User Manual for HUAWEI models including: R4875G1, R4875G1 Digital Rectifier, Digital Rectifier, Rectifier

PowerPoint 演示文稿

Fuxiaobing Huawei Technologies Co.,Ltd.

R4875G1 Rectifier User Manual V2.3

5 янв. 2025 г. — Overview. The R4875G1 is a digital rectifier with high efficiency and high power density. It supports a wide input voltage range and provides the 53.5 V DC ...

R4875G1 Rectifier User Manual

Welches Huawei-48V-Ladegerät genau? R4850G2 & Co... - DIY Akkus - Komponenten, Aufbau, Methoden, Problem - Akkudoktor Forum


File Info : application/pdf, 4 Pages, 484.09KB

PDF preview unavailable. Download the PDF instead.

R4875G1 Rectifier User Manual
R4875G1 Rectifier User Manual V2.3

Key Specifications

Efficiency

Peak efficiency: 97%  96% (230 V AC, 30%­80% load)

Dimensions (H x W x D)

40.8 mm x 105 mm x 269 mm

Weight

 2.2 kg

Cooling mode

Built-in fan (fan speed adjustment)

IP rating IP20

Overview
The R4875G1 is a digital rectifier with high efficiency and high power density. It supports a wide input voltage range and provides the 53.5 V DC or 57 V DC default output voltage. The rectifier provides comprehensive protection functions, supports soft start, and produces low noise. Multiple rectifiers can be connected in parallel. With the power monitoring technology, states of the rectifier and load are monitored in real time, and the output voltage can be adjusted.

Key Features
 Wide input voltage range  Wide operating temperature range  Low total harmonic distortion (THD)  Full digital control  Hot swappable  Supports a smart electricity meter  Supports CAN bus communication  Supports LED alarm display  Supports voltage adjustment, current
adjustment, and current equalization  Disconnects at above 320 V AC  RoHS compliance  TUV and CE certifications, CB report
Environment Specifications

Item

Specifications

Operating temperature range

­40 to +75

Storage temperature

range

­40 to +75

Item
Relative humidity
Altitude
Environmental requirements

Specifications
5% RH­95% RH (non-condensing)
 5000 m (When the altitude ranges from 2000 m to 5000 m, the operating temperature decreases by 1 for each additional 200 m.)
 There should be no conductive dust, corrosive gas, or explosion hazard.
 Dust, corrosive substances, pests, molds, and other indicators should be controlled in accordance with Class 3.1 requirements in ETSI EN 300 019-1-3 (V2.3.2 or a later version).
 If the module is configured in a direct ventilation cabinet or an outdoor cabinet, the IP rating of the cabinet must be greater than or equal to IP55.

Electrical Specifications

Item
Input

Specifications

Input voltage range 85 V AC­300 V AC

Input frequency

45 Hz­66 Hz Rated frequency: 50 Hz/60 Hz

Rated input current  21 A

Power factor THD
Output
Output voltage
Output power Peak efficiency: Regulated voltage precision Ripple and noise
Dynamic response
Standby power consumption Startup time

 0.97 (50%­100% load)  5% (50%­100% load)
42 V DC­58 V DC Rated voltage: 53.5 V DC / 57 V DC 4000 W (176 V AC­300 V AC) 4000 W­1600 W (176 V AC­85 V AC) 97%±0.2%
 ±0.6% x Vo
 200 mVp-p (bandwidth  20 MHz)  25%­50%, 50%­75% load: - Overshoot:  ±5% - Recovery time:  200 s (±0.6% x Vo)
 10%­90% load: - Overshoot:: ±5% - Recovery time:  1 ms (±1% x Vo)
 5 W
3s­10s

Output hold-up time >10 ms

Psophometrically weighted noise voltage
Wide-band noise voltage

 2 mV
 50 mV (3.4 kHz­150 kHz)  20 mV (0.15 MHz­30 MHz)

1

Copyright © Huawei Digital Power Technologies Co., Ltd. 2024. All rights reserved.

R4875G1 Rectifier User Manual V2.3

Other Specifications

Item

Specifications

Protection

Input overvoltage Protection threshold: > 300 V AC

protection

Recovery range: 290 V AC­300 V AC

Input undervoltage Protection threshold: < 80 V AC

protection

Recovery range: 80 V AC­90 V AC

Output overvoltage protection

Protection range: 56 V DC­60 V DC (can be set on the monitoring module) 1. If overvoltage occurs inside a
rectifier, the rectifier will latch off. 2. If the external voltage is greater
than 63 V DC for about 500 ms, the rectifier will latch off.

Output current limiting protection

See Figure 1.

Output shortcircuit protection

A long term short circuit is allowed. After the fault disappears, the rectifier is restored to a healthy state automatically.

Overtemperature The rectifier protects against

protection

overtemperature.

Safety/EMC/Lightning Protection

Certification & Safety

 TUV and CE certifications, CB report  Complies with IEC 62368-1,
IEC 60950-1 standards.

EMC

EN 55032, EN 55024, EN 61000-3-2, EN 61000-3-3, ETSI EN 300 386, ETSI EN201 468, ETSI EN 301489, and ITU-T K.20

Lightning protection

5 kA (8/20 µs)

Reliability

MTBF

 500,000 hours (40)

Audible Noise

Specifications

 55 dB(A) (40)

Output Feature Curves
Figure 1 Output feature curve
Figure 2 Output efficiency curve (230 V AC, 25)
Figure 3 Output power derating curve

2

R4875G1 Rectifier User Manual V2.3

Port Description
Figure 4 Rectifier edge connectors

· If the red indicator is on or the green indicator is off, check the PSU first and then power it on. (Shake the PSU to check whether there is abnormal sound, check whether the PSU has an odor, whether the edge connector is clean and intact, and whether the L/N and PE pins of the edge connector are short-circuited.) Do not directly power on the PSU. Otherwise, it may arc or become faulty.
Replacing a Rectifier
Figure 5 Removing a rectifier

Step 1: Push the locking latch leftwards.
Step 2: Pull out the handle and remove the rectifier from the subrack.
Figure 6 Installing a rectifier

Table 1 Rectifier edge connector definitions

Pin Definition

Function

1­2 OUTPUT-

Output 48 V­

3­5 PRE-CHARGE

Precharging

6

PRESENT

Rectifier in-position detection

7­8 OUTPUT+

Output 48 V+

9

P_ADJ

Power identification signal 1

10

N_ADJ

Power identification signal 2

11

AC_D2

Slot detection signal 2

12 13 14 15­16 17­18

AC_D1 CANL CANH
PE N

Slot detection signal 1 CAN low level CAN high level Protective earth
AC input neutral wire

19­20

L

AC input live wire

21 AC-PRECHAR

Input pre-charge

· Only trained and qualified personnel are allowed to install or service the module.
· A fuse is equipped for the input terminal L (The module does not apply to dual-live wire power scenarios).
· This product should be used in an environment that meets specifications described in the user manual.
· If the product is used with abnormal grid input or exposed to salt mist, dust, or water mist, the product may become faulty, and the resulting product exceptions or component damage are beyond the warranty scope.
· To prevent burns, wear protective gloves and exercise caution when removing a rectifier because it is hot during operation.

Step 1: Place a new rectifier in the correct slot, push the locking latch left, and pull out the handle.
Step 2: Gently push the rectifier along the guide rails into the subrack, close the handle, and flip the locking latch right to secure the handle.
Transportation
During transportation, the product must be securely placed in a packing case. The packing case must comply with related international standards and be printed with marks such as anti-collision and moisture prevention. The packing case containing the product can be transported by any means. Protect the packing case with the product from being dampened and knocked.
Storage
Unused products must be stored in packing cases and placed in a dry, well-ventilated warehouse where the temperature ranges from ­40°C to +75°C, the relative humidity is not greater than 80%, and no corrosive gas exists.
 In an indoor scenario, you are advised to power on the rectifier within seven days after unpacking. If the rectifier cannot be powered on in time, place it in an indoor environment that is dry and without corrosive gas.
 In an outdoor scenario, you are advised to power on the rectifier within 24 hours after unpacking. If the rectifier cannot be powered on in time, place it in an indoor environment that is dry and without corrosive gas.

3

R4875G1 Rectifier User Manual V2.3

Maintenance

 The equipment is powered by high-voltage electricity. Direct or indirect contact (especially through damp objects) with high-voltage electricity may result in serious injury or death.
 Non-standard and improper high-voltage operations may result in accidents such as fire or electric shock.
Table 2 describes the states of LEDs and the causes for faults. Table 2 LED description

Indicator Color Status

Description

Suggestion

Steady on The rectifier has AC input.

The status is normal.

Power indicator

Off The rectifier has no AC input.

Green

The rectifier is faulty.

Blinking at 0.5 Hz

The rectifier is being queried.

 Check whether the input voltage is normal.  If the input is normal, replace the rectifier. Replace the rectifier.
The status is normal.

Blinking at The rectifier is loading an application The rectifier automatically recovers after the

4 Hz program.

loading is finished, and no action is required.

Off

The rectifier is not protected, and there is no alarm.

The status is normal.

Alarm indicator

Yellow

Steady on

The rectifier has generated an alarm

due to ambient overtemperature.

Check that the air vent is not blocked and the

The rectifier has generated a shutdown ambient temperature is within the normal

alarm for protection due to ambient range.

overtemperature or undertemperature.

The rectifier is protected against input over/undervoltage.

Check the power grid voltage.

The rectifier is hibernating.

The status is normal.

Blinking at 0.5 Hz

The communication between the rectifier and the monitoring module is interrupted.

Replace the rectifier or monitoring module.

Off The rectifier is normal.

The status is normal.

Fault indicator
Red

The rectifier latches off due to output overvoltage, or the rectifier is not properly inserted.
Steady on The rectifier has no output due to an internal fault.

Remove the rectifier and then insert it after 1 minute.
Replace the rectifier.

The module is locked upon theft.

Contact the monitoring center to unlock the module.

Suggestions
1.Rectify a fault by referring to Table 2. 2.If you cannot rectify the fault according to Table 2, replace the rectifier. 3.Return the faulty rectifier to Huawei for repair.

Huawei Digital Power Technologies Co., Ltd. Huawei Digital Power Antuoshan Headquarters Futian, Shenzhen 518043 People's Republic of China https://e.huawei.com
4



References