USER MANUAL
Longo programmable controller LPC-3.GOT.002 Graphical Operation Terminal
Version 1
SMARTEH d.o.o. / Poljubinj 114 / 5220 Tolmin / Slovenia / Tel.: +386(0) 388 44 00 / e-mail: info@smarteh.si / www.smarteh.si

Longo programmable controller LPC-3.GOT.002
Written by SMARTEH d.o.o. Copyright © 2022, SMARTEH d.o.o. User Manual Document Version: 1 February, 2022
i

Longo programmable controller LPC-3.GOT.002
STANDARDS AND PROVISIONS: Standards, recommendations, regulations and provisions of the country in which the devices will operate, must be considered while planning and setting up electrical devices. Work on 100 .. 230 V AC network is allowed for authorized personnel only.
DANGER WARNINGS: Devices or modules must be protected from moisture, dirt and damage during transport, storing and operation.
WARRANTY CONDITIONS: For all modules LONGO LPC-3 ­ if no modifications are performed upon and are correctly connected by authorized personnel ­ in consideration of maximum allowed connecting power, warranty of 24 months is valid from the date of sale to the end buyer, but not more than 36 months after delivery from Smarteh. In case of claims within warranty time, which are based on material malfunctions the producer offers free replacement. The method of return of malfunctioned module, together with description, can be arranged with our authorized representative. Warranty does not include damage due to transport or because of unconsidered corresponding regulations of the country, where the module is installed. This device must be connected properly by the provided connection scheme in this manual. Misconnections may result in device damage, fire or personal injury. Hazardous voltage in the device can cause electric shock and may result in personal injury or death. NEVER SERVICE THIS PRODUCT YOURSELF! This device must not be installed in the systems critical for life (e.g. medical devices, aircrafts, etc.).
If the device is used in a manner not specified by the manufacturer, the degree of protection provided by the equipment may be impaired.
Waste electrical and electronic equipment (WEEE) must be collected separately!
LONGO LPC-3 complies to the following standards: · EMC: EN 55032:2002, EN 55035:2017, EN 61000-3-2:2014,
61000-3-3:2013 · LVD: IEC 61010-1:2010 (3rd Ed.), IEC 61010-2-201:2013 (1st Ed.)
Smarteh d.o.o. operates a policy of continuous development. Therefore we reserve the right to make changes and improvements to any of the products described in this manual without any prior notice.
MANUFACTURER: SMARTEH d.o.o. Poljubinj 114 5220 Tolmin Slovenia
ii

Longo programmable controller LPC-3.GOT.002
Longo programmable controller LPC-3.GOT.002
1 ABBREVIATIONS................................................................................1 2 DESCRIPTION...................................................................................2 3 FEATURES.......................................................................................3 4 INSTALLATION..................................................................................4
4.1 Block diagram....................................................................................... 4 4.2 Input & output connection interfaces...........................................................5 4.3 Mounting instructions.............................................................................. 7
5 TECHNICAL SPECIFICATIONS.................................................................9 6 CONNECTION & CONFIGURATION GUIDE.................................................10
6.1 Main connection scheme & configuration.....................................................10
7 PROGRAMMING GUIDE.......................................................................12
7.1 Basic functionalities.............................................................................. 12 7.2 GUI design and programming....................................................................15
8 MODULE LABELING...........................................................................16 9 SPARE PARTS..................................................................................17 10 CHANGES ....................................................................................18 11 NOTES........................................................................................19
iii

Longo programmable controller LPC-3.GOT.002

1 ABBREVIATIONS

PLC

Programmable logic controller

GUI

Graphical user interface

TCP

Transmission control protocol

RTU

Remote terminal unit

RTC

Real time clock

IDE

Integrated development environment

FBD

Function block diagram

LD

Ladder diagram

SFC

Sequential function chart

ST

Structured text

IL

Instruction list

CAN

Controller area network

COM

Communication

SD

Secure digital

LED

Light emitting diode

RAM

Random access memory

NV

Non volatile

PS

Power supply

1

Longo programmable controller LPC-3.GOT.002
2 DESCRIPTION
Smarteh LPC-3.GOT.002 graphical operation terminal is designed and developed as ideal solution for building automation as a supplement to LPC-2 modules. It is PLC based product with software tools allowing users to design GUI. Different communication protocols offers various connectivity opportunities. Aluminium frame with resistive touch screen offers an intuitive, clear and flexible interface between the user and the building. LPC-3.GOT.002 is equipped with Ethernet connection and can be used as a Modbus TCP/IP Master and/or Slave device or BACnet IP (B-ASC). USB port is used for local programming and debugging. Over TCP/IP, programming and debugging is possible via LAN (inside building) or even via WAN network (remotely over internet). LPC-3.GOT.002 is powered from external DC power supply. LPC-3.GOT.002 includes two galvanic isolated CAN bus for CANopen protocol and non-isolated RS-485 bus for Modbus RTU master protocol, used e.g. for local or remote connection to other LPC PLCs. It also has Smarteh bus port for connection with Smarteh LPC-2 slave devices. Integrated ''Setting Storage FLASH'', "RTC" and "NV RAM", does not need the battery for it is functioning. There is also a built-in buzzer which can be controlled through PLC program. Smarteh IDE (Integrated Development Environment) software tool is used with all the PLCs from the LPC family and it supports all five standard PLC programmable languages (FBD, LD, SFC, ST, IL). It also supports "off line'', ''on line'' debugging and local/remote program transferring. Distributed processing is supported which makes it possible to handle fast operations. GUI design tool supports large set of dynamic controls from buttons to indicators and enables connectivity between PLC programs and user interface. LPC-3.GOT.002 is an innovative and an attractive solution for a competitive price.
2

Longo programmable controller LPC-3.GOT.002
3 FEATURES
Figure 1: LPC-3.GOT.002
Table 1: Features
Aluminium frame with 7" LCD display and resistive touch screen - landscape or portrait orientation Graphical interface is freely designed by the user with GUI editor in SmartehIDE Ethernet connectivity with Modbus TCP/IP Slave (server) and/or Master (client) functionality, BACnet IP (B-ASC), web server and SSL Modbus RTU Master or Slave Smarteh bus USB port for debugging and application transfer Remote access and application transfer 2 galvanic isolated (2500 V DC) CAN port - one for master, one for slave RTC and 512 kB NV RAM with super capacitor for needed energy storage Micro SD Card slot Built-in buzzer controlled from PLC program Display brightness level controlled from PLC program Disconnectable spring type connectors Status LEDs Flush mount Quality design
3

Longo programmable controller LPC-3.GOT.002
4 INSTALLATION
4.1 Block diagram
Figure 2: LPC-3.GOT block diagram1
1 Coloured areas represents different voltage domains - galvanic isolated areas. Please refer to General technical specifications in TECHNICAL SPECIFICATION for details.
4

Longo programmable controller LPC-3.GOT.002

4.2 Input & output connection interfaces

Table 2: Power supply2

PS1.1 (+)

PLC power supply

PS1.2 (-)



8 .. 30 V DC, 2 A GND

Table 3: Switches

S1

Operation mode (RUN/STOP)

S2

COM2 RS-485 termination (Trm1)

S3

CAN2 bus termination (Trm2)

S4

CAN1 bus termination (Trm3)

RUN: PLC normal operational mode STOP: application not running
ON: corresponding channel is internally terminated with 120  OFF: no internal termination present
ON: corresponding channel is internally terminated with 120  OFF: no internal termination present
ON: corresponding channel is internally terminated with 120  OFF: no internal termination present

Table 4: CAN1 & CAN23

CAN1.1

CAN1 High (Hi) (Master)

CAN1.2

CAN1 Low (Lo) (Master)

CAN1.3

CAN1 reference point (GND1)

CAN2.1

CAN2 High (Hi) (Slave)

CAN2.2

CAN2 Low (Lo) (Slave)

CAN2.3

CAN2 reference point (GND1)

0 .. 5 V 0 V to CAN1 0 .. 5 V 0 V to CAN2

Table 5: COM2 RS-4854

COM2.1

RS-485 (A)

COM2.2 COM2.3

RS-485 (B) -- ()

COM2.4

+U

0 .. 5 V
GND Power supply output

2 Wires connected to the module must have cross sectional area at least 0.75 mm2. Minimum temperature rating of wire insulation must be 85 °C.
3 Wires connected to the module must have cross sectional area at least 0.14 mm2. Use twisted-pair cables of type CAT5+ or better, shielding is recommended. Minimum temperature rating of wire insulation must be 85 °C. Galvanic isolation of 2500 V DC between CAN1, CAN2 and rest of the PLC circuit is provided.
4 Different protocols like Modbus RTU Master can be selected inside Smarteh IDE. Wires connected to the module must have cross sectional area at least 0.14 mm2. Use twisted-pair cables of type CAT5+ or better, shielding is recommended.
5

Longo programmable controller LPC-3.GOT.002

Table 6: COM1 Smarteh bus

COM1.1

N.C.

COM1.2

(-)()

COM1.3

(+) PLC power supply

COM1.4

RS-485 (A) Smarteh bus

COM1.5

RS-485 (B) Smarteh bus

COM1.6

N.C.

Table 7: LEDs

LED RUN

Application running (green)

LED PWR LED1 (Rx) LED2 (Tx) LED3 (Rx) LED4 (Tx)

Power (green) COM1 Rx status (red) COM1 Tx status (green) COM2 Rx status (red) COM2 Tx status (green)

GND Power supply output
0 .. 5 V
ON: application is running OFF: application is stopped or PLC in boot mode ON: PLC is powered on OFF: PLC has no power supply OFF: No receiving packets ON: Receiving packets OFF: Not transmitting packets ON: Transmitting packets OFF: No receiving packets ON: Receiving packets OFF: Not transmitting packets ON: Transmitting packets

6

Longo programmable controller LPC-3.GOT.002
4.3 Mounting instructions
Figure 3: Housing dimensions
Dimensions in millimetres. EXTERNAL SWITCH OR CIRCUIT-BREAKER AND EXTERNAL OVERCURRENT PROTECTION: The unit is allowed to be connected to installation with over current protection that has nominal value of 6 A or less. All connections, PLC attachments and assembling must be done while LPC-3.GOT.002 is not connected to the main power supply. Wires connected to the PLC must have cross sectional area at least 0.75 mm2. Minimum temperature rating of wire insulation must be 85 °C.
7

Longo programmable controller LPC-3.GOT.002 Mounting instructions for enclosure door
1. Switch off power supply. 2. Make cut out and mounting holes - see Figure 4. 3. Mount LPC-3.GOT.002 to the provided place, using 3 mm screws. 4. Connect input, output and communication wires. 5. Switch on power supply.
Figure 4: Dimensions for cut out and mounting holes
8

Longo programmable controller LPC-3.GOT.002

5 TECHNICAL SPECIFICATIONS

Table 8: Technical specifications

Power supply PS1

8 .. 30 V DC

Inrush current

max. 2 A

Power consumption PS1

max. 5 W

Connection type for PS1

disconnectable spring type connectors for stranded wire 0.75 to 1.5 mm2

Connection type for CAN1, CAN2, COM2

disconnectable spring type connectors for stranded wire 0.14 to 1.5 mm2

Connection type for COM1

RJ-12 6/4

CAN1 or CAN2 isolation voltage to PS1 2500 V DC

COM2 RS-485 port

non isolated, 2 wire

COM1 Smarteh bus

non isolated

Ethernet

RJ-45, 10/100/1000T IEEE 802.3

USB

mini B type, device mode or host mode (USB On-TheGo), high-speed/full-speed

RTC

capacitor backed up with retention of cca. 14 days

Operating system

Linux

CPU

i.MX6 Single (ARM® CortexTM-A9) @ 1GHz

RAM

512 MB DDR3

Flash

4 GB eMMC 8bits (MLC type)

NV RAM

512 kB, capacitor backed up with retention cca. 14 days

Display

7", 800 × 480 resolution, 24 bit colour depth

Dimensions (L x W x H)

160 x 210 x 46 mm

Display dimensions (L x W)

85.5 x 154 mm

Weight

650 g

Ambient temperature

0 to 50°C

Ambient humidity

max. 95 %, no condensation

Maximum altitude

2000 m

Mounting position

vertical

Transport and storage temperature

-20 to 60 °C

Pollution degree

2

Over-voltage category

II

Electrical equipment

class II (double insulation)

Protection class front side

IP 65

Protection class back side

IP 30

9

Longo programmable controller LPC-3.GOT.002
6 CONNECTION & CONFIGURATION GUIDE
6.1 Main connection scheme & configuration
Figure 5: Main connection scheme5
5 Coloured areas represents galvanic isolated areas. Please refer to General technical specifications for details.
10

Longo programmable controller LPC-3.GOT.002
Figure 6: Grounding possibilities

LPC-3.GOT negative power supply pole connected to the Protective Earth (PE) earthing.

functional

LPC-3.GOT negative power supply poles not connected to the Protective Earth (PE) functional earthing.

11

Longo programmable controller LPC-3.GOT.002

7 PROGRAMMING GUIDE
This chapter is intended to offer the programmer additional informations about some of the functionalities and units integrated in this module.

7.1 Basic functionalities

RTC unit For RTC back-up and for Retain variables there is Super Capacitor instead of battery integrated inside PLC. This way, replacement of the discharged battery is avoided. The Retention time is minimum 14 days from the power down. RTC time provides date and time information.

Modbus TCP/IP master unit When configured for Modbus TCP/IP Master / Client mode, the LPC-3.GOT.002 functions as a master device, controlling the communications with other slave devices such as sensors, inverters, other PLCs, etc. LPC-3.GOT.002 sends Modbus TCP/IP commands to and receives Modbus TCP/IP responses from the slave units.
Following commands are supported:
01 ­ Read Coil Status 02 ­ Read Input Status 03 ­ Read Holding Registers 04 ­ Read Input Registers 05 ­ Write Single Coil 06 ­ Write Single Register 15 ­ Write Multiple Coils 16 ­ Write Multiple Registers
Note: each of this command can read/write up to 10000 addresses.

Modbus TCP/IP slave unit Modbus TCP slave has 10000 addresses in each memory section:

Coils: Discrete inputs: Input register: Holding registers:

00000 to 09999 10000 to 19999 30000 to 39999 40000 to 49999

Supports up to 5 connections to the slave units (defined with MaxRemoteTCPClient parameter). Highest scan rate is 100 ms.

Modbus RTU master unit When configured for Modbus RTU Master mode, the the LPC-3.GOT.002 functions as a master device, controlling the communications with other slave devices such as sensors, inverters, other PLCs, etc. LPC-3.GOT.002 sends Modbus RTU commands to and receives Modbus RTU responses from the slave devices.
Following commands are supported:
01 ­ Read Coil Status 02 ­ Read Input Status

12

Longo programmable controller LPC-3.GOT.002

03 ­ Read Holding Registers 04 ­ Read Input Registers 05 ­ Write Single Coil 06 ­ Write Single Register 15 ­ Write Multiple Coils 16 ­ Write Multiple Registers
Note: each of this commands can read/write up to 246 bytes of data. For analog (Input and Holding registers) this means 123 values, while for digital (Statuses and Coils) this means 1968 values. When higher quantity of data is required, LPC-3.GOT.002 can execute up to 32 same or different supported commands simultaneous.
Physical layer: RS-485 Supported baud rates: 9600, 19200, 38400, 57600 and 115200bps Parity: None, Odd, Even. Stop bit: 1

Modbus RTU slave unit Modbus TCP slave has 1023 addresses in each memory section:

Coils: Discrete inputs: Input register: Holding registers:

00000 to 01023 10000 to 11023 30000 to 31023 40000 to 41023

Highest scan rate is 100 ms.

Smarteh RS485 bus for connectivity with LPC-2 system Port COM1 is used for communication with LPC-2 slave modules. All communication settings are configured in SmartehIDE software program.

BACnet IP unit When configured for BACnet IP (B-ACS), following commands are supported:
Data Sharing
ReadProperty-B (DS-RP-B) WriteProperty-B (DS-WP-B)
Device and Network Management
Dynamic Device Binding-B (DM-DDB-B) Dynamic Object Binding-B (DM-DOB-B) Device Communication Control-B (DM-DCC-B) Time Synchronization-B (DM-TS-B) UTCTimeSynchronization-B (DM-UTC-B)
For more information, please contact producer.

CANopen unit CANopen unit consists of Master and Slave communication ports. They are independent, thus can be connected to two different CAN network at the same time.
The ports can operate at baud rates 50 kbps, 125 kbps or 250 kbps.
It follows the internationally standardized (EN 50325-4) CAN-based higher-layer protocol for

13

Longo programmable controller LPC-3.GOT.002
embedded control systems. Advised rules and concepts by this standard must be followed to fulfil the conditions and so achieving normal operation and results. The structure of the network as cable type and lengths, baud rates, number of the nodes and termination must be taken into account within the recommendations and requirements, when designing the network. The bus network can consist of at least one Master and at list one Slave node by the standard, but it is advised that with increased number of nodes, the Master node fastest interval is extended. Below are two examples:
Example 1: network with 1 master and 9 slaves, every slave have defined 32 (4x8) byte of data and baud rate 125 Kbps. Fastest Cycle time for this configuration is 50 ms. Example 2: network with 1 master and 4 slaves, every slave have defined 4 byte of data and baud rate 250 Kbps. Fastest Cycle time for this configuration is 5 ms. 5 ms is the fastest recommended cycle time. It is recommended to power-up all the nodes on the same network at the same time, if some or all nodes had been reprogrammed (to reinitialize the communication properly).
Figure 7: CAN Master and Slave wiring diagram example
RUN/STOP Switch Run: Status RUN status LED "on" indicate that the user graphical application is up and user
program is running. Stop: When the switch is turn to STOP state, the RUN status LED is "off" and application is
stopped. PLC task cycle time Main PLC task interval (under Project tab -> Resource  Tasks  Interval) time is not recommended to be set lower than 50 ms.
14

Longo programmable controller LPC-3.GOT.002
7.2 GUI design and programming
Figure 8: LPC Manager interface example6
Figure 9: Inkscape open source tool7
NOTE: Recommended minimum size of the touch object is 10 x 10 mm.
6 Configuration of the PLC is done using Smarteh IDE software tool. Please refer to LPC Manager user manual for details. 7 Configuration of the PLC is done using Inkscape open source tool.
15

Longo programmable controller LPC-3.GOT.002
8 MODULE LABELING
Figure 10: Label
Label (sample):
XXX-N.ZZZ
P/N: AAABBBCCDDDEEE S/N: SSS-RR-YYXXXXXXXXX D/C: WW/YY
Label description: 1. XXX-N.ZZZ - full product name.  XXX-N - Product family  ZZZ - product 2. P/N: AAABBBCCDDDEEE - part number.  AAA - general code for product family,  BBB - short product name,  CCDDD - sequence code, · CC - year of code opening, · DDD - derivation code,  EEE ­ version code (reserved for future HW and/or SW firmware upgrades). 3. S/N: SSS-RR-YYXXXXXXXXX - serial number.  SSS ­ short product name,  RR ­ user code (test procedure, e.g. Smarteh person xxx),  YY ­ year,  XXXXXXXXX­ current stack number. 4. D/C: WW/YY - date code. · WW ­ week and · YY ­ year of production.
Optional 1. MAC 2. Symbols 3. WAMP 4. QR code 5. Other
16

Longo programmable controller LPC-3.GOT.002

9 SPARE PARTS
For ordering spare parts following Part Numbers should be used:

LPC-3.GOT.002

LPC-3.GOT.002 Graphical operation terminal P/N: 226GOT20002001

Flush mounting box Gewiss 48006

Flush mounting box P/N: 206FMB10001001

17

Longo programmable controller LPC-3.GOT.002

10 CHANGES