TECHNICAL SPECIFICATIONS - RPSI

GENERAL SPECIFICATIONS:
RPSI Series Evaporative coolers are designed to supply evaporatively cooled or ventilation air and are produced in 2 different capacities to suit a variety of installation requirements.
CABINET
The cabinet is constructed from marine grade aluminium, incorporating channel section corner pillars, mounted on a heavy gauge base frame for structural stability. Many components are powder coated for extra corrosion protection. Cabinet fasteners are stainless steel, aluminium or zinc plated for extra corrosion protection. The cooler is available in three (3) different discharge orientations ­ Down (D), Side (S) and Top (T). Side and Top configuration are supplied with a flexible duct connector.
All coolers are available in "Basalt" grey.
FAN & MOTOR
The fan is a forward curved centrifugal blower and moulded from plastic. The fan scroll is moulded from plastic for corrosion protection. The motor is electronically commutated permanent magnet, incorporating sealed ball bearings. The motor rotor is external to the stator and is injection moulded from glass reinforced fire resistant polymer. For safety, the motor is fitted with auto re-set overload protection.
WATER RESERVOIR
The water reservoir is a single piece rotational moulded tank made from polyethylene, providing a thick walled, robust and corrosion free component.

COOLING PADS
The cooler is fitted with either Chillcel® (C) fabricated, honeycomb, high efficiency filter pads or Aspen (A) shredded wood wool fibre pads (RPSI2800 only). Pads are located in moulded plastic UV stabilised louvres to enhance the appearance of the unit, protect the pads and minimize water splash.
ELECTRICAL
The electrical control box is pre-wired within the cooler and incorporates an isolating switch. A 4m long power supply cord is supplied as standard on all models. Provision is included in the control box for plug-in connection of drain valve and solenoid kits.
CONTROL
All RPSI model coolers are compatible with the full range of Seeley MagIQtouch and MagIQcool wall controls. Connection of the wall control to the cooler is via a 20m low voltage cable. WiFi, RF, BMS and Switch Plate control options are also available.
WATER
Water supply connection is 1/2" BSP. A float valve is used to control water level in the cooler. The cooler is fitted with a bleed system to control water salinity in the unit and an overflow is provided to allow the unit to be connected to drainage. Optional Water Manager kits are available for improved salinity management.

1 of 4

It is a policy of Seeley International to introduce continual product improvement. Accordingly, specifications are subject to change without notice.

ES E257-A AU2410

TECHNICAL SPECIFICATIONS - RPSI
DOWN DISCHARGE

BOTTOM

1150

1150

Water Inlet

Drain 90

90 Electrical Entry (Down & Side
Discharge)
1190

264 555
TOP DISCHARGE
322 507

555 297
269 390

255
SIDE DISCHARGE

575 155
Electrical Entry (Top Discharge)

390
505 322 507

Dimensions are in mm
2 of 4

It is a policy of Seeley International to introduce continual product improvement. Accordingly, specifications are subject to change without notice.

ILL3989
ES E257-A AU2410

TECHNICAL SPECIFICATIONS - RPSI

MODEL

RPSI2500 DOWN / TOP

RPSI2500 SIDE

RPSI2800 DOWN / TOP

RPSI2800 SIDE

PERFORMANCE Cooling Capacity* @ 80Pa

9.0 kW (Chillcel®)

8.3 kW (Chillcel®)

10.8 kW (Chillcel®) 9.1 kW (Aspen)

9.7 kW (Chillcel®) 9.7 kW (Aspen)

Voltage

240 V / 1~ / 50Hz

240 V / 1~ / 50Hz

240 V / 1~ / 50Hz

240 V / 1~ / 50Hz

Electrical Rated Current

6 A

6 A

9 A

9 A

Input Power

1.3 kW

1.3 kW

1.9 kW

1.9 kW

Supply

20 L/m 100kPa - 800kPa

20 L/m 100kPa - 800kPa

20 L/m 100kPa - 800kPa

20 L/m 100kPa - 800kPa

SERVICES

Water

Max Temperature Inlet

40 ºC 1/2" Male BSP

40 ºC 1/2" Male BSP

40 ºC 1/2" Male BSP

40 ºC 1/2" Male BSP

Drain

1-1/2" Male BSP

1-1/2" Male BSP

1-1/2" Male BSP

1-1/2" Male BSP

Drain Flow Rate

15 L/min

15 L/min

15 L/min

15 L/min

Duct Connections

550 x 550mm Down 390 x 507 Top

390 x 507 Side

550 x 550mm Down 390 x 507 Top

390 x 507 Side

Fan Fan
Size

Centrifugal 460mm

Centrifugal 460mm

Centrifugal 460mm

Centrifugal 460mm

Type

Variable Speed, ECM Variable Speed, ECM Variable Speed, ECM Variable Speed, ECM

AIR SYSTEMS

Power

750 W

750 W

1500 W

1500 W

Motor

Max Speed

510 rpm

510 rpm

680 rpm

680 rpm

Overload

Auto Reset

Auto Reset

Auto Reset

Auto Reset

IP Rating

IPX2

IPX2

IPX2

IPX2

COOLING PADS Material & Size

4x Chillcel® 800 x 890 x 90mm

3x Chillcel® 800 x 890 x 90mm

4x Chillcel® Pads 800 x 890 x 90mm
or 4x Aspen Pads 800 x 890 x 70mm

3x Chillcel® Pads 800 x 890 x 90mm
or 3x Aspen Pads 800 x 890 x 70mm

Reservoir Capacity

48 L

48 L

48 L

48 L

Type

Centrifugal

Centrifugal

Centrifugal

Centrifugal

Power

25W

25W

25W

25W

Pump

Max Flow Rate

21 L/min

21 L/min

21 L/min

21 L/min

WATER SYSTEMS

Voltage IP Rating

230V / 1~ / 50 Hz IPX4

230V / 1~ / 50 Hz IPX4

230V / 1~ / 50 Hz IPX4

230V / 1~ / 50 Hz IPX4

Optional Water Manager Kit (sold separately)

Inlet Valve Water Probes Drain Valve

24 VAC Solenoid Valve
2-pin Conductivity Probe
24 VAC Vertical

24 VAC Solenoid Valve
2-pin Conductivity Probe
24 VAC Vertical

24 VAC Solenoid Valve
2-pin Conductivity Probe
24 VAC Vertical

24 VAC Solenoid Valve
2-pin Conductivity Probe
24 VAC Vertical

DIMENSIONS

Shipping Operating

1200mm Long x 1200mm Wide x 1255mm High
1150mm Long x 1150mm Wide x 1190mm High

1200mm Long x 1200mm Wide x 1255mm High
1150mm Long x 1150mm Wide x 1190mm High

1200mm Long x 1200mm Wide x 1255mm High
1150mm Long x 1150mm Wide x 1190mm High

1200mm Long x 1200mm Wide x 1255mm High
1150mm Long x 1150mm Wide x 1190mm High

WEIGHT

Shipping Operating inc. water

120 kg 140 kg

110 kg 130 kg

120 kg 140 kg

110 kg 130 kg

*Down discharge model tested to Australian Standard AS 2913-2000 with design condition of: 380C dry-bulb, 210C wet-bulb and 27.40C room exit temperature.

3 of 4

It is a policy of Seeley International to introduce continual product improvement. Accordingly, specifications are subject to change without notice.

ES E257-A AU2410

TECHNICAL SPECIFICATIONS - RPSI

Performance Summary Static Pressure (Pa) RPSI2500 Airflow (L/s) RPSI2800 Airflow (L/s)

0 2400 2740

40 2290 2650

80 2130 2530

120 1950 2390

160 1760 2230

200 1560 2050

240 1210 1840

280 1030 1570

Static Pressure (Pa)

300 250 200 150 100
50 0 500

Fan Curve

RPSI2500

RPSI2800

1000

1500

Airflow (L/s)

2000

2500

3000

MAGIQTOUCH CONTROLS
RPSI is compatible with a wide range of MagIQtouch control solutions, including Wall Controllers, Building Management System (BMS) Controllers and Sensor Accessories.
Contact your local Sales office for compatible kits and installation literature.

AIR

SPEED

COOL

OFF

OFF

ON

ON

INTERNATIONAL

BBMMSS IINNDDUUSSTTRRIIAL CONTROLLER M1

BBMMS INDUSTTRRIIAALLCCOONNTTRROOLLLEERRMMS1 PWR /
ERROR CODE

+12VDC POWER 0VDC INPUT SIG ACTUAL FAN
SPEED GND OUTPUT SIG ERROR
STATUS GND OUTPUT SIG SET FAN
SPEED GND INPUT SIG SYSTEM GND ON INPUT SIG
COOL INPUT GND

4 of 4

It is a policy of Seeley International to introduce continual product improvement. Accordingly, specifications are subject to change without notice.

ES E257-A AU2410


Adobe PDF Library 17.0 Adobe InDesign 20.0 (Windows)