User Guide for Bard models including: Q-TEC QWS Series High Efficiency Geothermal, Heat Pump R-410A

S3419 (2021 05)

QW2S2-A QW2S2-B QW2S2-C QW3S2-A QW3S2-B QW3S2-C QW4S2-A QW4S2-B QW4S2-C QW5S2-A QW5S2-B QW5S2-C

QW2S2-A, QW2S2-B, QW2S2-C, QW3S2-A, QW3S2-B, QW3S2-C, QW4S2-A, QW4S2-B, QW4S2-C, QW5S2-A, QW5S2-B, QW5S2-C

Q-TEC™ QWS Series High Efficiency Geothermal/Water Source ...

both soft and manual lockouts for high and low pressure controls. High Pressure Switch: Protects refrigerant circuit against excessively high pressure. Low Pressure Switch: Provides loss of charge protection plus protects against freeze-up of coaxial coil during heating mode due to water flow or temperature problems. Two

Q-TEC™ QWS Series High Efficiency Geothermal/Water Source

The Q-TEC Series self contained packaged water-to-air heat pump is designed to be installed inside a building structure against an exterior exposed wall ...

Form No. S3419-0521 Supersedes S3419-617 Page 1 of 26 The Q-TEC Series self contained packaged water-to-air heat pump is designed to be installed inside a building structure against an exterior exposed wall when ventilation


File Info : application/pdf, 26 Pages, 1.03MB

S3419
Q-TECTM QWS Series High Efficiency Geothermal/Water Source Packaged Step-Capacity Heat Pump -- R-410A

2 to 5 Ton

2-Stage Compressors

Extended Range Operation: 25° to 110°F EWT

The Q-TEC Series self contained packaged water-to-air heat pump is designed to be installed inside a building structure against an exterior exposed wall when ventilation option is selected. When no ventilation option is used, the QWS Series units can be installed in any interior space accessible to water supply system and condensate drain.
Q-TEC's design provides "whisper" quiet operation with total comfort for the occupants at high efficiency levels and eliminates the need for roof-mounted equipment and outside condensing units and can meet your specific architectural requirements.
Q-TEC's "quiet technology" provides extremely low indoor sound levels by using special components and materials in the construction of the unit. By using special motors and sound insulation we have built a heat pump system that is significantly quieter than competitive product available today.
Q-TEC is suitable for both new construction and renovation projects for schools, modular buildings and light commercial buildings. A variety of ventilation options are designed to address your project's indoor air quality.
The Q-TEC Series unique design allows all maintenance and service to be performed inside the building to facilitate multi-story installations. Access to air filters and controls is accomplished through a hinged front panel for easy accessibility. All Q-TEC Series models are built on heavy duty permanent rollers for easy installation and removal.

Engineered Features

Step Capacity Compressor: Copeland step capacity (2-stage) scroll compressors are designed for increased efficiency, quieter operation and improved reliability for longer life.
Reduced Sound Level: Compressor sound cover and double isolation grommets reduce sound levels. Discharge muffler used on all models.
R-410A Refrigerant: Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.

Electrical Components: Are easily accessible for routine inspection and maintenance through front service panels. Circuit breaker standard on all 208/230V models and rotary disconnect standard on all 460V models. Circuit breaker/rotary disconnect access is through lockable access panel. Lock and key provided as standard equipment.
Hot Water Coil: A plenum mounted hot water coil is available for both duct-free and ducted applications.

Liquid Line Filter Drier: Standard on all models.

Air Filter: Two-inch pleated MERV 8 filter is standard.

Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
Indoor Blower System: All models feature a variable speed (ECM) motor providing super high efficiency, low sound levels and soft start capabilities. The motor is self adjusting to provide the proper airflow rate at high static pressure for ducted installations without user adjustment or wiring changes. Dual blower and 30-second ramp up and ramp-down on motor used for quiet operation.
High Efficiency Coaxial Water Coil: Fully insulated to minimize sweating. Copper or cupro-nickel coils available. Copper coils approved for Ground Loop and Closed Loop Boiler / Tower only.
Fluid Flow Switch: Provided for coaxial coil to protect against loss of water flow.
Double O-Ring Water Connections (Optional): Positive water-tight connections with built-in union. 1" female NPT fittings also available.
Pumping System: Unit can be connected to central piping/pumping system from well field, boiler/tower or optional pump module can be installed inside unit for individual earth loop applications.
Copper Tube/Aluminum Fin Evaporator Coil: Grooved copper tubing and enhanced aluminum fins provide maximum heat transfer and high energy efficiency. Evaporator coil constructed with hydrophilic fin stock that seals fin surface against aluminum oxide formation, is resistant to mold and mildew growth (tested to ASTM D3273, no growth) and reduces beading of condensate on the fin surface.
Cabinet: Constructed of 20 gauge pre-painted or vinyl laminated galvanized steel. Choice of either two tone vinyl finish with "slate" front panels and "platinum" cabinet for designer appearance, or painted steel. Vinyl finish is very resistant to scratching and marring and is very easy to clean. Tamper resistant fasteners are provided for access panels. Unit includes built-in rollers for easy installation into wall sleeve and removal for service if necessary. Hinged, lockable front panel for filter service and access to primary functional electrical controls.

Compressor Control Module: Built-in off-delay timer adjustable from 30 seconds to 5 minutes. Two-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls.
High Pressure Switch: Protects refrigerant circuit against excessively high pressure.
Low Pressure Switch: Provides loss of charge protection plus protects against freeze-up of coaxial coil during heating mode due to water flow or temperature problems. Two switches are installed, and the factory wired switch is for fresh water applications.
Diagnostic Light: System service - indicates high or low pressure switch operation for compressor protection. Located inside control panel.
Stainless Steel Drain Pan: Provides extended life of the evaporator drain pan for maximum corrosion resistance.
Side Trim Piece Extension ­ Optional: Trim kits available for covering the space between unit and wall for spaces from 4" to 12".
Optional Ventilation Packages: Optional energy recovery ventilator can provide up to 450 cfm of outside air and exhaust through the unit while maintaining indoor comfort and humidity levels. Other available options include commercial room ventilator with exhaust, and barometric damper without exhaust. Outside wall and ventilation sleeve are required for installations with ventilation option.
Optional Ventilation Wall Sleeve: Required for ventilation options only. Constructed of 16 gauge galvanized steel, coated with epoxy primer and a baked on polyester enamel paint, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03. Ordered separately.

Insulation: Cabinet is fully insulated with foil covered, high density fiberglass insulation with sealed edge treatment and special sound deadening insulation material in the compressor section. All insulation is designed to resist mold and mildew growth and facilitate ease of cleaning.

Form No. S3419-0521

Supersedes S3419-617

Page

1 of 26

Specifications - 2 and 3 Ton

MODELS ELECTRICAL RATING ­ 60 HZ
Operating Voltage Range COMPRESSOR ­ CIRCUIT A
Voltage Rated Load Amps Branch Circuit Selection Current Lock Rotor Amps MOTOR & EVAPORATOR Blower Motor HP/SPD Blower Motor ­ Amps Filter Sizes (inches) STD. SHIPPING WEIGHT ­ LBS.

QW2S2-A

QW2S2-B

230/208 - 1 230/208 - 3

197-253

QW2S2-C 460 - 3 414-506

230/208

460

9.1/10.6

5.1/5.9

3.2

11.7

6.5

3.5

58.3

55.4

28

1/3 / Variable

2.4

1 - 16x20x2 & 1 - 16x16x2

530

530

550

QW3S2-A

QW3S2-B

230/208 - 1 230/208 - 3

197-253

QW3S2-C 460 - 3 414-506

230/208

460

13.2/15.8

10.1/12.0

6.0

15.8

12

6.0

83

73

38

1/2 / Variable

3.1

1 - 16x20x2 & 1 - 16x16x2

535

535

555

Specifications - 4 and 5 Ton

MODELS ELECTRICAL RATING ­ 60 HZ
Operating Voltage Range COMPRESSOR ­ CIRCUIT A
Voltage Rated Load Amps Branch Circuit Selection Current Lock Rotor Amps MOTOR & EVAPORATOR Blower Motor HP/SPD Blower Motor ­ Amps Filter Sizes (inches) STD. SHIPPING WEIGHT ­ LBS.

QW4S2-A

QW4S2-B

230/208 - 1 230/208 - 3

197-253

QW4S2-C 460 - 3 414-506

230/208

460

18.7/22.1

12.4/14.7

6.7

22.1

14.7

6.7

104

83.1

41

3/4 / Variable

3.6

1 - 16x25x2 & 1 - 16x16x2

555

555

575

QW5S2-A

QW5S2-B

230/208 - 1 230/208 - 3

197-253

QW5S2-C 460 - 3 414-506

230/208

460

21.1/23.3

12.8/14.2

6.3

27.2

16.6

7.3

152.9

110

52

3/4 / Variable

4.0

1 - 16x25x2 & 1 - 16x16x2

620

620

645

See Page 9 for Electrical Specifications

Indoor Blower Performance ­ CFM (0.00" through 0.50" H O) 2

Model

Rated ESP.

Max. ESP j

Blower Only k

Rated 1st
Stage

2nd Stage De-Rated
l

2nd Stage Rated m

QW2S2

0.10

0.5

600

800

900

950

QW3S2

0.15

0.5

675

900

1050

1150

QW4S2

0.20

0.5

825

1200

1300

1450

QW5S2

0.20

0.5

875

1400

1500

1650

NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions, and at both 230/208 or 460 volts.

j Maximum ESP (inches WC) shown is with 2" MERV 6 pleated filter. k Continuous CFM the total airflow being circulated during continuous blower operation. l Optional 2nd Stage CFM ­ the unit is factory shipped to operate on full 2nd Stage airflow. If the optional 2nd Stage airflow is
desired, it requires removal of gray wire from "Y2" terminal of low voltage terminal strip in unit main control panel. This reduces
system capacity performance by approximately 2% total (-4% Sensible, +2% Latent) at the same energy efficiency. m Rated CFM for ducted applications ­ required for maximum performance rating.

Form No. S3419-0521

Supersedes S3419-617

Page

2 of 26

ISO 13256-1 Performance Data j

MODEL QW2S QW3S QW4S QW5S

System Capacity Modulation
Full Part
Full Part
Full Part
Full Part

Fluid Flow Rate GPM
7.0
8.0
9.0
11.0

Airflow CFM
950 800
1150 900
1450 1200
1650 1400

MODEL QW2S QW3S QW4S QW5S

System Capacity Modulation
Full Part
Full Part
Full Part
Full Part

Fluid Flow Rate GPM
6.1
8.6
11.5
13.7

Airflow CFM
950 800
1150 900
1450 1200
1650 1400

Ground Loop Heat Pump AHRI Certified to ISO 13256-1:1998

Cooling Brine Full Load 77°F Part Load 68°F

Heating Brine Full Load 32°F Part Load 41°F

Capacity BTUH

EER BTU/W

Capacity BTUH

COP

25,600 20,200

18.2 24.8

19,600 15,600

3.95 4.00

35,600 27,200

17.0 22.5

29,000 22,000

3.65 3.85

49,500 38,000

17.2 22.4

36,000 30,000

3.35 3.85

58,500 45,500

16.4 21.6

46,000 38,000

3.60 4.05

Water Loop Heat Pump AHRI Certified to ISO 13256-1:1998

Cooling -- EWT 86°F

Heating -- EWT 68°F

Capacity BTUH

EER BTU/W

Capacity BTUH

COP

24,800 17,800

15.6 17.4

31,600 24,000

5.20 5.95

35,400 25,600

15.0 16.0

44,600 33,000

4.30 5.10

47,500 35,000

15.1 16.0

57,000 43,000

4.30 4.80

56,500 42,000

14.5 15.6

69,500 52,000

4.40 4.95

j ISO Standard 13256-1:1998, "Water to Air and Brine to Air Heat Pumps", which includes watt allowance for water pumping. Cooling capacity based on 80.6°F DB, 66.2°F WB entering air temperature. Heating capacity based on 68°F DB entering air temperature.

All 1-phase models meet the minimum efficiency requirements of the Energy Star (ES) efficiency program for Ground Loop applications. Currently, there is no ES efficiency program for 3-phase equipment or for Water Loop applications.

Correction Factors @ Increased Water Flows

Rated Flow Plus
2 GPM 3 GPM 4 GPM

Cooling

BtuH

Watts

1.005

0.988

1.007

0.984

1.008

0.979

Heating

BtuH

Watts

1.006

1.002

1.009

1.003

1.011

1.003

Bard is an ISO 9001:2008 Certified Manufacturer

· Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition.

Form No. S3419-0521

Supersedes S3419-617

Page

3 of 26

QW2S2

Full Load Capacities based upon rated flow of 7 GPM of 15% methanol/mass at 950 CFM airflow.

COOLING FULL LOAD

HEATING FULL LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
25.2

Sensible Capacity (MBtuH)
19.1

Sensible to Total Ratio
0.75

Power Input (KW)
1.02

Heat of Rejection (MBtuH)
28.3

EER 21.1

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

24.2 23.3 22.3 21.4 20.4 19.5

18.8 18.4 18.1 17.8 17.4 17.1

0.77 0.79 0.81 0.83 0.85 0.87

1.20 1.37 1.55 1.73 1.91 2.08

27.9 27.5 27.0 26.6 26.1 25.7

19.0 16.9 14.9 12.8 10.7 8.6

25°

19.0

82.5

30°

20.3

83.8

40°

22.9

86.2

50°

65°

25.5

88.6

60°

28.8

91.7

50°

27.1

19.8

0.72

1.04

30.4

22.4

70°

32.1

94.7

60° 70° 80° 90° 100° 110°

75° DB 63° WB

26.1 25.1 24.0 23.0 22.0 21.0

19.5 19.2 18.9 18.5 18.2 17.9

0.74 0.77 0.79 0.81 0.83 0.85

1.21 1.39 1.57 1.75 1.92 2.10

30.0 29.5 29.1 28.6 28.2 27.7

20.2 18.0 15.8 13.6 11.5 9.3

80°

25°

30°

40°

50°

70°

35.4 18.5 19.8 22.4 24.9

97.8 87.2 88.3 90.7 93.1

50°

29.0

20.5

0.70

1.06

32.6

23.7

60°

28.2

96.1

60° 70° 80° 90° 100° 110°

80° DB 67° WB

28.0 26.9 25.8 24.8 23.7 22.6

20.2 19.9 19.6 19.3 19.0 18.7

0.72 0.74 0.76 0.78 0.80 0.82

1.23 1.41 1.59 1.76 1.94 2.12

32.2 31.7 31.2 30.8 30.3 29.9

21.4 19.1 16.8 14.5 12.2 9.9

70° 80° 25° 30° 40°

31.4 34.7 18.7 20.0 22.6

99.1 102.1 92.3 93.5 95.9

50°

31.1

21.2

0.67

1.08

34.9

24.9

50°

75°

25.2

98.3

60°

30.0

20.9

0.69

1.25

34.5

22.5

70°

28.8

20.6

0.71

1.43

34.0

20.1

80°

85° DB 71° WB

27.7

20.3

0.73

1.61

33.5

17.8

90°

26.6

20.0

0.76

1.78

33.0

15.4

60° 70° 80°

28.5 31.7 35.0

101.4 104.4 107.4

100°

25.4

19.7

0.78

1.96

32.6

13.0

110°

24.3

19.5

0.80

2.14

32.1

10.6

Full Load Capacities based upon rated flow of 7 GPM of 15% methanol/mass at 800 CFM airflow.

COOLING PART LOAD

HEATING PART LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
20.0

Sensible Capacity (MBtuH)
16.1

Sensible to Total Ratio
0.79

Power Input (KW)
0.58

Heat of Rejection (MBtuH)
21.8

EER 27.0

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

19.0 17.9 16.9 15.9 14.8 13.8

15.7 15.2 14.7 14.2 13.8 13.3

0.82 0.85 0.87 0.90 0.93 0.95

0.72 0.86 1.00 1.14 1.28 1.42

21.2 20.5 19.9 19.3 18.6 18.0

23.9 20.8 17.8 14.7 11.6 8.5

25°

11.1

77.8

30°

12.7

79.7

40°

15.9

83.4

50°

65°

19.0

87.0

60°

21.4

89.8

50°

21.5

16.7

0.77

0.59

23.4

28.6

70°

23.8

92.6

60° 70° 80° 90° 100° 110°

75° DB 63° WB

20.4 19.3 18.2 17.1 16.0 14.9

16.3 15.8 15.3 14.9 14.4 13.9

0.79 0.82 0.85 0.87 0.90 0.93

0.73 0.87 1.01 1.15 1.29 1.43

22.7 22.1 21.4 20.8 20.1 19.4

25.4 22.1 18.9 15.7 12.4 9.2

80°

25°

30°

40°

50°

70°

26.2 10.9 12.4 15.5 18.6

95.4 82.6 84.4 87.9 91.5

50°

23.0

17.3

0.74

0.60

25.1

30.3

60°

21.0

94.2

60° 70° 80° 90° 100° 110°

80° DB 67° WB

21.9 20.7 19.5 18.4 17.2 16.0

16.9 16.4 15.9 15.5 15.0 14.5

0.77 0.79 0.82 0.85 0.87 0.90

0.74 0.88 1.02 1.16 1.30 1.44

24.4 23.7 23.0 22.3 21.6 20.9

26.9 23.5 20.1 16.6 13.2 9.8

70° 80° 25° 30° 40°

23.3 25.7 11.0 12.5 15.7

97.0 99.7 87.7 89.5 93.1

50°

24.7

17.9

0.71

0.62

26.9

31.9

50°

75°

18.8

96.8

60°

23.4

17.4

0.74

0.76

26.1

28.4

70°

22.2

17.0

0.77

0.89

25.4

24.8

80°

85° DB 71° WB

20.9

16.5

0.79

1.03

24.7

21.2

90°

19.7

16.1

0.82

1.17

24.0

17.6

60° 70° 80°

21.2 23.6 25.9

99.5 102.3 105.0

100°

18.5

15.6

0.84

1.31

23.2

14.1

110°

17.2

15.1

0.87

1.45

22.5

10.5

Form No. S3419-0521

Supersedes S3419-617

Page

4 of 26

Power Input (KW)
1.51 1.54 1.60 1.67 1.76 1.84 1.93 1.55 1.58 1.65 1.72 1.80 1.89 1.98 1.74 1.77 1.85 1.93 2.02 2.12 2.22
Power Input (KW)
1.12 1.12 1.13 1.14 1.14 1.15 1.15 1.15 1.15 1.16 1.17 1.18 1.18 1.19 1.29 1.29 1.30 1.31 1.32 1.33 1.33

Heat of Absorption COP (MBtuH)

13.6 14.8 17.2 19.6 22.7 25.7 28.7 13.2 14.4 16.7 19.0 22.0 24.9 27.9 12.9 14.0 16.2 18.5 21.3 24.2 27.1

3.7 3.9 4.2 4.5 4.8 5.1 5.4 3.5 3.7 4.0 4.25 4.6 4.9 5.2 3.2 3.3 3.6 3.8 4.1 4.4 4.7

Heat of Absorption COP (MBtuH)

7.2 8.7 11.9 15.0 17.4 19.9 22.3 6.9 8.5 11.5 14.6 16.9 19.3 21.6 6.7 8.2 11.2 14.2 16.4 18.7 21.0

2.9 3.3 4.1 4.9 5.5 6.1 6.7 2.8 3.2 3.9 4.7 5.2 5.79 6.35 2.5 2.8 3.5 4.2 4.7 5.2 5.7

QW3S2

Full Load Capacities based upon rated flow of 8 GPM of 15% methanol/mass at 1150 CFM airflow.

COOLING FULL LOAD

HEATING FULL LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
32.5

Sensible Capacity (MBtuH)
22.0

Sensible to Total Ratio
0.67

Power Input (KW)
1.42

Heat of Rejection (MBtuH)
36.9

EER 19.3

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

31.9 31.2 30.5 29.8 29.1 28.4

22.1 22.2 22.3 22.4 22.6 22.7

0.69 0.71 0.73 0.75 0.77 0.80

1.70 1.98 2.26 2.53 2.81 3.09

37.0 37.2 37.3 37.4 37.5 37.7

17.5 15.8 14.0 12.2 10.4 8.6

25°

26.1

86.0

30°

28.2

87.7

40°

32.5

91.2

50°

65°

36.8

94.7

60°

40.5

97.6

50°

34.9

22.8

0.65

1.45

39.6

20.5

70°

44.2

100.6

60° 70° 80° 90° 100° 110°

75° DB 63° WB

34.2 33.5 32.8 32.1 31.4 30.7

23.0 23.1 23.3 23.4 23.6 23.8

0.67 0.69 0.71 0.73 0.75 0.77

1.73 2.00 2.28 2.56 2.83 3.11

39.8 40.0 40.1 40.3 40.5 40.6

18.6 16.7 14.9 13.0 11.1 9.2

80°

25°

30°

40°

50°

70°

47.9 25.5 27.6 31.8 36.0

103.5 90.5 92.2 95.6 99.0

50°

37.5

23.6

0.63

1.48

42.5

21.7

60°

39.6

101.9

60° 70° 80° 90° 100° 110°

80° DB 67° WB

36.7 36.0 35.3 34.5 33.8 33.1

23.8 24.0 24.2 24.4 24.6 24.8

0.65 0.67 0.69 0.71 0.73 0.75

1.75 2.03 2.31 2.58 2.86 3.14

42.7 42.9 43.1 43.4 43.6 43.8

19.7 17.7 15.8 13.8 11.8 9.8

70° 80° 25° 30° 40°

43.2 46.8 25.8 27.9 32.1

104.8 107.7 95.8 97.5 100.9

50°

40.1

24.4

0.60

1.51

45.5

22.8

50°

75°

36.4

104.3

60°

39.3

24.6

0.62

1.78

45.8

20.8

70°

38.6

24.8

0.64

2.06

46.0

18.7

80°

85° DB 71° WB

37.8

25.1

0.66

2.34

46.3

16.7

90°

37.1

25.3

0.68

2.61

46.5

14.6

60° 70° 80°

40.0 43.7 47.3

107.2 110.2 113.1

100°

36.3

25.6

0.70

2.89

46.8

12.6

110°

35.5

25.8

0.72

3.17

47.0

10.5

Full Load Capacities based upon rated flow of 8 GPM of 15% methanol/mass at 900 CFM airflow.

COOLING PART LOAD

HEATING PART LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
26.5

Sensible Capacity (MBtuH)
18.4

Sensible to Total Ratio
0.68

Power Input (KW)
0.72

Heat of Rejection (MBtuH)
28.7

EER 27.0

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

24.9 23.4 21.8 20.3 18.7 17.1

17.8 17.2 16.6 16.0 15.4 14.8

0.71 0.74 0.77 0.79 0.82 0.85

0.93 1.15 1.36 1.57 1.79 2.00

27.8 26.9 25.9 25.0 24.1 23.1

23.7 20.4 17.1 13.8 10.5 7.1

25°

17.4

82.9

30°

19.0

84.6

40°

22.2

87.8

50°

65°

25.4

91.1

60°

28.8

94.6

50°

28.5

19.1

0.66

0.73

30.8

28.7

70°

32.2

98.2

60° 70° 80° 90° 100° 110°

75° DB 63° WB

26.8 25.1 23.5 21.8 20.2 18.5

18.5 17.9 17.3 16.7 16.1 15.5

0.68 0.71 0.74 0.77 0.80 0.83

0.94 1.16 1.37 1.59 1.80 2.02

29.9 28.9 27.9 26.9 25.9 25.0

25.2 21.7 18.2 14.7 11.2 7.7

80°

25°

30°

40°

50°

70°

35.7 17.1 18.6 21.7 24.8

101.7 87.5 89.1 92.3 95.5

50°

30.5

19.8

0.63

0.75

33.1

30.3

60°

28.2

99.0

60° 70° 80° 90° 100° 110°

80° DB 67° WB

28.8 27.0 25.2 23.5 21.7 19.9

19.2 18.6 18.0 17.4 16.8 16.2

0.66 0.69 0.72 0.75 0.77 0.80

0.96 1.18 1.39 1.61 1.82 2.04

32.0 31.0 30.0 28.9 27.9 26.9

26.7 23.0 19.3 15.6 11.9 8.2

70° 80° 25° 30° 40°

31.5 34.9 17.2 18.8 21.9

102.4 105.9 92.7 94.3 97.6

50°

32.7

20.4

0.61

0.76

35.4

32.0

50°

75°

25.1

100.8

60°

30.8

19.8

0.64

0.98

34.3

28.1

70°

28.9

19.3

0.67

1.19

33.2

24.3

80°

85° DB 71° WB

27.1

18.7

0.69

1.41

32.1

20.4

90°

25.2

18.1

0.72

1.62

31.1

16.5

60° 70° 80°

28.5 31.8 35.2

104.3 107.8 111.2

100°

23.3

17.5

0.75

1.84

30.0

12.7

110°

21.4

16.9

0.78

2.05

28.9

8.8

Power Input (KW)
2.19 2.27 2.43 2.58 2.68 2.78 2.87 2.25 2.33 2.49 2.65 2.75 2.85 2.95 2.53 2.62 2.80 2.98 3.09 3.20 3.31

Heat of Absorption COP (MBtuH)

18.4

3.5

20.2

3.6

24.0

3.9

27.8

4.2

31.1

4.4

34.5

4.7

37.8

4.9

17.8

3.3

19.6

3.5

23.3

3.7

27.0

4.0

30.2

4.2

33.5

4.4

36.7

4.7

17.3

3.0

19.1

3.1

22.6

3.4

26.1

3.6

29.3

3.8

32.5

4.0

35.6

4.2

Power Input (KW)
1.55 1.57 1.61 1.65 1.70 1.75 1.81 1.59 1.61 1.65 1.69 1.75 1.80 1.86 1.79 1.81 1.85 1.90 1.96 2.02 2.08

Heat of Absorption COP (MBtuH)

12.0

3.3

13.5

3.6

16.6

4.0

19.6

4.5

22.9

5.0

26.1

5.4

29.4

5.8

11.6

3.2

13.1

3.4

16.1

3.8

19.0

4.3

22.2

4.7

25.4

5.1

28.5

5.5

11.3

2.8

12.7

3.0

15.6

3.5

18.5

3.9

21.5

4.2

24.6

4.6

27.7

5.0

Form No. S3419-0521

Supersedes S3419-617

Page

5 of 26

QW4S2

Full Load Capacities based upon rated flow of 9 GPM of 15% methanol/mass at 1450 CFM airflow.

COOLING FULL LOAD

HEATING FULL LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
52.1

Sensible Capacity (MBtuH)
32.2

Sensible to Total Ratio
0.59

Power Input (KW)
2.09

Heat of Rejection (MBtuH)
58.5

EER 21.4

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

48.8 45.5 42.1 38.8 35.5 32.2

31.4 30.5 29.7 28.9 28.1 27.2

0.63 0.67 0.71 0.75 0.79 0.83

2.40 2.71 3.02 3.33 3.63 3.94

56.1 53.7 51.2 48.8 46.4 43.9

19.1 16.8 14.4 12.1 9.8 7.4

25°

33.0

87.6

30°

35.3

89.2

40°

39.9

92.4

50°

65°

44.6

95.6

60°

50.0

99.3

50°

56.0

33.4

0.57

2.13

62.9

22.7

70°

55.4

103.0

60° 70° 80° 90° 100° 110°

75° DB 63° WB

52.4 48.9 45.4 41.8 38.3 34.7

32.6 31.8 31.0 30.2 29.4 28.5

0.61 0.65 0.69 0.73 0.77 0.81

2.44 2.74 3.05 3.36 3.67 3.97

60.3 57.7 55.2 52.6 50.0 47.5

20.3 17.8 15.4 12.9 10.4 8.0

80°

25°

30°

40°

50°

70°

60.9 32.2 34.5 39.1 43.6

106.7 92.1 93.7 96.8 99.9

50°

60.0

34.6

0.55

2.17

67.4

24.1

60°

48.9

103.5

60° 70° 80° 90° 100° 110°

80° DB 67° WB

56.3 52.5 48.7 45.0 41.2 37.4

33.8 33.0 32.2 31.4 30.6 29.8

0.59 0.63 0.67 0.70 0.74 0.78

2.47 2.78 3.09 3.39 3.7 4.01

64.7 62.0 59.3 56.5 53.8 51.1

21.5 18.9 16.3 13.7 11.1 8.6

70° 80° 25° 30° 40°

54.2 59.5 32.6 34.9 39.5

107.2 110.8 97.3 98.9 102.1

50°

64.3

35.7

0.53

2.21

72.2

25.3

50°

75°

44.1

105.2

60°

60.3

34.9

0.57

2.51

69.3

22.6

70°

56.3

34.2

0.61

2.82

66.4

19.9

80°

85° DB 71° WB

52.3

33.4

0.64

3.13

63.6

17.2

90°

48.3

32.6

0.68

3.43

60.7

14.5

60° 70° 80°

49.4 54.8 60.2

108.9 112.6 116.3

100° 110°

44.2 40.2

31.8 31.0

0.72 0.76

3.74 4.04

57.8 54.9

11.8 9.1

Full Load Capacities based upon rated flow of 9 GPM of 15% methanol/mass at 1200 CFM airflow.

COOLING PART LOAD

HEATING PART LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
37.4

Sensible Capacity (MBtuH)
26.7

Sensible to Total Ratio
0.71

Power Input (KW)
1.07

Heat of Rejection (MBtuH)
40.8

EER 26.6

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

35.4 33.4 31.4 29.4 27.4 25.4

25.5 24.4 23.3 22.2 21.1 20.0

0.72 0.73 0.74 0.76 0.77 0.78

1.36 1.64 1.93 2.21 2.50 2.78

39.6 38.4 37.2 36.0 34.9 33.7

23.5 20.3 17.2 14.1 11.0 7.9

25°

23.1

83.6

30°

25.1

85.2

40°

29.0

88.4

50°

65°

32.9

91.5

60°

36.4

94.3

50°

40.2

27.7

0.68

1.09

43.8

28.2

70°

39.9

97.1

60° 70° 80° 90° 100° 110°

75° DB 63° WB

38.1 36.0 33.8 31.7 29.6 27.4

26.6 25.4 24.3 23.2 22.1 20.9

0.69 0.71 0.72 0.73 0.75 0.76

1.38 1.66 1.95 2.23 2.52 2.80

42.5 41.3 40.1 38.8 37.6 36.4

24.9 21.6 18.3 15.0 11.7 8.5

80°

25°

30°

40°

50°

70°

43.4 22.6 24.5 28.4 32.2

99.9 88.2 89.7 92.8 95.9

50°

43.1

28.7

0.66

1.12

46.9

29.8

60°

35.6

98.7

60° 70° 80° 90° 100° 110°

80° DB 67° WB

40.9 38.6 36.3 34.1 31.8 29.5

27.5 26.4 25.3 24.1 23.0 21.9

0.67 0.68 0.70 0.71 0.72 0.74

1.40 1.69 1.97 2.26 2.54 2.83

45.6 44.4 43.1 41.8 40.5 39.2

26.4 22.9 19.4 16.0 12.5 9.1

70° 80° 25° 30° 40°

39.0 42.4 22.8 24.8 28.7

101.4 104.1 93.4 94.9 98.1

50°

46.2

29.6

0.63

1.14

20.3

31.4

50°

75°

32.6

101.2

60°

43.8

28.5

0.65

1.42

48.9

27.8

70°

41.4

27.3

0.66

1.71

47.5

24.2

80°

85° DB 71° WB

39.0

26.2

0.67

1.99

46.2

20.6

90°

36.6

25.0

0.69

2.28

44.8

16.9

60° 70° 80°

36.0 39.4 42.9

104.0 106.7 109.5

100°

34.1

23.9

0.70

2.57

43.5

13.3

110°

31.7

22.8

0.71

2.85

42.1

9.7

Form No. S3419-0521

Supersedes S3419-617

Page

6 of 26

Power Input (KW)
2.89 2.97 3.12 3.26 3.47 3.67 3.88 2.97 3.05 3.20 3.35 3.56 3.77 3.98 3.33 3.42 3.59 3.76 4.00 4.23 4.47
Power Input (KW)
2.09 2.12 2.17 2.22 2.26 2.30 2.34 2.15 2.18 2.23 2.28 2.32 2.36 2.40 2.42 2.44 2.50 2.56 2.60 2.65 2.70

Heat of Absorption COP (MBtuH)

22.8

3.4

24.8

3.5

29.0

3.7

33.1

4.0

37.8

4.2

42.6

4.4

47.3

4.6

22.1

3.2

24.1

3.3

28.1

3.6

32.2

3.8

36.7

4.0

41.3

4.2

45.9

4.4

21.4

2.9

23.4

3.0

27.3

3.2

31.2

3.4

35.6

3.6

40.1

3.8

44.5

4.0

Heat of Absorption COP (MBtuH)

15.7

3.2

17.6

3.5

21.4

3.9

25.2

4.3

28.5

4.7

31.9

5.1

35.2

5.5

15.2

3.1

17.1

3.3

20.7

3.7

24.4

4.1

27.7

4.5

30.9

4.8

34.2

5.2

14.8

2.8

16.6

3.0

20.1

3.3

23.7

3.7

26.9

4.0

30.0

4.4

33.2

4.7

QW5S2

Full Load Capacities based upon rated flow of 11 GPM of 15% methanol/mass at 1650 CFM airflow.

COOLING FULL LOAD

HEATING FULL LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
55.3

Sensible Capacity (MBtuH)
36.1

Sensible to Total Ratio
0.65

Power Input (KW)
2.37

Heat of Rejection (MBtuH)
62.6

EER 19.6

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

Power Input (KW)

60°

53.2

35.3

0.66

2.82

61.8

17.6

25°

42.2

91.9

3.83

70°

51.1

34.5

0.68

3.26

61.0

15.7

80°

70° DB 59° WB

49.0

33.7

0.69

3.71

60.2

13.7

30° 40°

45.0 50.6

93.7 97.3

3.94 4.18

90°

46.9

32.9

0.70

4.15

59.4 11.74

100°

44.8

32.1

0.72

4.60

58.6

9.7

50°

65°

56.3

100.9

4.42

110°

42.7

31.3

0.73

5.04

57.8

7.8

60°

62.7

105.0

4.71

50°

59.4

37.5

0.63

2.41

67.2

20.8

70°

69.1

109.1

5.00

60° 70° 80° 90° 100° 110°

75° DB 63° WB

57.2 55.0 52.7 50.5 48.3 46.1

36.7 35.9 35.2 34.4 33.6 32.8

0.64 0.65 0.67 0.68 0.69 0.71

2.86 3.30 3.75 4.19 4.64 5.08

66.4 65.6 64.8 64.0 63.2 62.4

18.7 16.6 14.6 12.5 10.4 8.4

80°

25°

30°

40°

50°

70°

75.4 41.3 44.0 49.5 55.0

113.2 96.3 98.1 101.6 105.1

5.28 3.93 4.05 4.3 4.54

50°

63.7

38.8

0.60

2.46

72.1

22.0

60°

61.3

109.1

4.84

60° 70° 80° 90° 100° 110°

80° DB 67° WB

61.3 59.0 56.7 54.3 52.0 49.7

38.1 37.3 36.5 35.8 35.0 34.2

0.62 0.63 0.65 0.66 0.67 0.69

2.90 3.35 3.79 4.24 4.68 5.12

71.2 70.4 69.6 68.8 68.0 67.2

19. 17.6 15.5 13.3 11.1 8.9

70° 80° 25° 30° 40°

67.5 73.8 41.7 44.5 50.0

113.1 117.1 101.6 103.4 107.0

5.13 5.43 4.41 4.55 4.82

50°

68.2

40.1

0.58

2.51

77.1

23.1

50°

75°

55.6

110.5

5.10

60°

65.7

39.4

0.60

2.95

76.3

20.9

70°

63.2

38.6

0.61

3.40

75.5

18.6

80°

85° DB 71° WB

60.8

37.9

0.62

3.84

74.7

16.3

90°

58.3

37.1

0.64

4.28

73.8

14.1

60° 70° 80°

61.9 68.2 74.6

114.5 118.6 122.6

5.43 5.76 6.09

Heat of Absorption COP (MBtuH)

28.7

3.2

31.1

3.3

35.9

3.5

40.7

3.7

46.1

3.9

51.5

4.0

56.9

4.2

27.8

3.1

30.2

3.2

34.8

3.4

39.5

3.5

44.7

3.7

50.0

3.9

55.2

4.0

27.0

2.8

29.3

2.9

33.8

3.0

38.3

3.2

43.4

3.3

48.5

3.5

53.6

3.6

100° 110°

55.8 53.4

36.4 35.6

0.65 0.66

4.73 5.17

73.0 72.2

11.8 9.5

Full Load Capacities based upon rated flow of 11 GPM of 15% methanol/mass at 1400 CFM airflow.

COOLING PART LOAD

HEATING PART LOAD

Entering Fluid
Temp. (°F)
50°

Entering Air Temp. (°F)

Total Capacity (MBtuH)
43.4

Sensible Capacity (MBtuH)
29.4

Sensible to Total Ratio
0.67

Power Input (KW)
1.41

Heat of Rejection (MBtuH)
47.8

EER 23.7

Entering Fluid Temp. (°F)

Entering Air Temp.
(°F)

Total Capacity (MBtuH)

Leaving Air Temp.
(°F)

Power Input (KW)

60° 70° 80° 90° 100° 110°

70° DB 59° WB

41.4 39.5 37.5 35.6 33.6 31.6

28.6 27.8 26.9 26.1 25.3 24.5

0.69 0.70 0.72 0.74 0.75 0.77

1.78 2.16 2.53 2.91 3.29 3.66

46.9 46.0 45.2 44.3 43.4 42.6

21.0 18.3 15.6 12.9 10.2 7.5

25°

30.8

87.8

2.85

30°

32.9

89.4

2.90

40°

37.2

92.6

3.00

50°

65°

41.5

95.8

3.11

60°

46.4

99.4

3.21

50°

46.6

30.5

0.65

1.43

51.3

25.1

70°

51.4

103.0

3.32

60° 70° 80° 90° 100° 110°

75° DB 63° WB

44.5 42.5 40.4 38.3 36.2 34.2

29.7 28.9 28.1 27.3 26.5 25.7

0.66 0.68 0.70 0.71 0.73 0.75

1.81 2.19 2.56 2.94 3.31 3.69

50.4 49.5 48.6 47.7 46.9 46.0

22.3 19.4 16.6 13.8 10.9 8.1

80°

25°

30°

40°

50°

70°

56.3 30.1 32.2 36.4 40.6

106.7 92.3 93.9 97.0 100.1

3.43 2.93 2.98 3.09 3.19

50°

50.0

31.6

0.62

1.46

55.0

26.5

60°

45.4

103.6

3.30

60° 70° 80° 90° 100° 110°

80° DB 67° WB

47.8 45.6 43.4 41.2 39.0 36.8

30.8 30.0 29.2 28.4 27.6 26.8

0.64 0.66 0.67 0.69 0.71 0.72

1.84 2.22 2.59 2.97 3.35 3.72

54.1 53.2 52.2 51.3 50.4 49.5

23.6 20.6 17.6 14.6 11.7 8.7

70° 80° 25° 30° 40°

50.2 55.0 30.4 32.6 36.8

107.2 110.7 97.5 99.1 102.3

3.41 3.52 3.29 3.35 3.46

50°

53.5

32.6

0.60

1.49

58.9

28.0

50°

75°

41.0

105.4

3.58

60°

51.2

31.8

0.62

1.87

57.9

24.9

70°

48.9

31.1

0.64

2.25

57.0

21.7

80°

85° DB 71° WB

46.5

30.3

0.65

2.62

56.0

18.6

90°

44.2

29.5

0.67

3.00

55.1

15.5

60° 70° 80°

45.9 50.8 55.6

109.0 112.6 116.2

3.71 3.83 3.95

100°

41.9

28.7

0.68

3.38

54.1

12.4

Heat of Absorption COP (MBtuH)

20.7

3.2

22.7

3.3

26.6

3.6

30.6

3.9

35.2

4.2

39.7

4.5

44.3

4.8

20.1

3.0

22.0

3.2

25.9

3.4

29.7

3.7

34.1

4.0

38.6

4.3

43.0

4.6

19.5

2.7

21.4

2.9

25.1

3.1

28.8

3.4

33.1

3.6

37.4

3.9

41.7

4.1

110°

39.5

27.9

0.70

3.76

53.2

9.3

Form No. S3419-0521

Supersedes S3419-617

Page

7 of 26

Water Coil Pressure Drop (Fresh Water)

Model GPM
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

QW2S & QW3S

PSID Ft. Hd.

0.1

0.23

0.5

1.15

1.2

2.77

1.7

3.92

2.3

5.31

3.1

7.15

4.1

9.46

QW4S PSID Ft. Hd.

0.9 1.4 2.3 3.2 4.1 5.1 6.1 7.1 8.2 9.4 10.6

2.08 3.23 5.31 7.38 9.46 11.77 14.07 16.38 18.92 21.69 24.45

QW5S PSID Ft. Hd.

2

4.61

2.5

5.77

3.2

7.38

3.9

9.00

4.7

10.84

5.5

12.69

6.4

14.76

7.3

16.84

8.1

18.69

9

20.76

9.9

22.84

NOTE:
For pump options 3, 4 and 5 add 1.5 head to Table values as
allowance for QW*S internal piping.
Additional feet head allowance for external piping to loop must be
included and determined by others.

Required Flow Rates for Water Loop Installations

Flow rate required GPM fresh water

QW2S 6.1

QW3S 8.6

QW4S 11.5

QW5S 13.7

Required Flow Rates for Ground Loop Installations

Flow rate required GPM Methanol, Propylene Glycol or Ethanol j
j See Antifreeze table below.

QW2S 7

QW3S 8

QW4S 9

QW5S 11

Antifreeze Percentages by Volume for Ground Loop Installations j

Type

Minimum Temperature for Freeze Protection 10°F (-12.2°C) 15°F (-9.4°C) 20°F (-6.7°C) 25°F (-3.9°C)

Methanol

25%

21%

16%

10%

Ethanol k

29%

25%

20%

14%

100% USP Food Grade Propylene Glycol

27%

24%

20%

13%

j Loop antifreeze protection must be determined based on loop design and geographic location. k Must not be denatured with any petroleum based product.

Unit Charge Rates
UNIT
QW2S2 - High Efficiency Step Capacity Geothermal Indoor Heat Pump QW3S2 - High Efficiency Step Capacity Geothermal Indoor Heat Pump QW4S2 - High Efficiency Step Capacity Geothermal Indoor Heat Pump QW5S2 - High Efficiency Step Capacity Geothermal Indoor Heat Pump

Std. Unit Lbs.
6.1875

Dehum. Units - Lbs.
6.1875

6.00

6.00

7.0625

7.0625

7.625

7.625

Form No. S3419-0521

Supersedes S3419-617

Page

8 of 26

Ventilation System Packages -- Optional

Q-TEC models are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All ventilation packages are factory installed. If no option is ordered, the ventilation intake and exhaust are sealed with a blank-off plate.
NOTE: A ventilation wall sleeve QWVS42 with outdoor louver grille is required for all installations that intend to utilize one of the built-in ventilation options of the QW*S Series heat pumps. If a ventilation option is not to be utilized, do not order ventilation wall sleeve.

COMMERCIAL ROOM VENTILATOR (Option V)

OPTIONAL

The built-in commercial room ventilator is internally mounted and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced

through the ventilation louver grille. It includes a built-in exhaust air damper. Spring return on power loss or deactivation. The commercial room ventilator (CRV)

is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be

easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on

room occupancy. Complies with ANSI/ASHRAE Standard 62.1 "Ventilation for Acceptable Indoor Air Quality".

COMMERCIAL ROOM VENTILATOR (Option W)

OPTIONAL

The built-in commercial room ventilator is internally mounted and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced

through the ventilation louver grille. It includes a built-in exhaust air damper. Spring return on power loss or deactivation. The commercial room ventilator (CRV)

is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be

easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on

room occupancy. Complies with ANSI/ASHRAE Standard 62.1 "Ventilation for Acceptable Indoor Air Quality". Option W has 0 - 10 VDC actuator for DDC control

by others.

ENERGY RECOVERY VENTILATOR (Option R)

OPTIONAL

The energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE

Standard 62.1. The ERV is internally mounted and allows up to 450 CFM (depending upon speed setting) of fresh air and exhaust through the unit while

maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat

transfer efficiency is up to 64% during summer and 79% during winter conditions.

The ERV consists of a unique "rotary energy recovery cassette" that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only. The ERV has a filter for the exhaust air to keep the rotary wheels clean and free of any debris introduced through the room return air grille. The intake and exhaust rates can be independently selected. Factory set on medium intake and low exhaust. Intake and exhaust air paths have shut-off dampers to eliminate the ingress of outside air when ventilation system is off.

ENERGY RECOVERY VENTILATOR (Option S)

OPTIONAL

The energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE

Standard 62.1. The ERV is internally mounted and allows up to 450 CFM (depending upon speed setting) of fresh air and exhaust through the unit while

maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat

transfer efficiency is up to 64% during summer and 79% during winter conditions.

The ERV consists of a unique "rotary energy recovery cassette" that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only. The ERV has a filter for the exhaust air to keep the rotary wheels clean and free of any debris introduced through the room return air grille. The intake and exhaust rates can be independently selected. Factory set on medium intake and low exhaust. Intake and exhaust air paths have shut-off dampers to eliminate the ingress of outside air when ventilation system is off.

Equipped with Intelligent Frost Control that cycles the ventilation air intake damper closed for 4 minutes out of every 32 minutes of ERV operation when the outdoor air is below 10°F. This sequence allows the ERV to operate with zero outdoor air intake and allows conditioned room air to defrost any accumulated frost if present on the cassette wheels.

ENERGY RECOVERY VENTILATOR (Option T)

OPTIONAL

The energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE

Standard 62.1. The ERV is internally mounted and allows up to 450 CFM (depending upon speed setting) of fresh air and exhaust through the unit while

maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat

transfer efficiency is up to 64% during summer and 79% during winter conditions.

The ERV consists of a unique "rotary energy recovery cassette" that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only. The ERV has a filter for the exhaust air to keep the rotary wheels clean and free of any debris introduced through the room return air grille. The intake and exhaust rates can be independently selected. Factory set on medium intake and low exhaust. Intake and exhaust air paths have shut-off dampers to eliminate the ingress of outside air when ventilation system is off.

Additional controls to permit lower ventilation intake airflow (105 - 225 CFM based on selected intake blower speed and room tightness) and controlled by an occupancy signal, and then can increase to maximum of 450 CFM and controlled by CO2 input signal.

ELECTRICAL SPECIFICATIONS

MODEL

RATED VOLTS & PHASE

NO. FIELD POWER
CIRCUITS

l MINIMUM CIRCUIT AMPACITY

j MAXIMUM EXTERNAL FUSE OR CIRCUIT BREAKER

k FIELD POWER
WIRE SIZE

k GROUND WIRE SIZE

QW2S2-A0Z

230/208-1

1

19

30

10

10

QW2S2-B0Z

230/208-3

1

12

20

12

12

QW2S2-C0Z

460-3

1

7.5

15

14

14

QW3S2-A0Z

230/208-1

1

25

40

8

10

QW3S2-B0Z

230/208-3

1

20

30

10

10

QW3S2-C0Z

460-3

1

11

15

14

14

QW4S2-A0Z

230/208-1

1

33

50

8

10

QW4S2-B0Z

230/208-3

1

24

35

8

10

QW4S2-C0Z

460-3

1

13

20

12

14

QW5S2-A0Z

230/208-1

1

41

60

6

10

QW5S2-B0Z

230/208-3

1

28

40

8

10

QW5S2-C0Z

460-3

1

13

20

12

12

j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

k Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.

l These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest revision) article

310 for power conductor sizing.

Form No. S3419-0521

Supersedes S3419-617

Page

9 of 26

450

400

F 350

R

E 300

S

H

FM C 250

IR

A

A I

ESH FR

200

R

150

C F 100
M
50

0

QW2S CRV AIRFLOW VS. DAMPER POSITION

5

10

15

20

25

30

DAMPER POSITION

Full Load Part Load Blower Only

550

500

F 450

R 400 E

S 350

H FM

C IR

300

AA

I ESH 250

R FR

200

C 150 F
M 100

50

0

QW3S CRV AIRFLOW VS. DAMPER POSITION

Rated Full Load Optional Full Load Part Load Blower Only

5

10

15

20

25

30

DAMPER POSITION

Form No. S3419-0521

Supersedes S3419-617

Page

10 of 26

600

550

500

F R 450

E 400

S

H

FM350 C

IR A

300

A I

ESH FR

250

R

200

C 150 F
M 100

50

0

QW4S CRV AIRFLOW VS. DAMPER POSITION

Full Load Optional Full Load Part Load Blower Only

5

10

15

20

25

30

DAMPER POSITION

650

600

550
F

R 500

E
450
S

H FM400

A

C IR A

350

I ESH 300 R FR 250

C 200 F 150 M
100

50

0

QW5S CRV AIRFLOW VS. DAMPER POSITION

Full Load Optional Full Load Part Load Blower Only

5

10

15

20

25

30

DAMPER POSITION

Form No. S3419-0521

Supersedes S3419-617

Page

11 of 26

Energy Recovery Ventilator Performance Tables

SUMMER COOLING PERFORMANCE (INDOOR DESIGN CONDITIONS 75°DB/62°WB)

Ambient O.D.

VENTILATION RATE 450 CFM 65% EFFICIENCY

VENTILATION RATE 375 CFM 66% EFFICIENCY

VENTILATION RATE 300 CFM 67% EFFICIENCY

DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL

75 21465 14580 6884 13952 9477 4475 17887 12150 5737 11805 8018 3786 14310 9720 4590 9587 6512 3075

105 70 14580 14580 0 9477 9477 0 12150 12150 0 8018 8018 0 9720 9720 0 6512 6512 0

65 14580 14580 0 9477 9477 0 12150 12150 0 8018 8018 0 9720 9720 0 6512 6512 0

80 31590 12150 19440 20533 7897 12635 26325 10125 16200 17374 6682 10692 21060 8100 12960 14110 5427 8683

75 21465 12150 9314 13952 7897 6054 17887 10125 7762 11805 6682 5123 14310 8100 6210 9587 5427 4160

100 70 12352 12150 202 8029 7897 131 10293 10125 168 6793 6682 111 8235 8100 135 5517 5427 90

65 12150 12150 0 7897 7897 0 10125 10125 0 6682 6682 0 8100 8100 0 5427 5427 0

60 12150 12150 0 7897 7897 0 10125 10125 0 6682 6682 0 8100 8100 0 5427 5427 0

80 31590 9720 21870 20533 6318 14215 26325 8100 18225 17374 5345 12028 21060 6480 14580 14110 4341 9768

75 21465 9720 11744 13952 6318 7634 17887 8100 9787 11805 5345 6459 14310 6480 7830 9587 4341 5246

95

70 12352 9720 2632 8029 6318 1711 10293 8100 2193 6793 5345 1447 8235 6480 1755 5517 4341 1175

65 9720 9720 0 6318 6318 0 8100 8100 0 5345 5345 0 6480 6480 0 4341 4341 0

60 9720 9720 0 6318 6318 0 8100 8100 0 5345 5345 0 6480 6480 0 4341 4341 0

80 31590 7290 24300 20533 4738 15794 26325 6075 20250 17374 4009 13365 21060 4860 16200 14110 3256 10854

75 21465 7290 14175 13952 4738 9213 17887 6075 11812 11805 4009 7796 14310 4860 9450 9587 3256 6331

90

70 12352 7290 5062 8029 4738 3290 10293 6075 4218 6793 4009 2784 8235 4860 3375 5517 3256 2261

65 7290 7290 0 4738 4738 0 6075 6075 0 4009 4009 0 4860 4860 0 3256 3256 0

60 7290 7290 0 4738 4738 0 6075 6075 0 4009 4009 0 4860 4860 0 3256 3256 0

80 31590 4860 26730 20533 3159 17374 26325 4050 22275 17374 2672 14701 21060 3240 17820 14110 2170 11939

75 21465 4860 16605 13952 3159 10793 17887 4050 13837 11805 2672 9132 14310 3240 11070 9587 2170 7416

85

70 12352 4860 7492 8029 3159 4870 10293 4050 6243 6793 2672 4120 8235 3240 4995 5517 2170 3346

65 4860 4860 0 3159 3159 0 4050 4050 0 2672 2672 0 3240 3240 0 2170 2170 0

60 4860 4860 0 3159 3159 0 4050 4050 0 2672 2672 0 3240 3240 0 2170 2170 0

75 21465 2430 19035 13952 1579 12372 17887 2025 15862 11805 1336 10469 14310 1620 12690 9587 1085 8502

70 12352 2430 9922 8029 1579 6449 10293 2025 8268 6793 1336 5457 8235 1620 6615 5517 1085 4432 80
65 4252 2430 1822 2764 1579 1184 3543 2025 1518 2338 1336 1002 2835 1620 1215 1899 1085 814

60 2430 2430 0 1579 1579 0 2025 2025 0 1336 1336 0 1620 1620 0 1085 1085 0

70 12352 0 12352 8029 0 8029 10293 0 10293 6793 0 6793 8235 0 8235 5517 0 5517

75

65 4252 0 4252 2764 0 2764 3543 0 3543 2338 0 2338 2835 0 2835 1899 0 1899

60 0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

WINTER HEATING PERFORMANCE (INDOOR DESIGN CONDITIONS 70°F DB)

Ambient O.D.

450 CFM 80% EFFICIENCY

DB/°F

VLT

HRS

VLS

65

2430

1944

486

60

4860

3888

972

55

7290

5832

1458

50

9720

7776

1944

45

12150

9720

2430

40

14580 11664

2916

35

17010 13608

3402

30

19440 15552

3888

25

21870 17496

4374

20

24300 19440

4860

15

26730 21384

5346

10

29160 23328

5832

5

31590 25272

6318

0

34020 27216

6804

-5

36450 29160

7290

-10

38880 31104

7776

Form No. S3419-0521

Supersedes S3419-617

Page

12 of 26

VENTILATION RATE

375 CFM 81% EFFICIENCY

VLT

HRS

VLS

2025

1640

385

4050

3280

770

6075

4920

1154

8100

6561

1539

10125

8201

1924

12150

9841

2309

14175 11481

2693

16200 13122

3078

18225 14762

3463

20250 16402

3848

22275 18042

4232

24300 19683

4617

26325 21323

5002

28350 22964

5387

30375 24604

5771

32400 26244

6156

300 CFM 82% EFFICIENCY

VLT

HRS

VLS

1620

1328

292

3240

2656

583

4860

3985

875

6480

5313

1166

8100

6642

1458

9720

7970

1750

11340

9298

2041

12960 10627

2333

14580 11955

2624

16200 13284

2916

17820 14612

3208

19440 15941

3499

21060 17269

3791

22680 18598

4082

24300 19926

4374

25920 21254

4666

NOTE: Sensible performance only is shown for winter application.
LEGEND:
VLT = Ventilation Load - Total VLS = Ventilation Load - Sensible VLL = Ventilation Load - Latent HRT = Heat Recovery - Total HRS = Heat Recovery - Sensible HRL = Heat Recovery - Latent WVL = Winter Ventilation Load WHR = Winter Heat Recovery

BTU/HR

Optional Hot Water Coil Performance ­ Heating Capacity @ 180°F Water & 70°F Return Air
100000

90000

80000 70000 60000 50000

1.5GPM 2GPM 4GPM 6GPM 8GPM 10GPM

40000

30000

700

800

900

1000

1100

1200

1300

1400

1500

CFM

Hot Water Coil Correction Factors

Ennterinng Air Temp (F)
50 55 60 65 70 75 80

100 0.455 0.409 0.363 0.318 0.272 0.227 0.182

110 0.545 0.500 0.455 0.409 0.363 0.318 0.272

120 0.636 0.591 0.545 0.500 0.455 0.409 0.363

130 0.727 0.682 0.636 0.591 0.545 0.500 0.455

Ennterinng Water Temperature (F)

140

150

160

0.818 0.909 1.000

0.773 0.864 0.955

0.727 0.818 0.909

0.682 0.773 0.864

0.636 0.727 0.818

0.591 0.682 0.773

0.545 0.636 0.727

170 1.091 1.045 1.000 0.955 0.909 0.864 0.818

180 1.182 1.136 1.091 1.045 1.000 0.955 0.909

190 1.273 1.227 1.182 1.136 1.091 1.045 1.000

200 1.364 1.318 1.273 1.227 1.182 1.136 1.091

Form No. S3419-0521

Supersedes S3419-617

Page

13 of 26

Installation Overview of Ventilation Wall Sleeve
Exterior Wall View
NOTE: OPENING DIMENSIONS ARE ± .250
29.750

35.250

33.000

MIS-1612

NOTE: Wall opening and wall sleeve required only when one of the ventilation options is utilized. Installations not utilizing any ventilation option can be made in any interior space accessible to electrical supply, water supply system and condensate drain.

QW2S, QW3S - 42.000" QW4S, QW5S - 48.000"

SUPPLY AIR

OPTIONAL FREE

(X)

BLOW PLENUM BOX

HIGH VOLTAGE ELECTRICAL ENTRANCE (TOP-REAR-SIDE)

RETURN AIR
90" 104"
BOTTOM TRIM PIECE

Form No. S3419-0521

Supersedes S3419-617

Page

14 of 26

14" to 5"

WALL SLEEVE
VENTILATION AIR DIVIDER

18 9/16"

33 7/8" 28 7/8"

35" 29 1/2"
33"

17 9/16"
6 1/8"
MIST ELIMINATOR

PERMANENT ROLLERS

LOW VOLTAGE ELECTRICAL ACCESS (TOP-SIDE)
CIRCUIT BREAKER, ROTARY, OR TOGGLE DISCONNECT AND LOCKING COVER
MIS-2739 B
Unit and Wall Sleeve Opening

Installation Overview ­ Unit Installed with Free Blow Plenum Box

Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)

SUPPLY AIR OPENING 2 7/16"
10" 20 3/8" (DUCT SIZE)

2 1/16" 1 3/4"

TOP VIEW (SHOWN WITHOUT FREEBLOW PLENUM)

"E" (DUCT SIZE)
"A"
"B" "C"

2 15/16"

UNIT

DIM. "A"

QW2S, QW3S 8 5/8"

QW4S, QW5S 8 3/4"

DIM. "B" DIM. "C" DIM. "D" DIM. "E"

42"

30"

43"

25"

48"

40"

49"

30"

(OPTIONAL) HIGH VOLTAGE

ELECTRICAL ENTRANCE

6 3/4"

LOW VOLTAGE

ELECTRICAL ENTRANCE

7/8"

(OPTIONAL) LOW VOLTAGE

3 3/16" ELECTRICAL ENTRANCE

(OPTIONAL) LOW VOLTAGE

ELECTRICAL ENTRANCE

1 1/8"

FREEBLOW PLENUM BOX (OPTIONAL)

(OPTIONAL) HIGH VOLTAGE ELECTRICAL ENTRANCE
1 15/16"

(OPTIONAL) HIGH VOLTAGE ELECTRICAL ENTRANCE

14"

SUPPLY AIR GRILLE

1 11/16" 11 3/4"

16 5/8" (OPTIONAL) THERMOSTAT

(OPTIONAL)

CO2 SENSOR

37 1/8"

FILTER

104"

ACCESS

DOOR

36 1/16"
CONDENSER DOOR

3 3/4" CIRCUIT BREAKER ACCESS AND LOCKING COVER
RETURN AIR GRILLE
15 5/8"
68 3/4" "C"
36 7/8"

3 3/8"

3 3/8"

3 1/16" ACCESS 5 7/16" FOR FLUID CONNECTION FOR DORFC PUMP APPLICATION

FACTORY

CONNECTED

CONDENSATE

DRAIN

CONNECTION

3/4" PVC MALE

ADAPTER

3"

11 1/2"

30 7/8"
6 7/8" 8" 19"

VENT EXHAUST VENT INTAKE
1" BETWEEN OPENINGS
6.00" 4.625"
34 1/4" TO FLOOR
LEVEL 20"

"D" FRONT VIEW

RIGHT SIDE VIEW

FLUID CONNECTION

POINTS FOR FACTORY

INSTALLED PUMP OPTIONS 3, 4, OR 5 (INLET ON LEFT,

BACK VIEW

OUTLET ON RIGHT AS VIEWED FROM BACK OF UNIT)

MIS-2737 D

Form No. S3419-0521

Supersedes S3419-617

Page

15 of 26

Supply Duct Connections for Ducted Installations

MODEL

"A"

"B"

QW2S, QW3S 10"

25"

QW4S, QW5S 10"

30"

"A"
"B" SUPPLY DUCT TO BE FIELD SUPPLIED

ATTACHMENT SCREWS TO BE FIELD SUPPLIED

ROOM SIDE OF QW UNIT

DUCT FLANGE PROVIDED WITH UNIT
MIS-2742 A

Form No. S3419-0521

Supersedes S3419-617

Page

16 of 26

QRS-Series Sound Plenum
The QRS3 - QRS5 Series Sound Plenum has been designed for use with QW*S units. Installation is quick and easy with removal/replacement of six existing screws from the unit cabinet. Once installed the sound plenum enhances the current quiet operation of the Q-TEC Series units, and the hinged door with cam locks (one lockable) provides easy access to the basic Q-TEC system. Model selection is based on equipment cabinet size and finish.

Sound Plenum Part Number

Plenum Finish

QRS3-X QRS3-4 QRS3-V

Painted Steel - Beige
Painted Steel - Buckeye Gray Texture Vinyl j

QRS5-X QRS5-4 QRS5-V

Painted Steel - Beige
Painted Steel - Buckeye Gray Texture Vinyl j

j Front Panels Slate Finish; Side Panels Gray Paint.

Compatible with Equipment Selection
QW2S & QW3S
QW4S & QW5S

8.250" "A"

UNIT QRS3 QRS5

DIM. "A" 42" 48"

Features: · Compatible with new or existing QWS units. · Removable cam latch hinged doors, with center latch lockable. · Easy unit service design. · Sound absorbing insulation. · Reduces equipment operating levels and general muffling of basic unit operation. Actual sound reduction may vary depending upon site variables.

QRS SOUND PLENUM

QW*S UNIT
MIS-2794

Form No. Supersedes Page

MIS-2267
S3419-0521 S3419-617 17 of 26

QRASP ­ Series Return Air Sound Plenum
The QRASP3 - QRASP5 Series Sound Plenum has been designed for use with sound absorbing side panels. It is similar in design to the QSP Sound Plenum, but also incorporates additional sound attenuation panels on both sides as shown. Installation is quick and easy with removal/replacement of six existing screws from the unit cabinet. Once installed the sound plenum enhances the current quiet operation of the Q-TEC Series units, and the hinged door with cam locks (one lockable) provides easy access to the basic Q-TEC system. Model selection is based on equipment cabinet size and finish.

Sound Plenum Part Number
QRASP3-X QRASP3-4 QRASP3-V
QRASP5-X QRASP5-4 QRASP5-V

Plenum Finish
Painted Steel - Beige Painted Steel - Buckeye Gray
Texture Vinyl j
Painted Steel - Beige Painted Steel - Buckeye Gray
Texture Vinyl j

j Front Panels Slate Finish; Side Panels Gray Paint.

Compatible with Equipment Selection
QW2S & QW3S
QW4S & QW5S

Features: · Compatible with new or existing QW*S units. · Removable cam latch hinged doors, with center latch lockable. · Easy unit service design. · Incorporates additional sound absorbing side panels. · Sound absorbing insulation. · Reduces equipment operating levels and general muffling of basic unit operation. Actual sound reduction may vary depending upon site variables.

7" OBSTRUCTION

UNIT DIM A QRASP3 55 13/16" QRASP5 61 13/16"
7"
OBSTRUCTION

12" MINIMUM

8 1/4" "A"

12" MINIMUM

27 11/16"

MIS-2785 A

Form No. S3419-0521

Supersedes S3419-617

Page

18 of 26

91 1/8" 90"

7 1/4"

MIS-2735 A

Bard QW2S2 Series Q-TEC Sound Data Matrix (dBA @ 10 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS42 Return Grille

450 CFM
33.8 38.0

QPBS42 QRS Plenum

450 CFM
32.7 37.1

QPBS42 QRASPS Plenum
450 CFM
32.0 36.0

Duct Free Silencer QRASPS Plenum
450 CFM
30.4 35.6

Ducted Return Grille

450 CFM
31.8 38.3

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
34.5

300 CFM
39.3

375 CFM
42.9

39.3 36.4 53.5 36.9
450 CFM
48.1

38.0 35.4

ERV Off
33.0

300 CFM
36.1

375 CFM
39.0

450 CFM
45.0

37.7 34.6

ERV Off
31.1

300 CFM
33.6

375 CFM
35.0

450 CFM
41.8

36.5 33.6 49.9

ERV Off
30.4

300 CFM
32.8

375 CFM
34.7

450 CFM
43.8

38.2 35.7 51.9 36.9

ERV Off
31.6

300 CFM
39.1

375 CFM
42.9

450 CFM
47.9

Part Load

38.2 41.5 43.7 47.4

39.4 40.8 41.6 42.9

37.1 38.2 38.3 41.3

34.5 35.8 36.9 42.9

36.5 40.8 43.7 47.4

Full Load

40.3 42.5 44.3 48.0

39.4 40.6 41.8 44.3

38.3 38.7 39.4 42.9

35.5 36.4 38.3 43.7

37.6 40.7 43.4 48.7

Integrated dBA

37.1 40.6 43.4 47.9

36.8 38.6 40.3 44.4

35.0 36.3 37.0 41.9

32.9 34.5 36.1 43.6

34.7 39.9 43.2 47.9

Sound Power Full Load

60.3

56.2

Outdoor @ 10 Feet

60.8

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.

Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

11/4/2013

ERV Off
30.8 37.6 37.0 34.8

Ducted
Ducted QRS Plenum
450 CFM
30.7 37.2 37.8 34.8

300 CFM
35.4 38.6 38.1 36.9

375 CFM
38.4 40.7 40.3 39.4

450 CFM
43.7 43.3 45.7 44.0

ERV Off
29.8 36.9 36.3 34.0
35.9

Ducted QRASPS Plenum
450 CFM
30.0 35.9 36.6 33.7 52.9

300 CFM
32.5 36.0 36.2 34.4

375 CFM
35.2 38.2 38.3 36.7

450 CFM
41.8 42.8 43.3 42.3 56.9 53.7

Bard QW2S2 Series Q-TEC Sound Data Matrix (dBA @ 5 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS42 Return Grille

450 CFM
35.5 38.9

QPBS42 QRS Plenum

450 CFM
33.9 38.8

QPBS42 QRASPS Plenum
450 CFM
32.8 36.4

Duct Free Silencer QRASPS Plenum
450 CFM
31.7 36.3

Ducted Return Grille

450 CFM
33.8 39.1

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
35.8

300 CFM
41.8

375 CFM
46.1

39.8 37.5
450 CFM
51.3

39.7 36.9

ERV Off
33.9

300 CFM
37.1

375 CFM
40.7

450 CFM
46.1

38.6 35.4

ERV Off
32.4

300 CFM
35.0

375 CFM
36.6

450 CFM
43.8

38.0 34.8

ERV Off
31.7

300 CFM
34.1

375 CFM
36.3

450 CFM
44.8

40.3 37.2

ERV Off
33.5

300 CFM
41.8

375 CFM
46.3

450 CFM
50.8

Part Load

39.8 43.1 46.5 50.7

40.9 41.9 43.7 44.1

37.2 38.0 39.2 43.6

34.9 36.0 37.8 44.2

38.4 43.0 46.7 51.2

Full Load

41.0 43.9 46.8 50.8

40.7 41.5 43.2 45.5

38.8 39.1 40.0 44.4

36.8 37.5 39.3 45.0

39.3 43.1 46.7 50.8

Integrated dBA

38.3 42.6 46.3 51.1

38.1 39.7 42.1 45.6

35.6 36.8 38.1 43.9

33.9 35.4 37.3 44.7

36.5 42.4 46.5 50.9

Sound Power

Full Load

Outdoor @ 10

Feet

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.

Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

11/4/2013

ERV Off
31.9 39.7 38.6 36.5

Ducted
Ducted QRS Plenum
450 CFM
31.8 40.0 40.2 37.1

300 CFM
36.4 40.8 39.7 38.5

375 CFM
40.1 42.3 42.1 41.1

450 CFM
44.9 44.7 44.8 44.8

ERV Off
30.8 36.9 37.2 34.5

Ducted QRASPS Plenum
450 CFM
30.7 37.4 37.8 34.9

300 CFM
33.9 36.6 37.2 35.4

375 CFM
36.8 38.9 39.2 37.9

450 CFM
43.8 44.5 44.7 44.1

Form No. S3419-0521

Supersedes S3419-617

Page

19 of 26

Form No. S3419-0521

Supersedes S3419-617

Page

20 of 26

Bard QW3S2 Series Q-TEC Sound Data Matrix (dBA @ 10 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS42 Return Grille

450 CFM
35.4 41.4

QPBS42 QRS Plenum

450 CFM
33.2 39.0

QPBS42 QRASPS Plenum
450 CFM
32.9 38.4

Duct Free Silencer QRASPS Plenum
450 CFM
30.9 38.5

Ducted Return Grille

450 CFM
31.3 41.5

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
33.3

300 CFM
40.7

375 CFM
45.0

43.8 39.8 55.8 40.0
450 CFM
49.5

41.5 37.5

ERV Off
32.4

300 CFM
37.0

375 CFM
39.9

450 CFM
43.9

41.0 37.0

ERV Off
31.3

300 CFM
33.4

375 CFM
35.7

450 CFM
41.7

40.1 36.3 52.4

ERV Off
29.7

300 CFM
32.5

375 CFM
34.9

450 CFM
41.4

42.1 38.5 54.1

ERV Off
31.5

300 CFM
39.7

375 CFM
44.6

450 CFM
48.8

ERV Off
30.4

Part Load

44.5 46.6 47.6 50.4

38.8 40.5 42.1 45.4

39.1 38.7 39.6 43.0

37.0 36.8 38.0 42.7

38.2 41.9 44.9 49.2

37.2

Full Load

42.9 44.4 46.8 50.8

40.1 41.2 42.5 45.9

39.7 39.8 40.1 43.5

38.3 38.4 39.1 42.9

40.9 43.4 45.8 49.6

38.8

Integrated dBA

40.6 43.6 46.1 50.0

36.7 39.0 48.7 44.7

36.4 36.8 37.9 42.4

34.7 35.3 36.8 42.0

36.6 41.1 44.9 49.0

35.1

Sound Power Full Load

62.2

55.6

65.3

Outdoor @ 10 Feet

39.6

53.8

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.
Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods 10/28/2013

Ducted
Ducted QRS Plenum
450 CFM
30.9 38.2 39.6 35.9
300 CFM 375 CFM 450 CFM
36.1 39.9 44.6 38.2 40.4 45.3 40.1 41.6 45.4 37.6 40.4 44.9

ERV Off
28.6 36.8 38.0 34.3

Ducted QRASPS Plenum
450 CFM
29.7 37.3 38.8 35.0 50.2

300 CFM
32.4 36.5 38.4 35.2

375 CFM
34.8 37.7 39.3 36.7

450 CFM
40.4 42.6 42.0 41.3 54.1

Bard QW3S2 Series Q-TEC Sound Data Matrix (dBA @ 5 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS42 Return Grille

450 CFM
36.5 42.2

QPBS42 QRS Plenum

450 CFM
34.3 39.8

QPBS42 QRASPS Plenum
450 CFM
33.7 39.6

Duct Free Silencer QRASPS Plenum
450 CFM
32.0 40.4

Ducted Return Grille

450 CFM
33.0 42.0

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
34.6

300 CFM
43.0

375 CFM
48.2

45.3 41.0
450 CFM
52.8

42.5 38.4

ERV Off
33.4

300 CFM
37.7

375 CFM
41.9

450 CFM
45.7

42.0 38.0

ERV Off
32.2

300 CFM
34.2

375 CFM
37.4

450 CFM
42.1

41.0 37.6

ERV Off
31.0

300 CFM
33.6

375 CFM
36.2

450 CFM
42.1

44.0 39.7

ERV Off
33.1

300 CFM
42.3

375 CFM
48.7

450 CFM
52.5

ERV Off
31.5

Part Load

46.2 48.0 50.5 53.6

39.9 41.2 43.2 46.7

41.7 40.8 41.5 46.0

39.6 39.4 40.3 45.7

39.9 44.4 48.6 52.9

39.0

Full Load

44.4 46.4 49.5 53.8

41.1 41.2 43.9 47.2

41.0 41.0 41.5 45.4

39.9 40.1 40.5 44.8

42.9 46.2 49.6 53.4

40.2

Integrated dBA

42.2 45.4 49.1 53.2

37.7 39.5 42.6 46.2

38.3 38.2 39.6 44.0

36.7 37.2 38.5 43.8

38.4 43.8 48.8 52.8

36.6

Sound Power

Full Load

Outdoor @ 10

Feet

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.
Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

10/28/2013

Ducted
Ducted QRS Plenum
450 CFM
32.7 39.5 41.0 37.4
300 CFM 375 CFM 450 CFM
37.3 41.6 46.0 39.8 42.0 46.8 41.1 43.0 46.7 38.9 42.0 46.3

ERV Off
29.8 39.2 39.5 36.2

Ducted QRASPS Plenum
450 CFM
30.7 39.3 40.1 36.6

300 CFM
33.5 39.0 39.8 36.9

375 CFM
36.7 40.1 40.5 38.6

450 CFM
41.4 44.1 43.6 42.6

Bard QW4S2 Series Q-TEC Sound Data Matrix (dBA @ 10 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS48 Return Grille

450 CFM
39.1 44.7

QPBS48 QRS Plenum

450 CFM
38.6 42.8

QPBS48 QRASPS Plenum
450 CFM
37.0 42.2

Duct Free Silencer QRASPS Plenum
450 CFM
36.9 41.0

Ducted Return Grille

450 CFM
34.9 40.0

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
39.5

300 CFM
42.0

375 CFM
45.0

45.3 42.5 59.5 41.0
450 CFM
49.6

44.2 41.3

ERV Off
38.5

300 CFM
39.8

375 CFM
40.9

450 CFM
46.1

43.1 40.2

ERV Off
37.6

300 CFM
38.1

375 CFM
38.5

450 CFM
44.0

42.1 39.4 58.0

ERV Off
37.2

300 CFM
37.9

375 CFM
38.3

450 CFM
43.2

42.5 38.6 57.2 40.0

ERV Off
36.0

300 CFM
40.0

375 CFM
43.6

450 CFM
48.0

ERV Off
34.8

Part Load

45.2 46.2 47.0 50.8

43.1 43.4 44.0 47.0

42.1 42.1 42.5 45.3

40.9 41.0 41.5 44.9

41.0 42.5 45.1 48.5

38.9

Full Load

46.0 46.8 47.5 51.1

44.2 44.4 45.0 47.5

43.0 43.2 43.2 45.8

41.6 41.7 42.0 45.1

43.1 44.1 45.7 48.8

40.8

Integrated dBA

43.1 44.4 46.1 50.2

41.4 42.0 42.7 46.6

40.3 40.6 40.8 44.7

39.3 39.7 40.1 44.0

39.5 41.6 44.4 48.3

37.6

Sound Power Full Load

65.7

61.7

64.8

Outdoor @ 10 Feet

53.8

39.6

53.8

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.

Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

9/27/2013

Ducted
Ducted QRS Plenum
450 CFM
34.4 38.1 40.8 37.2

300 CFM
36.9 39.8 41.5 38.8

375 CFM
39.6 41.1 42.5 40.6

450 CFM
45.2 45.4 45.7 45.3

ERV Off
33.0 37.4 39.1 35.9

Ducted QRASPS Plenum
450 CFM
31.3 36.4 39.0 35.1 50.8

300 CFM
34.5 37.7 39.3 36.6

375 CFM
36.1 38.5 39.6 37.5

450 CFM
42.3 42.4 42.8 42.4 57.8

Bard QW4S2 Series Q-TEC Sound Data Matrix (dBA @ 5 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS48 Return Grille

450 CFM
40.5 46.1

QPBS48 QRS Plenum

450 CFM
40.0 44.2

QPBS48 QRASPS Plenum
450 CFM
37.7 43.4

Duct Free Silencer QRASPS Plenum
450 CFM
37.5 42.5

Ducted Return Grille

450 CFM
37.5 42.0

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
40.6

300 CFM
43.8

375 CFM
48.2

47.1 44.1
450 CFM
52.0

45.8 42.8

ERV Off
39.5

300 CFM
41.3

375 CFM
42.3

450 CFM
47.1

44.0 41.2

ERV Off
38.1

300 CFM
39.4

375 CFM
39.6

450 CFM
46.4

43.4 40.6

ERV Off
38.0

300 CFM
38.9

375 CFM
39.6

450 CFM
46.4

44.4 40.8

40.0

ERV Off
37.5

300 CFM
42.9

375 CFM
47.2

450 CFM
51.1

ERV Off
35.5

Part Load

46.2 47.4 49.5 52.6

44.7 45.1 45.7 48.2

43.3 43.4 43.8 47.2

42.2 42.3 42.8 46.7

42.6 45.0 48.4 51.8

40.1

Full Load

47.2 48.4 50.1 53.1

45.4 45.9 46.9 48.8

43.6 44.5 44.4 47.3

42.8 42.6 43.4 47.1

45.1 46.4 48.6 52.0

42.5

Integrated dBA

44.2 46.0 48.9 52.4

42.7 43.5 44.4 47.7

41.1 41.9 42.0 46.8

40.4 40.7 41.4 46.6

41.2 44.3 47.8 51.4

38.8

Sound Power

Full Load

Outdoor @ 10 Feet

39.6

53.8

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.

Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

9/27/2013

Ducted
Ducted QRS Plenum
450 CFM
35.5 39.8 42.6 38.8

300 CFM
38.0 41.1 43.2 40.2

375 CFM
40.8 42.7 44.1 42.0

450 CFM
45.7 46.0 46.6 45.9

ERV Off
34.5 38.5 40.6 37.3

Ducted QRASPS Plenum
450 CFM
33.4 37.9 40.4 36.7

300 CFM
35.9 39.5 41.1 38.2

375 CFM
37.5 40.1 41.6 39.2

450 CFM
44.4 45.1 45.2 44.7

Form No. S3419-0521

Supersedes S3419-617

Page

21 of 26

Form No. S3419-0521

Supersedes S3419-617

Page

22 of 26

Bard QW5S2 Series Q-TEC Sound Data Matrix (dBA @ 10 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS48 Return Grille

450 CFM
41.6 46.5

QPBS48 QRS Plenum

450 CFM
40.1 45.8

QPBS48 QRASPS Plenum
450 CFM
38.7 45.4

Duct Free Silencer QRASPS Plenum
450 CFM
37.8 43.1

Ducted Return Grille

450 CFM
37.2 43.0

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
42.0

300 CFM
43.1

375 CFM
44.0

47.5 44.6
450 CFM
48.1

46.6 43.7

ERV Off
40.3

300 CFM
40.8

375 CFM
41.2

450 CFM
44.7

46.4 43.1

ERV Off
38.7

300 CFM
40.0

375 CFM
40.5

450 CFM
44.2

43.9 41.1 53.7

ERV Off
38.0

300 CFM
38.5

375 CFM
39.5

450 CFM
42.8

45.1 41.3 58.9 41.0

ERV Off
37.8

300 CFM
42.2

375 CFM
45.7

450 CFM
50.2

ERV Off
36.1

Part Load

47.2 47.4 47.9 49.9

45.1 45.0 45.6 46.8

43.8 44.1 44.4 46.4

43.4 42.9 42.8 45.0

43.9 44.9 47.2 51.6

42.7

Full Load

47.9 48.3 48.5 50.4

45.9 46.2 46.4 47.5

44.9 45.0 45.5 46.6

44.1 44.3 44.3 45.6

46.1 46.9 48.6 52.0

45.0

Integrated dBA

45.2 45.7 46.2 49.1

43.2 43.4 43.8 45.9

41.9 42.5 42.9 45.3

41.3 41.3 41.6 44.0

42.2 44.1 46.7 50.9

40.9

Sound Power Full Load

65.6

60.2

65.9

Outdoor @ 10 Feet

39.6

53.8

39.6

53.8

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.

Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

9/27/2013

Ducted
Ducted QRS Plenum
450 CFM
35.4 41.4 43.3 39.6

300 CFM
38.1 43.1 45.2 41.6

375 CFM
40.3 43.7 45.1 42.4

450 CFM
45.7 46.9 47.7 46.4

ERV Off
34.0 39.5 41.9 38.0

Ducted QRASPS Plenum
450 CFM
34.7 39.9 41.4 38.1

300 CFM
35.2 40.0 42.2 38.6

375 CFM
36.6 40.7 42.4 39.3

450 CFM
40.0 42.4 43.8 41.5 56.8

Bard QW5S2 Series Q-TEC Sound Data Matrix (dBA @ 5 feet)
Duct Free

Supply Air Treatment Return Air Treatment
Vent Option CRV
Ventilation Only
Part Load

QPBS48 Return Grille

450 CFM
43.0 47.8

QPBS48 QRS Plenum

450 CFM
41.2 46.5

QPBS48 QRASPS Plenum
450 CFM
39.5 46.0

Duct Free Silencer QRASPS Plenum
450 CFM
38.3 44.6

Ducted Return Grille

450 CFM
39.8 45.6

Full Load
Integrated dBA
Sound Power Full Load
Outdoor @ 10 Feet
Vent Option ERV
Blower Only

ERV Off
42.5

300 CFM
44.7

375 CFM
46.4

48.6 45.9
41.0
450 CFM
50.1

47.5 44.5

ERV Off
41.6

300 CFM
42.1

375 CFM
42.7

450 CFM
48.1

44.8 43.1

ERV Off
39.7

300 CFM
41.1

375 CFM
41.8

450 CFM
45.7

45.0 42.2

ERV Off
38.6

300 CFM
40.0

375 CFM
40.4

450 CFM
45.1

47.6 43.9

ERV Off
39.8

300 CFM
45.7

375 CFM
50.0

450 CFM
53.9

ERV Off
37.5

Part Load

48.6 49.1 49.5 51.6

46.2 46.4 46.6 48.7

45.9 46.2 46.1 48.3

44.8 44.4 44.9 46.7

45.3 47.8 50.6 54.2

43.8

Full Load

49.3 49.5 50.4 52.1

47.2 47.4 47.4 48.8

46.7 47.0 47.1 48.6

45.8 45.9 45.9 47.2

48.4 49.9 52.1 54.7

45.6

Integrated dBA

46.3 47.2 48.2 50.9

44.4 44.7 45.0 48.4

43.6 44.2 44.4 47.1

42.6 42.9 43.2 46.0

44.1 47.3 50.6 54.1

41.9

Sound Power

Full Load

Outdoor @ 10

Feet

1 Integrated values calculated per ANSI/ASA S12.60-2009/Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3 HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17% 2 Integrated Sound Vales are also applicable for use in learning spaces for CHPS and LEED schools; EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in prescribed in ANSI S12.60, classroom must achieve a maximum background noise level of 45 dBA. 3 All data recorded at rated GPM per Bard product specifications.

Results Referenced Were Recorded In The Bard Manufacturing Company, Inc. Sound Lab Facility

Actual Field Application Results May Vary With Classroom Design and Construction Methods

9/27/2013

Ducted
Ducted QRS Plenum
450 CFM
36.5 42.7 44.4 40.8

300 CFM
39.6 44.5 45.9 42.8

375 CFM
41.8 45.1 46.6 43.9

450 CFM
45.9 48.3 49.0 47.2

ERV Off
34.9 40.7 43.4 39.3

Ducted QRASPS Plenum
450 CFM
35.8 41.3 42.6 39.4

300 CFM
36.2 41.5 43.6 39.9

375 CFM
37.8 41.8 43.8 40.6

450 CFM
41.9 43.8 44.9 43.1

Optional Accessories ­ Must be Used for Each Installation with Ventilation Options

Ventilation Wall Sleeves:

QWVS42

Ventilation wall sleeve for walls up to 14 inches thick. NOTE: Unless they are to be field-supplied, side trim kit must be ordered for all installations.

Ventilation Louvers:

QLW-10

Standard Clear Painted Enamel Finish for vent option

QLW-20

Standard Medium Bronze Painted Enamel Finish for vent option

QLW-30

Standard Dark Bronze Painted Enamel Finish for vent option

QLW-*

Optional Louver Finishes available (See Form S3508)

Contact your Bard Sales Representative for Custom Finish Louver information

Side Trim Kits -- Required for All Installations Unless Field-Supplied

NOTE: The following accessory items must be selected so the finish (color) is matched to the QWS model that they will be used with.

Side Trim Extension Kits:

Unit Compatibility

Model

Color

Model

Color

Model

Color

Model

Color

Space from back of unit to wall

QSTX-V-6

Platinum Vinyl QSTX-4-6

Gray Paint QSTX-X-6

Beige Paint QSTX-1-6

White Paint 4" to 6"

All

QSTX-V-8

Platinum Vinyl QSTX-4-8

Gray Paint QSTX-X-8

Beige Paint QSTX-1-8

White Paint 6" to 8"

All

QSTX-V-10

Platinum Vinyl QSTX-4-10 Gray Paint QSTX-X-10

Beige Paint QSTX-1-10

White Paint 8" to 10"

All

QSTX-V-12

Platinum Vinyl QSTX-4-12 Gray Paint QSTX-X-12

Beige Paint QSTX-1-12

White Paint 10" to 12"

All

Optional Accessories -- Additional Items as Determined by Job Specifications

Duct-Free Plenum Boxes:

Unit Compatibility

QPB42-V QPBS42-V QPBS42-V-8 QPB48-V QPBS48-V QPBS48-V-8

Platinum Vinyl QPB42-4 Platinum Vinyl QPBS42-4 Platinum Vinyl QPBS42-4-8 Platinum Vinyl QPBS48-4 Platinum Vinyl QPBS48-4 Platinum Vinyl QPBS48-4-8

Gray Paint QPB42-X Gray Paint QPBS42-X Gray Paint QPBS42-X-8 Gray Paint QPBS48-X Gray Paint QPBS48-X Gray Paint QPBS48-X-8

Beige Paint QPB42-1 Beige Paint QPBS42-1 Beige Paint QPBS42-1-8 Beige Paint QPBS48-1 Beige Paint QPBS48-1 Beige Paint QPBS48-1-8

White Paint Front supply, 4-way deflection grille White Paint Same as QPB42, plus 2-way deflection grille on each side White Paint Same as QPBS42 and 8" Height j White Paint Front supply, 4-way deflection grille White Paint Same as QPB48, plus 2-way deflection grille on each side White Paint Same as QPBS48 and 8" Height j

QW2S, QW3S QW2S, QW3S QW2S, QW3S QW4S, QW5S QW4S, QW5S QW4S, QW5S

Top Fill Systems for Finishing Plenum Boxes to Ceilings:

Unit Compatibility

QPBX42-9-V QPBX42-10-V QPBX48-9-V QPBX48-10-V

Platinum Vinyl QPBX42-9-4 Gray Paint QPBX42-9-X Platinum Vinyl QPBX42-10-4 Gray Paint QPBX42-10-X Platinum Vinyl QPBX48-9-4 Gray Paint QPBX48-9-X Platinum Vinyl QPBX48-10-4 Gray Paint QPBX48-10-X

Beige Paint QPBX42-9-1 Beige Paint QPBX42-10-1 Beige Paint QPBX48-9-1 Beige Paint QPBX48-10-1

White Paint Use with QPB42 or QPBS42 (adjusts to ceilings up to 9'9") White Paint Use with QPB42 or QPBS42 (adjusts to ceilings up to 10'5") White Paint Use with QPB48 or QPBS48 (adjusts to ceilings up to 9'9") White Paint Use with QPB48 or QPBS48 (adjusts to ceilings up to 10'5")

QW2S, QW3S QW4S, QW5S

Cabinet Extensions for Ducted Applications:

Unit Compatibility

QCX10A-V QCX15A-V

Platinum Vinyl QCX10A-4 Platinum Vinyl QCX15A-4

Gray Paint QCX10A-X Gray Paint QCX15A-X

Beige Paint QCX10A-1 Beige Paint QCX15A-1

White Paint

20" height (adjusts for ceilings up to 9'7"; add QPBX42-9 for 9'7" to 10'3" finished ceiling heights)

White Paint

20" height (adjusts for ceilings up to 9'7"; add QPBX48-9 for 9'7" to 10'3" finished ceiling heights)

QW2S, QW3S QW4S, QW5S

Hot Water Coils with Plenum Boxes:

Unit Compatibility

QPBHW42-F-V QPBHW48-F-V QPBHW42-D-V QPBHW48-D-V

Platinum Vinyl QPBHW42-F-4 Gray Paint Platinum Vinyl QPBHW48-F-4 Gray Paint Platinum Vinyl QPBHW42-D-4 Gray Paint Platinum Vinyl QPBHW48-D-4 Gray Paint

QPBHW42-F-X QPBHW48-F-X QPBHW42-D-X QPBHW48-D-X

Beige Paint QPBHW42-F-1 Beige Paint QPBHW48-F-1 Beige Paint QPBHW42-D-1 Beige Paint QPBHW48-D-1

White Paint White Paint White Paint White Paint

Free blow plenum box Free blow plenum box Ducted plenum box Ducted plenum box

QW2S, QW3S QW4S, QW5S QW2S, QW3S QW4S, QW5S

NOTE: The same top fill system and cabinet extensions can be used with hot water coil plenum boxes as with standard plenum boxes. j 8" Plenum Box height may affect sound level of supply air and unit.

Form No. S3419-0521

Supersedes S3419-617

Page

23 of 26

WATER CONNECTION OPTIONS
Female National Pipe Thread (NPT) Connections (Piping Option "P")
1" Female National Pipe Thread (NPT) copper fitting connections at inlet and outlet of co-axial water coil. No internal pump options available with piping option "P".
Double O-Ring Water Connections (Piping Option "X")
IMPORTANT NOTE: Water coils can be equipped with male half of double O-ring fittings and a mating half must be used. No other type of fitting will mate up. The DORFC Flow Centers also have double O-ring connections on both heat pump and loop sides of flow center. Depending upon pump and piping options ordered, additional double O-ring fittings and hose may be required. Fittings are available for threaded, barbed, soldered and fusion connections.

Elbow, 1" MPT X Double O-ring with 1/4" Port and Pressure/
Temperature Test Plugs
DORMP1-90
Elbow, 1" MPT X Double O-ring with 1/4" Port and
1/4" Brass Pipe Plugs
DORMP1-90P

1" MPT X Double O-ring DORMP1-S

1" FPT X Double O-ring DORFP1-S

Elbow, 1" Hose Barb X Double O-ring with 1/4" Port and Pressure/
Temperature Test Plugs
DORB1-90-4HC
Elbow, 1" Hose Barb X Double O-ring with 1/4" Port and 1/4" Brass Pipe Plugs
DORB1-90P-4HC

1" Hose Barb X Double O-ring
DORB1-S-4HC

1-1/4" Socket Fusion X Double O-ring
DORF125-S

1" Copper Sweat X Double O-ring with 1/4" FPT Port &
Pressure/Temperature Test Plugs
DORS1-S

Individual Double O-Ring Fitting Packs (Qty 2 per pack)

DORMP1-90

(2) 1" MPT 90° double o-ring elbows with 1/4" FPT ports and 8603-026 pressure/temperature test plugs

DORMP1-90P (2) 1" MPT 90° double o-ring elbows with 1/4" FPT ports and 1/4" brass pipe plugs

DORMP1-S

(2) 1" MPT straight double o-ring fittings

DORFP1-S

(2) 1" FPT straight double o-ring fittings

DORB1-90-4HC

(2) 1" barbed 90° double o-ring elbows with 1/4" FPT ports, 8603-026 pressure/temperature test plugs and (4) SS 1" hose clamps

DORB1-90P-4HC

(2) 1" barbed 90° double o-ring elbows with 1/4" FPT ports, 1/4" brass pipe plugs and (4) SS 1" hose clamps

DORB1-S-4HC (2) 1" barbed straight double o-ring fittings with (4) 1" SS hose clamps

DORF125-S

(2) 1.25" fusion straight double o-ring fittings

DORS1-S

(2) 1" copper sweat straight double o-ring fittings with 1/4" FPT ports and 8603-026 pressure/temperature test plugs

Optional Hose

Form No. S3419-0521

Supersedes S3419-617

Page

24 of 26

HK1-25

(1) 25' section of 1" ID 150 PSI hose

Flow Centers & Individual Pumps w/Double O-Ring Connections (See Pump Ratings Below)

Pump Option
1
2
3 4 5

Pump Model DORFC-1
DORFC-2
UPS15-42F UP26-64F UPS26-99FC

No. of Pumps

Description

1

Loop Flow Center w/Insulated Cabinet, 230V-60Hz-1Ph, Double O-ring Fittings, UP26-99F Pump, Brass Isolation & Flush Valves Built-In

2

Loop Flow Center w/Insulated Cabinet, 230V-60Hz-1Ph, Double O-ring Fittings, UP26-99F Pump, Brass Isolation & Flush Valves Built-In

1 Pump with Isolation Valves, 230V-60Hz-1Ph, Piped to Rear of Cabinet, Double O-ring Connections

1 Pump with Isolation Valves, 230V-60Hz-1Ph, Piped to Rear of Cabinet, Double O-ring Connections

1 Pump with Isolation Valves, 230V-60Hz-1Ph, Piped to Rear of Cabinet, Double O-ring Connections

Installation Method
Can be factory or field installed
Factory installed
only

DORFC-2

UPS26

Flow Center and Individual Pump Accessories

Bard Part Number Required Quantity

Description

Used With

QWRK

Consists of control relay, two 3A circuit breakers, all wiring and all Included with factory installed DORFC Flow

1

installation parts

Centers and UPS Pumps. Order only if field

installing any flow center or pump.

QWHK

Consists of two 1" x 33" 200 PSIG hoses with SS braided sheathing Included with units for factory installed

1

and fitted with straight double o-ring fittings one end and 90° elbow DORFC's. Order only if field installing DORFC.

double o-ring fittings with P/T ports installed on opposite end.

j This is factory installed if flow center or pump is factory installed.

Loop Pump Modules and Individual Pump Capacities jk

For Use with Pump QWS Models l Option

Pump Model

No. of Pumps

No. of Speeds

Speed

5

6

7

8

WATER FLOW in GPM 9 10 11 12 13 14 15 16

ALL

1

DORFC-1

1

1

Single 29.5 29 28.5 28 27.5 26.5 25.5 24.5 23 22.5 22 21

ALL

2

DORFC-2

2

1

Single 59 58 57 56 55 53 51 49 46 45 44 42

QW2 - 3S

3

UPS15-42F

1

High 12.1 11.5 10.7 9.7 8.8 8

------------

3 Medium 6.8 5.7 4.5 -- -- -- -- -- -- -- -- --

Low -- -- -- -- -- -- -- -- -- -- -- --

QW2 - 3S

4

UP26-64F

1

1

Single 21.5 21 20 19 18 17 16.5 16 15 14 13 12.5

QW3 - 5S

5 UPS26-99FC 1

High 29.5 29 28.5 28 27.5 26.5 25.5 24.5 23 22.5 22 21 3 Medium 23.5 22.2 21.5 20.3 19.5 18.5 17.8 16.5 15.3 14.3 13.3 12.4
Low 15.3 13.8 12.4 10.9 9.8 8.4 -- -- -- -- -- --

j Pump output shown in feet head @ GPM at top of columns. k Refer to Water Coil Pressure Drop table (Page 8) for feet head allowances for basic QW*S complete system. Additional feet head allowance from basic unit to
main piping loop must be included and determined by others. l Pump options shown can be factory installed in models as shown. Suitability of each must be determined by others based on QWS requirements, plus the
loop design requirements designed by others.

Ground Loop Service Accessories for Installations with DORFC Flow Centers

Heat Pump Model

Bard Part Number DORCL1-90 CLB1-S GGK-1 DORGHMT

Required Quantity Each Each Each Each

Description (2) 90° double o-ring quick-connect cam-lever male fittings for flush attachment to loop flow center (2) 1" straight barbed quick-connect cam-lever female fittings to connect to DORCL1-90 fittings above (1) Geo-Gooser w/shut-off valve, 0-100 PSI gauge, garden hose connection, P/T fitting 1/8' probe (2) Double o-ring x male garden hose adapter fitting for loop flow center (to burp/boost loop)

1" Cam Lever Male X Double O-ring
DORCL1-90

CLB1-S

Garden Hose Male X O-ring (single) Adapter
DORGHMT

GGK-1

Form No. S3419-0521

Supersedes S3419-617

Page

25 of 26

QW*S Step Capacity Series Q-TEC Geothermal HP Model Nomenclature

QW 3 S 2

A 0Z B

X VX

C

X

MODEL NUMBER | Q-TEC Model

KW 0Z - OKW

FILTER OPTIONS X - 2-Inch Pleated

COIL OPTIONS C - Copper water

CAPACITY |

(MERV8)

N - Cupronickel

2 - 2 Ton 3 - 3 Ton 4 - 4 Ton 5 - 5 Ton

STEP CAPACITY | REVISION |

VOLTS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3

COLOR 1 - White paint 4 - Buckeye Gray paint X - Beige paint

NOTE: Copper Coils approved for Ground Loop and Closed Loop Boiler/Tower only.

V - Platinum w/Slate

SPECIALTY

Front (Vinyl)

PRODUCTS j

(Non-Standard) |

CLIMATE CONTROL OPTIONS (Factory Mounted)

X = 24V Terminal Block Only k

D = 8403-060 Electronic/Programmable Thermostat w/Humidity Control

VENTILATION OPTIONS B - Blank-off Plate V - Commercial Ventilator - Motorized w/Exhaust Spring Return R - Energy Recovery Ventilator w/Independent Intake & Exhaust Control S - Energy Recovery Ventilator w/Intelligent Frost Control Option T - Energy Recovery Ventilator w/Occupied Space CFM Control Option

H = 8403-060 Prog. Thermostat w/Humidity Control + 8403-067 CO2 Controller
K = 24V Terminal Block + 8403-067 CO2 Controller Only 1 = CompleteStat CS9B-THO (Temp, Humidity & Occupancy) l 2 = CompleteStat CS9B-THOC (THO + CO2) l 3 = CompleteStat CS9BE-THO (THO w/Ethernet) m 4 = CompleteStat CS9BE-THOC (THO + CO2 w/Ethernet) m 5 = 8403-069 Viconics VT7652H5000B w/BACnet 

6 = 8403-069 Viconics + 8403-067 CO2 Controller 

7 = 8403-071 Viconics VT7600H5500B Non-Prog w/BACnet & PIR cover

8 = 8403-075 Viconics VT7600H5000B Non-Prog w/BACnet + 8403-067

CO2 Controller 

NOTE: j Insert "D" for dehumidification with hot gas reheat. Reference 7960-658 for complete details. k If "X" control option is selected, then thermostat and humidistat, if applicable, or DDC control system must be field supplied. l CS9B-THO and -THOC are BACnet w/shielded twisted pair wiring. m CS9BE-THO and -THOC are BACnet w/shielded twisted pair wiring and Ethernet port.  Not available for Dehumidification Models.

FACTORY INSTALLED PUMP & PIPING OPTIONS
X - None; all pump & water connections field installed, requires field piping to the coaxial water coil using double o-ring fittings, which must be ordered separately.
P - None; all pump & water connections field installed, requires field piping to the coaxial water coil 1" Female NPT wrought copper fittings.
1 - DORFC-1 double o-ring flow center, single Grundfos UP26-99F pump piped to water coil with 150 PSI reinforced hose
2 - DORFC-2 double o-ring flow center, double Grundfos UP26-99F pump piped to water coil with 150 PSI reinforced hose
3 - Single Grundfos UPS15-42F pump, isolation valves both ends, piped with copper to double o-ring fittings back corners of unit
4 - Single Grundfos UP26-64F pump, isolation valves both ends, piped with copper to double o-ring fittings back corners of unit
5 - Single Grundfos UPS26-99-FC pump, isolation valves both ends, piped with copper to double o-ring fittings back corners of unit

See Pages 23, 24 & 25 for Additional Required and Optional Field Installed Accessories

Optional Field Installed Hard Start Kits for 1-Phase Models j

Unit Model

Field Installed Part Number

QW2S2-A only

SK111

QW3S2-A only

SK111

QW4S2-A only

SK118

QW5S2-A only

SK118

j Start Capacitor and potential relay start kit can be used with all -A single phase models only. Increases starting torque 9x. Not used on -B or -C three phase models.

Optional Field Installed Evap. Drain Pan Overflow Kit

Part Number Description

8620-219

24VAC 0.4A SPST NC Switch to shutdown compressor. Can be converted to NO action to use for alarm circuit.

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com

Form No. S3419-0521

Supersedes S3419-617

Page

26 of 26

Due to our continuous product improvement policy, all specifications subject to change without notice.
Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.

Form No. S3419
May 2021
Supersedes: S3419-617

