HMI WING HY Control Panel Manual
Version 04.2021
Product Overview
The HMI WING HY is a control panel designed for all types of WING EC air curtains. It features an intuitive interface with a touch keypad and a backlit screen, ensuring ease of use. Constructed from high-quality electronic materials, it is designed for continuous operation on a 230 V AC single-phase power supply. The controller is easily installed in a standard Ø60 mm flush mounting box using a provided mounting bracket, which also facilitates easy removal. Electrical connections are made directly to a terminal block on the rear of the unit. The panel allows for three-stage regulation of fan speed for EC motors and three-stage regulation of heating power. An integrated thermostat and programmer function enable weekly scheduling of operating parameters, including separate settings for weekdays and weekends, with up to four heating periods per day.
Automatic Operation Modes
With an external door sensor installed, the controller offers three automatic operation modes:
- Door (default): Heating with air supply or air supply only, maintaining a set temperature. Active only when the door is open.
- Room: Heating with air supply or air supply only (air supply activated manually), maintaining a set temperature. Active regardless of the door sensor status.
- Door + Room: Heating with air supply or air supply only, maintaining a set temperature. Active depending on the door sensor status.
The HMI WING HY controller optimizes air curtain operation for continuous and reliable performance, with features designed for significant energy savings.
Control Panel Interface and Operation
The control panel displays various icons and information:
- Fan Speed: Indicates the current fan speed setting.
- Timer: Shows the status of the timer function.
- Clock/Calendar: Displays the current time and day of the week.
- Heating Mode: Indicates the heating status (e.g., single or double heating coil operation).
- Wi-Fi Icon: Indicates Wi-Fi connectivity status.
- Lock Icon: Indicates if the screen lock is active.
- Door Status Icon: Shows whether the door is open or closed.
Key functions and their operation:
- Heating Mode: Adjusts heating power levels.
- Calendar Programming: Allows setting weekly operating schedules.
- Screen Lock: Prevents unintended changes to settings.
- Door Sensor: Detects door status for automatic mode adjustments.
Advanced Settings (Mode A)
To enter advanced settings mode A, press and hold the [QA] buttons for 5 seconds while the controller is off. Use the [Set] button to navigate through settings and [^]/[v] buttons to change values. Pressing any other button exits programming mode.
Key Settings in Mode A:
No. | Function | Set point |
---|---|---|
IP | Modbus RTU Communication - Address | N/A |
A0 | Automatic Operation Modes: Door [1], Room [0], Door+Room [2] | Selection [0, 1, 2] |
A1 | Heating Power Level: No heating [0], 1st level [1], 2nd level [2], 3rd level [3] | Selection [0, 1, 2, 3] |
A2 | Temperature Sensor Calibration | Max. ±8°C in 0.5°C steps |
A3 | Heating Mode: Heating [0], Ventilation [1], Heating+Ventilation [2] | Selection [0, 1, 2] |
A4 | Hysteresis of Differential Adjuster | 0.5 / 1 / 2 |
A5 | First Speed Value | 15-80% |
A6 | Second Speed Value | 15-90% |
A7 | Third Speed Value | 15-100% |
A8 | Fan Speed Delay | 30-200 s |
A9 | Backlight Time | 5-600 s |
AA | Door Optimum | 0, +1, +2, +3 |
AB | Door Sensor Logic | NO [0], NC [1] |
AC | Min. Fan Speed during Cooling Down | 45-100% |
AD | Min. Fan Speed | Display only |
AE | Calendar-based Work | No [0], Yes [1] |
AF | Time Mode | 12h [1]; 24h [0] |
B0 | Buttons Blockade | Selection |
B1 | Extra Heating Time | 0-90 s |
Bo | Default Settings | Hold [Fan] button |
BU | Version Number | XX |
Advanced Settings (Mode C)
To enter advanced settings mode C, press and hold the [Set] button for 5 seconds while the controller is off. Use the [Set] button to navigate and [^]/[v] buttons to change values. Pressing any other button exits programming mode.
Key Settings in Mode C:
No. | Function | Set point |
---|---|---|
C0 | Temperature Units | °C / °F |
C1 | Min. Temperature | 5-15°C |
C2 | Max. Temperature | 16-40°C |
C3 | Modbus RTU Communication - Speed | N/A |
C4 | Modbus RTU Communication - Parity | N/A |
Wiring and Connections
Wiring Diagrams: Refer to the specific wiring diagrams for individual Volcano EC heaters. Full electrical diagrams are available for download at www.vtsgroup.com.
Terminal List:
- L: 230 V AC Live
- N: 230 V AC Neutral
- H1, H2: Heating Outputs
- Ao: Analog Output (0-10V)
- GND: Analog Ground
- DS: Door Sensor Input
Suggested Electric Wire Sizes:
- L, N: 2x1 mm²
- H, C: 2x1 mm²
- AO, GND: 2x0.5 mm² LIYCY
- External Temperature Sensor: 2x0.5 mm² LIYCY
Wi-Fi Communication and Tuya Smart App
The HMI WING HY controller supports Wi-Fi communication and can be controlled via the Tuya Smart application, available for Android and iOS devices.
First Connection:
- Ensure both your smartphone and the HMI controller are within the same network range. Enabling GPS on your phone can facilitate the connection process.
- In the Tuya app, find "Thermostat" under the "small devices" category.
- On the controller, press and hold the "fan" and "set" buttons until the Wi-Fi icons appear and start blinking.
- Confirm the connection attempt in the Tuya app and enter your Wi-Fi network password. Connection may take several minutes. The icons will stop blinking once connected.
Subsequent connections follow the same procedure. Once paired, the controller and phone do not need to be in the same Wi-Fi network.
Control via App:
The Tuya Smart app allows users to view and modify all controller functions. Advanced settings require the password: 123456. Control can be managed through either the app or the controller itself.
Door Optimum Function
The "Door Optimum" function (setting AA) allows for adjusting fan speed based on door status:
- +0: No fan speed increase when the door is open.
- +1: Fan speed increases by one level when the door is open.
- +2: Fan speed increases by two levels when the door is open.
This function's behavior depends on the operating mode:
- In thermostat mode, "Door Optimum" has no effect as temperature is the primary control parameter.
- In door or door+room modes, "Door Optimum" adjusts fan speed upon door opening and closing.
Extra Heating Time Function
The B1 function allows programming a room heating period after the door closes, with a duration adjustable from 0 to 90 seconds.
Device Operation
- Switching Off: Press and hold the power button to turn off the panel.
- Switching On: Touch the power button to turn on the panel.
Technical Specifications
Parameter | Specification |
---|---|
Type | Control panel, regulator |
Temperature Measurement | -10 °C to +99 °C; NTC10K |
Operation | Physical keypad buttons. Advanced Settings A: Hold [QA] for 5s (device off). Advanced Settings C: Hold [Set] for 5s (device off). |
Calendar Function | Weekly calendar programming (individual settings per day) |
Communication | Modbus RTU protocol |
Transmission Speed | 2400/4800/9600 bps |
Outputs | 1 Analog Output (0-10V, 8-bit, Imax=20mA), 2 Relay Outputs (250 VAC, AC1 500 VA for 230 VAC) |
Power Supply | 230 V AC |
Power Consumption | 1.5 VA |
Display | Backlit graphic LCD (white text, blue background) |
Construction Material | ABS + Plexiglas |
Dimensions (W x H x D) | 86 mm x 86 mm x 17 mm |
Installation | Standard Ø60 mounting box with mounting bracket |
Weight | 150 g |
Error Messages
- E1: Internal temperature sensor error.
Norms and Standards
The use of advanced technology and high-quality standards in VTS Group products results from continuous development. Differences between documentation and actual device functionality may occur. Data, drawings, and descriptions in this manual cannot be used as a basis for legal claims.