TSD077-99-Fusion-Loop-Module-Installation-Issue-9
Loop Module Installation Guide

Fusion Partno FCX-532-001

Description
Fusion Loop Module

POWER
FAULT ISOLATOR
ACTIVE

1 Pre installation

Installation must conform to applicable local installation codes

!

and should only be installed by a fully trained competent person.

· Ensure the loop module is installed as per the site survey.

· Refer to step 3 to ensure optimised wireless performance.

· If using remote aerials with this product, refer to the remote aerial installation guide (MK293) for more information.

· A maximum of 5 loop modules can be connected per loop.

· This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.

2 Components

12

3

4

5

1 4x corner covers, 2 4 x lid screws, 3 Loop module lid, 4 Loop module PCB, 5 Loop module back box

3 Mounting location guidelines

For optimum wireless

performance, the following

2 m

must be observed:

· Ensure the loop

module is not installed

within 2 m of other

wireless or electrical

equipment

(not

including the control

panel).

0.6 m

Loop

POWER FAULT ISOLATOR

ACTIVE

module

FIRE
Control panel
Fire Alarm Control

· Ensure the loop module is not installed within 0.6 m of metal work.

4 Optional PCB removal
· Remove the three circled retaining screws, before unclipping the PCB.

RESET

TX RX RADIO

POWER
FAULT
ISOLATE WD

ON

12 34 56 78 1 2 3 4 5 6 7

0V

RX

HELP

TX

3V

BACK

LOOP IN
-

LOOP OUT
-

+ SCR + SCR

5 Remove cable entry points
· Drill the cable entry points as necessary.
= DO NOT use = Available cable
entry points ©2024 EMS Ltd. All rights reserved.

6 Fix to the wall
· All five circled fixing positions are available for use as required.
· The key hole can also be used for locating and fixing where required.

Page 1 of 2

TSD077-99 (Issue 9) 10/01/2024 AJM

7 Connection wiring

· Loop cables should only be passed via the access points available. · Flame retardant cable glands must be used. · DO NOT leave excess cable inside the loop module.

Single loop module. Control panel
Screen

Scr

Loop module 1
Loop Loop IN OUT
+- +-

Loop + OUT -

Loop + IN -

Screen not connected

Multiple loop modules (max. 5)
Loop module 1 Loop Loop
IN OUT +- +-

Scr Scr

Scr Scr

Loop module 2
Loop Loop IN OUT
+- +-

Scr

Loop module 3
Loop Loop IN OUT
+- +-

Scr

Control panel
Screen
Loop + OUT -
Loop + IN -

Screen not connected

9 Apply power

Apply power to the control panel. The normal LED states for the Loop Module are as below:
· The green POWER LED will illuminate.

· The other LEDs should be extinguished.

POWER FAULT ISOLATE

+ SCR + SCR

RESET

TX RX RADIO

POWER
FAULT
ISOLATE WD

ON

12 34 56 78 1 2 3 4 5 6 7

0V

RX

HELP

TX

3V

BACK

LOOP IN
-

LOOP OUT
-

Scr

8 Configuration

· Set the loop module address using the on-board 8 way switch. · Available selections are shown in the table below.

Addr. 1 2 3 4
5 6 7 8 9 10

DIL
SWITCH
SETTING
1. . . . . . 8 10000000 01000000 11000000 00100000 10100000 01100000 11100000 00010000 10010000 01010000

51 11001100 52 00101100 53 10101100 54 01101100 55 11101100 56 00011100 57 10011100 58 01011100 59 11011100 60 00111100

101 10100110 102 01100110 103 11100110 104 00010110 105 10010110

Addr. 11 12 13 14 15 16 17 18 19 20
61 62 63 64 65 66 67 68 69 70
106 107 108 109 110

DIL SWITCH SETTING 1. . . . . . 8 11010000 00110000 10110000 01110000 11110000 00001000 10001000 01001000 11001000 00101000
10111100 01111100 11111100 00000010 10000010 01000010 11000010 00100010 10100010 01100010
01010110 11010110 00110110 10110110 01110110

Addr. 21 22 23 24
25 26 27 28 29 30

DIL
SWITCH
SETTING
1. . . . . . 8 10101000 01101000 11101000 00011000 10011000 01011000 11011000 00111000 10111000 01111000

71 11100010 72 00010010 73 10010010 74 01010010 75 11010010 76 00110010 77 10110010 78 01110010 79 11110010 80 00001010

111 11110110 112 00001110 113 10001110 114 01001110 115 11001110

Addr. 31 32 33 34 35 36 37 38 39 40
81 82 83 84 85 86 87 88 89 90
116 117 118 119 120

DIL SWITCH SETTING 1. . . . . . 8 11111000 00000100 10000100 01000100 11000100 00100100 10100100 01100100 11100100 00010100
10001010 01001010 11001010 00101010 10101010 01101010 11101010 00011010 10011010 01011010
00101110 10101110 01101110 11101110 00011110

Addr. 41 42 43 44
45 46 47 48 49 50

DIL
SWITCH
SETTING
1. . . . . . 8 10010100 01010100 11010100 00110100 10110100 01110100 11110100 00001100 10001100 01001100

91 11011010 92 00111010 93 10111010 94 01111010 95 11111010 96 00000110 97 10000110 98 01000110 99 11000110 100 00100110

121 10011110 122 01011110 123 11011110 124 00111110 125 10111110 126 01111110

· The system can now be programmed.
· Refer to the Fusion programming manual (TSD062) for details of compatible FireCell devices and full programming information.

10 Close loop module
· Ensure that the loop module PCB is correctly inserted and the PCB retaining screws are refitted.
· Refit the loop module lid, ensuring LEDs are not damaged by the light pipe when refitting.

POWER
FAULT ISOLATOR
ACTIVE

Specification

Operating temperature

-10 to +55 °C

Storage temperature

5 to 30 °C

Humidity

0 to 95% non-condensing

Operating voltage

17 to 28 VDC

Operating current

17 mA (typical) 91mA (max.)

IP rating

IP54

Operating frequency

868 MHz

Output transmitter power 0 to 14 dBm (0 to 25 mW)

Signalling protocol

X

Panel protocol

XP

Dimensions (W x H x D)

270 x 205 x 85 mm

Weight

0.95 kg

Location

Type A: For indoor use

©2024 EMS Ltd. All rights reserved.

Regulatory information

Manufacturer

Carrier Manufacturing Poland Sp. z o.o. Ul. Kolejowa 24. 39-100 Ropczyce, Poland

Year of manufacture Certification Certification body

See devices serial number label
13 0905

CPR DoP Approved to

0359-CPR-0222
EN54-17:2005. Fire detection and fire alarm systems. Part 17:Short-circuit isolators.
EN54-18:2005. Fire detection and fire alarm systems. Part 18:Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems.

European Union Directives

EMS declares that this device is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk

2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info Dispose of your batteries in an environmentally friendly manner according to your local regulations.

Page 2 of 2

TSD077-99 (Issue 9) 10/01/2024 AJM

