Installation Guide for FoundationTM models including: BAYTBUE320, G-EB 036-060, G-ED 036-060, BAYTBGF320, GB 036-060, GD 036-060, BAYTBUE320 Gas and Electric Connections Packaged Rooftop Units, BAYTBUE320, Gas and Electric Connections Packaged Rooftop Units, and Electric Connections Packaged Rooftop Units, Electric Connections Packaged Rooftop Units, Connections Packaged Rooftop Units, Packaged Rooftop Units, Rooftop Units, Units

Through-the-Base Gas and Electric Connections

2 days ago — Read this manual thoroughly before operating or servicing this unit. Safety advisories appear throughout this manual as required. Your personal safety and.


File Info : application/pdf, 2 Pages, 1.19MB

PDF preview unavailable. Download the PDF instead.

ACC-SVN189D-EN 08232024
Installation Instructions
Through-the-Base Gas and Electric Connections
FoundationTM Packaged Rooftop Units 3 to 5 Tons

Model Number:

Used With:

Through-the-Base Electric

BAYTBUE320*

G/EB*036-060

G/ED*036-060

Through-the-Base Gas BAYTBGF320*

GB*036-060 GD*036-060

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

August 2024

ACC-SVN189D-EN
©2024

4
General Information
These instructions describe field assembly and installation for through-the-base gas and through-the-base electric options. Instructions are for units with a 1/2-inch gas supply line.

Inspection
1. Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company. Replace damaged parts with authorized parts only.
2. Compare the order number on the shipping label with the accessory identification information on the ordering and shipping documents to verify that the correct accessory has been received.

Parts List

Through-the-Base Gas

Through-the-Base Electric

Description

Qty

Description

Qty

Fitting - Pipe: 0.50 NPS X 3.50 length, Black Finish 3 Connector - Conduit, 1/2 Straight 1

Union - Ground Joint, 0.50-in. NPTI

2 Connector - Conduit, 1 1/4 Straight 1

Elbow: 90 Degree, 0.50-in.

2

--

--

Tee Pipe: 0.50 NPTI

1

--

--

Cap, Pipe: 0.50 NPS

1

--

--

Fitting - Pipe: 0.50 NPS X 3.00 length, Black Finish 1

--

--

Valve: Gas Shut-Off 0.50 NPTI

1

--

--

Fitting - Pipe: 0.50 NPS X 8.00 length, Black Finish 1

--

--

Fitting - Pipe: 0.50 NPS X 6.00 length, Black Finish 1

--

--

Elbow: NPS 90 Degree

1

--

--

Grommet - Molded, 0.825-0.919 ID MLD

2

--

--

TBUG Bracket

1

--

--

Union - Pipe, Ground Joint

2

--

--

1
Warnings, Cautions, and Notices
Read this manual thoroughly before operating or servicing this unit. Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

NOTICE

Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

2
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
· Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
· When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
· If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other countryspecific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

3
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
· All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
· Non-Trane personnel should always follow local regulations.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

5
Installation
WARNING Hazardous Voltage and Gas!
Failure to turn off gas or disconnect power before servicing could result in an explosion or electrocution which could result in death or serious injury. Turn off the gas supply and disconnect all electric power, including remote disconnects, before servicing the unit. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
Figure 1. Through-the-base fittings location
TBUE Low Volt.

6

Table 1. Through-the-base holes size chart

BAY Kit Number BAYTBGF320*
BAYTBUE320*

Connection Size 1/2 1/2 1-1/4

Usage

Hole Size On Base Pan

TBUG

1-5/8

TBUE ­ Low Voltage

7/8

TBUE ­ High Voltage

1-3/4

1. Locate three embossed dimples in the base pan near the base of the compressor (see Figure 1). These dimples mark the locations where high voltage power, control wires, and gas connection will be routed through the roof curb and the unit base pan.
2. Using a round knockout hole punch, punch out embossed dimples. See Table 1 for correct punch size.
Installation ­ Through-the-Base Gas
Note: See Figure 2 for installation steps below.
1. Slide grommet over gas supply line and fit the line through the gas connection hole in the base pan (see Figure 1). 2. Apply pipe sealant on threads of the gas supply line. Tighten an elbow on the gas supply. 3. Apply sealant on 6-inch fitting and add pipe union to the other end. 4. Apply sealant on 8-inch fitting and tighten on the pipe union. Slide the grommet over 8-inch fitting and hook in the grommet to support bracket. 5. Thread and tighten the gas shut-off valve on to the other end of 8-inch pipe fitting. 6. Apply pipe sealant on threads of a 1/2-inch elbow, thread and tighten into the other end of the shut-off valve. 7. Apply pipe sealant on threads of 3-inch fitting and thread the fitting into the other end of the 1/2-inch elbow. 8. Apply pipe sealant on threads of a 1/2-inch Tee, thread and tighten into 3-inch fitting coming off of the elbow. 9. Thread and tighten a 3.5-inch pipe fitting onto the lower end of the 1/2-inch tee and thread and tighten cap at the end. 10.Apply pipe sealant on threads of 1/2-inch 90°elbow. Thread and tighten into tee on one end and 3.5-inch fitting on other end. 11.Apply pipe sealant on pipe union and thread and tighten into the 3.5-inch fitting. 12.Apply sealant to both ends of 3.5-inch fitting, slide through opening on the side post. Thread and tighten the 3.5-inch pipe on one end into pipe union and other
end into gas valve.

TBUG

TBUE High Volt.

7

Figure 2. Through-the-base gas connection

Support bracket 1/2-in. x 6-in. pipe fitting

Pipe union

Grommet

90° elbow

Screw

See detail A

1/2-in. x 3 1/2-in. pipe fitting
Pipe union 1/2-in. x 3 1/2-in. pipe fitting 1/2-in. elbow Tee

1/2-in. x 8-in. pipe fitting
Gas shut-off valve
1/2-in. elbow

1/2-in. x 3-in. pipe fitting 1/2-in. x 3 1/2-in. pipe fitting Pipe cap

Customer gas supply pipe Grommet 0.600

DETAIL A

8 Installation ­ Through-the-Base Electric
Note: See Figure 3 for installation steps below. 1. Install electrical bulkhead connectors. Place one connector beneath the base pan and mount the other above the base pan. 2. When the electrical bulkhead connectors are in place, field supplied and installed liquid tight conduit connectors and conduits may be attached to the connectors. 3. Pull correctly rated high voltage and low voltage wires through appropriate conduits (see Figure 1) and connect to the unit. Refer to the Installation, Operation, and
Maintenance ship-with manual. Important: Follow all local and national electrical codes when installing electrical service to the rooftop.
Figure 3. Through-the-base electrical conduits

SEAL BETWEEN WIRING AND CONDUIT WITH
WEATHER PROOF SEALER TO PREVENT AIR LEAKAGE

CONTROL WIRING CONDUIT POWER WIRING CONDUIT

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

ACC-SVN189D-EN 23 Aug 2024 Supersedes ACC-SVN189C-EN (Jul 2024)