ICM517A Surge Protective Device

Product Information and Installation Guide

Safety Information

⚡ ELECTRICAL SHOCK HAZARD – Before installing this unit, turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position.

ATTENTION: No replaceable or repairable parts. (French: ATTENTION: Aucune pièce remplaçable ou reparable)

⚠️ WARNING – SHOCK HAZARD – DO NOT OPEN; (French: ATTENTION – RISQUE DE CHOC – NE PAS OUVRIR)

Device is intended to be connected only to panel connection. All wiring must conform to national, state and local electrical codes. 14AWG wire or larger required. Product contains no serviceable parts.

Mode of Operation

The ICM517A is UL Rated as a Type 2 device and must be installed before the equipment it is intended to protect. It can be installed at the A/C disconnect or an indoor/outdoor electrical panel. Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical amperes, 240V max, when protected by a circuit breaker rated 15-60A maximum and 120V minimum. Device wires should be kept at a minimal length to increase response time and effectiveness of the control. Contains no serviceable parts. An LED indicates when surge protection is present.

Warranty: Limited lifetime product, up to a 3-year $10,000 connected equipment warranty.

Installation Instructions

  1. Turn off the main breaker and/or main power to the service disconnect.
  2. Remove the cover on the service disconnect or the electrical panel.
  3. Mount through conduit connection of electrical panel:
    • Remove one lock nut and sealing ring on the unit.
    • Feed the wires into the electrical panel service disconnect.
    • Re-secure the lock nut and sealing ring (refer to mounting instructions).
  4. Route the green wire to the grounding lug and secure.
  5. Connect the two black wires and one white wire (refer to wiring diagrams for 120 & 240VAC).
    • For electrical panel: Connect to the closest two-pole breaker (240VAC).
    • For electrical panel: Connect to the closest single-pole breaker (120VAC).
    • For A/C disconnect: Connect to the disconnect load side terminals.
  6. Reinstall the cover on the service disconnect or the electrical panel.
  7. Restore power; the LED should be on, indicating 120 VAC present from black to green and black to white.
  8. Close the electrical panel or cover.

Wiring Diagrams

120 VAC Wiring

Indoor Installation (120 VAC Shown)

Connect the ICM517A unit's green wire to the Ground Bus. Connect the white wire to the Neutral Bus. Connect the black wire to the appropriate breaker terminal.

Outdoor Installation (120 VAC Shown)

Connect the ICM517A unit's green wire to Ground. Connect the white wire to Neutral. Connect the black wire to the Line 1 terminal.

240 VAC Wiring

Indoor Installation (240 VAC Shown)

Connect the ICM517A unit's green wire to the Ground Bus. Connect the two black wires to the terminals of the closest two-pole breaker.

Outdoor Installation (240 VAC Shown)

Connect the ICM517A unit's green wire to Ground. Connect the two black wires to the Line 1 and Line 2 terminals.

Mounting Diagram

1. Thread one lock nut all the way down the ICM517A nipple as far as it will go and remove the second lock nut, setting it aside.

2. Install the ICM517A nipple through the knockout in the disconnect box.

3. Install the rubber washer over the nipple on the inside of the disconnect box.

4. Install the second lock nut on the nipple and tighten down until the assembly is secure, adjusting the outer nut if needed to tighten up the assembly.

Specifications

Feature Details
Service Voltage 120/240 volt, single phase
Maximum Surge Current 100,000 amps
Maximum Energy Dissipation 1,020 joules
Installation Point Electrical panel, electrical disconnect
Diagnostics Green light indicates surge suppression present
Enclosure NEMA Type 4X waterproof metal enclosure
AC Protection Modes L-L, L-N, L-G, N-G
Conduit Connection 3/4"
Dimensions 5.0" L x 3.06" W x 1.75" D
Weight 0.55 lbs.

Limited Lifetime Protection Warranty

For warranty information and registration, please go to www.icmcontrols.com and click on Warranty Registration.

Models: ICM517A, ICM517A Surge Protective Device, Surge Protective Device, Protective Device

File Info : application/pdf, 1 Pages, 327.91KB

ICM517A-LIAF212-6

References

Adobe PDF Library 17.0 Adobe InDesign 18.4 (Macintosh)

Related Documents

Preview ICM517A Surge Protective Device Installation, Operation & Application Guide
Comprehensive guide for installing, operating, and applying the ICM517A Type 2 Surge Protective Device. Includes specifications, wiring diagrams, safety warnings, and warranty information from ICM Controls.
Preview ICM517A-LITE Surge Protective Device Installation Guide
Installation, operation, and application guide for the ICM517A-LITE UL Rated Type 2 Surge Protective Device from ICM Controls. Includes specifications, wiring diagrams, and mounting instructions.
Preview ICM Controls ICM517A Surge Protective Device Installation Guide
Comprehensive installation, operation, and application guide for the ICM Controls ICM517A Single-Phase Surge Protective Device. Includes wiring diagrams, specifications, and safety information.
Preview The Need for Surge Protection in HVAC Systems During Colder Months
This white paper from ICM Controls explains the critical need for surge protection in HVAC systems, especially during colder months. It details winter-related electrical risks, surge protection device specifications, recommended products, and implementation strategies to prevent costly repairs and ensure system longevity.
Preview ICM495-30A/60A Disconnect with Internal Surge Protection Installation Guide
Installation, operation, and application guide for the ICM495-30A/60A disconnect with internal surge protection. Includes features, specifications, mode of operation, replacement parts, and installation instructions.
Preview ICM Surge Protection Comparison: ICM517A-LITE, ICM517A, ICM518 & Competitors
Detailed comparison of ICM Controls' ICM517A-LITE, ICM517A, and ICM518 surge protection devices against models from MARS, RectorSeal, Ditek, Intermatic, and Eaton. Features, specifications, and ratings for protecting equipment from electrical surges.
Preview ICM Controls SENTRY 3N1 Single-Phase Voltage & Surge Protected Disconnect
Detailed overview of the ICM Controls SENTRY 3N1, a single-phase voltage and surge protected disconnect device for HVAC/R and other applications. Features include surge protection, voltage monitoring, and a 40A contactor.
Preview ICM517A-LITE Surge Protection Device - ICM Controls
Discover the ICM517A-LITE, a compact Type 2 Surge Protective Device (SPD) from ICM Controls. This device offers reliable surge protection for single-phase equipment, featuring superior TMOV technology, a 60,000 amps surge capacity, and a NEMA Type 4X waterproof enclosure. Ideal for protecting motors, electronics, HVAC systems, and appliances.