product overview for GE, Ward Leonard models including: AC Magnetic Starters, GE, Ward Leonard, LVR, LVP, IC5130B, IC5130D, IC5131B, IC5131D, IC5900, MIL-D-17762, Contactor Panels, Dripproof Starters, Reduced-voltage Starters, Manual Starters, Manual Heaters, AC Contactors, IC5181C, IC5181D, MIL-C-2212, MIL-C-740

4175-04 brochure - 5nov03.xpr

Ward-Leonard Product-Brochure

[ Radieus Equipment Literature ]

GE and Ward Leonard AC Magnetic Starters and Contactors

Ward Leonard AC Magnetic Starters ...

www.radie.us

Ward-Leonard Product-Brochure
AC Magnetic Starters (GE)

Description of Operation

With Local or Remote Start-Stop Selector Switch (LVR) Control

Starting

Turning the selector switch to START energizes "M" and starts the motor.

Stopping

The motor will be stopped by (1) Turning the selector swtich to STOP, by (2) An overload which trips OL, and by (3) Loss of, or low line voltage (LVR).

Restarting

The motor will be restarted after (1) Turning the selector switch to START, after (2) Pressing the "OL" reset button, and after (3) The return to normal line voltage.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Size of Starter

Catalog Number

With Local Pushbuttons

0

139B2810G1S2

1

139B2811G1S2

2

139B2812G1S2

3

139B2813G1S2

With Remote Pushbuttons

0

139B6357G1S2

1

149B2103G1S7

2

187B6165G1S2

3

194B8503G1S2

Size of Starter

Catalog Number

With Local Selector Switch

0

157B2115G1S2

1

194B8502G1S2

2

194B8510G1S2

3

194B8504G1S2

With Remote Selector Switch

0

194B8505G1S2

1

194B8506G1S2

2

194B8507G1S2

3

194B8508G1S2

Description

Catalog Number

Nonreversing Dripproof IC5130B Watertight IC5130D

Reversing

Dripproof IC5131B Watertight IC5131D

AC Magnetic Starters (GE)

Description of Operation

With Local (And Provisions for Remote) Start-Stop Pushbutton (LVP) Control

Starting

Pressing the START pushbutton energizes "M" and starts the motor.

Stopping

The motor will be stopped by (1) Pressing the STOP pushbutton, by (2) An overload which trips OL, and by (3) Loss of, or low line voltage (LVR).

Restarting

The motor will be restarted after (1) Pressing the START pushbutton, after (2) Pressing the "OL" reset button and then pressing the START pushbutton, and after (3) Pressing the START pushbutton after the return to normal line voltage.

Size Single-speed

Max. Motor HP Rating

115 Volts

440 Volts

Continuous Current Rating Amps

0

2

5

18

1

3

10

27

2

7.5

25

45

3

1.5

50

90

4*

25

100

135

5*

­

200

270

6*

­

400

540

Two-speed, One-winding, Constant-torque, Variable-torque, or Constant-horsepower (Max Hp rating for constant-horsepower motors shown in parentheses).

0

2 (1)

5 (3)

18

1

3 (2)

10 (7.5)

27

2

7.5 (­)

25 (20)

45

3

15 (­)

50 (40)

90

4*

25 (­)

100 (75)

135

Two-speed, Two-winding, Constant-torque, Variable-torque, or Constant-horsepower (Max Hp rating for constant-horsepower motors shown in parentheses).

0

2 (1)

5 (3)

18

1

3 (2)

10 (7.5)

27

2

7.5 (­)

25 (20)

45

3

15 (­)

50 (40)

90

4*

25 (­)

100 (75)

135

* Select induction type overload relay if third O/L required.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Type IC5900

Size of Starter
0 1 2 3

Catalog Number
139B2816G1S2 139B2817G1S2 139B2818G1S2 139B8509G1S2

Controllers for Life Boat Winches

Max. Motor Hp

Size

(440 Volts)

0

1

1

5

2

15

3

30

4

60

5

150

6

300

NOTE: Controllers are designed to meet Specification MIL-D-17762. Includes main contactor in addition to reversing contactors.

Contactor Panels

Continuous Current Rating Amps (600 Volts Max.)

Heater

Tungsten

Size

Load

Lighting

0

18

10

1

27

15

2

45

30

3

90

60

4

135

120

5

270

180

6

540

­

NOTE: Construction same as single-speed, full-voltage, nonreversing starter except for omission of overload relay.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Magnetic Starters (GE)

Dripproof Starters (Dimensions and Weights)

Size

Mounting

Height

Accross-the-line, Single-speed

Nonreversing Width

0

BHD

14

7.75

1

BHD

14

7.75

2

BHD

14

7.75

3

BHD

17

8.88

4

BHD

18

14

5

BHD

30

22

6

BHD

30

22

Accross-the-line, Two-speed

0

BHD

22

7.75

1

BHD

22

7.75

2

BHD

22

7.75

3

BHD

28

8.88

4

BHD

20

18

Reduced-voltage, Single-speed

2

BHD

30

24

3

BHD

36

24

4

BHD

36

24

5

Deck

50

30

6

Deck

70

30

Dimensions in Inches

Depth

Height

7.38

22

7.38

22

7.38

22

9

28

10

20

12

30

14

30

7.38

22

7.38

22

7.38

22

8

36

10

36

10

­

12

­

12

­

20

­

20

­

Reversing Width
7.75 7.75 7.75 8.88 18 24 24
18 18 18 24 24
­ ­ ­ ­ ­

Contactor Panels

Continuous Current

Rating Amps (600 Volts Max.)

Size

(440 Volts)

0

1

1

5

2

15

3

30

4

60

5

150

6

300

NOTE: Construction same as single-speed, full-voltage, nonreversing starter except for omission of overload protection.

Size of Starter
0 1 2 3

Catalog Number
139B2816G1S2 139B2817G1S2 139B2818G1S2 139B8509G1S2

Depth
7.38 7.38 7.38 9.13 10 12 14
8 8 8 10 10
­ ­ ­ ­ ­

Approx. Weight in Lbs. Nonreversing Reversing

25

40

25

40

28

48

45

75

80

110

150

210

170

250

40

75

40

75

48

100

75

195

110

210

200

­

265

­

325

­

685

­

1100

­

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Magnetic Starters (WL)

Size Starter

Max. Motor Hp

(3 Ph. 60 Hz)

115 V

440 V

Accross-the-line, Single-speed

Non-reversing

Reversing

Dripproof

Watertight

Dripproof

Watertight

Catalog Number*

0

2

5

4010-3801-

4010-3401-

4210-3801-

4210-3401-

1

3

10

4011-3801-

4011-3401-

4211-3801-

4211-3401-

2

7.5

25

4012-3801-

4012-3401-

4212-3801-

4212-3401-

3

15

50

4013-3801-

4013-3401-

4213-3801-

4213-3401-

4

25

100

4014-3801-

4014-3401-

4214-3801-

4214-3401-

5

­

200

4015-3801-

4015-3401-

4215-3801-

4215-3401-

6

­

400

4016-3801-

4016-3401-

4216-3801-

4216-3401-

Accross-the-line, Two-speed, One Winding Constant or Variable Torque

0

2

5

4310-1801-

1

3

10

4311-1801-

2

7.5

25

4312-1801-

3

15

50

4313-1801-

4

25

100

4314-1801-

5

­

200

4315-1801-

6

­

400

4316-1801-

Accross-the-line, Two-speed, One Winding Constant or Variable Torque

4310-14014311-14014312-14014313-14014314-14014315-14014316-1401-

4910-18014911-18014912-18014913-18014914-18014915-18014916-1801-

4910-14014911-14014912-14014913-14014914-14014915-14014916-1401-

0

2

5

4310-2802-

4310-2402-

4910-2802-

4910-2402-

1

3

10

4311-2802-

4311-2402-

4911-2802-

4911-2402-

2

7.5

25

4312-2802-

4312-2402-

4912-2802-

4912-2402-

3

15

50

4313-2802-

4313-2402-

4913-2802-

4913-2402-

4

25

100

4314-2802-

4314-2402-

4914-2802-

4914-2402-

5

­

200

4315-2802-

4315-2402-

4915-2802-

4915-2402-

6

­

400

4316-2802-

4316-2402-

4916-2802-

4916-2402-

* For complete catalog number add coil soffic numbers from next page.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Magnetic Starters (WL)

Size Starter

Max. Motor Hp (3 Ph., 440 V, 60 Hz)

Nonreversing

Dripproof

Watertight

Catalog Number*

Reduced Voltage Autotransformer ­ Single-speed

1

3

10

27

2

7.5

25

45

3

1.5

50

90

4*

25

100

135

5*

­

200

270

6*

­

400

540

Reduced Voltage Autotransformer ­ Two-speed, Two Winding Constant or Variable Torque

1

3

10

27

2

7.5

25

45

3

1.5

50

90

4*

25

100

135

5*

­

200

270

6*

­

400

540

Reduced Voltage Autotransformer ­ Two-speed, One Winding Constant or Variable Torque

1

3

10

27

2

7.5

25

45

3

1.5

50

90

4*

25

100

135

5*

­

200

270

6*

­

400

540

* For complete Catalog Number add coil suffix numbers from above table.

Coil Suffix Numbers

A.C. Volts (60 Hz)
115 220 440

Suffix Nos.
11 21 41

AC Control Centers

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Across-the-Line Starters - Nonreversing, Single speed

Starter Size
0, 1, 2 3, 4 5, 6

Dripproof Enclosure

Dimensions Approx. in Inches

A

B

C

8 1/2 16 17

13 20 34 3/8

7 8 10 1/4

Weight lbs.
18 24 105

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Manual Starters

Type IC5900

Specification

MIL-C-2212

Rating Rated Ambient

Size 0 50o C

Duty

Designed for continuous duty and general-purpose service unless otherwised specified.

Enclosure

Dripproof

Forms

Flush mounting for panel installation. Dripproof enclosure for surface mounting. Dripproof lockable with provisions for locking in open position by maximum of two padlocks (not supplied).

Overload Protection

Thermostatic bimetal

Low-voltage release effect Contacts remain closed on low voltage, allowing motor to restart upon return of power.

Poles

Three-pole (for single-phase A.C. or D.C., use the two outside poles).

Cable Entrance

Provisions for cable entrance at both top and bottom.

Surface-mounted starter

Ordering Information
Specify form number of starter (e.g., IC5900B2) and catalog number of heaters required (e.g., 81D900) from heater table.

Description
Surface-mounted Flush-mounted Lockable, surface-mounted Switch mechanism (replacement only)

IC5900 Form
B2 M1 B5 A1

Weight in Ounces
42 26 44 16

Max Motor Hp Rating

AC, 3 Ph, 60 Hz

AC, 1 Ph, 60 Hz

DC

Volts

Hp

115

1.5

220

2

440

3

Volts

Hp

115

1

230

1.5

440

2

Volts

Hp

115

1

230

1

Continuous current - 15 amps

Tungsten lamp load - 8 amps

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Manual Heaters

Catalog
Number
81D900 81D901 81D902 81D903 81D904 81D905 81D906 81D907 81D908 81D909 81D910 81D911 81D912 81D913 81D914 81D915 81D916 81D917 81D918 81D919 81D920 81D921 81D922 81D923 81D924 81D925 81D926 81D927 81D928 81D929 81D930 81D931

Rating
Amps
0.37 .42 .46 .52 .58 .63 .70 .78 .87 .96 1.05 1.15 1.26 1.39 1.53 1.68 1.84 2.01 2.20 2.41 2.63 2.87 3.13 3.42 3.73 4.07 4.43 4.82 5.24 5.71 6.22 6.77

Continuous Motor

Load Range ­ Amp

Minimum

Maximum

0.29

0.32

.33

.36

.37

.40

.41

.45

.46

.50

.51

.55

.56

.61

.62

.68

.69

.75

.76

.83

.84

.91

.92

1.00

1.01

1.10

1.11

1.21

1.22

1.33

1.34

1.46

1.47

1.60

1.61

1.75

1.76

1.75

1.92

2.09

2.10

2.28

2.29

2.49

2.50

2.72

2.73

2.97

2.98

3.24

3.25

3.53

3.54

3.85

3.86

4.19

4.20

4.56

4.57

4.97

4.98

5.41

5.42

5.89

Catalog
Number
81D932 81D933 81D934 81D935 81D936 81D937 81D938 81D939 81D940 81D941 81D942

Rating
Amps
7.38 8.03 8.75 9.53 10.4 11.3 12.2 13.4 14.5 15.8 17.3

Wiring Symbol

Type IC5900

Continuous Motor

Load Range ­ Amp

Minimum

Maximum

5.90

6.42

6.43

6.99

7.00

7.61

7.62

8.29

8.30

9.03

9.04

9.83

9.84

10.6

10.7

11.6

11.7

12.6

12.7

13.7

13.8

15.0

Surface-mounted Form

Flush-mounted Form

AC Contactors

Specification Application Type
Rated Ambient Duty Insulation

MIL-C-2212
Motor control, heater and tungsten lamp switching.
Select standard type (IC5181C) or quiet type (IC5181D) when control is to meet standard MIL-C-740. All quiet contactors undergo special testing at the factory. 50o C
Continuous
Class B (coils are Class A)

Size 0, 1

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5181
Size 2

Size 3, 4

Size 6

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Contactors

Type IC5181

Standard

Quiet

Basic Catalog Number IC5181

Basic Catalog Number IC5181

115 V Coil

440 V Coil

Number of

115 V Coil

440 V Coil

Number of

Size

Poles

60 Hz

60 Hz

Auxiliary Contacts

60 Hz

60 Hz

Auxiliary Contacts

0

2

C100D3

C100D6

2

C100D3

C100D6

4

3

C100A3

C100A6

2

C100A3

C100A6

4

4

C100B3

C100B6

2

C100B3

C100B6

4

5

C100C3

C100C6

2

C100C3

C100C6

4

D100D3

D100D6

2

D100D3

D100D6

4

D100A3

D100A6

2

D100A3

D100A6

4

D100B3

D100B6

2

D100B3

D100B6

4

D100C3

D100C6

2

D100C3

D100C6

4

1

3

C101A3

C101A6

2

C101A3

C101A6

4

4

C101B3

C101B6

2

C101B3

C101B6

4

5

C101C3

C101C6

2

C101C3

C101C6

4

D101A3

D101A6

2

D101A3

D101A6

4

D101B3

D101B6

2

D101B3

D101B6

4

D101C3

D101C6

2

D101C3

D101C6

4

2

3

C102A3

C102A6

2

C102A3

C102A6

4

4

C102B3

C102B6

2

C102B3

C102B6

4

5

C102C3

C102C6

2

C102C3

C102C6

4

D102A3

D102A6

2

D102A3

D102A6

4

D102B3

D102B6

2

D102B3

D102B6

4

D102C3

D102C6

2

D102C3

D102C6

4

3

3

C103A3

C103A6

2

C103A3

C103A6

4

C103A3

C103A6

6

C103A3

C103A6

8

D103A3

D103A6

2

D103A3

D103A6

4

D103A3

D103A6

6

D103A3

D103A6

8

4

3

C104A3

C104A6

2

C104A3

C104A6

4

C104A3

C104A6

6

C104A3

C104A6

8

D104A3

D104A6

2

D104A3

D104A6

4

D104A3

D104A6

6

D104A3

D104A6

8

5

3

C105A3

C105A6

2

C105A3

C105A6

4

C105A3

C105A6

6

C105A3

C105A6

8

D105A3

D105A6

2

D105A3

D105A6

4

D105A3

D105A6

6

D105A3

D105A6

8

6

3

C106A3

C106A6

2

C106A3

C106A6

4

C106A3

C106A6

6

C106A3

C106A6

8

D106A3

D106A6

2

D106A3

D106A6

4

D106A3

D106A6

6

D106A3

D106A6

8

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Contactors

Type IC5181

Auxiliary Contact Ratings

Volts

Carry

Make

Amperes

Break

One Contact

Two Contacts in Series

115 VAC

10

440 VAC

10

115 VDC

Inductive

10

Noninductive 10

230 VDC

Inductive

10

Noninductive 10

60

10

­

60

5

­

60

1

2

60

5

10

60

0.5

1

60

2

4

Control Power Requirements

Amperes Holding

Amperes Inrush

Size

115 V

440 V

115 V

440 V

0, 1

0.33

0.08

2.1

0.5

2

.63

.15

5.0

1.2

3, 4

.75

.18

10.9

2.6

5, 6

1.2

.40

32.0

10.0

Note: Pick-up voltage is approximately 74-79% of rated coil voltage. Drop-out voltage is approximately 40-45% of rated coil voltage.

Note: Auxiliary contacts can be changed from N.O. to N.C. and vice versa without addition of parts.

Application

Motor Horsepower Non-

plugging and Nonjogging Duty Encl.

Single

Rating

Phase Three Phase

Amp

Size

115 V 115 V 440 V Cont

0

1

2

5

18

1

2

3

10

27

2

3

7.5

25

45

3

7.5

15

50

90

4

­

25

100 135

5

­

­

200 270

6

­

­

400 540

Tungsten

Lamp

Load Make

Amp

Amp

10

108

15

162

30

270

60

540

120 810

180 1620

­

3240

Note: Enclosed rating shown is 90% of open rating.

Break Amp
108 162 270 540 810 1620 3240

Auxiliary Contact Arrangements

No. of Auxiliary Contacts

Size 0 ­ 1 ­ 2 Contactors

N.O.

Arrangements N.C.

Catalog No. Indicator

0 2
4
No. of Auxiliary Contacts

0

0

2

0

1

1

0

2

0

4*

1

3*

2

2

3

1

4

0

Size 3 ­ 4 ­ 5 ­ 6 Contactors

N.O.

Arrangements N.C.

XX
BX AX CX
CC AC AA AB BB
Catalog No. Indicator

0

0

0

XX

2

2

0

XBXX

1

1

XAXX

0

2

XCXX

4

0

4

XCCX

1

3

XACX

2

2

XAAX

3

1

XABX

4

0

XBBX

6

6

0

BBBX

5

1

ABBX

4

2

ABAX

3

3

AAAX

2

4

ACAX

1

5

ACCX

0

6

CCCX

8

8

0

BBBB

7

1

ABBB

6

2

ABBA

5

3

AABA

4

4

AAAA

3

5

AACA

2

6

ACCA

1

7

ACCC

0

8

CCCC

*This auxiliary contact arrangement is not available on Size 0 and 1 contactors. Size 0 and 1 contactors are design limited to two N.C. auxiliary contacts.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Contactors

Type IC5181

Ordering Information
Order by complete catalog number. Complete catalog number consists of the basic catalog number, plus an auxiliary contact indicator.
Example: A standard Size 2 contactor with 3 poles, 440 VAC, 60 Hz coil and 2 N.O. and 2 N.C. auxiliary contacts is:
IC5181C102A6AA
Basic Catalog Number Auxiliary Contact Indicator
Mechanical Interlocks: For mechanical interlocking of two contactors for reversing or multispeed starters, refer to Company for quotation.
Unlisted Ratings: For other unlisted voltages or frequencies or for application on DC, refer to Company for quotation.

Typical Cat. No. Size 0, 1, and 2

IC5181C100A6AA

Basic No.

Right side Aux. Contact Block

Device Form Left side Aux. Contact Block

Coil Group No.

Typical Cat. No. Size 3, 4, 5, and 6

IC5181C103A6XAAX

Basic No.

Right side outer Aux. Contact Block

Device Form Right side Aux. inner Contact Block

Coil Group No. Left side inner Aux. Contact Block

Left side outer Aux. Contact Block

Outline and Mounting Dimensions (in Inches)

AC Contactors

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5181

Outline and Mounting Dimensions (in Inches)

AC Contactors

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5181

Outline and Mounting Dimensions (in Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Magnetic Contactors

Series 4691 A.C. Magnetic Contactors, both standard and low noise types, are available in Sizes 0-6. Used for motor starting, lamp switching, and heater controls. The 4691 Series meets all applicable military specifications.
Contactors are solenoid operated featuring totally enclosed double break alloy contacts, accessible line, load, and coil terminals and continuous duty operating coils. Contactor parts are compactly arranged on a steel base plate.

Specification
Operation Function Type Duty Ambient Insulation

MIL-C-2212 A.C. Control MIL-C-23742 Group Control MIL-C-901 Hi-Shock MIL-STD-167 Vibration MIL-STD-740 Acceptable Noise Criteria (quiet type)
Magnetic solenoid
Line, accelerating or control contactors.
Series 4691, Types N160 thru N176
Continuous 50o C
Class B (coils are Class A)

Size 0

Series 4691

Auxiliary Contacts Auxiliary contacts for electrical interlocking, maintaining and other control circuit applications are available in N.O. and N.C. types. Auxiliaries are rated at 5 amps., 440 volts, 60 Hz., (make or break). A maximum of 3 auxiliaries per contactor can be furnished.
Mechanical Interlocks Mechanically interlocked contactors can be furnished for reversing and multispeed applications.

Size 1

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Magnetic Contactors

Application

Type No. Size

N160-1 0

N161

1

N162

2

N163

3

N164

4

N175-1 5

N176

6

Motor Horsepower

Nonjogging Duty

Single

Phase

Three Phase

115 V

115 V

440 V

1

2

5

2

3

10

3

7 1/2

25

7 1/2

15

50

­

25

100

­

­

200

­

­

400

Elec. Rating Amps. Cont.
18 27 45 90 135 270 540

Tungsten Lamp Load Amps

Make Amps

10

108

15

162

30

270

60

540

120

810

180

1620

­

3240

Break Amps
108 162 270 540 810 1620 3240

Control Power Requirements

Amperes Holding

Size

115 V

220 V

440 V

0, 1, 2

0.29

0.13

0.06

3, 4

1.2

.51

.27

5, 6

1.4

­

.32

Amperes Inrush

115 V

220 V

1.9

0.91

12.3

5.6

4.3

­

440 V
0.38 2.8 0.94

Notes: The 356L1 coil and a 15 watt (actual load) 833 ohm resistor are connected in series across the output of a full wave bridge rectifier for 115 volts 60 hertz service voltage.
The 356L2 coil and a 58 watt (actual load) 3.2K ohm resistor are connected in series across the ouput of a full wave bridge rectifier for 440 volt 60 hertz service voltage.

Series 4691
Repair Parts
Repair parts normally furnished in accordance with applicable part allowance list include:
1 set of contacts 1 set of springs 1 shunt of coil of each size and type
Ordering Information
When ordering Series 4691 A.C. Contactors, specify:
1. Type No. or Contactor size 2. Coil voltage and frequency 3. No. of auxiliary contactors
(N.O. or N.C.) 4. Open or enclosed 5. Repair parts (if required) 6. Special environmental
requirements 7. Application

Contactor

Size

A

B Auxiliaries

1

2

0, 1, 2 3, 4 5, 6

6 1/8

7 1/16

10 15/16 ­

16 3/4 ­

7 1/16
­ ­

3
8 1/16 ­ ­

Dimensions in Inches (approx.)

D Aux.

C

1 or 2 E

F Dia. G

5 1/16 8 11/16 16 3/4

­ 31/32 ­

3 9/16
6 5/16 15 3/8

(4) 17/64 5/16 (4) 13/32 11/16 (4) 9/16 7/8

H
4 1/4 7 1/8 14 1/2

I
5/16 11/16 7/8

J
5/16 11/16 13/16

K
5 1/2 9 9/16 15 1/8

Weight in Lbs. Approx.
5 21 85

Dimensions

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC Relays

Type IC5182

Series N147 Overload Relays are of the magnetically operated self reset type, designed for use on A.C. or D.C. motor starters and controllers for Navy Service A applications.

Specification Application Forms
Contacts Rated Ambient Duty Insulation

MIL-C-2212
Auxiliary relay, control relay, or undervoltage relay. Select standard form (IC5182), or quiet form (IC5182D) when control is to meet standard MIL-STD-740. All quiet AC relays undergo special testing at the factory. Available in 2, 4, 6, and 8 contact versions. 50o C Continuous Class B (coil is Class A)

Type IC5182 AC Relay

Number of Contacts
2 4 6 8

Basic Catalog Number IC5182

Standard

Quiet

115 V Coil

440 V Coil

115 V Coil

C120A3 C120A3 C120A3 C120A3

C120A6 C120A6 C120A6 C120A6

D120A3 D120A3 D120A3 D120A3

440 V Coil
D120A6 D120A6 D120A6 D120A6

Ordering Information
Order by complete catalog number. Complete catalog number consists of the basic catalog number, plus a contact arrangement indicator.
Example: A standard relay having a 440 VAC, 60 Hz coil and 6 N.O. and 2 N.C. contacts is: IC5182C120A6ABBA
Basic Catalog Number Contact Arrangement Indicator
Unlisted Ratings: For other unlisted voltages or frequencies or for application on D.C., refer to Company.

Control Power Requirements

Volts
115 440

Amperes Holding Amperes Inrush

0.33

2.1

.08

0.5

Contact Ratings (Amperes)

Volts

Carry

Break One 2 Contacts Make Contact in Series

115 VAC

10 60

10

-

440 VAC

10 60

5

-

115 VDC

Inductive

10 60

1

2

Noninductive

10

60

5

10

230 VDC

Inductive

10 60

0.5

1

Noninductive

10

60

2

4

AC Relays
Outline and Mounting Dimensions

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5182

Contact Arrangements

No. of Auxiliary Contacts 2 4
6
8

N.O.
2 1 0
0 1 2 3 4
6 5 4 3 2
8 7 6 5 4

Arrangements N.C.
0 1 2
4 3 2 1 0
0 1 2 3 4
0 1 2 3 4

Contact Arrangement Indicator
XBXX XAXX XCXX
XCCX XACX XAAX XABX XBBX
BBBX ABBX ABAX AAAX ACAX
BBBB ABBB ABBA AABA AAAA

Thermal Overload Relays

Type N154 Relay is an ambient compensated single pole inverse time thermal overload relay suitable for A.C. or D.C. service. It is specifically designed for use with motor starters and controllers that are to be applied on Navy Service A applications.

Specification Function Operation Type Heaters
Compensation
Insulation Adjustment Voltage Contact Rating

MIL-C-2212
Motor overload protection Thermal inverse time delay type, manual reset Series N154 Interchangeable, Heaters available with current trip range 0.36 to 275 amps. Ambient compensation within 0.3% per degree change in ambient temperature between 20 oC and 70 oC. Class A Trip current adjustable +/- 10% of heater rating. A.C. 600 volts max., D.C. 250 volts max. Normally closed contact will carry and break 6 amps. max. A.C. and 200 V.A. with a max. of 2 amps. D.C.

Dimensions (Approximate)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Series N154

Series N154 Thermal Overload Relay

Use with

Ampere Rating Catalog

Contactor Size Nominal

Number

0, 1

25

N154-1

2

50

N154-2

3

100

N154-3

4

150

N154-4

5

300

N154-5*

* Relays must be used with current transformer. Consult Factory for transformer selection.

Ordering Information
When ordering Series N154 Overload Relays, specify:
1. Catalog Number 2. Motor type, H.P. and nameplate amperes.
When ordering heaters, specify Heater Part Number and Motor Full Load Amperes. Heaters furnished separately.

Repair Parts
Repair parts are normally furnished in accordance with the applicable part allowance list include:
1 set of overload heaters (wt. 2 oz. each)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Thermal Overload Relays

Heaters
Full Load Motor Amperes
.28 - .30 .31 - .34 .35 - .39 .40 - .44 .45 - .50 .51 - .56 .57 - .64 .65 - .73 .74 - .30 .82 - .92 .93 - 1.05 1.06 - 1.19 1.20 - 1.35 1.36 - 1.53 1.54 - 1.73 1.74 - 1.94 1.95 - 2.1 2.2 - 2.5 2.6 - 2.8 2.9 - 3.2 3.3 - .3.6 3.7 - 4.0 4.1 - 4.5 4.6 - 5.3 5.4 - 6.0 6.1 - 6.7 6.8 - 7.7 7.8 - 9.0 9.1 - 10.3 10.4 - 11.7 11.8 - 13.0

Heater Marking
.36 .40 .45 .51 .58 .65 .73 .83 .94 1.06 1.20 1.36 1.54 1.74 1.95 2.21 2.50 2.83 3.20 3.65 4.15 4.65 5.25 5.95 6.75 7.70 8.70 10.2 11.7 13.2 14.8

Catalog Number
104.813.11 104.813.12 104.813.13 104.813.14 104.813.15 104.813.16 104.813.17 104.813.18 104.813.19 104.813.20 104.813.21 104.813.22 104.813.23 104.813.24 104.813.25 104.813.26 104.813.27 104.813.28 104.813.29 104.813.30 104.813.31 104.813.32 104.813.33 104.813.34 104.813.35 104.813.36 104.813.37 104.813.38 104.813.39 104.813.40 104.813.41

Series N154

Full Load Motor Amperes
13.1 - 14.0 14.1 - 16.0 16.1 - 18.0 18.1 - 20.3 20.4 - 22.9 23.0 - 25.4 25.5 - 27.0 28 - 31 32 - 35 36 - 38 39 - 42 43 - 45 46 - 48 49 - 52 53 - 57 58 - 63 64 - 71 72 - 80 81 - 89 90 - 98 99 - .108 109 - 118 119 - 125 126 - 136 137 - 151 152 - 163 164 - 180 181 - 190 191 - 199 200 - 205

Heater Marking
16.0 18.0 20.5 23.0 26.0 29.5 32.0 35.0 41.0 44.0 49.0 53.0 58.0 62.0 67.0 73.0 81.0 91.0 102.0 113.0 123.0 137.0 149.0 157.0 173.0 190.0 205.0 223.0 244.0 275.0

Catalog Number
104.813.42 104.813.43 104.813.44 104.813.45 104.813.46 104.813.47 104.813.48 104.813.49 104.813.50 104.813.51 104.813.52 104.813.53 104.813.54 104.813.55 104.813.56 104.813.57 104.813.58 104.813.59 104.813.60 104.813.61 104.813.62 104.813.63 104.813.64 104.813.65 104.813.66 104.813.67 104.813.68 104.813.69 104.813.70 104.813.71

Thermal Overload Relays

Specification Application Type
Form Voltage

MIL-C-2212
Use for motor overload protection. Heater type with interchangeable heater elements and adjustable trip setting. Trip current can be varied +/- 10% from factory setting. Dual element (two pole) with one N.C. contact. Use only one pole for single phase A.C. or D.C. 600 volts maximum.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5882D

Outline and Mounting Dimensions (in inches)

Type IC5882D Overload Relay
Ordering Information
To order overload relay with heaters specify overload relay catalog number and heater catalog number.
Example: IC5882D122B with two Type 81D363 heaters.
Overload relay or heaters may be ordered as separate items (not assembled together) by specifying appropriate catalog number and quantity of each required.

Contact Ratings (Amperes)

Carry Continuous 10

Make Momentary 30

115 VAC 15

Break

440 VAC

115 VDC

5

0.35

230 VDC 0.17

Thermal Overload Relays

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5882D

Heaters
Use With Contactor Size 0, 1
2
3
4, 5, 6*

Reset Rod Length
Short Long
Short Long
Short Long
­

Catalog Number
IC5882D121A IC5882D121B IC5882D122A IC5882D122B IC5882D123A IC5882D123B ­

*Size 4: USE induction overload relay on page 26 Size 5 & 6: USE overload relay Cat. No. IC5882D121 with two 200:5 current transformers.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Thermal Overload Relays

Heaters

Max. Cont. Full Load Motor Amp for 40º C Rise Motors
Size 0, 1, 2

Heater Rating Amps @ 40º C

0.37 - 0.38

0.44

0.39 - 0.42

0.48

0.43 - 0.46

0.53

0.47 - 0.50

0.58

0.51 - 0.56

0.64

0.57 - 0.62

0.71

0.63 - 0.67

0.77

0.68 - 0.74

0.85

0.75 - 0.82

0.94

0.83 - 0.90

1.03

0.91 - 0.99

1.14

1.00 - 1.09

1.25

1.10 - 1.20

1.37

1.21 - 1.31

1.50

1.32 - 1.44

1.65

1.45 - 1.59

1.82

1.60 - 1.74

2.00

1.75 - 1.92

2.20

1.93 - 2.11

2.42

2.12 - 2.31

2.65

2.32 - 2.55

2.92

2.56 - 2.80

3.20

2.81 - 3.09

3.54

3.10 - 3.42

3.92

3.43 - 3.75

4.3

3.76 - 4.10

4.7

4.11 - 4.54

5.2

4.55 - 4.98

5.7

4.99 - 5.45

6.25

5.46 - 6.03

6.9

6.04 - 6.65

7.6

6.66 - 7.25

8.3

7.26 - 8.05

9.2

8.06 - 8.83

10.1

8.84 - 9.70

11.1

Catalog Number
81D303 81D304 81D305 81D306 81D307 81D308 81D309 81D310 81D311 81D312 81D313 81D314 81D315 81D316 81D317 81D318 81D319 81D320 81D321 81D322 81D323 81D324 81D325 81D326 81D327 81D328 81D329 81D330 81D331 81D332 81D333 81D334 81D335 81D336 81D337

Note: Ultimate trip current will be 90%-100% of heater rating.

Max. Cont. Full Load Motor Amp for 40º C Rise Motors
Size 0, 1, 2

Heater Rating Amps @ 40º C

9.71 - 10.6

12.2

10.7 - 11.7

13.4

11.8 - 12.7

14.5

12.8 - 13.9

15.9

14.0 - 15.2

17.4

15.3 - 16.8

19.3

16.9 - 18.5

21.3

18.6 - 20.6

23.6

20.7 - 22.5

25.9

22.6 - 24.9

28.5

25.0 - 27.3

31.3

27.4 - 30.0

34.5

30.1 - 33.0

37.9

33.1 - 36.4

41.9

36.5 - 44.0

46.0

40.1 - 44.2

50.6

Size 3

22.6 - 24.9

28.5

25.0 - 27.3

31.3

27.4 - 30.0

34.5

30.1 - 33.0

37.9

33.1 - 36.4

41.7

36.5 - 40.0

46.0

40.1 - 44.2

50.6

44.3 - 48.6

55.7

48.7 - 53.6

61.3

53.7 - 58.8

67.4

58.9 - 64.7

74.1

64.8 - 71.1

81.5

71.2 - 78.3

89.7

78.4 - 86.0

98.6

86.1 - 94.0

108

94.1 - 103.0

119

Type IC5882D
Catalog Number
81D338 81D339 81D340 81D341 81D342 81D343 81D344 81D345 81D346 81D360 81D361 81D362 81D363 81D364 81D365 81D366
81D400 81D401 81D402 81D403 81D404 81D405 81D406 81D407 81D408 81D409 81D410 81D411 81D412 81D413 81D414 81D415

Thermal Overload Relays

Specification Application
Type
Form Reset Voltage

MIL-C-2212
Use for overload protection of A.C. motors where highly accurate, ambient compensated overload relays are required. Choose medium-trip relay for most applications. Use slowtrip relay if it is necessary to have motor ride through long over load periods. Use fast-trip relay for motors that heat rapidly. See characteristic curves for comparative time-current characteristics.
Induction type with interchangeable coils and adjustable trip setting. Trip current can be varied +/- 10% from factory setting. Compensation is such that trip current will not vary more than 3 percent for each 10o C change in ambient temperature.
Single element (one pole) with one N.C. contact. Use two relays in two lines of a three phase circuit.
Reset manually with one reset button or electrically with reset relay on page 32
600 volts maximum.

Ordering Information
To order overload relay with heating coil, specify overload relay catalog number with heating coil suffix number. Example: IC5882-34JJ200 To order overload relay only (less coil) specify overload relay catalog number only. Example: IC5882-34JJ To order heating coil only specify heating coil catalog number plus suffix number. Example: 1D5G200

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Induction Type IC5882-34

Contact Ratings

Carry

Amperes

Break

Make

115 VAC 440 VAC

10

30

20

5

Type of Trip
Slow Medium Fast

Overload Relay Catalog Number
IC5882-34KK IC5882-34JJ IC5882-34MM

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Thermal Overload Relays

Induction Type IC5882-34

Heaters Coils (Sizes 0-4)

Max. Cont. Full Load Motor Amp for 40º C 0R.i5s7e -M0o.t6o2rs 0.57 - 0.62 0.63 - 0.69 0.70 - 0.76 0.77 - 0.82 0.83 - 0.91 0.92 - 1.00 1.01 - 1.10 1.11 - 1.20 1.21 - 1.33 1.34 - 1.45 1.46 - 1.60 1.61 - 1.77 1.78 - 1.94 1.95 - 2.13 2.14 - 2.33 2.34 - 2.58 2.59 - 2.82 2.83 - 3.10 3.11 - 3.40 3.41 - 3.74 3.75 - 4.12 4.13 - 4.54 4.55 - 4.94 4.95 - 5.48 5.49 - 6.03 6.04 - 6.66 6.67 - 7.32 7.33 - 8.03 8.04 - 8.83 8.84 - 9.70 9.71 - 10.8 10.9 - 11.9 12.0 - 13.0 13.1 - 14.2 14.3 - 15.7 15.8 - 17.1 17.2 - 18.2

Coil Rating 0in.7A1mps 0.71 0.78 0.86 0.94 1.03 1.13 1.24 1.36 1.50 1.65 1.80 2.00 2.20 2.42 2.65 2.92 3.22 3.52 3.87 4.25 4.68 5.15 5.65 6.20 6.85 7.55 8.34 9.16 10.0 11.1 12.2 13.5 14.9 16.1 17.8 19.6 21.7

Coil Catalog Number is ID5G Plus Suffix Listed Below

Medium-trip IC5882-34JJ
200 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236

Slow-trip IC5882-34KK C20o0il Suffix 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236

Fast-trip IC5882-34MM
­ ­ 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235

NOTE: Ultimate trip current will be 90-100% of coil rating. * Use next higher rating

Max. Cont. Full Load Motor Amp for 40º C 0R.i5s7e -M0o.t6o2rs 18.3 - 20.0 20.1 - 22.0 22.1 - 24.4 24.5 - 26.1 26.2 - 27.1 27.2 - 27.4 27.5 - 28.7 28.8 - 29.4 29.5 - 30.4 30.5 - 31.4 31.5 - 32.5 32.6 - 33.9 34.0 - 34.8 34.9 - 35.9 36.0 - 38.4 38.5 - 40.3 40.4 - 40.6 40.7 - 44.1 44.2 - 49.0 49.1 - 53.7 53.8 - 55.3 55.4 - 60.5 60.6 - 60.8 60.9 - 63.0 63.1 - 63.9 64.0 - 69.5 69.6 - 69.6 69.7 - 73.1 73.2 - 74.0 74.1 - 81.0 81.1 - 85.0 85.1 - 88.2 88.3 - 96.9 97 - 98 99 - 106.5 106.6 - 111 112 - 121 122 - 127 128 - 133

Coil Rating 0in.7A1mps 22.9 25 27.5 29.5 30.6 31.2 32.4 33.3 34.4 35.7 36.7 38.5 39.3 41.7 43.3 45.5 45.8 50 55 61 62.5 68.8 69 71.5 72.5 78.7 79 83 83.5 92 96.6 100 110 110 121 125 137 144 150

Coil Catalog Number is ID5G Plus Suffix Listed Below

Medium-trip IC5882-34JJ
200 237 238 239 240 * 241 * 242 * 243 * 244 * 245 * 246 * 247 248 * 249 253 * 250 * 254 * * 251 255 * 252 * 256 * 64 85 * 272

Slow-trip IC5882-34KK 2C0o0il Suffix 237 238 239 240 * 241 * 242 * 243 * 244 * 245 * 246 * 247 248 * 249 253 * 250 * 254 * * 251 255 * 252 * 256 * 64 85 * 272

Fast-trip IC5882-34MM
­ 236 237 238 * 239 * 240 * 241 * 242 * 243 * 244 * 245 246 247 248 * * 249 * 253 * 250 254 * 251 255 * 252 * 269 * 64 85 *

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Thermal Overload Relays

Induction Type IC5882-34

Characteristic Curves

Outline and Mounting Dimensions (In Inches)

Wiring Symbol

Magnetic Overload Relays

Series N147 Overload Relays are of the magnetically operated self reset type, designed for use on A.C. or D.C. motor starters and controllers for Navy Service A applications.

Specification
Function Operation Compensation Adjustment Insulation Voltage

MIL-R-2033
Motor overload protection. Magnetic inverse time delay type, self reset. Ambient compensated between 20o C and 70o C Trip current adjustable +/- 10% of nominal current rating. Class A Normally closed contact will carry and break 5 amps 440 volts max. A.C. and 1 amp D.C

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Series N147

Ordering Information
When ordering N147 Magnetic Overload Relays, the following information is requested: 1. Series No. of relay 2. Motor type, H.P. and nameplate amperes 3. Location of coil terminal studs (left or right hand side of relay)

N147 Magnetic Overload Relay
Repair Parts
Repair parts normally furnished in accordance with applicable part allowance list include: 1 Relay operating coil

Dimensions (Approximate)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Magnetic Overload Relays

Series N147

Full Load Motor Current Amperes Relay Tripping

Min.

Max.

Amps.

0.50

0.54

0.625

0.61

0.67

0.77

0.68

0.72

0.84

0.73

0.79

0.91

0.80

0.86

0.99

0.87

0.94

1.08

0.95

0.03

1.18

1.04

1.13

1.30

1.14

1.24

1.43

1.25

1.35

1.57

1.36

1.47

1.68

1.48

1.61

1.85

1.62

1.75

2.03

1.76

1.86

2.14

1.87

1.96

2.26

1.97

2.16

2.47

2.17

2.37

2.72

2.38

2.61

2.98

2.62

2.80

3.27

2.81

2.96

3.41

2.97

3.23

3.70

3.24

3.53

4.05

3.54

3.87

4.43

3.88

4.23

4.85

4.24

4.61

5.30

4.62

5.04

5.79

5.05

5.50

6.33

5.51

5.97

6.84

5.98

6.52

7.47

6.53

7.10

8.16

7.11

7.52

8.60

7.53

8.24

9.40

8.25

8.95

10.3

8.96

9.67

11.0

9.68

10.6

12.1

10.7

11.6

13.3

11.7

12.6

14.6

12.7

13.9

16.1

14.0

15.1

17.4

15.2

16.7

19.1

16.8

18.2

21.0

18.3

20.0

23.0

20.1

22.0

25.3

Coil Nos.
151L901 151L1 151L2 151L3 151L4 151L5 151L6 151L7 151L8 151L9 151L10 151L11 151L12 151L13 151L14 151L15 151L16 151L17 151L18 151L19 151L20 151L21 151L22 151L23 151L24 151L25 151L26 151L27 151L28 151L29 151L30 151L31 151L32 151L33 151L34 151L35 151L36 151L37 151L38 151L39 151L40 151L41 151L42

NOTE: Full load columns based on coil ratting of 115% to 125% of full load current. * These coils used with overload relays employing terminal boards.

Full Load Motor Current Amperes Relay Tripping

Min.

Max.

Amps.

22.1

24.0

27.7

24.1

26.5

30.4

26.6

29.0

33.3

29.1

32.0

36.3

32.1

35.0

39.7

35.1

38.0

43.4

38.1

41.0

48.3

41.1

43.1

50.2

43.1

46.0

52.8

46.1

49.0

58.0

49.1

52.0

61.0

52.1

55.0

64.5

55.1

59.0

68.3

59.1

62.0

72.5

62.1

67.0

77.3

67.1

72.0

83.0

72.1

77.0

89.3

77.1

84.0

96.7

84.1

91.9

105.5

92.1

101

116

102

114

129

115

126

145

127

131

150

132

143

165

144

153

174

154

167

192

168

183

210

184

201

231

202

209

254

210

230

263

231

252

289

253

278

318

279

306

350

307

337

385

338

369

424

418

457

525

462

501

578

507

550

635

Coil Nos.
151L43 151L44 151L45 151L146* 151L147* 151L148* 151L149* 151L150* 151L151* 151L152* 151L153* 151L154* 151L155* 151L156* 151L157* 151L158* 151L159* 151L160* 151L161* 151L162* 151L163* 151L164* 151L172* 151L165* 151L173* 151L166* 151L174* 151L167* 151L175* 151L176* 151L168* 151L177* 151L178* 151L169* 151L179* 151L180* 151L170* 151L181*

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC and DC Magnetic Relays

Series N130

Series N130 Magnetic Relays are recommended for applications where the pilot or control circuit must be established and interrupted repeatedly. These auxiliary control relays in one, two, three and four pole combinations are available for operation on A.C. (480 volts max.) and D.C. (250 volts max.) circuits. All pole combinations can be obtained with or without magnetic blowouts. Optional Features Contact assemblies other than those listed are available with or without blowouts.

Specification Operation Function Duty Ambient Insulation Enclosure Vibration

MIL-C-2212* Magnetic Auxiliary Control Relay Continuous 50o C Class B For enclosed service MIL-STD-167 (ships) Type 1

*For use where opening and closing of contacts, in excess of 10 milliseconds, under shock, does not affect the operation of associated equipment.

N130 Relay: 3 pole N.O. and 3 pole N.C.

Optional Features
Contact assemblies other than those listed are available with or without blowouts. Special coil insulation other than Class "A" applied as standard, can be furnished. In certain instances where ambient conditions or space limitations dictate, Class "H" coil insulation can be supplied at additional cost.
Similarly, Class "B" insulation can be furnished where required at additional cost.
Enclosure either dripproof or watertight are available on special order.
Special requirements such as destructive tests, relays for special applications, should be referred to the Home Office.

Contact Ratings*

Max. Volts

Amps A.C. (60 Hz)

125

25

250

25

480

15

* Ratings are non-inductive

Amps D.C. without Blowouts with Blowouts

3

30

1

30

-

-

N130 Relay: 2 pole N.O.
Drawings
Dimension sketches for all contact combinations are availble without charge. Master plans and special drawings will be quoted on request.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC and DC Magnetic Relays

Series N130

No. of Poles 1 - Single Break 1 - Double Break 2 - Single Break 3 - Single Break
4 - Single Break

Type of Contacts
SPNO or SPNC SPNO and SPNC
SPNO or SPNC
DPNO or DPNC DPNO and DPNC
3 PNO 3 PNC 3 PNC and 3 PNO
4 PNO 4 PNC 4 PNC and 4 PNO

Dimensions (in Inches)

Without Blowouts

A

B

C

2 1/2 2 1/2

4 7/8 6

3 3/16 3 3/16

2 1/2

4 7/8

3 3/16

2 1/2 2 1/2

4 7/8 6

3 3/16 3 3/16

3 5/8 3 5/8 3 5/8

4 7/8 5 1/8 6 5/8

3 3/16 3 3/16 3 3/16

4 3/4 4 3/4 4 3/4

4 7/8 5 1/8 6 7/8

3 3/16 3 3/16 3 3/16

With Blowouts

A

B

C

2 1/2 2 1/2

5 3/4

3 1/2

7 11/16 3 1/2

3 5/8

5 3/4

3 1/2

3 5/8 3 5/8

5 3/4

3 1/2

7 11/16 3 1/2

4 7/16 4 7/16 4 7/16

5 1/2 6 7 11/16

3 1/2 3 1/2 3 1/2

5 7/8 5 7/8 5 7/8

6 3/4 7 1/4 8 3/8

3 1/2 3 1/2 3 1/2

1/32" insulator (furnished with relay) must be used for steel panel mounting.

Single Pole, Single Break
D.C.

Coil Voltage
115 230 440

1 Pole N.O.
N130-6410 N130-7410 ­

1 Pole N.C.
N130-6411 N130-7411 ­

1 Pole N.O. 1 Pole N.C.
N130-6419 N130-7419 ­

1 Pole N.O.
N130-6510 ­ N130-8510

When ordering relays with blowouts, specify Cat. No. followed by the letter "B". Example: N130-6410B.

A.C.
1 Pole N.C. N130-6511 ­ N130-8511

1 Pole N.O. 1 Pole N.C.
N130-6519 ­ N130-8519

Ordering Information
When ordering catalog listed N130 Relays specify:
1. Catalog Number
For special assemblies furnish: 1. Number of poles and contact arrangement (include number and location of blowouts if required)

2. Contact current, voltage, and frequency 3. Coil voltage and frequency 4. Application 5. Repair parts, if required0

Repair Parts
Repair parts normally furnished in accordance with applicable part allowance list include:
1 set of contacts 1 set of spring 1 shunt of coil

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

AC and DC Magnetic Relays

Single Pole, Double Break

Coil Voltage
115 230 440

D.C.
1 Pole N.O.
N130-6413 N130-7413 ­

1 Pole N.C.
N130-6414 N130-7414 ­

A.C.
1 Pole N.O.
N130-6513 ­ N130-8513

1 Pole N.C.
N130-6514 ­ N130-8514

Double Pole, Single Break
D.C.

Coil Voltage
115 230 440

2 Poles N.O.
N130-6420 N130-7420 ­

2 Poles N.C.
N130-6421 N130-7421 ­

2 Poles N.O. 2 Poles N.C.
N130-6429 N130-7429 ­

2 Poles N.O.
N130-6520 ­ N130-8520

Three Pole, Single Break
D.C.

Coil Voltage
115 230 440

3 Poles N.O.
N130-6430 N130-7430 ­

3 Poles N.C.
N130-6431 N130-7431 ­

3 Poles N.O. 3 Poles N.C.
N130-6439 N130-7439 ­

3 Poles N.O.
N130-6530 ­ N130-8530

Four Pole, Single Break
D.C.

Coil Voltage
115 230 440

4 Poles N.O.
N130-6440 N130-7440 ­

4 Poles N.C.
N130-6441 N130-7441 ­

4 Poles N.O. 4 Poles N.C.
N130-6449 N130-7449 ­

4 Poles N.O.
N130-6540 ­ N130-8540

When ordering relays with blowouts, specify Cat. No. followed by the letter "B". Example: N130-6410B.

A.C.
2 Poles N.C. N130-6521 ­ N130-8521
A.C.
3 Poles N.C. N130-6531 ­ N130-8531
A.C.
4 Poles N.C. N130-6541 ­ N130-8541

Series N130
2 Poles N.O. 2 Poles N.C. N130-6529 ­ N130-8529
3 Poles N.O. 3 Poles N.C. N130-6539 ­ N130-8539
4 Poles N.O. 4 Poles N.C. N130-6549 ­ N130-8549

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Reset Relays

Type IC5882A300 and IC5882A400

Specification Application
Duty
Voltage

MIL-C-2212
Use for remote resetting of Types IC5882D and IC5882-34 overload relays. Short time, 30 minutes, 200o C maximum temperature.
600 volts maximum.

For Use With Overload Relay

Reset Relay Catalog Number

115 VAC

440 VAC

IC5882D121A* IC5882D122A* IC5882D123A*

IC5882A400H12 IC5882A400H12 IC5882A400H12

UC5882A400H14 UC5882A400H14 UC5882A400H14

IIC5882-34KK** IIC5882-34KK** IIC5882-34KK**

IC5882A300B12 IC5882A300B12 IC5882A300B12

UC5882A300B14 UC5882A300B14 UC5882A300B14

* Resets only the short reset rod version of Type IC5882D overload relay. ** Resets two Type IC5882-34 overload relays.

Ordering Information
Order by catalog number. Overload relay is ordered separately.

Reset Relays
Outline and Mounting Dimensions (In Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5882A300 and IC5882A400

Reset Relays
Outline and Mounting Dimensions (In Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5882A300 and IC5882A400

Master Switches

Specification Application Enclosure Types
Rating Duty Ambient Contacts

MIL-C-2212
Remote control of magnetic starters. Surface mounting. Watertight. C - 4 positions max., 8 circuits max. D - 4 positions max., 20 circuits max. C and D - 10 amps carry. Continuous 50o C Both spring return and maintaining contacts available.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5847

Ordering Information
When ordering Type IC5847 Master Switches specify: 1. IC Type (e.g. IC5847C) 2. Number of circuits 3. Number of positions 4. Circuit configuration 5. Nameplate marking (position identification)

Type IC5847 Master Switch

Type IC5847 A B C D

Ampere Rating

Number of Circuits (Max)

No Longer Available

No Longer Available

10

8

10

12

20

Electrical Ratings (Amperes)

Rating

Amperes (Inductive Circuit) AC, 60 Hz 115 V 230 V 440 V

DC 115 V

Types IC5847C and IC5847D

Make 10

8

5

8

Break 10

5

3

5

Carry 10

10

10

10

Types IC5847A and IC5847B

Make 24

24

24

24

Break 24

12

5

2

Carry 20

20

20

20

230 V
5 2 10
24 0.7 20

Master Switches
Outline and Mounting Dimensions (In Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5847

Type Dimensions in Inches

IC5847 A

B

C

D

C

2.75

7.00

8.00

6.00

D

3.50

10.80 11.80 9.80

Wgt. in Lbs.
9.5 13.5

Limit Switches

Specification Application
Enclosures
Mounting Shaft Extension Lever Operation Insulation Weight

MIL-C-2212
For general shipboard use with deck machinery, material-handling equipment, machine tools, and elevators. Submersible (15 ft., 30 min.) or explosion-proof (Class 1, Group D). Enclosure is of ductile iron. Molded parts are Navy-approved fireresistant material. Gasket and "O" ring are of oil resistant compound. Brackets provide for either left-hand side or back mounting. Right-hand standard or left-hand if specified. Spring return. Lever travels in either direction. Class A or Class B Approximately 14 lbs.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5896

Contacts
1 N.O. and 1 N.C.

Features Standard Form
Overlapping Contacts

Type of Lever
None Roller Straight

Submersible Limit Switch IC5896 - Form
A1A1 A1A2 A1A3

Explosion-proof Limit Switch
A1D1 A1D2 A1D3

None

A1T1

­

Roller

A1T2

­

Straight

A1T3

­

2 N.O.

Standard Form

None Roller Straight

Contacts operate on CW rotation only

None Roller Straight

A1B1 A1B2 A1B3
A1U1 A1U2 A1U3

A1E1 A1E2 A1E3
­ ­ ­

2 N.C.

Standard Form

None Roller Straight

A1C1 A1C2 A1C3

A1F1 A1F2 A1F3

NOTE: Form numbers listed are for right-hand shaft extensions (see "Mounting Dimensions"). For left-hand shaft extensions add suffix "L" to form number (example: IC5895-A1A1L).

Contact Ratings

Ratings

Amps

Carry Continuous

10

Break, inductive

115 VAC

30

230 VAC

20

440 VAC

5

125 VDC

0.4

250 VDC

0.2

Limit Switches
Outline and Mounting Dimensions (In Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5896

Submersible Switch

Explosion-proof Switch

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Limit Switches

Series 4976 Limit Switches are for application on hoists, elevators, steering gear, and other shipboard equipment requiring an electrical limit switch for automatic control operation. Type N47A or B has a steel enclosure; Type N94A a brass enclosure. A wide selection of lever arms, cam arrangements, (overtravel) and contact combinations are offered on both types.

Specification
Operation Enclosure Duty Ambient Insulation Ratings

MIL-C-2212**
Automatic Watertight or submersible 15 ft. - without space heater*. Continuous 50o C Class B 5 amps, 500 volts, A.C. 60 Hz 10 amps, 220 volts, A.C. 60 Hz. 2 amps., 115 volts, D.C.

*Space heater can be provided.
**For use where opening of contacts, in excess of 10 milliseconds, under shock, does not affect the operation of associated equipment.

N47 Limit Switch Assemblies Without Lever Arms

Contacts

Steel Box

A

B

Left Hand

­

Left Hand

N.C.

Left Hand

N.C.

N.O. ­ N.O.

Left Hand Left Hand Left Hand Left Hand

­ N.C. N.C. N.O.

N.O. ­ N.O. N.O.

Right Hand ­ Right Hand N.C. Right Hand N.C.

N.O. ­ N.O.

Right Hand Right Hand Right Hand Right Hand

­ N.C. N.C. N.O.

N.O. ­ N.O. N.O.

NOTE: Lever arms available with or without roller.

Watertight Type Number
N47A-60 N47A-61 N47A-62
N47A-63 N47A-64 N47A-65 N47A-66
N47A-70 N47A-71 N47A-72
N47A-73 N47A-74 N47A-75 N47A-76

Submersible (15 Foot)
N47B-60 N47B-61 N47B-62
N47B-63 N47B-64 N47B-65 N47B-66
N47B-70 N47B-71 N47B-72
N47B-73 N47B-74 N47B-75 N47B-76

Series 4976
Ordering Information
When ordering Series 4976 Limit Switches, spedify: 1. Type No. (e.g. Type N47A-60) 2. Type contacts (e.g. N.O. contacts) 3. Operating shaft location (e.g. left or right hand) 4. Cam configuration (e.g. Cam Fig. 1) 5. Type lever arm (e.g. Type A) 6. Type enclosure (e.g. watertight or submersible) 7. Space heater, if required
Repair Parts
Repair parts normally furnished in accordance with applicable part allowance list include:
1 set of contacts 1 set of springs

Limit Switches

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Series 4976

Cam Selection Lever Arms

Limit Switches
N94A Limit Switch Assemblies without Levers (Dimensions)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Series 4976

Brass Box

A

Contact

C

B

Left or Right Hand

N.C.

­

Left or Right Hand

­

­

­ N.C.

Left or Right Hand Left or Right Hand

N.O. ­

N.O. ­

­ N.O.

Left or Right Hand Left or Right Hand

N.C. ­

N.O. ­

­ N.C.

Left or Right Hand Left or Right Hand

N.C. ­

N.O. ­

­ N.C.

Left or Right Hand Left or Right Hand

N.O. ­

N.O. ­

­ N.C.

* Same type numbers apply to Watertight or Submersible Enclosed.

D
­ ­
­ N.O.
­ N.O.
­ ­
­ ­

Type Number* N94A-2 N94A-3 N94A-4 N94A-5 N94A-6

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbuttons, Indicating Light, and Rotary Switch Stations

Series 4975

Series 4975 Pushbutton Stations are designed for shipboard control applications requiring heavy duty watertight master switches. Stations are available with one, two or three elements equipped with maintained or momentary contacs and with indicating lights. For panel or switchboard mounting individual N.O., N.C. or D.T. elements can be supplied.

Specification

MIL-C-2122

Operation Enclosure Duty Ambient Insulation Ratings

Manual Watertight (without space heater*) Continuous 50o C Class B 1 Amp., 250 volts D.C. 5 amps., 500 volts A.C.

*Space heater can be furnished.

Ordering Information
1. Specify Type Number, i.e. NS101-1
2. For special assemblies specifyA- Number of elements and location B- Type of elements and legend plate marking C- Indicator lens color, if required and circuit voltage

Pushbutton element for panel or switchboard mounting
Indicating Lights
Indicating lights for 115 or 440 volt A.C. or 115 or 230 volt D.C. service can be included in one, two, or three button stations. Lights for 440 volt A.C. service are of the transformer type. Clear, red, blue, amber or green lenses are available.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbuttons Stations

Control Station (Two Elements)

Type of Element

Top

Bottom

Legend Plate Marking***

Top

Bottom

N.O. D.T. D.T.

N.O. D.T. D.T.

Open Positive Start

Close Negative Open

D.T. Blue Lens** Red Lens**

D.T. Amber Lens** White Lens**

Open (specify) (specify)

Close (specify) (specify)

D.T. N.O. N.O.

D.T. N.C. N.C.

Man.-Auto. Start Start Emer.

Slow-Fast Stop Stop

N.O. Red Lens* D.T.

N.O. N.O. N.O.

Emer. Run (specify) Man.-Auto.

Stop-Start Stop-Start Stop-Start

D.T. N.O.

N.O. N.C.

Slow-Fast Start

Stop-Start Stop

Type Nos.
NS201-1 NS203-1 NS203-2
NS203-3 NS204T3 NS204T4
NS205-1 NS207-1 NS207-2
NS213-1 NS216-1 NS221-1
NS221-2 NS230-1

Series 4975

Control Station (One Element)

Type of Element

Legend Plate Marking***

Type Nos.

N.O. N.O. N.O. N.O.

Start Reset Start Emergency Emergency Run

NS101-1 NS101-2 NS101-3 NS101-4

N.C. N.C. N.C.

Stop Test Emergency Stop

NS102-1 NS102-2 NS102-3

D.T. Red Lens* Green Lens* Red Lens* Green lens*

Emergency Stop (specify) (specify) (specify) (specify)

NS103-1 NS104-1 NS104-2 NS104-T3 NS104-T4

N.O. N.O. N.O.

Off - On Stop - Start Stop - Run

NS105-1 NS105-2 NS105-3

D.T.

Man. - Auto

NS106-1

D.T.

Slow - Fast

NS106-2

Control Station (Three Elements)

Type of Element

Top

Center

Bottom

D.T.

D.T.

N.C.

D.T.

D.T.

N.C.

D.T.

D.T.

N.C.

Green Lens* D.T. N.O.

D.T. D.T. N.O.

D.T. N.O. N.C.

Red Lens*

N.O.

N.C.

Red Lens*

N.O.

N.C.

Green Lens** N.O.

N.C.

Red Lens** N.O.

N.C.

D.T.

N.O.

N.C.

D.T.

N.O.

N.C.

D.T.

N.O.

N.C.

Red Lens* Red Lens** Red Lens*

N.O. N.O. N.O.

N.O. N.O. D.T.

Legend Plate Marking***

Top

Center

Fast Fast Emer. Forward

Slow Slow Emer. Reverse

Motor Running Man.-Auto Emer. Run

Off-On Slow-Fast Start

(specify) Motor Running Power On Motor Running

Start Start Start Start

Slow-Fast Man-Auto Slow-Fast

Start Start Start Emer.

Power On Power On (specify)

Start Start Emer. Run

Bottom
Stop Stop Stop
Run-Auto Stop-Start Stop
Stop Stop Stop Stop
Stop Stop Stop
Off-On Off-On Man-Auto

Type Nos.
NS309-1 NS309-2 NS309-3
NS320-1 NS321-1 NS322-1
NS338-1 NS338-2 NS338T4 NS338T5
NS340-1 NS340-2 NS340-3
NS347-1 NS347T2 NS360-1

* For 115 volt circuits
** For 440 volt circuits
*** Legend plate markings other than the markings listed available. The maximum number of characters per legend plate is 14.

Pushbuttons Stations

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Special Assemblies

Type
2-Button 2-Button 3-Button 3-Button

Marking
(specify) (specify) (specify) (specify)

Series 4975
Description (2) Indicator Lights - 115 V (2) Indicator Lights - 440/6 V (3) Indicator Lights - 115 V (3) Indicator Lights - 440/6 V

Key to Symbols

Diagram Symbols
Switchboard Mounted Units (Dropproof or Watertight)
Standard Contact Arrangement N.O., N.C., or D.T. Pushbutton ­ momentary D.T., 2-position Rotary Switch ­ maintained 3-point N.O. Pushbutton ­ momentary

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbutton, Indicating Light, and Rotary Switch Stations

Specification Application
Enclosure Pushbuttons Selector Switches Indicating Lights Duty. Ambient

MIL-C-2212
Control of magnetic starters from remote locations. Surface mounted. Watertight. Conduit entrance, top or bottom. Momentary contact type. Both spring return and maintaining contacts available. Dual-lamp type. Uses T-1 3/4 midget screw lamps. Continuous 50o C

Type IC5844

Ordering Information
1. Order by complete catalog number. The most frequently ordered standard stations are listed on page 48. Order these stations by the complete catalog number listed whenever possible.
2. Order by complete description, including IC number Quantity and type of each element desired Nameplate marking (lens cap marking if indicating element)
Example: IC5844L containing one indicating light element 1G marked "motor running" and one rotary switch element 3 marked "stop" (pos c) and "run" (pos D)

Basic Station
IC5844K IC5844L IC5844M

Maximum Number of Elements
2 3 5

Electrical Ratings

Rating Push Button

Amperes (Inductive circuit)

A.C., 60 Hz

115 V

230 V

Make

60

60

Break

6

3

Carry

10

10

Selector Switch

Make

10

8

Break

10

5

Carry

10

10

440 V
60 1.5 10
5 3 10

D.C. 115 V
60 2.2 10
8 5 10

230 V
60 1.1 10
5 2 10

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbuttons, Indicating Light, and Rotary Switch Stations

Electrical Arrangements

Element Arrangement
One pushbutton Two pushbuttons Three pushbuttons Four pushbuttons Five pushbuttons
One indicating light Two indicating lights Three indicating lights Four indicating lights Five indicating lights

One rotary switch Two rotary switches Three rotary switches

One P.B. with

One indicating light Two indicating lights One rotary switch One ind. light and one rotary sw.

Two P.B. with

One indicating light Two indicating lights Three indicating lights One rotary switch Two rotary switches

Three P.B. with

One indicating light Two indicating lights One rotary switch Two rotary switches

One I.L. with

One rotary switch

Two I.L. with

One rotary switch

Refer to Company for arrangements not listed.

Order Station Type
IC5844K IC5844K IC5844L IC5844M IC5844M
IC5844K IC5844K IC5844L IC5844M IC5844M
IC5844K IC5844L IC5844M
IC5844K IC5844L IC5844L IC5844L
IC5844L IC5844M IC5844M IC5844L IC5844M
IC5844M IC5844M IC5844M IC5844M
IC5844L
IC5844L

Type IC5844

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Pushbuttons, Indicating Light, and Rotary Switch Stations Type IC5844

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbuttons, Indicating Light, and Rotary Switch Stations Type IC5844

Standard Pushbutton Stations

FEoleumr epnuts(hs)buatntodnNamplate Markings

FPiovseitpiounsh1button

Position 2

IC5844M IPCo5s8it4io4nM3

Complete Catalog Number

1P Start 2P Stop (red) 1P Emer. Run 2P Emer Stop (red) 1P Reset 1P Test 1P Bypass 1P Start 1P On 3P Hoist 3P Forward 3P High Speed 3P Fast 3P Forward 3P Hoist 1P Start 3P High Speed

­ ­ ­ ­ ­ ­ ­ 2P Stop (red) 2P Off 3P Lower 3P Reverse 3P Low Speed 3P Slow 3P Reverse 3P Lower 2P Stop (red) 3P Low Speed

­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ ­ 2P Stop (red) 2P Stop (red) 2P Stop (red) 1P Emer. Run 2P Stop (red)

IC5844K1PXXXX04AA IC5844K2PXXXX04AE IC5844K1PXXXX04AB IC5844K2PXXXX04AC IC5844K1PXXXX04AD IC5844K1PXXXX04AG IC5844K1PXXXX04AH IC5844K1P2PXX01AA IC5844K1P2PXX01AF IC5844K3P3PXX01AB IC5844K3P3PXX01AE IC5844K3P3PXX01AN IC5844L3P3P2P07AA IC5844L3P3P2P07AJ IC5844L3P3P2P07AH IC5844L1P2P1P07AD IC5844L3P3P2P07AG

Standard Rotary Switch Stations

FEoleumrepnut(ssh) abnudttoNnamplate Markings

IC5844M

F(AivlleSptautisohnbsuAttroenSingle Element) ComplIeCte58C4a4taMlog Number

3S Stop (red) ­ Start 3S Off ­ On 4S Local ­ Remote 4S Manual ­ Auto 1S Manual ­ Off ­ Auto 1S Slow ­ Stop (red) ­ Fast 1S Raise ­ Stop (red) ­ Lower

IC5844K3SXXXX03AA IC5844K3SXXXX03AB IC5844K4SXXXX03AC IC5844K4SXXXX03AP IC5844K1SXXXX03MA IC5844K1SXXXX03MN IC5844K1SXXXX03MH

Standard Combination Stations

FEoleumr epnuts(hs)buatntodnNamplate Markings

FPiovseitpiounsh1button

Position 2

IC5844M IPCo5s8it4io4nM3

1G Motor Running 1P Start

2P Stop (red)

Complete Catalog Number IC5844L1G1P2P10AA

Standard Indicating Light Stations

FEoleumr epnuts(hs)buatntodnNamplate Markings

FPiovseitpiounsh1button

Position 2

IC5844M IC5844M

1G Motor Running 1W Power Available 1G Fast 1G High Speed 1G Up

­ ­ 1G Slow 1G Low Speed 1G Down

Complete Catalog Number
IC5844K1GXXXX06AA IC5844K1WXXXX06AB IC5844K1G1GXX02AA IC5844K1G1GXX02AB IC5844K1G1GXX02AC

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbuttons, Indicating Light, and Rotary Switch Stations
Outline and Mounting Dimensions (In Inches)

Type IC5844

Type IC5844K

Type IC5844L

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Pushbuttons, Indicating Light, and Rotary Switch Stations
Outline and Mounting Dimensions (In Inches)

Type IC5844

Type IC5844M

Panel-mounted Selector Switches

Specification Application
Positions

MIL-C-2212
Where ever maintained contact switching of control circuits is required. Two or three position switches are available.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5846

Outline and Mounting Dimensions (In Inches)

Selector Switch

Contact Ratings (Amperes)

Volts

Carry Continuous

115 VAC

10

440 VAC

10

115 VDC

10

230 VDC

10

Interrupt
3.0 0.5 1.0 0.3

Contact Arrangement
Double-pole single-throw Single-pole double-throw
with mid position Single-pole double throw

Catalog Number 5729122G1
5729122G2 5729122G3

Ordering Information
Order selector by catalog number. Nameplate, if required, must be ordered separately. Order standard nameplate by catalog number. Specify marking for special nameplate.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Panel-mounted Selector Switches

Type IC5846

Standard Selector-switch Nameplates

Nameplate Marking
Stop ­ Start Off ­ On Stop ­ Run Auto ­ Hand Manual ­ Auto Local ­ Remote Off ­ Auto Low ­ High Man ­ Off ­ Auto Hand ­ Off ­ Auto Low ­ Off ­ Auto Run ­ Off ­ Auto On ­ Off ­ Remote Blank Special Nameplate Marking

Catalog Number
NP93396C NP93396A NP94647B NP94647D NP97168A NP97168B NP97261C NP99265B NP145872B NP97261D NP97261B NP145872A NP110849A NP161895A ­

Outline and Mounting Dimensions (In Inches)

Rotary and Momentary Selector Switches
Styles JF and JFM
Silver to Silver Contacts · Silver overlay on bronze - Low contact resistance · Self-wiping actions · Non-shorting - break before make · Solder connections
Watertight Mounting · "O" ring construction on shaft and mounting bushing · Non-turn device included · Single hole mounting for 3/8 - 32 thread
Kel-F Sections · Unitized construction · Available in one to five sections
Positive Index Mechanism (Style JF) · Twelve positions · Thirty (30) degree increments · Conveniently located adjustable stops
Spring Return Index (Style JFM) · Return positioning from both left and right
Qualified Product Listed (QPL) tested and approved per MIL-S-21604 for both styles: · Circuit configuration · Temperature rise · Contact resistance · Endurance · Torque · Seal · Dielectric withstanding voltage · Insulation · Shock and Vibration · Terminal strength · Strength of mounting bushing · Visual and mechanical

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Panel-mounted Selector Switches

Type IC5846

Switch arrangement is basically a 4 pole, 2 position break before make (non-shorting) switch deck. Choose from 1 to 5 decks. As many as 20 circuits, if 5 decks used, can be transferred at one time.

Rotor Contact Configuration
Nickel plated brass handle will be furnished unless otherwise specified. Use of small soldering iron to attach wires to terminals is highly recommended to prevent damage due to excessive wear and tension to the Kel-F sections. Rosin core solder is best to use when soldering the terminal leads.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Panel-mounted Pushbuttons

Specification
Application Forms Contacts

MIL-C-2212
Momentary operation in control circuits of magnetic starters. Standard, oiltight, and watertight forms are available. Select from three contact arrangements listed below.

Ordering Information
Order pushbutton by catalog number. Nameplate, if required, must be ordered separately. Order standard nameplate by catalog number. Specify marking for special nameplate.)

Contact Arrangement
1 N.O., 1 N.C. 2 N.O. 2 N.C.

Standard
5729215G1 5729215G23 5729215G22

Catalog Number

Watertight

W/ Black

W/ Red

Oiltight

Rubber Cap

Rubber Cap

5729215G18 5729215G19 5729215G20

205A234G5B 205A234G6B 205A234G8B

205A234G5R 205A234G6R 205A234G8R

Contact Ratings (Amperes)

Volts

Carry Continuous

115 VAC

10

440 VAC

10

115 VDC

10

230 VDC

10

Interrupt
3.0 .75 1.1 .55

Wiring Symbols

Type IC5845
Watertight Oiltight

Standard

Panel-mounted Pushbuttons

Standard Nameplates

Nameplate Marking

Catalog Number Standard

Stop* Start Off On Forward Reverse Hoist Lower High Speed Low Speed Fast Slow Emergency Run Emergency Stop* Emergency Start Test Switch Run Jog Reset ­

NP161882D NP161882B NP161882N NP161882P NP161882G NP161882H NP161882R NP161882S NP161882C NP161882E NP161882J NP161882K NP161882L NP161882T NP156339A NP161882M NP161882F NP161882U NP100505D NP161882A

* Red letters ** Navy approved adhesive backed "stick-on" type.

Oiltight
NP93003A NP93003B NP93286C NP93286D NP99360C NP99360D NP93286E NP93286F NP94562C NP94562D NP93286G NP93286H NP93286A NP93286J NP93286K NP93286L NP93286M NP93286N NP93286P NP93286B

Watertight**
245A6295P004 245A6295P005 245A6295P028 245A6295P029 245A6295P035 245A6295P036 245A6295P037 245A6295P038 245A6295P039 245A6295P040 245A6295P002 245A6295P003 245A6295P030 245A6295P021 245A6295P041 245A6295P042 245A6295P043 245A6295P044 245A6295P032 245A6295P001

Pushbutton Standard
Oiltight
Watertight

Contact Arrangement

Dimensions in Inches Front of Panel Back of Panel

Maximum Panel Thickness

Weight in Ounces

1 N.O., 1 N.C. 0.38

1.47

0.13

4

2 N.O.

0.38

2.00

0.13

4

2 N.C.

0.38

2.13

0.13

4

1 N.O., 1 N.C. 0.31

1.82

0.25

5

2 N.O.

0.31

2.35

0.25

5

2 N.C.

0.31

2.48

0.25

5

1 N.O., 1 N.C. 0.50

1.82

0.19

6

2 N.O.

0.50

2.35

0.19

6

2 N.C.

0.50

2.48

0.19

6

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5845

Panel-mounted Pushbuttons
Outline and Mounting Dimensions (In Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5845

Power Terminal Boards

Specification Application
Rating.

MIL-C-2212 and MIL-E-917
These one-piece terminal boards are for use in power circuits up to the amp rating listed. 50 through 600 amps, 600 volts (max.), number of points - three.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5885

Outline and Mounting Dimensions (In Inches)

Dimenstions in Inches

Front Mtg.

Term.

Rating Amp A

B

C

D

E

of Base

Hole Diam.

Screw Size

Weight in Lbs.

Type IC5885 three-point power terminal board

50

1.38

2.94

0.89

1.16

0.69

1.50

0.22

0.19

0.38

100

2.00

3.66

1.13

1.41

1.00

1.56

0.22

0.25

0.69

150

2.00

3.66

1.13

1.41

1.00

1.56

0.22

0.31

0.81

400

2.50

4.82

1.47

1.88

1.25

2.38

0.31

0.50

2.00

600

3.50

6.32

1.97

2.38

1.75

2.38

0.31

0.50

3.25

Ordering Information
Order by catalog number.

Rating Amp

Number of Points

Catalog Number

50

3

100

3

150

3

400

3

600

3

8690261G1 8690262G1 8690262G2 147A3155G1 144A2191G1

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Automatic Bus Transfers

Series 4685

Series 4685 Automatic Bus Transfers provide for the automatic or manual transfer of three phase A.C. loads from the ship's service supply to the emergency supply in case of low voltage or voltage failure. When normal conditions are restored, the load will be transferred automatically to the ship's service supply.

Specification

MIL-S-17773 (Ships)

Enclosure Operation Switching Mechanism Duty Ambient Insulation Mounting Transfer Position Ratings

Dripproof or Watertight* Automatic Contactors, motor driven Continuous 50o C Class A Bulkhead Two way Amperes: 25, 50, 100, 150, 300, and 600 Voltage: 120 or 450 3 ph., A.C., 60 Hz. or 400 Hz.

*Can be furnished less enclosure for switchboard mounting.

Types
Amp Rating

Type ABT-A1 Part No. 60 Hz*

25

N296

50

N297

100

N294

150

N298

300

N299

600

N293

* For 400 Hz. Add "-41" to Part No.

Type ABT-A2 Part No. 60 Hz*
N286 N287 N284 N288 N289 N283

Type ABT-A3 Part No. 60 Hz*
N276 N277 N274 N278 N279 N273

A.C. Automatic Bus Transfer, dripproof enclosure
Types
ABT-A1-Automatic, for A.C. service, instantaneous without phase failure operation.
ABT-A2-Automatic, for A.C. service, instantaneous with phase failure operation.
ABT-A3-Automatic, for A.C. service, time delay without phase failure operation.
Ordering Information
When ordering A.C. Automatic Bus Transfers, the following information is requested:
1. Type (i.e. Type ABT-A1) 2. A.C. voltage 3. Current in amperes 4. Type of enclosure

Repair Parts
Repair parts normally furnished in accordance with applicable part allowance list include:
1 set of contacts 1 set of springs

Automatic Bus Transfers

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Series 4685

Dripproof Enclosure Dimensions*

Amp Rating Size

Approximate Dimensions (inches)

A

B

C

25, 50, 100 150 300 600

19 1/2 28 30 36

16 24 26 32

1111////2222

12 18 18 22

*Watertight enclosure dimensions available on request.

D 11163331111/1///2622

E
13 3/4 18 23 23

F

11 14 19 19

3113////8224

Fuse Blocks

Specification
Application
Construction Rating Form Catalog Number

Fuse block meets MIL-E-917 and MIL-S-901 (for shock). Fuse clips meet MIL-F-21346.
Use fuse blocks for holding cartridge-type fuses through 30 amps. Designed for use with style F61 fuses (9/16 " dia. x 2" long) of Specification MIL-F-15160. Molded plastic block. Copper-clad steel fuse clips. 30 amps, 600 volts (max.) Single pole 9108323G1

Outline and Mounting Dimensions (In Inches)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Type IC5898
Type IC5898 Fuse Block
Ordering Information
Order by catalog number.

Control Circuit Transformers

Series 106.531 Transformers reduce supply voltage to 115 volts A.C. in control cricuits of motor starters, controllers and other equipment.

Specification
Type Application Duty Ambient Insulation

MIL-C-2212, MIL-T-16315 where applicable, MIL-E-917
Series 106.531, Control Circuit Voltage step down. Continuous 50o C Class B

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
Series 106.531

Dimensions (Approx.)

Typical Control Circuit Transformer

\

Catalog

V.A.

Volts, 60 Hz

Dimensions - Approx. (in inches)

Number

Rating

Primary Secondary A

B

C

D

E

106.531-1 106.531-2 106.531-3 106.531-5 106.531-6 106.531-7

500 1000 2000 3000 1500 250

440

115

440

115

440

115

440

115

440

115

440

115

5 1/4

4 3/8

4 3/8

5 3/8

1/8

7 1/8

3 7/8

5 3/4

5 1/8

.134

9

4 3/4

7 1/2

6 3/8

3/16

9

5 3/8

7 1/2

7 3/8

3/16

7 1/8

4 13/16 5 3/4

6 1/8

.134

4 1/2

3 7/8

3 3/4

4 3/8

1/8

F
3 3/4 5 6 6 5 1/4

G

H

3 1/2

5/16

3

5/16

3 3/4

5/16

4 3/8

5/16

3 15/16 5/16

3

5/16

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Indicator Lights
Two Lamps vs. One Lamp
The Dualamp Indicator Light revolutionizes the single lamp concept. When there is only one lamp and it is out, it may mean a real signal indication or just a burnt out lamp. This element of doubt is eliminated with the Dualamp since no two lamps burn out simultaneously. When both lamps are out it means a real signal indication.
The Dualamp Indicator Light uses 2.5 volts alternating current (VAC) lamps in parallel which are independently supplied by a 1.8 VAC closely regulated transformer for a long lamp life. Depending on the indicator light selected, it can be used on voltages such as 117 or 450 VAC. Dualamp Indicator Lights are also available for direct current voltages (VDC). Inquiries on other line voltages that may not be listed are invited. Hardware (Oring, hex nut, cup washer) are included. Midget screw base lamps and lenses are purchased separately.

Lamp
W-L-00111/56 (#1769:MS15612-3)
W-L-00111/46 (#342:MS15612-5)
W-L-00111/45 (#335:MS15612-2)

Rated Volts
2.5 6 28

Design Candlepower Filament

Life Avg. Primary

Amps. (Approx.)

Designation (Hrs.)

Service

0.20

0.20

0.04

0.04

0.04

0.34

C-2R C-2V C-2F

500 1000 1000

A.C. D.C. A.C.

Various Lengths Available
Lamp Accomodation
Dualamp Indicator Lights use incandescent midget screw base lamp in accordance with federal specification W-L-00111 and industry numbers. Two per unit. Clear finish.

Indicator Light
The Dualamp Indicator Light has been tested and approved for dielectric withstanding voltage, moisture resistance, voltage regualtion, temperature rise, shock, vibration, visual and dimensional. Application with 50, 60, or 400 Hz A.C. systems.

JHSLC P/N
LH 81/1 LH 98/2 LH 98/3 LH 98/4 JHS 1410
JHS 1510 JHS 1610

Primary VAC

Secondary VAC

12

1.8

26

1.8

117

1.8

450

1.8

400

1.8

(3000) Spike

220

1.8

440

1.8

(3000) Spike

Lamp Accomodation
W-L-00111/56 (#1769:ms15612-3)

Lenses Available
LC 38 thru 45

Dimensions

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LH 98

Indicator Light

The Dualamp Indicator Light lampholder is used for direct current applications and where personnel safety must be obtained without putting a ground on the system. The lamp sockets are recessed into an insulated core and the circuit is automatically disconnected when the lens is removed to replace the lamps. The two lamps are connected to a resistor contained within the unit.

JHSLC P/N

Primary Secondary

VAC

VAC

Resistor Rating

Lamp Accomodation

Lenses Available

LH 96/1 6

6

LH 96/2 12

6

LH 96/3 24

6

LH 96/4 48

6

LH 96/5 120

6

LH 96/6* 240

6

none 300 ohm 5 W 600 ohm 5 W 1200 ohm 5 W 2800 ohm 5 W 6300 ohm 5 W

W-L-00111/46 (#342:MS15612-5

LC 38 thru 45

*The resistor for this unit must be mounted externally due to length.

Dimensions (Approx.)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LH 96

VDC VDC

(Bulb)

Indicator Light
The Dualamp Indicator Light lampholder is used for direct current applications and where personnel safety must be obtained without putting a ground on the system. The lamp sockets are recessed into an insulated core and the circuit is automatically disconnected when the lens is removed to replace the lamps. The two lamps are connected to separated resistors thereby featuring the same Dualamp advantages.
Lamp Accomodation: W-L-00111/46 (Industry #342; MS15612-5)
Lenses Available: LC 38 thru 45 (see page 67)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LH 95

Dimensions (Approx.)

Indicator Light

The Dualamp Indicator Light has been tested and approved for dielectric withstanding voltage, moisture resistance, voltage regualtion, temperature rise, shock, vibration, visual and dimensional. Application with 50, 60, or 400 Hz A.C. systems.

JHSLC P/N
LH 94/1 LH 94/2 LH 94/3 LH 94/4

Primary VAC
12 26 117 450

Secondary VAC
1.8 1.8 1.8 1.8

Lamp Accomodation
W-L-00111/56 (#1769:MS15612-3)

Lenses Available
LC 32 thru 45

Dimensions (Approx.)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LH 94

Lenses

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LC 38 thru 45
LC 41 thru 45
These panel mounted lenses are in accordance with MIL-L-3661/55 thru 59. Any engraving must be specified along with color since these lenses are specially engraved to your order.

LC 38 MIL-L-3661/52

LC 39 MIL-L-3661/53

LC 38 MIL-L-3661/52

Color

P/N

Colorless Red White Blue Green Yellow

LC 38 CN1 LC 38 RN1 LC 38 WT1 LC 38 BN1 LC 38 GN1 LC 38 YN1

LC 39 MIL-L-3661/53

Color

P/N

Colorless Red Blue Green Yellow

LC 39 CN1 LC 39 ED1 LC 39 BD1 LC 39 GD1 LC 39 YD1

Material: Plexiglass

Material Glass

LC 40 MIL-L-3661/54

LC 40 MIL-L-3661/54

Color

P/N

Colorless Red White Blue Green Yellow Unfrosted Colorless

LC 40 CN3 LC 40 EN3 LC 40 WT3 LC 40 BN3 LC 40 GN3 LC 40 YN3
LC 40 TN3

Material: Plastic

MS 17140
Flush type indicator light lenses are available in various colors. Engraving must be specified.

Indicator Light Holder
This light is to be used on alternating current where space behind the panel is limited and where a light with the built-in transformers which can be mounted elsewhere on the panel and can be connected to the LH 97 to obtain the required voltages. The lamp screw shells are grounded to the case so that when the lamps are removed, there is no shock hazard to personnel.
Application with 50, 60, or 400 Hz A.C. systems.
Lamp Accomodation - W-L-00111/56 (#1769; MS15612-3)
Lenses Available - LC38 thru 45 (see page 67)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LH 97

Dimensions (Approx.)

Indicator Light Transformer
Without lamp or lens accomodation, this self-contained transformer indicator light can be used in conjunction with the LH97 lampholder. The LH93 power transformer unit has been tested and approved for dielectric withstanding voltage, moisture resistance, voltage regulation, temperature rise, shock, vibration, visual and dimensional.
Application with 50, 60, or 400 Hz A.C. systems.
This unit is available in different primary voltage ranges from 12 VAC (LH93/1); 26 VAC (LH93/2); 117 VAC (LH93/3); 450 VAC (LH93/4) with secondary voltage at 1.8 VAC.

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801
LH 93

Dimensions (Approx.)

Ward Leonard Electric Company Inc. 401 Watertown Road
Thomaston, CT 06787 USA Tel: 860-283-5801

Switch Boxes (for Sound Powered Telephone) Types A-17A and A-19A

This telephone system elminates need to have a power source from the outside or with a battery. Power is supplied by the person's voice thus communications are not disrupted due to power outage.
· Shock per MIL-S-901
· Vibration MIL-STD-167
· Watertight MIL-STD-108E
· Dielectric Test
· Insulation resistance
· Electrical continuity
· Non-magnetic (less than 2.0 mu)

Symbol 2861.1 Type A-19A

Includes 20 Rotary Selector Switches

Symbol 2860.1 Type A-17A


QuarkXPress(tm) 6.0 QuarkXPress(tm) 6.0