Product Description
This fan coil line offers exceptional application flexibility, suitable for upflow, downflow, horizontal right, or horizontal left configurations. All JCI Unitary Products air handlers and coils can utilize a TXV (Thermostatic Expansion Valve) for optimal performance and refrigerant control. Single-piece air handlers are available with 'Flex-coils' for field installation of an R-22 or R-410A TXV or piston to meet specific refrigerant requirements. Some models are available with a factory-installed TXV.
Key Features
- RC2 Rigid Case Construction: Provides interior endoskeleton for structural support, smooth sides, and insulation retention.
- Powder-painted: G30 galvanized steel case offers corrosion and rust creep resistance.
- MaxAlloy™ Coil: Long-life aluminum coils designed for lasting performance and efficiency.
- Quality Construction: Structural components made of Aluminum or G90 galvanized steel to prevent corrosion.
- Improved Insulation Design: Single-piece construction with no external screws minimizes thermal transmission and prevents sweating; foil-faced insulation for easy cleaning.
- Thermostatic Expansion Valve (TXV): Accessory chatleff-style TXV for easy installation and conversion to required refrigerant without brazing.
- Case Depth: 20.5" casing allows for easier attic access and fits tight applications.
- Thermoset Drain Pan: Features a positive slope for drainage, reducing potential for mold or contaminants.
- Factory Sealed: Achieves 2% or less total airflow leakage at specified test conditions for system airflow verification.
- Enhanced Filter Rack: Integrated internal filter racks accommodate 1" thick standard size filters.
- Electric Heat Kits: 6HK series of field-installed electric heat kits are available for easy installation and service.
- Cabinet Air Leakage: Less than 2.0% at 1.0 inch esp., tested per ASHRAE standard 193.
- Blowers: All models use direct-drive, standard ECM motors.
Certifications & Quality
The product is AHRI CERTIFIED®, ISO 9000 certified for Quality Management System, and designed, engineered & assembled in the USA, reflecting American Quality.
Visit us online at www.simplygettingthejobdone.com and www.colemanac.com. Additional rating information is available at www.ahridirectory.org.
Warranty Summary
Features a standard 5-year limited parts warranty. An extended 10-year limited parts warranty is available when the product is registered online within 90 days of purchase for replacement or closing for new home construction.
Nomenclature
Model nomenclature provides details on Product Type (A=Single Piece Air Handler), Position Motor Type (E=Multi Std ECM, V=Multi VS ECM, Z=Compact Up Std ECM), Options (C=Communications Ready, -=Standard), Nominal Unit Capacity (e.g., 18=1.5 Ton, 24=2 Ton, 36=3 Ton, 42=3.5 Ton, 48=4-Ton, 60=5-Ton), Cabinet Width (A=14.5", B=17.5", C=21.0", D=24.5"), TXV Indicator (X=no valve, BA-BF=Valve Size), Voltage (1=115-1-60, 2=208/230-1-60, 3=208/230-3-60, 4=460-3-60), Generation (1=1st Gen, 2=2nd Gen), and Style Letter (A=Style A, B=Style B).
Dimensions & Duct Connection
Diagram showing the physical layout and dimensions (A, B, C, D, E, F, G) of the air handler unit, including blower compartment, coil compartment, filter access, and refrigerant connections. A table provides specific dimensions and wiring knockout sizes for various AE models (e.g., AE18B*21, AE24B*21, AE36C*21, AE48D*21, AE60D*21).
Models | Dimensions¹ (Inches) | Wiring Knockouts² | Refrigerant Connections Line Size | ||||||
---|---|---|---|---|---|---|---|---|---|
A | B | C | D | E | Power | Control | Liquid | Vapor | |
AE18B*21 | 41 | 17-1/2 | 12-7/8 | 14-1/4 | 16-1/2 | 7/8" (1/2") | 7/8" (1/2") | 3/4" | 3/8" |
AE24B*21 | 41 | 17-1/2 | 12-7/8 | 14-1/4 | 16-1/2 | ||||
AE30B*21 | 47-1/2 | 17-1/2 | 19-1/2 | 14-1/4 | 16-1/2 | ||||
AE36B*21 | 47-1/2 | 17-1/2 | 19-1/2 | 14-1/4 | 16-1/2 | ||||
AE36C*21 | 51-1/2 | 21 | 22-5/8 | 17-3/4 | 20 | ||||
AE42C*21 | 51-1/2 | 21 | 22-5/8 | 17-3/4 | 20 | 1-3/8"(1") | 7/8" (1/2") | 3/8" | 3/8" |
AE43C*21 | 51-3/4 | 21 | 26-7/8 | 17-3/4 | 20 | ||||
AE48C*21 | 51-1/2 | 21 | 22-5/8 | 17-3/4 | 20 | ||||
AE48D*21 | 55-1/2 | 24-1/2 | 26-5/8 | 21-1/4 | 23-1/2 | 1-23/32" (1-1/4") | 7/8" | 7/8" | 7/8" |
AE60C*22 | 55-3/4 | 21 | 26-7/8 | 17-3/4 | 20 | ||||
AE60D*21 | 55-1/2 | 24-1/2 | 26-5/8 | 21-1/4 | 23-1/2 | 1-23/32" (1-1/4") | 7/8" | 7/8" | 7/8" |
1. All dimensions are in inches. 2. Actual size (conduit size).
Coil Technical Data
Table detailing coil specifications including model, application, refrigerant connection types, face area (sq. ft.), rows, fins per inch, coil size geometry, tube diameter, and fin type (e.g., Sine Wave) for various AE models.
Models¹ | Application | Refrig. Conn. Types | Face Area (Sq. Ft.) | Rows Deep | Fins Per In. | Coil Size | Tube Geometry | Tube Diameter | Fin Type |
---|---|---|---|---|---|---|---|---|---|
AE18BX21 | Cooling /Heat Pump | Sweat | 4.3 | 2 | 14 | (3) 12 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE18BBA21* | Cooling /Heat Pump | Sweat | 4.3 | 2 | 14 | (3) 12 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE24BX21 | Cooling /Heat Pump | Sweat | 5.0 | 2 | 14 | (3) 14 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE24BBA21* | Cooling /Heat Pump | Sweat | 5.0 | 2 | 14 | (3) 14 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE30BX21 | Cooling /Heat Pump | Sweat | 6.4 | 2 | 14 | (3) 18 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE30BBA21* | Cooling /Heat Pump | Sweat | 6.4 | 2 | 14 | (3) 18 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE36BX21 | Cooling /Heat Pump | Sweat | 7.1 | 2 | 14 | (3) 20 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE36BBA21* | Cooling /Heat Pump | Sweat | 7.1 | 2 | 14 | (3) 20 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE36BBE21* | Cooling /Heat Pump | Sweat | 7.1 | 2 | 14 | (3) 20 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE36CX21 | Cooling /Heat Pump | Sweat | 7.1 | 2 | 14 | (3) 20 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE36CBA21* | Cooling /Heat Pump | Sweat | 7.1 | 2 | 14 | (3) 20 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE36CBE21* | Cooling /Heat Pump | Sweat | 7.1 | 2 | 14 | (3) 20 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE42CX21 | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE42CBC21* | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE42CBF21* | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE43CX21 | Cooling /Heat Pump | Sweat | 6.7 | 3 | 12 | (2) 28 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE48CX21 | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE48CBC21* | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE48DX21 | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE48DBC21* | Cooling /Heat Pump | Sweat | 8.6 | 2 | 14 | (3) 24 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE60CX22 | Cooling /Heat Pump | Sweat | 10.0 | 2 | 14 | (3) 28 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE60CBC22* | Cooling /Heat Pump | Sweat | 10.0 | 2 | 14 | (3) 28 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE60DX21 | Cooling /Heat Pump | Sweat | 10.0 | 3 | 12 | (3) 28 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE60DBC21* | Cooling /Heat Pump | Sweat | 10.0 | 3 | 12 | (3) 28 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
AE60DBG21* | Cooling /Heat Pump | Sweat | 10.0 | 3 | 12 | (3) 28 x 17.1 | 1 x 0.866 | 3/8 | Sine Wave |
1. * Factory-Installed TXV option.
Cooling Capacity
Tables provide cooling capacity data (MBH) for various entering air conditions (Dry/Wet Bulb °F) and corresponding R-410A pressures (°F/PSIG) for different air handler models (e.g., 18B, 24B, 30B, 36B, 36C, 42C, 43C, 48C, 48D, 60C, 60D). Capacity factors for rated CFM vs. actual CFM are also provided.
Models | Rated CFM² | MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG) | |||
---|---|---|---|---|---|
35/107.9 | 40/118.9 | 45/130.7 | 50/143.3 | ||
18B | 600 | 85/72: 45.7 80/67: 38.5 75/62: 31.5 70/57: 24.4 | 41.6 33.9 26.5 19.5 | 36.8 28.5 20.5 15.2 | 30.5 22.3 15.9 11.5 |
24B | 800 | 85/72: 52.2 80/67: 43.6 75/62: 35.2 70/57: 27.1 | 47.5 38.3 29.5 20.7 | 41.8 31.9 22.7 15.5 | 35.0 24.5 16.2 11.4 |
30B | 1000 | 85/72: 75.3 80/67: 62.6 75/62: 50.2 70/57: 37.8 | 67.8 54.6 41.3 30.1 | 56.8 44.2 32.0 21.5 | 47.1 34.5 22.9 16.2 |
36B | 1200 | 85/72: 91.6 80/67: 76.5 75/62: 61.3 70/57: 47.5 | 82.4 65.4 51.2 38.1 | 71.3 54.6 40.0 28.7 | 59.4 42.8 30.5 22.3 |
36C | 1200 | 85/72: 91.6 80/67: 76.5 75/62: 61.3 70/57: 47.5 | 82.4 65.4 51.2 38.1 | 71.3 54.6 40.0 28.7 | 59.4 42.8 30.5 22.3 |
42C | 1400 | 85/72: 108.0 80/67: 93.3 75/62: 75.9 70/57: 60.7 | 98.4 82.1 64.4 49.9 | 88.1 69.7 53.1 39.4 | 73.8 57.0 41.9 32.4 |
1. Actual capacity varies with the outdoor A/C or H/P that is used with the system. 2. Airflow is calculated for each system tonnage.
Physical & Electrical Data - Cooling Only
Tables detail physical and electrical specifications for cooling-only operation, including blower diameter/width, motor HP and RPM, voltage, full load amps, filter type and size, and shipping/operating weight for various models.
Models | 18B | 24B | 30B | 36B | 36C | 42C |
---|---|---|---|---|---|---|
Blower - Diameter x Width | 10 x 8 | 10 x 8 | 10 x 8 | 10 x 8 | 11 x 10 | 11 x 10 |
HP | 1/3 HP | 1/3 HP | 1/3 HP | 1/2 HP | 1/2 HP | 1/2 HP |
Motor Nominal RPM | 1050 | 1050 | 1050 | 1050 | 1050 | 1050 |
Voltage | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 |
Full Load Amps @230V | 2.8 | 2.8 | 2.8 | 4.1 | 4.1 | 4.1 |
Filter¹ Type | DISPOSABLE OR CLEANABLE | |||||
Filter¹ Size | 16 x 20 x 1 | 16 x 20 x 1 | 16 x 20 x 1 | 16 x 20 x 1 | 20 x 20 x 1 | 20 x 20 x 1 |
Permanent Type Kit | 1PF0601 | 1PF0601 | 1PF0601 | 1PF0601 | 1PF0602 | 1PF0602 |
Shipping / Operating Weight (lbs) | 91/85 | 93/87 | 119/113 | 119/113 | 120/114 | 144/136 |
Models | 43C | 48C | 48D | 60C | 60D | |
Blower - Diameter x Width | 11 x 10 | 11 x 10 | 11 x 10 | 11 x 10 | 11 x 10 | |
HP | 3/4 HP | 3/4 HP | 3/4 HP | 3/4 HP | 3/4 HP | |
Motor Nominal RPM | 1050 | 1050 | 1050 | 1050 | 1050 | |
Voltage | 208/230 | 208/230 | 208/230 | 208/230 | 208/230 | |
Full Load Amps @230V | 6.0 | 6.0 | 6.0 | 6.0 | 6.0 | |
Filter¹ Type | DISPOSABLE OR CLEANABLE | |||||
Filter¹ Size | 20 x 20 x 1 | 20 x 20 x 1 | 22 x 20 x 1 | 20 x 20 x 1 | 22 x 20 x 1 | |
Permanent Type Kit | 1PF0602 | 1PF0602 | 1PF0603 | 1PF0602 | 1PF0603 | |
Shipping / Operating Weight (lbs) | 158/150 | 158/150 | 163/153 | 180/170 | 156/146 |
1. Field supplied.
Electrical Data - Cooling Only
Tables show Motor FLA (Full Load Amps), Minimum Circuit Ampacity, and MOP (Maximum Overcurrent Protection) for various air handler models.
Models | Motor FLA¹ | Minimum Circuit Ampacity | MOP² |
---|---|---|---|
18B/24B/30B | 2.8 | 3.5 | 15 |
36B/36C/42C | 4.1 | 5.1 | 15 |
43C/48C/48D/60C/60D | 6.0 | 7.5 | 15 |
1. FLA = Full Load Amps. 2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
Electric Heat Options & Performance
Information on electric heat kits (6HK series) and their performance data for 208/230-1-60 and 208/230-3-60 power supplies. Tables detail nominal kW, kW staging, and MBH output.
Heater Kit Models¹,² | Nominal kW @240V | Total Heat | kW Staging | ||||||
---|---|---|---|---|---|---|---|---|---|
kW | MBH | W1 Only | W1 + W2 | 208V | 230V | 208V | 230V | ||
6HK(0,1)6500206 | 2.4kW | 1.8 | 2.2 | 6.2 | 7.5 | 1.8 | 2.2 | 1.8 | 2.2 |
6HK(0,1)6500506 | 4.8kW | 3.6 | 4.4 | 12.3 | 15 | 3.6 | 4.4 | 3.6 | 4.4 |
6HK(0,1)6500806 | 7.7kW | 5.8 | 7.1 | 19.7 | 24.1 | 5.8 | 7.1 | 5.8 | 7.1 |
6HK(0,1)6501006 | 9.6kW | 7.2 | 8.8 | 24.6 | 30.1 | 7.2 | 8.8 | 7.2 | 8.8 |
6HK(1,2)6501306 | 12.5kW | 9.4 | 11.5 | 32 | 39.2 | 3.1 | 3.8 | 9.4 | 11.5 |
6HK(1,2)6501506 | 14.4kW | 10.8 | 13.2 | 36.9 | 45.1 | 3.6 | 4.4 | 10.8 | 13.2 |
6HK(1,2)6501806 | 17.3kW | 13 | 15.9 | 44.3 | 54.2 | 6.5 | 7.9 | 13 | 15.9 |
6HK(1,2)6502006 | 19.2kW | 14.4 | 17.6 | 49.2 | 60.2 | 7.2 | 8.8 | 14.4 | 17.6 |
6HK(1,2)6502506 | 24kW | 18 | 22 | 61.5 | 75.2 | 7.2 | 8.8 | 18 | 22 |
6HK36501025 | 9.6kW | 7.2 | 8.8 | 24.6 | 30.1 | 7.2 | 8.8 | 7.2 | 8.8 |
6HK36501525 | 14.4kW | 10.8 | 13.2 | 36.9 | 45.1 | 10.8 | 13.2 | 10.8 | 13.2 |
6HK36501825 | 17.3kW | 13 | 15.9 | 44.3 | 54.2 | 13 | 15.9 | 13 | 15.9 |
6HK46502025 | 19.2kW | 14.4 | 17.6 | 49.2 | 60.2 | 7.2 | 8.8 | 14.4 | 17.6 |
6HK46502525 | 24kW | 18 | 22 | 61.5 | 75.2 | 9 | 11 | 18 | 22 |
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect. 2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar. 3. 6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect. 4. For different power distributions, see conversion table on Page 5.
Electrical Data for Single Source Power Supply
Detailed tables provide electrical data for single-source power supplies (208/230-1-60 and 208/230-3-60), including heater amps, minimum circuit ampacity, and MOP for various air handler and heater models.
Air Handler Models | Heater Models¹,² | Heater Amps @240V | Min. Circuit Ampacity | MOP³ | ||
---|---|---|---|---|---|---|
208V | 230V | 208V | 230V | |||
18B | 6HK(0,1)6500206 | 10 | 14.3 | 15.5 | 15 | 20 |
6HK(0,1)6500506 | 20 | 25.1 | 27.4 | 30 | 30 | |
6HK(0,1)6500806 | 32 | 38.4 | 42.1 | 40 | 45 | |
6HK(0,1)6501006 | 40 | 46.8 | 51.3 | 50 | 60 | |
24B | 6HK(0,1)6500206 | 10 | 14.3 | 15.5 | 15 | 20 |
6HK(0,1)6500506 | 20 | 25.1 | 27.4 | 30 | 30 | |
6HK(0,1)6500806 | 32 | 38.4 | 42.1 | 40 | 45 | |
6HK(0,1)6501006 | 40 | 46.8 | 51.3 | 50 | 60 | |
6HK(1,2)6501306 | 52 | 60.0 | 66.0 | 60 | 70 | |
30B | 6HK(0,1)6500206 | 10 | 14.3 | 15.5 | 15 | 20 |
6HK(0,1)6500506 | 20 | 25.1 | 27.4 | 30 | 30 | |
6HK(0,1)6500806 | 32 | 38.4 | 42.1 | 40 | 45 | |
6HK(0,1)6501006 | 40 | 46.8 | 51.3 | 50 | 60 | |
6HK(1,2)6501306 | 52 | 60.0 | 66.0 | 60 | 70 | |
6HK(1,2)6501506 | 60 | 68.4 | 75.2 | 70 | 80 | |
36B | 6HK(0,1)6500206 | 10 | 15.9 | 17.1 | 20 | 20 |
6HK(0,1)6500506 | 20 | 26.8 | 29.0 | 30 | 30 | |
6HK(0,1)6500806 | 32 | 40.0 | 43.7 | 40 | 45 | |
6HK(0,1)6501006 | 40 | 48.4 | 53.0 | 50 | 60 | |
6HK(1,2)6501306 | 52 | 61.6 | 67.6 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 70.0 | 76.9 | 70 | 80 | |
6HK(1,2)6501806 | 72 | 83.3 | 91.5 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 91.7 | 100.8 | 100 | 110 | |
36C | 6HK(0,1)6500206 | 10 | 15.9 | 17.1 | 20 | 20 |
6HK(0,1)6500506 | 20 | 26.8 | 29.0 | 30 | 30 | |
6HK(0,1)6500806 | 32 | 40.0 | 43.7 | 40 | 45 | |
6HK(0,1)6501006 | 40 | 48.4 | 53.0 | 50 | 60 | |
6HK(1,2)6501306 | 52 | 61.6 | 67.6 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 70.0 | 76.9 | 70 | 80 | |
6HK(1,2)6501806 | 72 | 83.3 | 91.5 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 91.7 | 100.8 | 100 | 110 | |
42C | 6HK(0,1)6500206 | 10 | 15.9 | 17.1 | 20 | 20 |
6HK(0,1)6500506 | 20 | 26.8 | 29.0 | 30 | 30 | |
6HK(0,1)6500806 | 32 | 40.0 | 43.7 | 40 | 45 | |
6HK(0,1)6501006 | 40 | 48.4 | 53.0 | 50 | 60 | |
6HK(1,2)6501306 | 52 | 61.6 | 67.6 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 70.0 | 76.9 | 70 | 80 | |
6HK(1,2)6501806 | 72 | 83.3 | 91.5 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 91.7 | 100.8 | 100 | 110 | |
43C | 6HK(0,1)6500206 | 10 | 17.6 | 18.7 | 20 | 20 |
6HK(0,1)6500506 | 20 | 28.4 | 30.7 | 30 | 35 | |
6HK(0,1)6500806 | 32 | 41.6 | 45.3 | 45 | 50 | |
6HK(0,1)6501006 | 40 | 50.0 | 54.6 | 60 | 60 | |
6HK(1,2)6501306 | 52 | 63.2 | 69.3 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 71.7 | 78.5 | 80 | 80 | |
6HK(1,2)6501806 | 72 | 84.9 | 93.2 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 93.3 | 102.4 | 100 | 110 | |
48C | 6HK(0,1)6500206 | 10 | 18.3 | 19.5 | 20 | 20 |
6HK(0,1)6500506 | 20 | 29.1 | 31.4 | 30 | 35 | |
6HK(0,1)6500806 | 32 | 42.4 | 46.1 | 45 | 50 | |
6HK(0,1)6501006 | 40 | 50.8 | 55.3 | 60 | 60 | |
6HK(1,2)6501306 | 52 | 64.0 | 70.0 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 72.4 | 79.2 | 80 | 80 | |
6HK(1,2)6501806 | 72 | 85.6 | 93.9 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 94.0 | 103.2 | 100 | 110 | |
48D | 6HK(0,1)6500206 | 10 | 18.3 | 19.5 | 20 | 20 |
6HK(0,1)6500506 | 20 | 29.1 | 31.4 | 30 | 35 | |
6HK(0,1)6500806 | 32 | 42.4 | 46.1 | 45 | 50 | |
6HK(0,1)6501006 | 40 | 50.8 | 55.3 | 60 | 60 | |
6HK(1,2)6501306 | 52 | 64.0 | 70.0 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 72.4 | 79.2 | 80 | 80 | |
6HK(1,2)6501806 | 72 | 85.6 | 93.9 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 94.0 | 103.2 | 100 | 110 | |
6HK(1,2)6502506 | 100 | 115.7 | 127.1 | 125 | 150 | |
60C | 6HK(0,1)6500206 | 10 | 18.3 | 19.5 | 20 | 20 |
6HK(0,1)6500506 | 20 | 29.1 | 31.4 | 30 | 35 | |
6HK(0,1)6500806 | 32 | 42.4 | 46.1 | 45 | 50 | |
6HK(0,1)6501006 | 40 | 50.8 | 55.3 | 60 | 60 | |
6HK(1,2)6501306 | 52 | 64.0 | 70.0 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 72.4 | 79.2 | 80 | 80 | |
6HK(1,2)6501806 | 72 | 85.6 | 93.9 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 94.0 | 103.2 | 100 | 110 | |
60D | 6HK(0,1)6500206 | 10 | 18.3 | 19.5 | 20 | 20 |
6HK(0,1)6500506 | 20 | 29.1 | 31.4 | 30 | 35 | |
6HK(0,1)6500806 | 32 | 42.4 | 46.1 | 45 | 50 | |
6HK(0,1)6501006 | 40 | 50.8 | 55.3 | 60 | 60 | |
6HK(1,2)6501306 | 52 | 64.0 | 70.0 | 70 | 70 | |
6HK(1,2)6501506 | 60 | 72.4 | 79.2 | 80 | 80 | |
6HK(1,2)6501806 | 72 | 85.6 | 93.9 | 90 | 100 | |
6HK(1,2)6502006 | 80 | 94.0 | 103.2 | 100 | 110 | |
6HK(1,2)6502506 | 100 | 115.7 | 127.1 | 125 | 150 |
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect. 2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar. 3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
Electrical Data for Multi-Source Power Supply
Tables provide electrical data for multi-source power supplies (208/230-1-60 and 208/230-3-60), detailing heater amps, minimum circuit ampacity, and MOP for various models.
Air Handlers Models | Heater Models¹ | Heater Amps @240V | Min. Circuit Ampacity | MOP² | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
208V | 230V | 208V | 230V | 208V | 230V | 208V | 230V | |||||||
1st³ | 2nd | 1st³ | 2nd | 3rd | 1st³ | 2nd | 3rd | |||||||
24B | 6HK16501306 | 52 | 22.3 | 37.6 | 24.3 | 41.5 | 25 | 40 | 25 | 45 | ||||
6HK16501306 | 52 | 22.3 | 37.6 | 24.3 | 41.5 | 25 | 40 | 25 | 45 | |||||
30B | 6HK16501506 | 60 | 25.2 | 43.3 | 27.5 | 47.9 | 30 | 45 | 30 | 50 | ||||
6HK16501306 | 52 | 23.9 | 37.6 | 25.9 | 41.5 | 25 | 40 | 30 | 45 | |||||
6HK16501506 | 60 | 26.8 | 43.3 | 29.1 | 47.9 | 30 | 45 | 30 | 50 | |||||
36B | 6HK16501806 | 72 | 44.1 | 39.0 | 48.3 | 43.1 | 45 | 40 | 50 | 45 | ||||
6HK16502006 | 80 | 48.5 | 43.3 | 53.0 | 47.9 | 50 | 45 | 60 | 50 | |||||
36C | 6HK16501306 | 52 | 23.9 | 37.6 | 25.9 | 41.5 | 25 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 26.8 | 43.3 | 29.1 | 47.9 | 30 | 45 | 30 | 50 | |||||
6HK16501806 | 72 | 44.1 | 39.0 | 48.3 | 43.1 | 45 | 40 | 50 | 45 | |||||
6HK16502006 | 80 | 48.5 | 43.3 | 53.0 | 47.9 | 50 | 45 | 60 | 50 | |||||
42C | 6HK16501306 | 52 | 23.9 | 37.6 | 25.9 | 41.5 | 25 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 26.8 | 43.3 | 29.1 | 47.9 | 30 | 45 | 30 | 50 | |||||
6HK16501806 | 72 | 44.1 | 39.0 | 48.3 | 43.1 | 45 | 40 | 50 | 45 | |||||
6HK16502006 | 80 | 48.5 | 43.3 | 53.0 | 47.9 | 50 | 45 | 60 | 50 | |||||
43C | 6HK16501306 | 52 | 25.5 | 37.6 | 27.5 | 41.5 | 30 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 28.4 | 43.3 | 30.7 | 47.9 | 30 | 45 | 35 | 50 | |||||
6HK16501806 | 72 | 45.8 | 39.0 | 49.9 | 43.1 | 50 | 40 | 50 | 45 | |||||
6HK16502006 | 80 | 50.1 | 43.3 | 54.7 | 47.9 | 50 | 45 | 60 | 50 | |||||
48C | 6HK16501306 | 52 | 26.3 | 37.6 | 28.3 | 41.5 | 30 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 29.2 | 43.3 | 31.5 | 47.9 | 30 | 45 | 35 | 50 | |||||
6HK16501806 | 72 | 46.5 | 39.0 | 50.6 | 43.1 | 50 | 40 | 60 | 45 | |||||
6HK16502006 | 80 | 50.8 | 43.3 | 55.4 | 47.9 | 60 | 45 | 60 | 50 | |||||
48D | 6HK16501306 | 52 | 26.3 | 37.6 | 28.3 | 41.5 | 30 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 29.1 | 43.3 | 31.5 | 47.9 | 30 | 45 | 35 | 50 | |||||
6HK16501806 | 72 | 46.6 | 39.1 | 50.6 | 43.1 | 50 | 40 | 60 | 45 | |||||
6HK16502006 | 80 | 50.8 | 43.3 | 55.4 | 47.9 | 60 | 45 | 60 | 50 | |||||
6HK16502506 | 100 | 50.8 | 43.3 | 21.6 | 55.4 | 47.9 | 24.0 | 60 | 45 | 25 | 60 | 50 | 25 | |
60C | 6HK16501306 | 52 | 26.3 | 37.6 | 28.3 | 41.5 | 30 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 29.2 | 43.3 | 31.5 | 47.9 | 30 | 45 | 35 | 50 | |||||
6HK16501806 | 72 | 46.5 | 39.0 | 50.6 | 43.1 | 50 | 40 | 60 | 45 | |||||
6HK16502006 | 80 | 50.8 | 43.3 | 55.4 | 47.9 | 60 | 45 | 60 | 50 | |||||
60D | 6HK16501306 | 52 | 26.3 | 37.6 | 28.3 | 41.5 | 30 | 40 | 30 | 45 | ||||
6HK16501506 | 60 | 29.2 | 43.3 | 31.5 | 47.9 | 30 | 45 | 35 | 50 | |||||
6HK16501806 | 72 | 46.5 | 39.0 | 50.6 | 43.1 | 50 | 40 | 60 | 45 | |||||
6HK16502006 | 80 | 50.8 | 43.3 | 55.4 | 47.9 | 60 | 45 | 60 | 50 | |||||
6HK16502506 | 100 | 50.8 | 43.3 | 21.7 | 55.4 | 47.9 | 24.0 | 60 | 45 | 25 | 60 | 50 | 25 |
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect. 2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar. 3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
Power Wiring - Line Connections
Diagrams illustrating typical wiring configurations for single-phase and three-phase electric heat options, including single-source and multi-source power supplies. These diagrams show connections for power supply, terminal blocks, service disconnects, and circuits.
Blower Speed Connections
Diagram for Standard ECM - High Efficiency Motor showing connections for resistor, 230V transformer (L, C, G, N), and blower motor.
Accessories
Various accessories are available, including TXV Kits (for field installation on Flex-coils), Combustible Floor Base Accessories (S1-1FB1917, S1-1FB1921, S1-1FB1924) for downflow installations on combustible floors, Breaker Moisture Seal Accessories (S1-02435672000) to protect circuit breakers from humidity and dust, and compatible Coleman touch screen thermostats.
Limitations
Units must be wired and installed according to all national and local safety codes. Voltage limits are specified, with a normal operating voltage range of 187-253V for 208/230-1-60 systems. Airflow must remain within approved limits for electric heat, evaporator coils, and outdoor units.
Typical Applications
Diagrams illustrate typical installation configurations: Upflow, Downflow, Horizontal Right, and Horizontal Left.
Typical Thermostat Connection
Wiring diagrams are provided for various thermostat connection scenarios: Cooling Only, Cooling with Electric Heat (10 kW and below), Cooling with Electric Heat (13 kW and above), Single Stage Heat Pump and Electric Heat (10 kW and below), and Single Stage Heat Pump and Electric Heat (13 kW and above).
Air Flow Data (CFM)
Comprehensive tables provide Air Flow Data (CFM) for different models across various external static pressures (in. wc.) and blower motor speeds (#1 LO to #5 HI). These tables are based on testing at 230V and are applicable for other distribution voltages with minimal variation.
Models | Blower Motor Speed | External Static Pressure (in. wc.) | ||||||
---|---|---|---|---|---|---|---|---|
0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 | 0.70 | ||
18B | #5 HI | 1132 | 1107 | 1074 | 1053 | 1023 | 990 | 955 |
#4 MED-HI | 1025 | 994 | 971 | 943 | 912 | 878 | 803 | |
#3 MED | 821 | 798 | 764 | 727 | 657 | 599 | 536 | |
#2 MED-LO | 661 | 632 | 572 | 491 | 414 | 335 | 279 | |
#1 LO | 510 | 435 | 365 | 291 | 181 | 147 | 23 | |
24B | #5 HI | 1117 | 1078 | 1061 | 1034 | 1007 | 985 | 955 |
#4 MED-HI | 1032 | 1001 | 975 | 946 | 928 | 898 | 872 | |
#3 MED | 838 | 799 | 768 | 742 | 698 | 634 | 582 | |
#2 MED-LO | 644 | 620 | 582 | 521 | 440 | 378 | 284 | |
#1 LO | 474 | 421 | 336 | 279 | 187 | 144 | 70 | |
30B | #5 HI | 1113 | 1083 | 1057 | 1034 | 1007 | 977 | 941 |
#4 MED-HI | 1057 | 1021 | 1000 | 977 | 947 | 914 | 881 | |
#3 MED | 857 | 821 | 794 | 768 | 728 | 653 | 601 | |
#2 MED-LO | 675 | 641 | 607 | 533 | 460 | 408 | 345 | |
#1 LO | 489 | 457 | 386 | 324 | 261 | 209 | 158 | |
36B | #5 HI | 1323 | 1287 | 1264 | 1238 | 1210 | 1177 | 1149 |
#4 MED-HI | 1255 | 1222 | 1193 | 1170 | 1140 | 1113 | 1081 | |
#3 MED | 1052 | 1025 | 992 | 967 | 927 | 857 | 811 | |
#2 MED-LO | 855 | 823 | 799 | 739 | 691 | 637 | 572 | |
#1 LO | 653 | 622 | 574 | 507 | 463 | 411 | 353 | |
36C | #5 HI | 1562 | 1531 | 1496 | 1453 | 1416 | 1381 | 1348 |
#4 MED-HI | 1277 | 1240 | 1206 | 1165 | 1133 | 1083 | 1025 | |
#3 MED | 1078 | 1043 | 996 | 957 | 899 | 819 | 770 | |
#2 MED-LO | 881 | 836 | 810 | 749 | 658 | 578 | 537 | |
#1 LO | 707 | 677 | 595 | 524 | 451 | 405 | 346 | |
42C | #5 HI | 1594 | 1564 | 1530 | 1497 | 1459 | 1424 | 1382 |
#4 MED-HI | 1442 | 1408 | 1374 | 1338 | 1298 | 1251 | 1199 | |
#3 MED | 1249 | 1215 | 1179 | 1135 | 1082 | 1016 | 956 | |
#2 MED-LO | 1048 | 1008 | 962 | 905 | 840 | 761 | 683 | |
#1 LO | 881 | 833 | 786 | 708 | 623 | 540 | 481 | |
43C | #5 HI | 1743 | 1711 | 1675 | 1643 | 1607 | 1572 | 1528 |
#4 MED-HI | 1464 | 1425 | 1390 | 1353 | 1317 | 1272 | 1224 | |
#3 MED | 1259 | 1221 | 1178 | 1137 | 1088 | 1043 | 947 | |
#2 MED-LO | 1069 | 1031 | 978 | 924 | 865 | 760 | 704 | |
#1 LO | 825 | 782 | 727 | 621 | 566 | 519 | 470 | |
48C | #5 HI | 1759 | 1719 | 1685 | 1644 | 1611 | 1578 | 1540 |
#4 MED-HI | 1684 | 1639 | 1606 | 1569 | 1536 | 1489 | 1452 | |
#3 MED | 1511 | 1460 | 1427 | 1388 | 1347 | 1308 | 1262 | |
#2 MED-LO | 1305 | 1260 | 1212 | 1178 | 1121 | 1076 | 1027 | |
#1 LO | 1123 | 1068 | 1029 | 985 | 909 | 793 | 769 | |
48D | #5 HI | 1774 | 1726 | 1684 | 1651 | 1614 | 1574 | 1529 |
#4 MED-HI | 1709 | 1668 | 1619 | 1580 | 1548 | 1499 | 1459 | |
#3 MED | 1484 | 1436 | 1410 | 1372 | 1321 | 1284 | 1237 | |
#2 MED-LO | 1295 | 1254 | 1218 | 1167 | 1114 | 1069 | 1005 | |
#1 LO | 1102 | 1051 | 1011 | 962 | 890 | 831 | 766 | |
60C | #5 HI | 1964 | 1930 | 1897 | 1858 | 1823 | 1789 | 1752 |
#4 MED-HI | 1889 | 1855 | 1818 | 1791 | 1747 | 1716 | 1668 | |
#3 MED | 1693 | 1652 | 1627 | 1584 | 1551 | 1510 | 1462 | |
#2 MED-LO | 1486 | 1450 | 1411 | 1375 | 1335 | 1291 | 1252 | |
#1 LO | 1292 | 1247 | 1207 | 1172 | 1123 | 1055 | 990 | |
60D | #5 HI | 1907 | 1871 | 1835 | 1796 | 1762 | 1723 | 1681 |
#4 MED-HI | 1851 | 1816 | 1774 | 1742 | 1699 | 1659 | 1616 | |
#3 MED | 1648 | 1608 | 1569 | 1530 | 1492 | 1445 | 1404 | |
#2 MED-LO | 1456 | 1416 | 1371 | 1333 | 1289 | 1227 | 1163 | |
#1 LO | 1261 | 1221 | 1172 | 1120 | 1055 | 998 | 949 |
1. Air handler units have been tested to UL 1995 / CSA 22.2 No.236 standards up to 0.50" wc. external static pressure. 2. Dry coil conditions only, tested without filters. For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Heating applications tested at 0.50" w.c. esp. Airflow data shown is from testing performed at 230V. AE units use a standard ECM constant torque motor, and there is minimal variation of airflow at other distribution voltage values. The above data can be used for airflow at other distribution voltages.