms, troubleshooting, and optional features.
Preview Daikin EWYT_B EWAT_B Air Cooled Chiller/Heat Pump Operating Manual
Comprehensive operating manual for Daikin EWYT_B and EWAT_B series air-cooled chillers and heat pumps with scroll compressors, detailing controller functions, safety, and troubleshooting.
Preview Daikin MicroTech III Chiller Unit Controller Modbus Communication Module Installation and Maintenance Manual IM 969-6
Installation and maintenance guide for the Daikin MicroTech III Chiller Unit Controller Modbus Communication Module (IM 969-6), covering features, specifications, installation, network configuration, and troubleshooting for various Daikin chiller models.
Preview Daikin Light Commercial HVAC Catalog: Packaged Units & Split Systems
Explore Daikin's comprehensive catalog of light commercial HVAC solutions, featuring energy-efficient packaged air conditioners, heat pumps, gas/electric units, and split systems designed for optimal performance and reliability.
Preview Daikin EWYE-CZ Air-to-Water Heat Pump Units: Installation, Maintenance & Operation Manual
Explore the Daikin EWYE-CZ series air-to-water heat pump units with scroll compressors. This official manual details installation, operation, maintenance, safety guidelines, and technical specifications for models like EWYE019CZ through EWYE070CZ. Learn about R454C refrigerant and compliance with European directives for efficient and reliable climate control.