Model: 505,366M
Date: 01/08
Supersedes: 11/07
Check the unit for shipping damage and ensure all listed items are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
The 13ACD Air Conditioners, referred to as the outdoor unit, use HCFC-22 refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox 13ACD Engineering Handbook.
This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:
Diagram showing unit dimensions A and B. Dimension A is the width, and Dimension B is the depth. Measurements are provided in inches and millimeters.
Model Number | A | B |
---|---|---|
13ACD-018 | 24-1/4 (616) | 25-1/4 (641) |
13ACD-024 | 24-1/4 (616) | 25-1/4 (641) |
13ACD-030 | 24-1/4 (616) | 33-1/4 (845) |
13ACD-036 | 24-1/4 (616) | 33-1/4 (845) |
13ACD-042 | 28-1/4 (718) | 29-1/4 (743) |
13ACD-048 | 28-1/4 (718) | 37-1/4 (946) |
13ACD-060 | 28-1/4 (718) | 33-1/4 (845) |
⚠️ WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool. Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379-9900
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure caps and fasteners are appropriately tightened. Table 1 lists torque values for typical service and repair items.
Part | Recommended Torque | |
---|---|---|
Service valve cap | 8 ft.- lb. | 11 NM |
Sheet metal screws | 16 in.- lb. | 2 NM |
Machine screws #10 | 28 in.- lb. | 3 NM |
Compressor bolts | 90 in.- lb. | 10 NM |
Gauge port seal cap | 8 ft.- lb. | 11 NM |
When checking the system charge, use a manifold gauge set that features low-loss anti-blow back fittings. See Figure 1 for a typical manifold gauge connection setup.
The liquid and suction line service valves are typically used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
❗ IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc - Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess. Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
This diagram illustrates the connection of a gauge manifold to the outdoor unit's service valves, showing connections for liquid line, suction line, compressor, and a refrigerant drum. Each valve is equipped with a service port which has a factory-installed valve stem.
A service port cap protects the service port core from contamination and serves as the primary leak seal.
A valve stem cap protects the valve stem from contamination and assures a leak-free seal.
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
NOTE - To prevent stripping of the cap, the wrench should be appropriately sized and fit snugly over the cap before tightening the cap.
Figure 2. Cap Tightening Distances: Illustrates the amount of turn (1/6 turn and 1/12 turn) for tightening caps without a torque wrench.
Figure 3. Angle-Type Service Valve (Font-Seated Closed): Diagram showing the angle-type service valve in a closed position, indicating the service port cap and valve stem cap.
Figure 4. Angle-Type Service Valve (Back-Seated Opened): Diagram showing the angle-type service valve in an opened position.
A service port cap protects the service port core from contamination and serves as the primary leak seal.
A valve stem cap protects the valve stem from contamination and assures a leak-free seal.
NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 5. Ball-Type Service Valve: Diagram showing the ball-type service valve in a closed position, indicating the service port cap and valve stem cap.
Remove existing HCFC-22 refrigerant using one of the following methods:
Use this method if the existing outdoor unit is not equipped with manual shut-off valves, and plan on using existing HCFC-22 refrigerant to flush the system.
NOTE - Use recovery machine instructions for specific setup requirements.
Perform the following task:
Figure 6. Typical Refrigerant Recovery (Method 1): Diagram showing a typical refrigerant recovery setup using a recovery machine, manifold gauges, and a clean recovery cylinder connected to the outdoor unit.
Use this method if the existing outdoor unit is equipped with manual shut-off valves, and plan on using new HCFC-22 refrigerant to flush the system.
IMPORTANT
Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets. The following conditions may cause the compressor to stop functioning:
Once the compressor cannot pump down to a lower pressure due to one of the above system conditions, shut off the suction valve. Turn OFF the main power to the unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
NOTE - It may be necessary to bypass the low pressure switches if equipped to ensure complete refrigerant evacuation.
Perform the following task at the existing outdoor unit:
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to Figure 7 for mandatory installation clearance requirements.
Figure 7. Installation Clearances: Diagram illustrating required clearances around the outdoor unit for service access and airflow. Notes specify minimum clearances for different sides, top, and between units.
⚠️ CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Consider the following when positioning the unit:
Figure 8. Outside Unit Placement: Illustration showing how to position the unit away from windows and indicating that two 90° elbows installed in the line set will reduce line set vibration.
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in Figure 9.
Figure 9. Ground Level Slab Mounting: Diagram showing a unit placed on a slab above ground level, with a building structure in the background. It illustrates proper slab elevation to prevent water collection.
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or two inches per 5 feet (51 mm per 1524 mm) as illustrated in Figure 9.
Install the unit a minimum of six inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on page 8.
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings, floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
Also, consider the following when placing and installing a high-efficiency air conditioner:
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non-flare) series line set, or use field-fabricated refrigerant lines as listed in Table 2.
Model | Field Connections | Recommended Line Set | ||||
---|---|---|---|---|---|---|
Liquid Line | Suction Line | Liquid Line | Suction Line | L15 Line Sets | Field Fabricated | |
-018 | 3/8 in. (10 mm) | 3/4 in (19 mm) | 3/8 in. (10 mm) | 3/4 in (19 mm) | L15-41 15 ft. - 50 ft. (4.6 m - 15 m) | |
-024 | ||||||
-030 | 3/8 in. (10 mm) | 7/8 in (22 mm) | 3/8 in. (10 mm) | 7/8 in (22 mm) | L15-65 15 ft. - 50 ft. (4.6 m - 15 m) | |
-036 | ||||||
-042 | ||||||
-048 | ||||||
-060 | 3/8 in. (10 mm) | 1-1/8 in. (29 mm) | 3/8 in. (10 mm) | 1-1/8 in. (29 mm) | Field Fabricated |
NOTE - When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
The RFC1-metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the 13ACD is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 13ACD unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
This reference illustrates procedures which ensure proper refrigerant line set isolation:
Line set for heat pump applications can not be installed underground. For more information see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance.
Figure 10. Refrigerant Line Set: Installing Horizontal Runs: Diagram showing methods for isolating horizontal refrigerant lines using metal strapping, anchored heavy nylon wire ties, and sleeves to prevent contact with structural elements and reduce vibration.
Figure 11. Refrigerant Line Set: Installing Vertical Runs (New Construction Shown): Diagram illustrating vertical line set installation with isolation techniques, including using sleeves, wood blocks, and straps to prevent contact with walls and studs.
Figure 12. Refrigerant Line Set: Transition from Vertical to Horizontal: Diagram showing how to transition a refrigerant line set from a vertical to a horizontal run, using metal sleeves and straps for isolation and vibration reduction.
Use the following procedure to braze the line set to the new outdoor unit. Figure 13 is provided as a general guide for preparing to braze the line set to the outdoor unit.
⚠️ WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture. Check the high and low pressures before unbrazing.
⚠️ WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
NOTE - The fixed orifice or TXV metering device at the indoor unit will allow low pressure nitrogen to flow through the system.
NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing or 45 percent silver alloy for copper-to-brass or copper-to-steel brazing.
❗ IMPORTANT
Repeat procedure starting at paragraph 4 for brazing the suction line to service port valve.
Figure 13. Brazing Connections: A step-by-step visual guide to brazing refrigerant lines, showing cutting and deburring, removing valve cores, attaching gauges, wrapping with wet cloths, flowing nitrogen, brazing, and final checks.
Remove the existing HCFC-22 refrigerant flow control orifice or thermal expansion valve from the indoor coil.
If replacement parts are necessary for the indoor unit, order kit 69J46. The kit includes:
Figure 14. 69J46 Kit Components: Diagram showing the components included in the 69J46 replacement kit for indoor metering devices, such as brass nuts, Teflon rings, and liquid line assemblies.
Figure 16. Typical TXV Removal: Diagram illustrating the removal of a Thermal Expansion Valve (TXV) from an uncased coil, showing the liquid line assembly, equalizer line, sensing line, and distributor tubes.
Figure 15. Typical Fixed Orifice Removal: Diagram illustrating the removal of a fixed orifice metering device from an uncased coil, showing the liquid line orifice housing, Teflon ring, and fixed orifice.
13ACD units can be configured for use with HCFC-22 fixed orifice or TXV metering devices. This section provides instructions on installing either a fixed orifice or TXV refrigerant metering device.
Figure 17. Tightening Distance: Illustrates the amount of turn (1/8 turn and 1/2 turn) for tightening components, referencing torque specifications.
Figure 18. Typical Fixed Orifice Installation: Diagram showing the installation of a fixed orifice into the liquid line orifice housing, including the Teflon washer and liquid line assembly.
Model | Catalog Number | Part Number | Drill Size |
---|---|---|---|
018 | 10W95 | 100484-07 | 0.055 |
024 | 98M12 | 100484-12 | 0.062 |
030 | 11W00 | 100484-16 | 0.067 |
036 | 98M78 | 100484-24 | 0.076 |
042 | 10W86 | 100484-28 | 0.080 |
048 | 98M14 | 100484-36 | 0.089 |
060 | 98M15 | 100484-45 | 0.099 |
Use the Lennox catalog number to order a new or replacement fixed orifice kit.
The kit includes:
Figure 19. Fixed Orifice Kit Components: Diagram showing the components of a fixed orifice kit, including the extractor, Teflon ring, and sticker.
The TXV unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the TXV in a manner that will provide access for field servicing of the TXV. Refer to Figure 20 for reference during installation of TXV unit.
NOTE - Insulating the sensing bulb once installed may be required when the bulb location is external to the coil casing.
Figure 20. Typical TXV Installation: Diagram illustrating the installation of a TXV, showing connections for liquid line, suction line, equalizer line, and sensing bulb.
Figure 21. TXV Sensing Bulb Installation: Diagrams showing correct placement of the sensing bulb on suction lines of different diameters, emphasizing not to mount on the bottom of the line.
Figure 22. Copper Flare Seal Bonnet Removal: Diagram illustrating the removal of a flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port.
❗ IMPORTANT
When removing the brass nut, ensure that the copper flare seal bonnet is removed.
NOTE - To prevent any possibility of water damage, properly insulate all parts of the TXV assembly that may sweat due to temperature differences between the valve and its surrounding ambient temperatures.
Model | Catalog Number | Part Number |
---|---|---|
-018, -024, -030 and -036 | 26K34 | LB-85663J |
-042, -048 and -060 | 26K35 | LB-85663k |
Use the Lennox catalog number to order a TXV kit.
The above reference kits include:
Figure 23. TXV Kit Components: Diagram showing the components of a TXV kit, including the TXV, Teflon rings, mounting strap, and hardware.
❗ IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
⚠️ WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death.
⚠️ WARNING
Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in personal injury or death.
After the line set has been connected to both the indoor and outdoor units, check the line set connections at both the indoor and outdoor units unit for leaks. Use the following procedure to test for leaks:
NOTE - Normally, the high pressure hose is connected to the liquid line port; however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.
NOTE - Amounts of refrigerant will vary with line lengths.
⚠️ WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
❗ IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure; this indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE - The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
If the system is void of refrigerant, clean the system using the procedure described below.
⚠️ WARNING
Electric Shock Hazard. Can cause injury or death. Line voltage is present at all components on units with single-pole contactors, even when unit is not in operation! Unit may have multiple power supplies. Disconnect all remote electric power supplies before opening access panel. Unit must be grounded in accordance with national and local codes.
Figure 24. Typical Wiring Diagram: This diagram shows the electrical connections for the outdoor unit, including components like the compressor, outdoor fan, contactor, and various switches, along with power supply and thermostat connections.
Refer to the indoor unit installation instruction for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size. Figures 26 and 24 illustrate typical outdoor unit wiring diagrams for the 13ACD series heat pumps.
NOTE - For proper voltages, select thermostat wire gauge per the following table:
Wire run length | AWG # | Insulation type |
---|---|---|
Less than 100 feet (30 m) | 18 | Color-coded with a minimum temperature rating of 35°C. |
More than 100 feet (30 m) | 16 |
Figure 25. Separating High/Low Voltage Field Wiring (Typical Field Wiring): Diagram showing how to properly separate and secure high voltage and low voltage field wiring to prevent interference and ensure safety.
NOTE - 24VAC, Class II circuit connections are made in the low voltage junction box.
NOTE - Units are approved for use only with copper conductors.
NOTE - To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
NOTE - See unit wiring diagram for power supply connections. If indoor unit is not equipped with blower relay, it must be field-provided and installed (P-8-3251 or equivalent).
Figure 26. Typical Field Low Voltage Wiring: Diagram illustrating the typical low voltage wiring connections between the thermostat, indoor unit, and outdoor unit.
❗ IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
Check airflow using the Delta-T (DT) process using the illustration in Figure 27.
Use the illustration in Figure 28 to determine the correct charging method.
Figure 27. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart: A chart and procedure for determining proper indoor airflow by measuring dry-bulb and wet-bulb temperatures and calculating the Delta-T. It includes steps for determining desired DT, measuring temperature drop, and adjusting fan speed.
Figure 28. Determining Charge Method: A flowchart guiding the user to select the appropriate charging method (Subcooling TXV, Approach TXV, Weigh-In RFC, or Superheat RFC) based on the metering device type and outdoor ambient temperature.
Refrigerant Charge per Line Set Length
Liquid Line Set Diameter | Ounces per 5 feet (g per 1.5 m) adjust from 15 feet (4.6 m) line set* |
---|---|
3/8" (9.5 mm) | 3 ounce per 5' (85 g per 1.5 m) |
NOTE - *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Figure 29. HCFC-22 Weigh In TXV Method: Illustrates the weigh-in method for charging TXV/RFC systems, referencing the unit nameplate for charge information and providing a table for line set length adjustments.
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant based upon line length
BELOW
ABOVE
Outdoor Ambient 65°F (18°C)?
SUBCOOLING TXV
If refrigerant added or removed, verify charge using the approach method
If value is greater than shown, remove refrigerant; if less than shown, add refrigerant
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 200-250 psig (1379-1724 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.
SC° (Subcooling) Values (F:+/-1.0° [C: +/-0.6°]) | -018 | -024 | -030 | -036 | -042 | -048 | -060 |
---|---|---|---|---|---|---|---|
°F (°C)* | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction |
Any | 7 (3.8) | 12 (6.7) | 9 (5) | 10 (5.6) | 14 (8) | 10 (5.6) | 13 (7.2) |
*Temperature of air entering outdoor coil
Figure 30. HCFC-22 Subcooling TXV Charge: Provides steps and a table for charging a TXV system using the subcooling method, including measuring outdoor ambient temperature, liquid line temperature, and pressure.
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant based upon line length
BELOW
ABOVE
Outdoor Ambient 65°F (18°C)?
APPROACH TXV
If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temp too close to ambient temp, low approach), remove refrigerant.
If refrigerant added or removed, retest to confirm that unit is properly charged
APP° (Approach) Values (F:+/-1.0° [C: +/-0.6°]) | -018 | -024 | -030 | -036 | -042 | -048 | -060 |
---|---|---|---|---|---|---|---|
°F (°C)* | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction |
Any | 6 (3.3) | 6 (3.3) | 8 (4.4) | 12 (6.7) | 5 (2.8) | 6 (3.3) | 7 (3.8) |
*Temperature of air entering outdoor coil
Figure 31. HCFC-22 Approach TXV Charge: Provides steps and a table for charging a TXV system using the approach method, including measuring outdoor ambient temperature, liquid line temperature, and pressure.
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant based upon line length
BELOW
ABOVE
Outdoor Ambient 40°F (4°C)?
SUPERHEAT RFC
If refrigerant added or removed, retest to confirm that unit is properly charged
If value is greater than shown, add refrigerant; if less than shown, remove refrigerant.
SH° (Superheat) Values (+/-5°F) | 50 | 52 | 54 | 56 | 58 | 60 | 62 | 64 | 66 | 68 | 70 | 72 | 74 | 76 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Wet Bulb (air entering indoor coil) °F* | ||||||||||||||
40 | 15 | 18 | 20 | 23 | 26 | 29 | 32 | 34 | 38 | 41 | 43 | 46 | 48 | 51 |
45 | 13 | 16 | 18 | 21 | 24 | 27 | 30 | 33 | 36 | 39 | 41 | 44 | 46 | 49 |
50 | 11 | 14 | 16 | 19 | 22 | 25 | 28 | 31 | 34 | 37 | 39 | 42 | 44 | 47 |
55 | 9 | 12 | 14 | 17 | 20 | 23 | 27 | 30 | 33 | 36 | 38 | 40 | 42 | 44 |
60 | 7 | 10 | 12 | 15 | 18 | 21 | 24 | 27 | 30 | 33 | 35 | 38 | 40 | 43 |
65 | 6 | 10 | 13 | 16 | 19 | 21 | 24 | 27 | 30 | 33 | 36 | 38 | 41 | |
70 | 7 | 10 | 13 | 16 | 19 | 21 | 24 | 27 | 30 | 33 | 36 | 39 | ||
75 | 6 | 9 | 12 | 15 | 18 | 21 | 24 | 28 | 31 | 34 | 37 | |||
80 | 5 | 8 | 12 | 15 | 18 | 21 | 25 | 28 | 31 | 35 | ||||
85 | 8 | 11 | 15 | 18 | 21 | 25 | 28 | 31 | 35 | |||||
90 | 5 | 9 | 13 | 16 | 20 | 24 | 27 | 31 | ||||||
95 | 6 | 10 | 14 | 18 | 22 | 25 | 29 | |||||||
100 | 8 | 12 | 16 | 21 | 24 | 28 | ||||||||
105 | 5 | 9 | 13 | 17 | 22 | 26 | ||||||||
110 | 6 | 11 | 15 | 20 | 25 | |||||||||
115 | 8 | 14 | 18 | 24 |
* Dry-bulb temperature (°F) of entering outdoor ambient air.
Figure 32. HCFC-22 Superheat RFC Charge: Provides steps and a table for charging an RFC system using the superheat method, including measuring outdoor ambient temperature, suction line pressure, and suction line temperature.
NOTE - Do not attempt to charge system where a dash appears, system could be overcharged. Superheat is taken at suction line service port. Suction line superheat must never be less than 5°F at the suction line service port.
❗ IMPORTANT
Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
13ACD | -018 | -024 | -030 | -036 | -042 | -048 | -060 | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
°F (°C)* | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | Liquid / Suction | |||||||
Expansion Valve (TXV) | ||||||||||||||
65 (18) | 138/79 | 148/79 | 147/75 | 155/79 | 147/78 | 144/77 | 152/73 | |||||||
70 (21) | 148/80 | 160/79 | 159/75 | 169/80 | 158/78 | 152/77 | 164/75 | |||||||
75 (24) | 160/80 | 174/80 | 172/76 | 183/81 | 172/79 | 163/78 | 177/77 | |||||||
80 (27) | 174/81 | 188/81 | 186/77 | 199/81 | 189/79 | 179/78 | 192/78 | |||||||
85 (29) | 188/81 | 203/81 | 201/77 | 215/82 | 205/80 | 195/79 | 208/79 | |||||||
90 (32) | 204/81 | 220/82 | 216/78 | 233/82 | 222/81 | 212/80 | 225/80 | |||||||
95 (35) | 219/82 | 236/83 | 233/79 | 252/83 | 241/81 | 229/80 | 243/80 | |||||||
100 (38) | 236/82 | 253/83 | 250/80 | 271/83 | 259/82 | 245/81 | 261/81 | |||||||
105 (41) | 253/83 | 272/84 | 268/80 | 291/84 | 279/82 | 265/81 | 280/82 | |||||||
110 (43) | 272/84 | 291/85 | 287/81 | 311/85 | 299/83 | 287/82 | 299/83 | |||||||
115 (45) | 291/84 | 311/85 | 306/82 | 331/86 | 320/84 | 309/83 | 320/83 | |||||||
Fixed Orifice (RFC) | ||||||||||||||
65 (18) | 139/67 | 147/71 | 148/65 | 162/75 | 158/72 | 151/71 | 152/68 | |||||||
70 (21) | 149/70 | 159/73 | 161/67 | 174/76 | 170/75 | 161/73 | 165/71 | |||||||
75 (24) | 161/74 | 172/75 | 175/70 | 187/78 | 182/76 | 172/75 | 178/73 | |||||||
80 (27) | 175/77 | 186/77 | 190/73 | 201/79 | 195/78 | 185/76 | 193/76 | |||||||
85 (29) | 189/79 | 200/79 | 205/75 | 215/81 | 209/80 | 198/77 | 208/78 | |||||||
90 (32) | 203/81 | 216/81 | 221/77 | 231/82 | 224/81 | 213/79 | 224/80 | |||||||
95 (35) | 218/82 | 232/82 | 237/79 | 247/83 | 240/82 | 227/80 | 239/81 | |||||||
100 (38) | 234/83 | 247/83 | 254/80 | 265/84 | 256/84 | 243/81 | 258/82 | |||||||
105 (41) | 251/85 | 264/85 | 271/81 | 283/85 | 273/85 | 259/82 | 276/83 | |||||||
110 (43) | 269/86 | 285/86 | 289/82 | 302/86 | 290/86 | 276/84 | 294/85 | |||||||
115 (45) | 287/87 | 302/87 | 308/83 | 321/87 | 310/87 | 293/85 | 313/86 |
Disconnect gauge set and re-install both the liquid and suction service valve caps.
Figure 33. Installing Service Valve Caps: Diagram showing the outdoor unit service valves and indicating where to install the caps after disconnecting the gauge set.
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
⚠️ WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
⚠️ WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
At the beginning of each cooling season, the system should be checked as follows:
UNIT NAMEPLATE: ACTUAL:
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
UNIT NAMEPLATE: ACTUAL:
Figure 34. Cleaning debris from mesh: Diagram showing the mesh screen on the outdoor unit's coil guard, indicating the number of push pins used for different models, and illustrating how to remove debris.
❗ IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
NOTE - A white residue may appear on the coil guards and grilles on outdoor units. The residue is a non-toxic byproduct of manufacturing the flexible coating. It can be removed by wiping the coil guard with a cloth.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
⚠️ WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Thermostat operations vary from one thermostat to another. The following provides general operation procedures. Refer to the user's information manual provided with your thermostat for specific operation details.
Set the lever or dial to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature adjustment; turning the unit off-then back on-before pressures can equalize will put unusual stress on the unit's compressor.
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or furnace is operating. This mode is required when constant air circulation or filtering is desired.
Set the system switch for heating, cooling or auto operation. The auto mode allows the system to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings.
The temperature indicator displays the actual room temperature.
Your Lennox system may be controlled by a programmable thermostat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user's information manual provided with your thermostat for operation details.
If your system fails to operate, check the following before calling for service:
Refer to the Lennox 13ACD Engineering Handbook for the latest available accessories for this unit. Below is a list of accessories available at the time this instruction was publish.
Optional Accessory | Catalog Number | Part Number |
---|---|---|
Compressor Start Kit | 10J42 | LB-31200BM |
Loss of Charge Kit | 94J47 | LB-87620A |
Sound Cover | 69J03 | 69J0301 |
Replacement Liquid Line Drier | 12L71 | 12L7101 |
Plastic Feet Kit | 94J45 | LB-87156A |
Crankcase Heater - 40W | 93M04 | 100499-01 |
High Pressure Kit | 94J46 | LB-87620A |
![]() |
Lennox C33/CX34 Series Evaporator Coils Installation Instructions Detailed installation instructions for Lennox C33 and CX34 Series evaporator coils, covering unit installation, refrigerant line connections, metering device setup, static pressure testing, and maintenance. |
![]() |
Lennox Merit Series CBA25UH & 13ACX Air Handler Installation Instructions This document provides comprehensive installation instructions for Lennox Merit Series CBA25UH and 13ACX air handler units. It covers essential information such as safety warnings, required clearances, installation procedures, electrical connections, refrigerant piping, leak testing, evacuation, and start-up checks. |
![]() |
Lennox Merit Series ML17KC2 Air Conditioner Installation Instructions Comprehensive installation guide for the Lennox Merit Series ML17KC2 outdoor air conditioner, covering safety, clearances, refrigerant piping, electrical connections, and start-up procedures. |
![]() |
Lennox ML14KP1 Merit Series Heat Pump Installation Instructions Comprehensive installation guide for the Lennox ML14KP1 Merit Series Heat Pump, covering unit setup, refrigerant piping, electrical connections, start-up procedures, charging, and maintenance. |
![]() |
Lennox Merit Series ML17XC1 Air Conditioner Installation Instructions Comprehensive installation guide for the Lennox Merit Series ML17XC1 outdoor air conditioner, covering unit placement, refrigerant piping, electrical connections, and start-up procedures. Includes safety warnings, technical specifications, and maintenance tips. |
![]() |
Lennox Merit Series CBK45UHVT Air Handler Installation Instructions Comprehensive installation instructions for Lennox Merit Series CBK45UHVT Air Handler Units designed for R410A refrigerant. Covers unit overview, wiring diagrams, blower control and speed adjustment, electrical connections, requirements, dimensions, installation clearances, installation procedures for upflow, horizontal, and downflow applications, condensate drain setup, duct system and filters, refrigerant line brazing, unit sealing, check-out procedures, maintenance, and decommissioning. Includes safety warnings and important notes. |
![]() |
Lennox Merit Series 13ACX Units Installation Instructions Comprehensive installation guide for Lennox Merit Series 13ACX Air Conditioner Units, covering unit dimensions, parts, electrical connections, line set installation, refrigerant handling, leak testing, evacuation, and start-up procedures. |
![]() |
Lennox ML296DFVK Gas Furnace Installation Instructions This document provides comprehensive installation instructions for the Lennox ML296DFVK Merit Series Downflow Air Discharge gas furnace. It covers safety precautions, unit setup, venting, gas piping, electrical connections, and operational procedures. |