INSTALLATION INSTRUCTIONS

Merit® Series 13ACD Units

AIR CONDITIONER UNITS

Model: 505,366M

Date: 01/08

Supersedes: 11/07

Table of Contents

Shipping and Packing List

Check the unit for shipping damage and ensure all listed items are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.

The 13ACD Air Conditioners, referred to as the outdoor unit, use HCFC-22 refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox 13ACD Engineering Handbook.

This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:

Unit Dimensions

Diagram showing unit dimensions A and B. Dimension A is the width, and Dimension B is the depth. Measurements are provided in inches and millimeters.

Model NumberAB
13ACD-01824-1/4 (616)25-1/4 (641)
13ACD-02424-1/4 (616)25-1/4 (641)
13ACD-03024-1/4 (616)33-1/4 (845)
13ACD-03624-1/4 (616)33-1/4 (845)
13ACD-04228-1/4 (718)29-1/4 (743)
13ACD-04828-1/4 (718)37-1/4 (946)
13ACD-06028-1/4 (718)33-1/4 (845)

⚠️ WARNING

This product and/or the indoor unit it is matched with may contain fiberglass wool. Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.

Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379-9900

General Information

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.

Torque Requirements

When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.

PartRecommended Torque
Service valve cap8 ft.- lb.11 NM
Sheet metal screws16 in.- lb.2 NM
Machine screws #1028 in.- lb.3 NM
Compressor bolts90 in.- lb.10 NM
Gauge port seal cap8 ft.- lb.11 NM

Using Manifold Gauge Sets

When checking the system charge, use a manifold gauge set that features low-loss anti-blow back fittings. See Figure 1 for a typical manifold gauge connection setup.

Operating Service Valves

The liquid and suction line service valves are typically used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.

❗ IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc - Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess. Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.

Figure 1. Typical Manifold Gauge Connection Setup

This diagram illustrates the connection of a gauge manifold to the outdoor unit's service valves, showing connections for liquid line, suction line, compressor, and a refrigerant drum. Each valve is equipped with a service port which has a factory-installed valve stem.

Operating Angle-Type Service Valve

To Access Angle-Type Service Port:

A service port cap protects the service port core from contamination and serves as the primary leak seal.

  1. Remove service port cap with an appropriately sized wrench.
  2. Connect gauge to the service port.
  3. When testing is completed, replace service port cap and tighten as follows:
    • With Torque Wrench: Finger tighten and then tighten per Table 1.
    • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in Figure 2.

To Open and Close Angle-Type Service Valve:

A valve stem cap protects the valve stem from contamination and assures a leak-free seal.

  1. Remove stem cap with an appropriately sized wrench.
  2. Use a service wrench with a hex-head extension (3/16" for liquid-line valve sizes and 5/16" for suction-line valve sizes) to back the stem out counterclockwise as far as it will go.
  3. Replace the stem cap and tighten as follows:
    • With Torque Wrench: Tighten finger tight and then tighten per Table 1.
    • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in Figure 2.

NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.

NOTE - To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap.

Figure 2. Cap Tightening Distances: Illustrates the amount of turn (1/6 turn and 1/12 turn) for tightening caps without a torque wrench.

Figure 3. Angle-Type Service Valve (Font-Seated Closed): Diagram showing the angle-type service valve in a closed position, indicating the service port cap and valve stem cap.

Figure 4. Angle-Type Service Valve (Back-Seated Opened): Diagram showing the angle-type service valve in an opened position.

Operating Ball-Type Service Valve

To Access Ball-Type Service Port:

A service port cap protects the service port core from contamination and serves as the primary leak seal.

  1. Remove service port cap with an appropriately sized wrench.
  2. Connect gauge to the service port.
  3. When testing is completed, replace service port cap and tighten as follows:
    • With Torque Wrench: Finger tighten and then tighten per Table 1.
    • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise as illustrated in Figure 2.

To Open and Close Ball-Type Service Valve:

A valve stem cap protects the valve stem from contamination and assures a leak-free seal.

  1. Remove stem cap with a wrench.
  2. Use an appropriately sized wrench to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
  3. Replace the stem cap and tighten as follows:
    • With Torque Wrench: Finger tighten and then tighten per Table 1.
    • Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise as illustrated in Figure 2.

NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.

Figure 5. Ball-Type Service Valve: Diagram showing the ball-type service valve in a closed position, indicating the service port cap and valve stem cap.

Recovering Refrigerant from Existing System

Remove existing HCFC-22 refrigerant using one of the following methods:

METHOD 1:

Use this method if the existing outdoor unit is not equipped with manual shut-off valves, and plan on using existing HCFC-22 refrigerant to flush the system.

NOTE - Use recovery machine instructions for specific setup requirements.

Perform the following task:

  1. Disconnect all power to the existing outdoor unit.
  2. Connect to the existing unit a gauge set, clean recovery cylinder and a recovery machine. Use the instructions provided with the recover machine on how to setup the connections.
  3. Remove all HCFC-22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.

Figure 6. Typical Refrigerant Recovery (Method 1): Diagram showing a typical refrigerant recovery setup using a recovery machine, manifold gauges, and a clean recovery cylinder connected to the outdoor unit.

METHOD 2:

Use this method if the existing outdoor unit is equipped with manual shut-off valves, and plan on using new HCFC-22 refrigerant to flush the system.

IMPORTANT

Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:

Once the compressor cannot pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to the unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.

Perform the following task:

  1. Start the existing HCFC-22 system in the cooling mode and close the liquid line valve.
  2. Pump as much of the existing HCFC-22 refrigerant with the compressor back into the outdoor unit until you have reached the limitations of the outdoor system. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant in the system.

NOTE - It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.

  1. When the low side system pressures reach 0 psig, close the suction line valve.
  2. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.

Removing Existing Outdoor Unit

Perform the following task at the existing outdoor unit:

Positioning New Outdoor Unit

See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to Figure 7 for mandatory installation clearance requirements.

Figure 7. Installation Clearances: Diagram illustrating required clearances around the outdoor unit for service access and airflow. Notes specify minimum clearances for different sides, top, and between units.

POSITIONING CONSIDERATIONS

⚠️ CAUTION

In order to avoid injury, take proper precaution when lifting heavy objects.

Consider the following when positioning the unit:

Figure 8. Outside Unit Placement: Illustration showing how to position the unit away from windows and indicating that two 90° elbows installed in the line set will reduce line set vibration.

Placing Outdoor Unit on Slab

When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in Figure 9.

Figure 9. Ground Level Slab Mounting: Diagram showing a unit placed on a slab above ground level, with a building structure in the background. It illustrates proper slab elevation to prevent water collection.

Slab may be level or have a slope tolerance away from the building of not more than two degrees, or two inches per 5 feet (51 mm per 1524 mm) as illustrated in Figure 9.

Installing Outdoor Unit on Roof

Install the unit a minimum of six inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.

New or Replacement Line Set

This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on page 8.

If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings, floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.

Also, consider the following when placing and installing a high-efficiency air conditioner:

REFRIGERANT LINE SET

Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non-flare) series line set, or use field-fabricated refrigerant lines as listed in Table 2.

ModelField ConnectionsRecommended Line Set
Liquid LineSuction LineLiquid LineSuction LineL15 Line SetsField Fabricated
-0183/8 in. (10 mm)3/4 in (19 mm)3/8 in. (10 mm)3/4 in (19 mm)L15-41
15 ft. - 50 ft.
(4.6 m - 15 m)
-024
-0303/8 in. (10 mm)7/8 in (22 mm)3/8 in. (10 mm)7/8 in (22 mm)L15-65
15 ft. - 50 ft.
(4.6 m - 15 m)
-036
-042
-048
-0603/8 in. (10 mm)1-1/8 in. (29 mm)3/8 in. (10 mm)1-1/8 in. (29 mm)Field Fabricated

NOTE - When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:

MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET

The RFC1-metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.

If the 13ACD is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 13ACD unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.

Line Set Isolation

This reference illustrates procedures which ensure proper refrigerant line set isolation:

Line set for heat pump applications can not be installed underground. For more information see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance.

Figure 10. Refrigerant Line Set: Installing Horizontal Runs: Diagram showing methods for isolating horizontal refrigerant lines using metal strapping, anchored heavy nylon wire ties, and sleeves to prevent contact with structural elements and reduce vibration.

Figure 11. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown): Diagram illustrating vertical line set installation with isolation techniques, including using sleeves, wood blocks, and straps to prevent contact with walls and studs.

Figure 12. Refrigerant Line Set: Transition from Vertical to Horizontal: Diagram showing how to transition a refrigerant line set from a vertical to a horizontal run, using metal sleeves and straps for isolation and vibration reduction.

Brazing Connections

Use the following procedure to braze the line set to the new outdoor unit. Figure 13 is provided as a general guide for preparing to braze the line set to the outdoor unit.

⚠️ WARNING

Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before unbrazing.

⚠️ WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

  1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
  2. Remove service cap and core from both the suction and liquid line service ports.
  3. Connect gauge low pressure side to liquid line service valve.
  4. To protect components during brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint.
  5. Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the suction service valve. The TXV metering device at the indoor unit coil will allow low pressure nitrogen to flow through the system.

NOTE - The fixed orifice or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.

NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing.

  1. Braze the line to the liquid line service valve. Turn off nitrogen flow.

❗ IMPORTANT

Repeat procedure starting at paragraph 4 for brazing the suction line to service port valve.

  1. After all connections have been brazed, disconnect manifold gauge set from the service ports and remove wrapping. Reinstall the service port core for both of the outdoor unit's service valves.

Figure 13. Brazing Connections: A step-by-step visual guide to brazing refrigerant lines, showing cutting and deburring, removing valve cores, attaching gauges, wrapping with wet cloths, flowing nitrogen, brazing, and final checks.

Removing Indoor Unit Metering Device

Remove the existing HCFC-22 refrigerant flow control orifice or thermal expansion valve from the indoor coil.

REPLACEMENT PARTS

If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes:

Figure 14. 69J46 Kit Components: Diagram showing the components included in the 69J46 replacement kit for indoor metering devices, such as brass nuts, Teflon rings, and liquid line assemblies.

TYPICAL TXV REMOVAL PROCEDURE

Figure 16. Typical TXV Removal: Diagram illustrating the removal of a Thermal Expansion Valve (TXV) from an uncased coil, showing the liquid line assembly, equalizer line, sensing line, and distributor tubes.

  1. On fully cased coils, remove the coil access and plumbing panels.
  2. Remove any shipping clamps holding the liquid line and distributor assembly.
  3. Disconnect the equalizer line from the TXV equalizer line fitting on the suction line.
  4. Remove the suction line sensing bulb as illustrated in Figure 16.
  5. Disconnect the liquid line from the TXV at the liquid line assembly.
  6. Disconnect the TXV from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
  7. Remove and discard TXV and the two Teflon rings as illustrated in Figure 16.

TYPICAL FIXED ORIFICE REMOVAL PROCEDURE

Figure 15. Typical Fixed Orifice Removal: Diagram illustrating the removal of a fixed orifice metering device from an uncased coil, showing the liquid line orifice housing, Teflon ring, and fixed orifice.

  1. On fully cased coils, remove the coil access and plumbing panels.
  2. Remove any shipping clamps holding the liquid line and distributor assembly.
  3. Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
  4. Remove and discard fixed orifice, valve stem assembly if present and Teflon ring as illustrated in Figure 15.

Installing New Indoor Unit Metering Device

13ACD units can be configured for use with HCFC-22 fixed orifice or TXV metering devices. This section provides instructions on installing either a fixed orifice or TXV refrigerant metering device.

Figure 17. Tightening Distance: Illustrates the amount of turn (1/8 turn and 1/2 turn) for tightening components, referencing torque specifications.

Typical Fixed Orifice Installation Procedure

  1. Install the provided RFC orifice that was supplied with the outdoor unit as illustrated in Figure 18.
  2. Ensure that the fixed orifice supplied with the outdoor unit is installed with the nylon seat pointing toward the liquid line orifice housing.
  3. Apply a small amount of refrigerant oil on the Teflon ring and insert securely into the liquid line orifice housing.
  4. Attach the liquid line assembly to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in Figure 17, or 20 ft-lb.
  5. Place the supplied fixed orifice sticker on the indoor cabinet after installation.

Figure 18. Typical Fixed Orifice Installation: Diagram showing the installation of a fixed orifice into the liquid line orifice housing, including the Teflon washer and liquid line assembly.

ModelCatalog NumberPart NumberDrill Size
01810W95100484-070.055
02498M12100484-120.062
03011W00100484-160.067
03698M78100484-240.076
04210W86100484-280.080
04898M14100484-360.089
06098M15100484-450.099

Use the Lennox catalog number to order a new or replacement fixed orifice kit.

The kit includes:

Figure 19. Fixed Orifice Kit Components: Diagram showing the components of a fixed orifice kit, including the extractor, Teflon ring, and sticker.

Typical TXV Installation Procedure

The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the TXV in a manner that will provide access for field servicing of the TXV. Refer to Figure 20 for reference during installation of TXV unit.

  1. Install one of the provided Teflon rings around the stubbed end of the TXV and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
  2. Attach the stubbed end of the kit valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in Figure 17, or 20 ft-lb.
  3. Place the remaining Teflon washer around the other end of the TXV. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
  4. Attach the liquid line assembly to the TXV. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in Figure 17, or 20 ft-lb.
  5. Attach the suction line sensing bulb in the proper orientation as illustrated in Figure 21 using the clamp and screws provided.

NOTE - Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.

Figure 20. Typical TXV Installation: Diagram illustrating the installation of a TXV, showing connections for liquid line, suction line, equalizer line, and sensing bulb.

Figure 21. TXV Sensing Bulb Installation: Diagrams showing correct placement of the sensing bulb on suction lines of different diameters, emphasizing not to mount on the bottom of the line.

Figure 22. Copper Flare Seal Bonnet Removal: Diagram illustrating the removal of a flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port.

  1. Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the suction line as illustrated in Figure 22.
  2. Connect the equalizer line from the TXV to the equalizer suction port on the suction line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated in Figure 17.

❗ IMPORTANT

When removing the brass nut, ensure that the copper flare seal bonnet is removed.

NOTE - To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.

ModelCatalog NumberPart Number
-018, -024, -030 and -03626K34LB-85663J
-042, -048 and -06026K35LB-85663k

Use the Lennox catalog number to order a TXV kit.

The above reference kits include:

Figure 23. TXV Kit Components: Diagram showing the components of a TXV kit, including the TXV, Teflon rings, mounting strap, and hardware.

Testing for Leaks

❗ IMPORTANT

Leak detector must be capable of sensing HFC refrigerant.

⚠️ WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death.

⚠️ WARNING

Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in personal injury or death.

After the line set has been connected to both the indoor and outdoor units, check the line set connections at both the indoor and outdoor units unit for leaks. Use the following procedure to test for leaks:

  1. Connect an HCFC-22 manifold gauge set high pressure hose to the suction valve service port.

NOTE - Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.

  1. With both manifold valves closed, connect the cylinder of HCFC-22 refrigerant to the center port of the manifold gauge set. Open the valve on the HCFC-22 cylinder (suction only).
  2. Open the high pressure side of the manifold to allow HCFC-22 into the line set and indoor unit.
  3. Weigh in a trace amount of HCFC-22. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure].
  4. Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set.
  5. Disconnect the HCFC-22 cylinder.
  6. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

NOTE - Amounts of refrigerant will vary with line lengths.

  1. Adjust dry nitrogen pressure to 150 psig (1034 kPa).
  2. Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.
  3. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector.
  4. Check all joints for leaks.
  5. Purge dry nitrogen and HFC-410A mixture.
  6. Correct any leaks and recheck.
  7. After leak testing disconnect gauges from service ports.

Evacuating the System

⚠️ WARNING

Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.

❗ IMPORTANT

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.

Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.

  1. Connect manifold gauge set to the service valve ports as follows:
    • low pressure gauge to suction line service valve
    • high pressure gauge to liquid line service valve
  2. Connect micron gauge.
  3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
  4. Open both manifold valves and start the vacuum pump.
  5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).

NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure; this indicates a relatively large leak. If this occurs, repeat the leak testing procedure.

NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

  1. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.

Servicing Unit Delivered Void of Charge

If the system is void of refrigerant, clean the system using the procedure described below.

  1. Use nitrogen to pressurize the system and check for leaks. Repair all leaks.
  2. Evacuate the system to remove as much of the moisture as possible.
  3. Use nitrogen to break the vacuum and install a new filter drier in the system.
  4. Evacuate the system again. Then, weigh the appropriate amount of HCFC-22 refrigerant as listed on unit nameplate into the system.
  5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not verified, the compressor will fail in the future.

Electrical Connections

⚠️ WARNING

Electric Shock Hazard. Can cause injury or death. Line voltage is present at all components on units with single-pole contactors, even when unit is not in operation! Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel. Unit must be grounded in accordance with national and local codes.

Figure 24. Typical Wiring Diagram: This diagram shows the electrical connections for the outdoor unit, including components like the compressor, outdoor fan, contactor, and various switches, along with power supply and thermostat connections.

Refer to the indoor unit installation instruction for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. Figures 26 and 24 illustrate typical outdoor unit wiring diagrams for the 13ACD series heat pumps.

Wiring Connections

  1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring.
  2. Ground unit at unit disconnect switch or to an earth ground.
  3. Connect conduit to the unit using provided conduit bushing.
  4. Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and five feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight, drafts or vibrations.

NOTE - For proper voltages, select thermostat wire gauge per the following table:

Wire run lengthAWG #Insulation type
Less than 100 feet (30 m)18Color-coded with a minimum temperature rating of 35°C.
More than 100 feet (30 m)16

Figure 25. Separating High/Low Voltage Field Wiring (Typical Field Wiring): Diagram showing how to properly separate and secure high voltage and low voltage field wiring to prevent interference and ensure safety.

  1. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated in Figures 26 and 24.
  2. Do not bundle any excess 24VAC control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provided low voltage strain relief and to maintain separation of field installed low and high voltage circuits.

NOTE - 24VAC, Class II circuit connections are made in the low voltage junction box.

NOTE - Units are approved for use only with copper conductors.

NOTE - To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.

NOTE - See unit wiring diagram for power supply connections. If indoor unit is not equipped with blower relay, it must be field-provided and installed (P-8-3251 or equivalent).

Figure 26. Typical Field Low Voltage Wiring: Diagram illustrating the typical low voltage wiring connections between the thermostat, indoor unit, and outdoor unit.

Start-Up and Charging Procedures

❗ IMPORTANT

If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

  1. Rotate fan to check for binding.
  2. Inspect all factory- and field-installed wiring for loose connections.
  3. After evacuation is complete, open the liquid line and suction line service valves to release the refrigerant charge (contained in outdoor unit) into the system.
  4. Replace the stem caps and tighten as specified in Operating Service Valves on page 2.
  5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
  6. Set the thermostat for a cooling demand. Turn on power to the indoor unit and close the outdoor unit disconnect switch to start the unit.
  7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
  8. Check system for sufficient refrigerant by using the procedures listed under Testing and Charging System.

SETTING UP TO CHECK CHARGE

  1. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HCFC-22.
  2. Connect the manifold gauge set to the unit's service ports as illustrated in Figure 1.
    • low pressure gauge to suction service port
    • high pressure gauge to liquid service port

INDOOR AIRFLOW CHECK

Check airflow using the Delta-T (DT) process using the illustration in Figure 27.

DETERMINING CHARGE METHOD

Use the illustration in Figure 28 to determine the correct charging method.

Figure 27. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart: A chart and procedure for determining proper indoor airflow by measuring dry-bulb and wet-bulb temperatures and calculating the Delta-T. It includes steps for determining desired DT, measuring temperature drop, and adjusting fan speed.

Figure 28. Determining Charge Method: A flowchart guiding the user to select the appropriate charging method (Subcooling TXV, Approach TXV, Weigh-In RFC, or Superheat RFC) based on the metering device type and outdoor ambient temperature.

Weigh In TXV/RFC

Refrigerant Charge per Line Set Length

Liquid Line Set DiameterOunces per 5 feet (g per 1.5 m) adjust from 15 feet (4.6 m) line set*
3/8" (9.5 mm)3 ounce per 5' (85 g per 1.5 m)

NOTE - *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.

Figure 29. HCFC-22 Weigh In TXV Method: Illustrates the weigh-in method for charging TXV/RFC systems, referencing the unit nameplate for charge information and providing a table for line set length adjustments.

Subcooling TXV Charge

START: Measure outdoor ambient temperature

USE WEIGH-IN METHOD

Weigh-in or remove refrigerant based upon line length

BELOW

ABOVE

Outdoor Ambient 65°F (18°C)?

SUBCOOLING TXV

If refrigerant added or removed, verify charge using the approach method

If value is greater than shown, remove refrigerant; if less than shown, add refrigerant

BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 200-250 psig (1379-1724 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.

SC° (Subcooling) Values (F:+/-1.0° [C: +/-0.6°])-018-024-030-036-042-048-060
°F (°C)*Liquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / Suction
Any7 (3.8)12 (6.7)9 (5)10 (5.6)14 (8)10 (5.6)13 (7.2)

*Temperature of air entering outdoor coil

Figure 30. HCFC-22 Subcooling TXV Charge: Provides steps and a table for charging a TXV system using the subcooling method, including measuring outdoor ambient temperature, liquid line temperature, and pressure.

  1. Confirm proper airflow across coil using Figure 27.
  2. Compare unit pressures with Table 6, Normal Operating Pressures.
  3. Use SUBCOOLING to correctly charge unit or to verify the charge is correct.
  4. Set thermostat to call for heat (must have a cooling load between 70-80°F (21-26°C).
  5. Connect gauge set.
  6. Measure outdoor ambient temperature.
  7. When heat demand is satisfied, set thermostat to call for cooling.
  8. Allow temperatures and pressures to stabilize.
  9. NOTE - If necessary, block outdoor coil to maintain 325-375 psig.
  10. Record line temperature: LIQ° =
  11. Measure liquid line pressure and use the value to determine saturation temperature: SAT° =
  12. Subtract to determine subcooling (SC°): SAT° - LIQ° = SC°
  13. Compare results with table to the left.

Approach TXV Charge

START: Measure outdoor ambient temperature

USE WEIGH-IN METHOD

Weigh-in or remove refrigerant based upon line length

BELOW

ABOVE

Outdoor Ambient 65°F (18°C)?

APPROACH TXV

If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temp too close to ambient temp, low approach), remove refrigerant.

If refrigerant added or removed, retest to confirm that unit is properly charged

APP° (Approach) Values (F:+/-1.0° [C: +/-0.6°])-018-024-030-036-042-048-060
°F (°C)*Liquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / Suction
Any6 (3.3)6 (3.3)8 (4.4)12 (6.7)5 (2.8)6 (3.3)7 (3.8)

*Temperature of air entering outdoor coil

Figure 31. HCFC-22 Approach TXV Charge: Provides steps and a table for charging a TXV system using the approach method, including measuring outdoor ambient temperature, liquid line temperature, and pressure.

  1. Confirm proper airflow across coil using Figure 27.
  2. Compare unit pressures with Table 6, Normal Operating Pressures.
  3. Use APPROACH to correctly charge unit or to verify the charge is correct.
  4. Set thermostat to call for heat (must have a cooling load between 70-80°F (21-26°C).
  5. Connect gauge set.
  6. When heat demand is satisfied, set thermostat to call for cooling.
  7. Allow temperatures and pressures to stabilize.
  8. Record outdoor ambient temperature: AMB° =
  9. Record line temperature: LIQ° =
  10. Subtract to determine approach (APP°): LIQ° - AMB° = APP°
  11. Compare results with table to the left.

Superheat RFC Charge

START: Measure outdoor ambient temperature

USE WEIGH-IN METHOD

Weigh-in or remove refrigerant based upon line length

BELOW

ABOVE

Outdoor Ambient 40°F (4°C)?

SUPERHEAT RFC

If refrigerant added or removed, retest to confirm that unit is properly charged

If value is greater than shown, add refrigerant; if less than shown, remove refrigerant.

SH° (Superheat) Values (+/-5°F)5052545658606264666870727476
Wet Bulb (air entering indoor coil) °F*
401518202326293234384143464851
451316182124273033363941444649
501114161922252831343739424447
55912141720232730333638404244
60710121518212427303335384043
656101316192124273033363841
7071013161921242730333639
7569121518212428313437
80581215182125283135
8581115182125283135
9059131620242731
956101418222529
10081216212428
1055913172226
110611152025
1158141824

* Dry-bulb temperature (°F) of entering outdoor ambient air.

Figure 32. HCFC-22 Superheat RFC Charge: Provides steps and a table for charging an RFC system using the superheat method, including measuring outdoor ambient temperature, suction line pressure, and suction line temperature.

  1. Confirm proper airflow across coil using Figure 27.
  2. Compare unit pressures with Table 6, Normal Operating Pressures.
  3. Use SUPERHEAT to correctly charge unit or to verify the charge is correct.
  4. Set thermostat to call for heat (must have a cooling load between 70-80°F (21-26°C).
  5. Connect gauge set.
  6. When heat demand is satisfied, set thermostat to call for cooling.
  7. Allow temperatures and pressures to stabilize.
  8. Measure the suction line pressure and use the use value to determine saturation temperature: SAT° =
  9. Record suction line temperature: VAP° =
  10. Subtract to determine superheat (SH°): VAP° - SAT° = SH°
  11. Record the wet bulb temperature (air entering indoor coil): WB =
  12. Record outdoor ambient temperature.
  13. Compare results with table to the left.

NOTE - Do not attempt to charge system where a dash appears, system could be overcharged. Superheat is taken at suction line service port. Suction line superheat must never be less than 5°F at the suction line service port.

Normal Operating Pressures

❗ IMPORTANT

Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.

13ACD-018-024-030-036-042-048-060
°F (°C)*Liquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / SuctionLiquid / Suction
Expansion Valve (TXV)
65 (18)138/79148/79147/75155/79147/78144/77152/73
70 (21)148/80160/79159/75169/80158/78152/77164/75
75 (24)160/80174/80172/76183/81172/79163/78177/77
80 (27)174/81188/81186/77199/81189/79179/78192/78
85 (29)188/81203/81201/77215/82205/80195/79208/79
90 (32)204/81220/82216/78233/82222/81212/80225/80
95 (35)219/82236/83233/79252/83241/81229/80243/80
100 (38)236/82253/83250/80271/83259/82245/81261/81
105 (41)253/83272/84268/80291/84279/82265/81280/82
110 (43)272/84291/85287/81311/85299/83287/82299/83
115 (45)291/84311/85306/82331/86320/84309/83320/83
Fixed Orifice (RFC)
65 (18)139/67147/71148/65162/75158/72151/71152/68
70 (21)149/70159/73161/67174/76170/75161/73165/71
75 (24)161/74172/75175/70187/78182/76172/75178/73
80 (27)175/77186/77190/73201/79195/78185/76193/76
85 (29)189/79200/79205/75215/81209/80198/77208/78
90 (32)203/81216/81221/77231/82224/81213/79224/80
95 (35)218/82232/82237/79247/83240/82227/80239/81
100 (38)234/83247/83254/80265/84256/84243/81258/82
105 (41)251/85264/85271/81283/85273/85259/82276/83
110 (43)269/86285/86289/82302/86290/86276/84294/85
115 (45)287/87302/87308/83321/87310/87293/85313/86

Installing Service Valve Caps

Disconnect gauge set and re-install both the liquid and suction service valve caps.

Figure 33. Installing Service Valve Caps: Diagram showing the outdoor unit service valves and indicating where to install the caps after disconnecting the gauge set.

System Operation

The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.

Maintenance

⚠️ WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

⚠️ WARNING

Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.

At the beginning of each cooling season, the system should be checked as follows:

OUTDOOR UNIT

  1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
  2. Outdoor unit fan motor is pre-lubricated and sealed. No further lubrication is needed.
  3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
  4. Check all wiring for loose connections.
  5. Check for correct voltage at unit (unit operating).
  6. Check amp draw on outdoor fan motor.

UNIT NAMEPLATE: ACTUAL:

  1. Inspect drain holes in coil compartment base and clean if necessary.

NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.

INDOOR COIL

  1. Clean coil if necessary.
  2. Check connecting lines, joints and coil for evidence of oil leaks.
  3. Check condensate line and clean if necessary.

INDOOR UNIT

  1. Clean or change filters.
  2. Blower motors are prelubricated and permanently sealed. No more lubrication is needed.
  3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
  4. Belt Drive Blowers - Check belt for wear and proper tension.
  5. Check all wiring for loose connections.
  6. Check for correct voltage at unit. (blower operating)
  7. Check amp draw on blower motor.

UNIT NAMEPLATE: ACTUAL:

Figure 34. Cleaning debris from mesh: Diagram showing the mesh screen on the outdoor unit's coil guard, indicating the number of push pins used for different models, and illustrating how to remove debris.

❗ IMPORTANT

Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.

NOTE - A white residue may appear on the coil guards and grilles on outdoor units. The residue is a non-toxic byproduct of manufacturing the flexible coating. It can be removed by wiping the coil guard with a cloth.

Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:

  1. Make sure power is off before cleaning. Clean and inspect outdoor coil. The coil may be flushed with a water hose.
  2. The outdoor coil is protected by an inner mesh screen and a wire cage (see Figure 34). If debris has collected between the mesh screen and the coil and cannot be dislodged by spraying unpressurized water from inside coil surface to the outside, the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage.
  3. Then, using pliers to grip the head of the push pins, pull straight out to extract the push pins along one side of the coil. If necessary, remove the push pins along the back of the unit; it is usually unnecessary to fully remove the inner mesh screen.
  4. Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall the mesh screen by positioning it in its original position and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins.
  5. If the push pin is loose and tends not to stay in place, brush the fins with a fin brush (22 fins/in). Line up the push pin a couple fins to the right or left of the original hole and re-insert the pin.

Homeowner Information

⚠️ WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

Thermostat Operation

Thermostat operations vary from one thermostat to another. The following provides general operation procedures. Refer to the user's information manual provided with your thermostat for specific operation details.

Temperature Setting Levers

Set the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off-then back on-before pressures can equalize will put unusual stress on the unit's compressor.

Fan Switch

In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when constant air circulation or filtering is desired.

System Switch

Set the system switch for heating, cooling or auto operation. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings.

Temperature Indicator

The temperature indicator displays the actual room temperature.

PROGRAMMABLE THERMOSTATS

Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user's information manual provided with your thermostat for operation details.

Pre-Service Check

If your system fails to operate, check the following before calling for service:

Optional Accessories

Refer to the Lennox 13ACD Engineering Handbook for the latest available accessories for this unit. Below is a list of accessories available at the time this instruction was publish.

Optional AccessoryCatalog NumberPart Number
Compressor Start Kit10J42LB-31200BM
Loss of Charge Kit94J47LB-87620A
Sound Cover69J0369J0301
Replacement Liquid Line Drier12L7112L7101
Plastic Feet Kit94J45LB-87156A
Crankcase Heater - 40W93M04100499-01
High Pressure Kit94J46LB-87620A

Start-Up and Performance Checklist

Job Name:

Job Location:

Installer:

Unit Model No.:

Serial No.:

Nameplate Voltage:

Rated Load Ampacity: Compressor: Outdoor Fan:

Maximum Fuse or Circuit Breaker:

Electrical Connections Tight?

Indoor Filter clean?

Indoor Blower RPM:

S.P. Drop Over Indoor (Dry):

Discharge Pressure:

Suction Pressure:

Supply Voltage (Unit Off):

Outdoor Coil Entering Air Temp.:

Refrigerant Charge Checked?

Refrigerant Lines: Leak Checked?

Properly Insulated?

Outdoor Fan Checked?

Service Valves: --- Fully Opened?

Caps Tight?

Thermostat Calibrated? Properly Set? Level?

Voltage With Compressor Operating:

Job no.:

City:

State:

City:

State:

Date:

Service Technician:

PDF preview unavailable. Download the PDF instead.

Lennox 100484 07 Manual Goby Monitor Application version 4, 0, 0, 13

Related Documents

Preview Lennox C33/CX34 Series Evaporator Coils Installation Instructions
Detailed installation instructions for Lennox C33 and CX34 Series evaporator coils, covering unit installation, refrigerant line connections, metering device setup, static pressure testing, and maintenance.
Preview Lennox Merit Series CBA25UH & 13ACX Air Handler Installation Instructions
This document provides comprehensive installation instructions for Lennox Merit Series CBA25UH and 13ACX air handler units. It covers essential information such as safety warnings, required clearances, installation procedures, electrical connections, refrigerant piping, leak testing, evacuation, and start-up checks.
Preview Lennox Merit Series ML17KC2 Air Conditioner Installation Instructions
Comprehensive installation guide for the Lennox Merit Series ML17KC2 outdoor air conditioner, covering safety, clearances, refrigerant piping, electrical connections, and start-up procedures.
Preview Lennox ML14KP1 Merit Series Heat Pump Installation Instructions
Comprehensive installation guide for the Lennox ML14KP1 Merit Series Heat Pump, covering unit setup, refrigerant piping, electrical connections, start-up procedures, charging, and maintenance.
Preview Lennox Merit Series ML17XC1 Air Conditioner Installation Instructions
Comprehensive installation guide for the Lennox Merit Series ML17XC1 outdoor air conditioner, covering unit placement, refrigerant piping, electrical connections, and start-up procedures. Includes safety warnings, technical specifications, and maintenance tips.
Preview Lennox Merit Series CBK45UHVT Air Handler Installation Instructions
Comprehensive installation instructions for Lennox Merit Series CBK45UHVT Air Handler Units designed for R410A refrigerant. Covers unit overview, wiring diagrams, blower control and speed adjustment, electrical connections, requirements, dimensions, installation clearances, installation procedures for upflow, horizontal, and downflow applications, condensate drain setup, duct system and filters, refrigerant line brazing, unit sealing, check-out procedures, maintenance, and decommissioning. Includes safety warnings and important notes.
Preview Lennox Merit Series 13ACX Units Installation Instructions
Comprehensive installation guide for Lennox Merit Series 13ACX Air Conditioner Units, covering unit dimensions, parts, electrical connections, line set installation, refrigerant handling, leak testing, evacuation, and start-up procedures.
Preview Lennox ML296DFVK Gas Furnace Installation Instructions
This document provides comprehensive installation instructions for the Lennox ML296DFVK Merit Series Downflow Air Discharge gas furnace. It covers safety precautions, unit setup, venting, gas piping, electrical connections, and operational procedures.