User Manual for swatten models including: 9600, 25K6, SieB-H9600-F Battery Energy Storage System, Battery Energy Storage System, Energy Storage System, Storage System

User Manual Issue 1 Date 2023-0 - swatten

SieB-H-F Issue 1 User Manual Date 2023-07-31 Shanghai Sieyuan Watten Technology Co., Ltd. Powered by Sieyuan Electric Co., Ltd. www.swatten.com

User Manual

User Manual SieB-F (Au)

Australia - swatten


File Info : application/pdf, 36 Pages, 3.50MB

PDF preview unavailable. Download the PDF instead.

66bac60e4e653
User Manual
SieB-H-F

Issue Date

1 2023-07-31

Shanghai Sieyuan Watten Technology Co., Ltd.
Powered by Sieyuan Electric Co., Ltd.

www.swatten.com

All Rights Reserved
 All Rights Reserved No part of this document can be reproduced in any form or by any means without the prior written permission of Shanghai Sieyuan Watten Technology Co., Ltd.(hereinafter "Swatten").
 Trademarks Swatten and other Swatten trademarks used in this manual are owned by Swatten. All other trademarks or registered trademarks mentioned in this manual are owned by their respective owners.
 Software Licenses  It is prohibited to use data contained in firmware or software developed by Swatten, in part or in full,
for commercial purposes by any means.  It is prohibited to perform reverse engineering, cracking, or any other operations that compromise the
original program design of the software developed by Swatten.

Shanghai Sieyuan Watten Technology Co., Ltd.

Address: Website:

No. 3399 Huaning Rd. Minhang District, Shanghai 201100P. R. China https://www.swatten.com

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

I

SieB-H(9600~25K6)-F User Manual

About This Manual

About This Manual
The manual primarily encompasses product information, along with installation, operation, and maintenance guidelines. It will refer to the device as the "inverter" unless otherwise specified.  Target Audience
This manual is intended for professional technicians who have responsibilities for the installation, operation, and maintenance of inverters, as well as users who need to check inverter parameters. Installation Requirements: The installation of the inverter should only be carried out by professional technicians who meet the following requirements  Possess knowledge of electronics, electrical wiring, and mechanical expertise, and be familiar with electrical and mechanical schematics.  Have received professional training related to the installation and commissioning of electrical equipment.  Capable of promptly responding to hazards or emergencies that may arise during the installation and commissioning process.  Familiar with local standards and relevant safety regulations pertaining to electrical systems.  Thoroughly read this manual and understand the safety instructions associated with the operations.  How to Use This Manual  Please carefully read this manual before utilizing the product and store it in a readily accessible location.  All content, images, trademarks, and symbols in this manual are the property of Swatten. No part of this document may be reproduced by individuals not employed by Swatten without written authorization. The contents of this manual may be periodically updated or revised, and the specifications of the actual product purchased should take precedence.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

II

SieB-H(9600~25K6)-F User Manual

About This Manual

 Symbols This manual incorporates crucial safety instructions that are emphasized using specific symbols. These symbols are employed to ensure the safety of individuals and property during product usage or to assist in maximizing product performance efficiently.. It is essential to thoroughly comprehend the significance of the warning symbols to enhance your utilization of the manual.

DANGER Indicates the presence of high-risk potential hazards that, if not avoided, could result in severe injury or even death.
WARNING Indicates the presence of moderate-risk potential hazards that, if not avoided, could result in serious injury or even death.
CAUTION Indicates the presence of low-risk potential hazards that, if not avoided, may lead to minor or moderate injury.
NOTICE Indicates potential risks that, if not avoided, may result in device malfunctions or financial losses.

The "NOTE" designation is used to indicate supplementary information, emphasized content, or helpful tips that can assist you, such as problem-solving techniques or time-saving suggestions.
Change History
Changes between document issues are cumulative, meaning that each subsequent document issue includes all the changes made in earlier issues.
Issue 1 (2024-03-12) This issue is the first official release.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

III

SieB-H(9600~25K6)-F User Manual

Contents

Contents
1 Safety Precaution .................................................................................................................................................... 1 1.1 General Safety ................................................................................................................................................1 1.2 Battery Safety .................................................................................................................................................1 1.3 Emergency Measures ..................................................................................................................................... 3 1.3.1 Battery Electrolyte Leakage ................................................................................................................3 1.3.2 Fire ...................................................................................................................................................... 4 1.4 EU Declaration of Conformity .......................................................................................................................4
2 Product Introduction .............................................................................................................................................. 5 2.1 Product Overview .......................................................................................................................................... 5 2.2 Application Scenarios .................................................................................................................................... 5 2.3 Appearance .....................................................................................................................................................5 2.4 Dimensions .................................................................................................................................................... 7
3 Check and Storage .................................................................................................................................................. 9 3.1 Check Before Receiving ................................................................................................................................ 9 3.2 Scope of Delivery ...........................................................................................................................................9 3.3 Storage ......................................................................................................................................................... 10
4 System Installation ................................................................................................................................................11 4.1 Installation Requirements ............................................................................................................................ 11 4.2 Installing the Battery System ....................................................................................................................... 13 4.2.1 Moving the Equipment ......................................................................................................................13 4.2.2 Installing the Battery System ............................................................................................................ 13
5 Electrical Connection ............................................................................................................................................16 5.1 Safety Precaution ......................................................................................................................................... 16 5.2 Internal Electrical Connections of the Battery .............................................................................................17 5.2.1 Installing an Internal Ground Cable ..................................................................................................17 5.2.2 Installing Communication Terminals ................................................................................................17 5.2.3 Installing Internal DC Terminals & Protection Cover ......................................................................17 5.3 External Electrical Connections of the Battery ............................................................................................18 5.3.1 Connection the PE cable ................................................................................................................... 18 5.3.2 Connecting the Power Cable .............................................................................................................19 5.3.3 Connecting the Communication Cable ............................................................................................. 20
6 System Operation ..................................................................................................................................................22 6.1 Check Before Power ON ..............................................................................................................................22 6.2 Power ON the Battery System ..................................................................................................................... 22 6.3 Indicator Status ............................................................................................................................................ 22 6.3.1 Normal Status ....................................................................................................................................23 6.3.2 Alarming Status .................................................................................................................................23 6.3.3 Fault Status ........................................................................................................................................24
7 Maintenance .......................................................................................................................................................... 28 7.1 Power OFF the Battery System ....................................................................................................................28 7.2 Routine Maintenance ................................................................................................................................... 28
8 Appendix ................................................................................................................................................................ 29

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

IV

SieB-H(9600~25K6)-F User Manual

Contents

8.1 Technical Data ............................................................................................................................................. 29

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

V

SieB-H(9600~25K6)-F User Manual

1 Safety Precaution

1 Safety Precaution
Please ensure to strictly adhere to the safety instructions provided in the user manual during the operation of the system. These instructions are designed to ensure the safe and proper functioning of the equipment and to prevent any potential hazards or accidents.

NOTICE The products have been designed and tested to comply with applicable safety regulations. It is essential to read and follow all safety instructions and cautions before performing any operations. Failure to do so may result in personal injury or property damage, as these products are electrical equipment.

1.1 General Safety
NOTICE  The information in this user manual is subject to change due to product updates or other reasons. This
guide is not a substitute for the product labels or the safety precautions in the user manual unless specified otherwise. All descriptions are for guidance purposes only.  Before proceeding with any installations, carefully read and familiarize yourself with the user manual to understand the product and its associated precautions.  All operations should be carried out by trained and knowledgeable technicians who are well-versed in local safety regulations and standards.  When operating the equipment, utilize insulating tools and wear appropriate personal protective equipment (PPE) to ensure personal safety. This may include anti-static gloves, clothing, and wrist straps when handling electronic devices to protect both yourself and the equipment from damage.
1.2 Battery Safety
DANGER  Power off the equipment before performing any operations to avoid danger. Strictly follow the safety
precautions outlined in this manual and the safety labels on the equipment during operation. The battery system maintains a high voltage during operation.  The inverter used with the battery must be approved by the battery manufacturer. You can obtain the approved list of batteries and matched inverters through the official website.  Do not disassemble, modify, or replace any part of the battery or power control unit without official authorization from the manufacturer. Unauthorized actions may cause electrical shock or equipment damage, for which the manufacturer will not be held responsible.  Avoid hitting, pulling, dragging, squeezing, or stepping on the equipment, and do not expose the battery to fire. Mishandling the battery may lead to explosions.  Keep the battery away from high temperature environments. Ensure there is no direct sunlight or heat source near the battery. Temperatures exceeding 60 can cause fires.  Do not use a defective, broken, or damaged battery or power control unit. Damaged batteries may leak electrolyte.  During transportation, take precautions to protect the battery pack and its components. Ensure that transportation personnel are trained and record all transportation operations. Keep the equipment

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

1

SieB-H(9600~25K6)-F User Manual

1 Safety Precaution

balanced to prevent falls.  The battery equipment is heavy. Assign personnel according to its weight capacity to avoid exceeding
the carrying capacity of the human body and causing injuries.  If the battery fails to start, contact after-sales service immediately to prevent permanent damage to the
battery.  Do not move the battery system if it is connected to external battery modules. Contact after-sales
service for any battery replacement or addition needs.

CAUTION  Ensure the battery system is safeguarded during the transportation and storage phases.  Trained professionals should handle transportation and maintain a record of all operations.  Keep the equipment stable to prevent damage and minimize the risk of personal injuries.  Maintain a minimum distance of 30mm between cables and heating components or heat sources to
prevent damage to the cable insulation.  Tie cables of the same type together for organization and avoid entanglement or crossing of cables.  Keep cables of different types at least 30mm apart to prevent interference.  Follow proper cable management practices to ensure safety.

Label Description Symbol

Explanation

Do not disassemble the Battery pack

Do not immerse the battery pack in water

Do not short-circuit the battery

Do not leave the battery near by fire

Read Technical Manual Before Servicing

Flammable Fire Hazard warning symbol

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

2

SieB-H(9600~25K6)-F User Manual

Danger electrical hazard high voltage

1 Safety Precaution

CE mark of conformity. Regulatory compliance mark. UKCA mark of conformity. Read the user manual before maintenance! Recycling symbol

No waste.
1.3 Emergency Measures
1.3.1 Battery Electrolyte Leakage In case of electrolyte leakage from the battery module, it is crucial to avoid any contact with the leaked liquid or gas due to its corrosive nature. The electrolyte can cause skin irritation or chemical burns to individuals. If anyone accidentally comes into contact with the leaked substance, the following steps should be taken: i: Inhalation of the leaked substance: Immediately evacuate from the contaminated area. Seek immediate medical assistance. ii: Eye contact with the leaked substance: Rinse the affected eyes with clean water for at least 15 minutes. Seek immediate medical assistance. iii: Skin contact with the leaked substance: Thoroughly wash the affected area with soap and clean water. Seek immediate medical assistance. iv: Ingestion of the leaked substance: Induce vomiting, if possible.Seek immediate medical assistance. It is crucial to prioritize safety and take prompt action by seeking appropriate medical attention in case of any contact with the leaked electrolyte.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

3

SieB-H(9600~25K6)-F User Manual

1 Safety Precaution

1.3.2 Fire When the ambient temperature exceeds 150, there is a risk of the battery exploding. In the event of a fire involving the battery, it is important to be aware that poisonous and hazardous gases may be released. To effectively respond to a battery fire, please follow these guidelines:  Ensure the availability of a carbon dioxide (CO2) extinguisher, Novac1230, or FM-200 nearby. These types of fire extinguishers are suitable for tackling electrical fires, including battery fires.  Avoid using water or ABC dry powder extinguishers to extinguish the fire. Water can spread the fire and dry powder may not be effective in suppressing a battery fire.  If a fire occurs, contact the local fire department immediately. Firefighters should be equipped with full protective clothing and self-contained breathing apparatus to safely handle the situation. It is crucial to prioritize safety and take appropriate measures to handle battery fires, including the use of suitable fire extinguishers and protective equipment for firefighting personnel.

1.4 EU Declaration of Conformity

Shanghai Sieyuan Watten Technology Co., Ltd. hereby declares that the inverter without wireless communication modules sold in the European market meets the requirements of the following directives:  Electromagnetic compatibility Directive 2014/30/EU (EMC)  Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)  Battery Directive 2006/66/EC and Amending Directive 2013/56/EU  Waste Electrical and Electronic Equipment 2012/19/EU  Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No.RZUN2023-2770 (REACH) You can download the EU Declaration of Conformity on the official website: https://www.swatten.com

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

4

SieB-H(9600~25K6)-F User Manual

2 Product Introduction

2 Product Introduction
2.1 Product Overview
The battery system, comprising a power control unit (PCU) and battery modules, is responsible for storing and discharging electrical energy based on the needs of the solar energy storage system. The energy storage system operates with high-voltage direct current (DC) input and output ports.

NOTICE The battery system allows for capacity expansion, with a maximum of 8 battery modules that can be added to increase the usable energy of the system. It is important to strictly adhere to the expansion requirements specified by the manufacturer. For more information and detailed guidelines, please consult the Dealer or Manufacturer. Failure to follow the recommended expansion procedures may result in issues such as undervoltage, overvoltage, or voltage differences within the battery system.

2.2 Application Scenarios

2.3 Appearance
Battery system appearance

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

5

SieB-H(9600~25K6)-F User Manual

2 Product Introduction

No. 1 2, 3, 4 5

Parts PCU Battery modules Base

NOTICE  Make sure to install the power control unit (PCU) above the battery modules. Avoid installing any
battery modules above the PCU.  This manual provides instructions for the installation and electrical connection of 5 battery modules.

Battery appearance

No.

Parts

1

Ventilation value

2

Power Connector

3

Communication Connector

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

6

SieB-H(9600~25K6)-F User Manual
Base appearance

2 Product Introduction

No. 1
Power control appearance

Parts Grounding point

Right View

Front View

Left View

1 Communication terminal (COM) 4 Grounding point 7 Multifunction button indicator

2 Testing terminal 5 Air switch 8 Ventilation value

2.4 Dimensions

SieB-H-F series

Bottom View
3 DC terminal (BAT) 6 SOC indicator

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

7

SieB-H(9600~25K6)-F User Manual

2 Product Introduction

SieB-H-F

W

H

D

Battery module

615

165

360

Base

615

150

360

Power control unit

615

165

360

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

8

SieB-H(9600~25K6)-F User Manual

3 Check and Storage

3 Check and Storage
3.1 Check Before Receiving
Check the following items prior to receiving the product: 1. Inspect the outer packaging box for any signs of damage, such as holes, cracks, deformation, or other indications of equipment damage. If any damage is detected, refrain from unpacking the package and promptly notify the supplier. 2. Verify that the product model matches your request. If the product model does not correspond to your specifications, refrain from unpacking the product and contact the supplier. 3. Confirm that the deliverables include the correct model and all the necessary components. Ensure that the contents are complete and nothing is missing.
3.2 Scope of Delivery
Checking the Outer Packing inspect the outer packing for any signs of damage, such as holes or cracks. Additionally, verify the battery model to ensure it corresponds to your request. If you notice any damage or if the battery model is incorrect, refrain from unpacking the product, and promptly contact your dealer for further assistance. Checking Deliverables Upon unpacking the battery, carefully inspect the deliverables to ensure they are undamaged, complete, and free from any noticeable defects. If you find any missing or damaged items, promptly contact your dealer for resolution.Please refer to the Packing List within the packing case for specific information regarding the number of deliverables that should have been included with the battery. Power Control Unit

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

9

SieB-H(9600~25K6)-F User Manual
Item
A B C D E F G H I J K L Battery module

Name
HV Box Base
MC4 Expansion screws Installation bracket Grounding cable (For bottom one) Support legs Grounding terminal Grounding screws Communication terminal Quick installation manual Power cable with MC4 connectors

Quantity
1 1
1 4 4 1 4 3 3 1 1 1

3 Check and Storage

3.3 Storage
If the equipment is not intended for immediate installation or use, please ensure that the storage environment meets the following requirements:  Do not unpack the outer packing box or discard the desiccant.  If the equipment is not installed within three days of unpacking, repack and store it in the original
packing box.  Follow the labels and requirements on the packing box when stacking the equipment.  Take caution when stacking the equipment to prevent it from falling.  Keep the equipment away from flammable, explosive, and corrosive substances.  Maintain a minimum distance of two meters between the batteries and any heat source (e.g., radiator).  Store the equipment in a cool place away from direct sunlight.  Ensure the storage location is clean, with appropriate temperature and humidity levels to prevent
condensation.  Maintain a State of Charge (SOC) between 25% and 50% during storage. Perform charge-discharge
cycles every six months.  Recommended storage temperature: 0 to 35 (for periods less than one year), -20 to 0 or 35
to 45 (for periods less than one month).  Recommended storage humidity: 0% to 95% RH (without condensation). Do not install the battery if
moisture or condensation is present.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

10

SieB-H(9600~25K6)-F User Manual

4 System Installation

4 System Installation
4.1 Installation Requirements
Installation Environment Requirements:  Do not install the equipment near flammable, explosive, or corrosive materials.  Avoid installing the equipment in accessible areas, especially within reach of children. The equipment
generates high temperatures during operation, so touching the surface should be avoided to prevent burns.  Take care to avoid drilling holes near water pipes and buried cables in walls.  Install the equipment in a sheltered location to protect it from direct sunlight, rain, and snow. If necessary, construct a sunshade.  Ensure that the equipment is installed in a well-ventilated area to facilitate proper dissipation of heat. The installation space should be spacious enough for ease of operation.  The equipment's ingress protection rating determines whether it can be installed indoors or outdoors. Additionally, ensure that the temperature and humidity at the installation site are within the specified range.  Install the equipment at a suitable height for convenient operation, maintenance, electrical connections, and easy access to indicators and labels.  The installation altitude should not exceed 2000m above sea level.  Keep the equipment away from electromagnetic interference. If there are any radio or wireless communication devices operating below 30MHz near the equipment, ensure that the equipment is at least 30m away from those devices.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

11

SieB-H(9600~25K6)-F User Manual

4 System Installation

Mounting Support Requirements:  Ensure that the mounting support is made of nonflammable and fireproof materials.  The surface where the equipment is mounted should be sturdy enough to support the weight of the
product.  Position the battery system near a wall and securely install the locking brackets to prevent the battery
from accidentally falling.. Installation Angle Requirements  The equipment must be installed vertically, without any tilt or upside down.

 Ensure that the mounting support is made of nonflammable and fireproof materials. Installation Clearance Requirements  Ensure adequate clearance around the battery for proper heat dissipation.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

12

SieB-H(9600~25K6)-F User Manual
 If using multiple batteries, allocate specific spacing between them.

4 System Installation

NOTICE The distance is merely a suggested guideline, which can be adjusted based on the actual conditions.
4.2 Installing the Battery System
4.2.1 Moving the Equipment CAUTION
 All operations, including transportation, turnover, and installation, must comply with the laws and regulations of the country or region where the equipment is located.
 Before moving the equipment, carefully consider its weight and allocate an adequate number of personnel to ensure safe handling and to prevent personal injury.
 It is recommended to wear safety gloves during the moving process to minimize the risk of personal injury.
 Maintain balance and stability while moving the equipment to prevent it from falling or tipping over, which can result in both personal injury and equipment damage.
4.2.2 Installing the Battery System NOTICE  Make sure the base is positioned vertically on the floor.  Ensure that the base is securely attached to the wall with the arrow pointing outward.  Ensure that all batteries are securely attached to the wall with the arrow pointing outward.  When placing the upper battery module, align the holes of the upper and lower battery modules.  Ensure that the locking bracket is securely attached to the wall.  Do not install both locking brackets on one side; they should be installed on opposite sides for proper stability.

Step 1: Fix the adjustable feet securely onto the base, ensuring the base is level and stable without any tilting or shaking.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

13

SieB-H(9600~25K6)-F User Manual

4 System Installation

Step 2: Place the base on the wall where you intend to install it. Use a pencil or marker to mark the drilling positions on the wall. Then, remove the base from the wall.
Step 3: Carefully drill holes at the marked positions on the wall using an electric drill. Step 4:Insert the expansion bolts into the drilled holes and tighten them firmly. Make sure the base is properly
aligned and installed in the correct direction. Place the battery module on the installed base, ensuring it aligns with the base and is installed in the same direction. Step 5: Install the remaining batteries based on the specific type and configuration of your battery system. Follow the manufacturer's instructions for proper installation. Step 6: Stack the PCU on top of the last battery module, aligning it in the same direction. Tighten the screws between the battery modules to secure them in place. Step 7: Use a screwdriver to remove the terminal cover, preparing for Electrical Connection.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

14

SieB-H(9600~25K6)-F User Manual
.

4 System Installation

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

15

SieB-H(9600~25K6)-F User Manual
5 Electrical Connection
5.1 Safety Precaution

5 Electrical Connection

DANGER  Prior to any operations, ensure that the power is turned off to prevent any potential dangers. It is crucial
to strictly adhere to the safety precautions provided in this manual as well as the safety labels affixed to the equipment.  When conducting electrical connections, it is essential to follow the specifications and guidelines mandated by the local laws and regulations.  Properly organize and separate cables based on their types. Avoid entangling or crossing different cables.  During the process of crimping terminals, ensure that the cable conductor makes full contact with the terminal while ensuring that the cable insulation is not crimped with the terminal. This ensures optimal functionality and reliability of the device, preventing any potential damage to the terminal block and other related issues.

NOTICE  When conducting electrical connections, it is essential to wear appropriate personal protective

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

16

SieB-H(9600~25K6)-F User Manual

5 Electrical Connection

equipment such as safety shoes, safety gloves, and insulating gloves. These protective measures ensure your safety during the process.  It is recommended to have qualified professionals perform all electrical connections. Their expertise and knowledge ensure proper installation and reduce the risk of errors or accidents.  The cable colors mentioned in this document are for reference purposes only. It is crucial to ensure that the cable specifications meet the requirements set by local laws and regulations.

5.2 Internal Electrical Connections of the Battery

5.2.1 Installing an Internal Ground Cable DANGER Make sure to securely connect the PE cable to avoid the risk of electric shocks.

Step1: Make sure to connect the PE cable to both the battery power control modules and the battery expansion modules. This ensures proper grounding and safety during the operation of the battery system.

5.2.2 Installing Communication Terminals Connecting Communication Cables between the Power Control Unit and Battery Extension Modules.

5.2.3 Installing Internal DC Terminals & Protection Cover Step1: Insert the positive and negative connectors that came with the battery into the corresponding positive and negative battery cascading terminals (B+ and B ­ ). Make sure the connectors are securely and

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

17

SieB-H(9600~25K6)-F User Manual

5 Electrical Connection

properly inserted to ensure a reliable connection. Step2: Tighten and secure the protective cover onto the battery and PCU using screws, ensuring that they are
aligned and installed in the correct direction.

NOTICE After the positive and negative connectors snap into place, pull the DC input power cables back to ensure that they are connected securely. This will help ensure a reliable and stable connection between the components.
5.3 External Electrical Connections of the Battery
5.3.1 Connection the PE cable NOTICE  Prior to installing the equipment, connect the PE cable first. It is essential for safety purposes. Similarly, disconnect the PE cable before dismantling the equipment.  After crimping the cable, make sure that it has a drawing force of at least 400N. This will ensure a secure and reliable connection.  The PE cable should be connected to either the PCU or the base in the same manner. Follow the provided instructions for the specific equipment.  It is the responsibility of the customer to prepare the PE cable. The recommended specifications for the cable are as follows: - Type: Single-core outdoor copper cable - Cross-sectional area: 4-6mm2

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

18

SieB-H(9600~25K6)-F User Manual

5 Electrical Connection

5.3.2 Connecting the Power Cable NOTICE  Ensure battery system is powered off before connecting power cable to prevent high voltage hazards.  Customers should prepare DC input cable. Connect red power connector to red wire harness and black power connector to black wire harness. Use outdoor-compliant cable.  Properly install back cover without leaving any gaps.  Cover unused ports for protection.
DANGER High voltage precautions:  Prior to conducting any electrical operations, ensure that all cables are free of voltage.  Do not connect the DC switch and AC circuit breaker until the electrical connections are completed. To maintain IP65 protection, only use the provided connector.
Step 1: Strip the insulation from each DC cable by approximately 7 mm to 8 mm.
Step 2: Assembling the Crimp contact and cable, use the crimping pliers to securely assemble the cable ends.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

19

SieB-H(9600~25K6)-F User Manual

5 Electrical Connection

Step 3: Lead the cable through the cable gland and insert the crimp contact into the insulator until it audibly snaps into place. Pull the cable gently backward to ensure a firm connection. Tighten the cable gland and insulator using a torque of 2.5 N.m to 3 N.m.

Step 4: Verify the polarity correctness.

Step 5: Connect the positive terminal of the cable to the positive terminal of the battery, and connect the negative terminal of the cable to the negative terminal of the battery. When you hear a "Click", it indicates that the connection is complete.

5.3.3 Connecting the Communication Cable Step 1: Remove the waterproof protective cover from the PCU. Step 2: Disassemble the waterproof protective cover to prepare for wiring. Step 3: Thread the communication cables through the waterproof protective cover in sequence. Step 4: Connect the communication cables that pass through the protective cover to the communication ports on the PCU and tighten them. Step 5: Verify that the protective cover is installed correctly and securely.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

20

SieB-H(9600~25K6)-F User Manual

5 Electrical Connection

PIN 5 6
1, 2, 3, 4, 7, 8

Description CAN_H CAN_L N/A

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

21

SieB-H(9600~25K6)-F User Manual

6 System Operation

6 System Operation
6.1 Check Before Power ON
Check the following items before powering on to ensure the safety and proper functioning of the battery system:  Verify that the inverter is securely installed in a clean and well-ventilated location.  Ensure that the PE cable, power cable, communication cable, and terminal resistor are connected
correctly and securely.  Inspect the cable ties to ensure they are intact, properly routed, and evenly secured.  Seal any unused ports and terminals to prevent dust or debris from entering.
6.2 Power ON the Battery System
NOTICE  The installation of the DC breaker between the inverter and the battery must comply with the relevant
local laws and regulations.  The DC breaker should be capable of simultaneously isolating both the positive and negative
conductors.

Step 1: (Optional) Activate the breaker between the inverter and the battery system. Step 2: Activate the air switch of the battery system. Step 3: Power on the inverter in the system by following the instructions provided in the inverter's user manual.

6.3 Indicator Status

Button Indicator Green Red

Status Standby or Working Alarming or Faulty

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

22

SieB-H(9600~25K6)-F User Manual
6.3.1 Normal Status Button Indicator

SOC Indicator

Green for 2s, Off for 5s,
Cycling continuously

6 System Operation
Description SOC < 5% 5%  SOC < 25% 25%  SOC < 50% 50%  SOC < 75% 75%  SOC < 95% SOC  95%

NOTICE  The State of Charge (SOC) indicator remains continuously illuminated during the charging process.  The SOC indicator flashes once intermittently during the discharging process.

6.3.2 Alarming Status

Button indicator

SOC Indicator

Steady red

Alarm

Solutions

Low State of Charge (SOC) High Charging Current High Discharging Current High Terminal Temperature High Battery Temperature

Please get in touch with our after-sales service. Power off the system and wait for a duration of 2 hours. If the issue continues to persist after this period, kindly reach out to our after-sales service for further assistance and support. Power off the system and wait for a duration of 2 hours. If the issue continues to persist after this period, kindly reach out to our after-sales service for further assistance and support. Power off the system and wait for a duration of 2 hours. If the issue continues to persist after this period, kindly reach out to our after-sales service for further assistance and support. Power off the system and wait for a duration of 2 hours. If the issue continues to persist after this period, kindly reach out to our after-sales service for further assistance and support.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

23

SieB-H(9600~25K6)-F User Manual
Steady red

6.3.3 Fault Status

Button indicator

SOC Indicator

Steady red

6 System Operation

Reboot the battery system. If the issue

Low Temperature in continues to persist, please get in touch with

Charging Battery

our customer support team for further

assistance.

Reboot the battery system. If the issue

High Temperature in continues to persist, please get in touch with

Charging Battery

our customer support team for further

assistance.

Reboot the battery system. If the issue

Low Temperature in continues to persist, please get in touch with

Discharging Battery

our customer support team for further

assistance.

Reboot the battery system. If the issue

High Temperature in continues to persist, please get in touch with

Discharging Battery

our customer support team for further

assistance.

Reboot the battery system. If the issue

High Single Cell Voltage

continues to persist, please get in touch with our customer support team for further

assistance.

Reboot the battery system. If the issue

Low Single Cell Voltage

continues to persist, please get in touch with our customer support team for further

assistance.

Reboot the battery system. If the issue

Large Voltage Difference in continues to persist, please get in touch with

the Battery

our customer support team for further

assistance.

Reboot the battery system. If the issue

High Total Voltage

continues to persist, please get in touch with our customer support team for further

assistance.

Reboot the battery system. If the issue

Low Total Voltage

continues to persist, please get in touch with our customer support team for further

assistance.

Fault Insulation Fault

Solutions
Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

24

SieB-H(9600~25K6)-F User Manual
Steady red

6 System Operation

Sticking of Contactor

EEPROM Fault

Current Sensor Fault

Internal Fault

Communication

Balancing Fault

No Serial Number Error

Temperature Sensor Fault

Other Faults

Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance. Reboot the battery system. If the issue continues to persist, please get in touch with our customer support team for further assistance.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

25

SieB-H(9600~25K6)-F User Manual

6 System Operation

7 Viewing Battery information
If you are a residential user, please scan the QR code provided below to download the SOLARMAN Smart app. Alternatively, you can visit the website https://home.solarmanpv.com to access the app.

NOTICE If you want to check battery information, please complete the plant creation in Solarmanfirst. For details on how to create a plant in Solarman, please refer to Solarman App User Manual.
Accessing Battery Details on Solarman Application:
1. Log into the Solarman App, click on the established plant; then, the power flow from batteries will be displayed.

2. Scroll down on the real-time page to view real-time data; after clicking, you can monitor the operational status of the battery device by selecting parameters like battery charging and discharging.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

26

SieB-H(9600~25K6)-F User Manual

6 System Operation

3. Click on "Device," go into the inverter to monitor the battery device, where you can review parameters related to the battery as well as basic information about the battery.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

27

SieB-H(9600~25K6)-F User Manual

7 Maintenance

8 Maintenance
8.1 Power OFF the Battery System
DANGER  Ensure that the battery system is powered off before performing any operations or maintenance tasks.
Failure to do so may result in equipment damage or electric shocks.  To restart the battery, simply push the air switch.

To power off the battery system and prevent any potential damage, please follow one of the two methods below: Method one: Step 1: Refer to the user manual of the inverter and follow the instructions to turn off the inverter in the system. Step 2: Disconnect the air switch and ensure that the SOC indicator and multifunction button indicator of the PCU are switched off.

Method two: Step 1: Refer to the user manual of the inverter and follow the instructions to turn off the inverter in the system. Step 2: Long press the multifunction button indicator for more than 15 seconds, and confirm that the SOC indicator and multifunction button indicator of the PCU are switched off.

8.2 Routine Maintenance

WARNING

 If you encounter any issues that could potentially affect the battery or hybrid inverter, please contact the

after-sales service for assistance. Unauthorized disassembly is strictly prohibited.

 If you notice exposed copper conductors, please contact the after-sales service for assistance. Do not

touch or attempt to disassemble the equipment privately due to the risk of high voltage.

 In the event of any other emergencies, please contact the after-sales service immediately. Follow the

provided instructions or wait for the after-sales service personnel to assist you.

Maintaining Item

Maintaining Period

Check the securing of the locking brackets. If they are not

Once every 6 months

properly secured, tighten them as necessary.

Inspect the outer enclosure for any signs of damage or

Once every 6 months

breakage. If any issues are found, repair the painting or

contact the after-sales service for assistance.

Check for any exposed cables. If any cables are exposed,

Once every 6 months

replace them or contact the after-sales service for help.

Inspect the battery module for any dust accumulation. Clean Once every 6 months

the dust if present to prevent it from affecting heat

dissipation.

Check for the presence of any liquid or pests near the

Once every 6 months

battery. Take measures to prevent long-term intrusion.

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

28

SieB-H(9600~25K6)-F User Manual
9 Appendix

8 Parameters

9.1 Technical Data

Manufacturer

SieB-H-F Battery Energy Storage System-Home(HV)

System Model Type

SieB-H9600-F

SieB-H12K8-F

SieB-H16K0-F

Nominal Energy (kWh)

9.60

12.80

16.00

Usable Energy (kWh)*1

8.64

11.52

14.40

Module Type

SieB-H3200-F

Module Parameter

64V 50Ah 615*360*165mm 35kg

Cell Type

LPF (LiFePO4)

Module Configuration

3

4

5

Cell Configuration

1P60S

1P80S

1P100S

Nominal Voltage (V)

192

256

320

Operating Voltage Range (V)

171~216

228~288

285~360

Max. Continuous Current (A)*2

30

Max. Continuous Power (kW)*2

5.76

7.68

9.60

Communication

CN / RS485

Weight (Kg)

114.6

147.3

180.0

Dimensions (W*D*H) (mm)

615*360*730

615*360*880

615*360*1030

Operating Temperature ()

Charge: 0~50 / Discharge: -20~50

Storage Temperature ()

-20~45 (1 Months) / -20~25 (6 Months)

Humidity

5%~95%

Altitude (m)

2000

Enclosure Type

IP55 (Indoor / Outdoor)

Cooling

Natural convection

Installation Location

Floor-standing

Display

SOC indicatorStatus indicator

Safety

IEC62619, IEC63056, IEC62040-1, IEC62477-1, CEC

EMC Standard and Certification
Transportation

IEC61000-6-1/3 UN38.3

Others

CE, RoHS

Warranty*3

10 Years

1. Test conditions: 3.0V~3.5V, 0.2C Charge (CC-CV) and Discharge at 25±3;

2. Max. Continuous Current / Power derating will occur related to Temperration / SOC;

3. Refer to Swatten SieB-H-F Limited Warranty Letter;

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

29

SieB-H(9600~25K6)-F User Manual

8 Parameters

Manufacturer

SieB-H-F Battery Energy Storage System-Home(HV)

System Model Type

SieB-H19K2-F

SieB-H22K4-F

SieB-H25K6-F

Nominal Energy (kWh)

19.20

22.40

25.60

Usable Energy (kWh)*1

17.28

20.16

23.04

Module Type

SieB-H3200-F

Module Parameter

64V 50Ah 615*360*165mm 35kg

Cell Type

LPF (LiFePO4)

Module Configuration

6

7

8

Cell Configuration

1P120S

1P140S

1P160S

Nominal Voltage (V)

384

448

512

Operating Voltage Range (V)

342~432

399~504

456~576

Max. Continuous Current (A)*2

30

Max. Continuous Power (kW)*2

11.52

13.44

15.36

Communication

CN / RS485

Weight (Kg)

212.7

245.4

278.1

Dimensions (W*D*H) (mm)

615*360*1180

615*360*1330

615*360*1480

Operating Temperature ()

Charge: 0~50 / Discharge: -20~50

Storage Temperature ()

-20~45 (1 Months) / -20~25 (6 Months)

Humidity

5%~95%

Altitude (m)

2000

Enclosure Type

IP55 (Indoor / Outdoor)

Cooling

Natural convection

Installation Location

Floor-standing

Display

SOC indicatorStatus indicator

Safety

IEC62619, IEC63056, IEC62040-1, IEC62477-1, CEC

EMC Standard and Certification
Transportation

IEC61000-6-1/3 UN38.3

Others

CE, RoHS

Warranty*3

10 Years

1. Test conditions: 3.0V~3.5V, 0.2C Charge (CC-CV) and Discharge at 25±3;

2. Max. Continuous Current / Power derating will occur related to Temperration / SOC;

3. Refer to Swatten SieB-H-F Limited Warranty Letter;

Issue 1 (2024-03-12)

Shanghai Sieyuan Watten Technology Co., Ltd.

30



References