Installation Instructions Model SIM-16
Supervised Input Module

INTRODUCTION

The Model SIM-16 Supervised Input Module from Siemens Industry, Inc., is a remotely located, general purpose input module. It provides sixteen input circuits for remote system monitoring. Each input can be individually programmed as supervised (dry contacts only) or unsupervised (general-purpose input). The SIM-16 has two Form C relays. The relays and the inputs are programmable using the Zeus Programming Tool.

TB1

SIM-16

12345678

9 10 11 12 13 14 15 16

P2

P3

23 23

456
S1

9 01

78 78

9 01

456
S2

OPERATION

The SIM-16 is mounted in an enclosure that is remotely located from the Main Panel. Communication between the SIM-16 and the NIC-C (Network Interface Card) is through the Control Area Network (CAN) bus. Up to 99 SIM-16s can be used with a single NIC-C.

Each SIM-16 has two 10-position rotary switches that

are used to set the board address on the CAN which is a

TB4

6

sub-address of the NIC-C.

TB3

6

Every time a change of state of the input is detected, a

unique CAN message is sent to the NIC-C. A CAN

message from the NIC-C directed to the SIM-16 controls

1

the Form C relays.

1

12345678 9 10 11 12 13 14 15 16

PRE-INSTALLATION

Rotary Address Switches - Set the board address for each SIM-16 using both of the ten-position rotary switches located on the board (See Figure 1). Each of these addresses must be a sub-address of the NIC-C and must be the same as the addresses assigned in the Zeus Programming Tool.

TB2
Figure 1 SIM-16 Supervised Input Module

INSTALLATION

A SIM-16 may be installed in a REMBOX. When using REMBOX 2 or 4, mount the SIM-16 in one module space on a REMBOX2-MP, P/N 500-634211 or REMBOX4-MP, P/N 500-634212 using the four screws provided. (Refer to REMBOX2-MP/REMBOX4MP Installation Instructions, P/N 315-034211.) Up to 4 SIM-16s will fit in a REMBOX2; up to 8 SIM-16s will fit in a REMBOX4.

P/N 315-034060-6

Siemens Industry, Inc. Building Technologies Division
firealarmresources.com

WIRING

Refer to Figures 2-6.
Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
· Each SIM-16 module is a node in the CAN bus. · The SIM-16 can be installed with or without an RNI. Connect the CAN bus
and 24V as shown in Figures 2 and 3. · Up to 99 CAN modules, in any combination, can be connected to the CAN
bus of each NIC-C. · Each SIM-16 module is shipped with one CCS cable. · Cable connections for SIM-16 modules are shown in the following table:

SIM-16 CABLE CONNECTIONS

Cable Description

Part Number Connection

CCL CCS

CAN-CABLE-Long 599-634214 30 in., 6-conductor
CAN-CABLE-Short 555-133539 5½ in., 6-conductor

Connects P4 on RNI to first SIM-16. Also connects from SIM-16 to FCM/ LCM/SCM/CSB modules (on door).
Connects SIM-16 modules to SIM-16 or OCM-16 modules in a single row

The CAN bus requires a 120S termination at each end of the loop. Refer to the NIC-C Installation Instructions, P/N 315-033240 for details about CAN termination.

TO RNI, P4
CABLE MODEL # CCL

23 23 23 23 23 23 23 23

TB1

12345678

9 10 11 12 13 14 15 16

P2

P3

456 S1

9 01

9 01

456 S2

78 78
78 78
78 78
78 78

CABLE MODEL # CCS

TB1

12345678

9 10 11 12 13 14 15 16

P2

P3

TB1

12345678

9 10 11 12 13 14 15 16

P2

P3

456 S1

9 01

9 01

456 S2

456 S1

9 01

9 01

456 S2

TB1

12345678

9 10 11 12 13 14 15 16

P2

P3

456 S1

9 01

9 01

456 S2

CAN TERMINATOR, P/N 110-134215
(SHIPPED WITH NIC-C)

SIM-16

SIM-16

SIM-16

SIM-16

TB4

TB4

TB4

TB4

6

6

6

6

TB3

TB3

TB3

TB3

6

6

6

6

1

1

1

1

1

1

1

1

12345678 9 10 11 12 13 14 15 16

12345678 9 10 11 12 13 14 15 16

12345678 9 10 11 12 13 14 15 16

12345678 9 10 11 12 13 14 15 16

TB2

TB2

TB2

TB2

Figure 2 SIM-16 CAN Bus Connections With An RNI

Siemens Industry, Inc. Building Technologies Division

2
firealarmresources.com

P/N 315-034060-6

NOTES 1. All wiring supervised. 2. All wiring power limited to
NFPA 70 per NEC 760. 3. Wiring for TB1 and TB2 is 18
AWG min., 12 AWG max. 4. Wiring for TB3 and TB4 is
18AWG min., 16 AWG max. 5. CAN network max. line
resistance 15S. 6. Refer to the NIC-C
Installation Instructions, P/N 315-033240 for CAN network termination instructions.
Figure 3 SIM-16 Wiring Without An RNI

TO PSC-12/PSX-12, TB3 OR ANY REGULATED
POWER LIMITED POWER SUPPLY LISTED FOR FIRE PROTECTIVE SIGNALING USE

SIM-16

TO PSC-12, TB1 SEE NIC-C
INSTALLATION INSTRUCTIONS, P/N 315-033240 FOR WIRING DETAILS

TB3 +24 V 24 V RET SHIELD CAN + CAN ­ SHIELD
16 15 14 13 12 11 10 9
87654321
TB2

NOTES 1. Contacts are unsupervised. 2. 1A max @ 24VDC resistive. 3. All wiring must remain
inside the enclosure or within 20 feet in rigid conduit. 4. Wiring for TB1 and TB2 is 18 AWG min., 12 AWG max. 5. Wiring for TB3 and TB4 is 18AWG min., 16 AWG max.
Figure 4 SIM-16 Relay Connections

SIM-16

TB4

COM 6

TB3

Programmable Relay 2

N.C. 5

6

N.O. 4

Programmable Relay 1

COM 3 N.C. 2 N.O. 1

1 16 15 14 13 12 11 10 9 87654321

TB2

ELECTRICAL RATINGS
Siemens Industry, Inc. Building Technologies Division

24V Back Plane Current

0

Screw Terminal 24V Current

20mA +1.2mA / supervised input
+20mA / active relay

6.2V Back Plane Current

0

24V Standby Current

20mA +1.2mA / supervised input
+20mA / active relay

Output Power

CAN Network Pair

8V peak to peak max.
75mA max. (during msg transmission)

3

firealarmresources.com

P/N 315-034060-6

NOTES 1. All inputs supervised. 2. All inputs power limited to
NFPA 70 per NEC 760. 3. Wiring for TB1 and TB2 is 18
AWG min., 12 AWG max. 4. Maximum distance 500 feet
from SIM-16 to supervised input. 5. In the Zeus Programming Tool, select supervised for each supervised input. 6. Supervised and unsupervised inputs may be mixed on a single SIM-16. 7. Inputs #1 - 16 are programmable.
Figure 5 SIM-16 Supervised Input Wiring

TYPICAL *6.8K CONNECTION
(16 PLACES)
*SUPPLIED WITH THE SIM-16

TB1

12345678 9 10 11 12 13 14 15 16

INPUT #5

INPUT #2 INPUT #6

INPUT #9

SIM-16
16 15 14 13 12 11 10 9 87654321
TB2

INPUT #16

NOTES 1. All inputs unsupervised. 2. All inputs power limited to
NFPA 70 per NEC 760. 3. Wiring for TB1 and TB2 is 18
AWG min., 12 AWG max. 4. All inputs must remain
inside the enclosure or within 20 feet in rigid conduit. 5. In the Zeus Programming Tool, select unsupervised for each unsupervised input. 6. Supervised and unsupervised inputs may be mixed on a single SIM-16. 7. Inputs #1 - 16 are programmable.
Figure 6 SIM-16 Unsupervised Input Wiring

TYPICAL CONNECTION (16 PLACES)

INPUT #1

INPUT #2

INPUT #5

TB1

12345678 9 10 11 12 13 14 15 16

INPUT #6

INPUT #9

SIM-16
16 15 14 13 12 11 10 9 87654321
TB2 INPUT #16

For CE applications in Cerberus E100 systems refer to Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).

Siemens Industry, Inc. Building Technologies Division Florham Park, NJ

Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada

Siemens Gebäudesicherheit GmbH & Co. oHG D-80930 München

P/N 315-034060-6

firealarmresources.com

