Instruction Manual
RS Pro Infrared Temperature Sensor with Voltage Output and UART
Stock Number: 238-7241

EN

Introduction
The RS Pro UART Infrared Temperature Sensor is a device for measuring the temperature of the surface of a solid or liquid without contact. Its extremely small size makes it ideal for installation where space is restricted.
The sensor works by detecting infrared energy that is emitted by the target object. The temperature is available digitally via UART using the Modbus RTU protocol, or it can be monitored continuously via the DC voltage output, e.g. with industrial process instrumentation. The sensor also has a configurable alarm output.

Specifications
GENERAL

Measurable Temperature Range Analogue Output Alarm Output
Field of View Accuracy Repeatability Response Time Emissivity Emissivity Setting Range Max Temperature Span (Linear Output) Min Temperature Span (Linear Output) Spectral Range Supply Voltage Min. Supply Voltage (at Sensor)
Max Current Draw (Sensor) Open Collector Alarm Output

0 to 1000°C 0-5 V DC, linear with measured temperature Open collector with adjustable temperature threshold and hysteresis, configurable via UART 15:1 divergent optics ± 1.5% of reading or ± 1.5°C, whichever is greater ± 0.5% of reading or ± 0.5°C, whichever is greater 250 ms Default setting 0.95, adjustable via UART 0.20 to 1.00 1000°C
100°C
8-14 m 24 V DC (max 28 V DC) 6 V DC when using voltage output 5 V DC when using UART only 30 mA 6 to 24 V DC, 50 mA max (see Electrical Installation)

ENVIRONMENTAL

Environmental Rating Ambient Temperature Range Relative Humidity

IP65 0°C to 70°C 95% max. non-condensing

2

EN

CONFORMITY

Electromagnetic Compatibility (EMC)
RoHS Compliant

EN61326-1, EN61326-2-3 (Electrical Equipment for Measurement, Control and Laboratory Use - EMC Requirements)
Yes

CONFIGURATION

Configurable Parameters
Temperature Units Signal Processing Peak / Valley Hold

Temperature range (linear analogue output) Alarm output threshold and hysteresis Emissivity setting Reflection compensation (e.g. target in oven/furnace)
°C / °F
Averaging Period (0.25 to 60 seconds)
Hold Period (0.25 to 1200 seconds)

MECHANICAL SPECIFICATIONS

Construction Cable Length Weight with Cable

Black anodised aluminium and red ABS 1 metre 65 g

Optics (Field of View)

The sensor measures the average temperature within a spot. The size of this spot depends on the distance between the sensor and the target surface. The sensor may be used at longer distances than shown, and will measure a larger spot. The measurement accuracy is not affected by the measurement distance.
3

EN
Target Size
The size of the measured spot must not be larger than the target. The sensor should be positioned so that the measured spot size is smaller than the target.
Ambient Temperature
The sensing head may be used in ambient temperatures of up to 70°C. Avoid thermal shock. Allow 20 minutes for the unit to adjust to large changes in ambient temperature.
Atmospheric Quality
Smoke, fumes, dust and steam can contaminate the lens and cause errors in temperature measurement. In these types of environment, the optional air purge collar should be used to help keep the lens clean.
Optional Accessories
An adjustable mounting bracket and air purge collar are available. These may be ordered at any time and added on-site.
Mechanical Installation
The sensor can be attached to brackets or mountings of your own design, or you can use the optional mounting bracket accessories shown below. Use two M3 mounting screws (included) to fix the sensor to a mounting plate or bracket with a third, central hole for the sensor to "see" through. We recommend a hole of diameter 13 to 16 mm in a mounting plate of up to 2 mm thickness. Ensure the mounting does not obstruct the sensor's field of view (FOV); refer to the optical diagram in Specifications and allow a clear area twice the size of the FOV cone for maximum accuracy. 4

Dimensions and Connections (Analogue Output)

EN

For UART connections, see "Connections (UART)".
Mounting Bracket (RS Stock No. 905-8777)

5

EN
Air Purge Collar (RS Stock No. 905-8770)
The optional air purge collar is used to keep dust, fumes, moisture and other contaminants away from the lens. Air flows into the hose barb fitting and out of the front aperture. Air flow should be 5 to 15 litres per minute. Clean or "instrument" air is recommended.
Two M3 screws (included) secure both the air purge collar and the sensor to the mounting.
Electrical Installation
Check the length of the cable run between the temperature sensor and the measurement instrument. If necessary, the cable can be extended using a shielded cable with 4 or more cores (3 if the alarm output is not used). Ensure the shield is also extended. Connect power between the PWR+ and PWR- wires. Do not apply voltage to the incorrect wires as this will damage the sensor. See "Dimensions and Connections (Analogue Output)" and "Connections (UART)" for wiring. Ensure the supply voltage is suitable for the selected output type.
6

EN

Alarm
The sensor has an open collector alarm output. In an alarm condition, the alarm wire AL will sink current to ground through the attached load (e.g. a relay).
The alarm is deactivated for 30 seconds after power-up to allow for UART communication.
If using the alarm output, choose a load that draws no more than 50 mA when powered from 12 to 24 V DC. For example, if the alarm supply voltage is 24 V DC, ensure the load is at least 480  (24 V / 0.05 A = 480 ).

Analogue Output
If using the analogue output, use a 12 to 24 V DC power supply.
The temperature output is a 0-5 V DC signal measured between OP+ and PWR-. The output voltage is linear with measured temperature. The temperature range is configurable via UART.

UART Interface
The sensor's open collector alarm wire functions as the UART receive wire. The alarm is deactivated for 30 seconds after power-up to allow for UART communication. Once a valid Modbus command has been received, the sensor will remain in UART mode until powered down.

Connections (UART)
With power off, connect the sensor wires as follows:

Sensor wire AL (Yellow) PWR+ (Red) PWR- (Blue) OP+ (Green)

Function (UART) Receive +5 V DC 0 V Transmit

Ensure all connections are secure before applying power. 7

EN
USB Adapter
The sensor is compatible with the FTDI USB adapter (RS Stock No. 687-7786). Power is provided by the USB connection - no separate power supply is required when using the USB interface.
Connections (USB Adapter)

Use a terminal block to connect the sensor to the USB adapter. Ensure the USB adapter is not connected to the computer while making or breaking wire connections.

Connect the wires as follows:

Sensor wire AL (Yellow) PWR+ (Red) PWR- (Blue) OP+ (Green)

FTDI USB interface wire Orange Red Black Yellow

Ensure all connections are secure, then connect the USB interface to the PC.

RS Pro Config Software
The sensor is compatible with the RS Pro Config software, available as a free download from the RS website (note: alternatively, third-party Modbus software may be used).
System Requirements

·

Windows 7 or newer

·

USB 2.0 port, Internet access (for software download)

Installation

1

Download and run the software installer from the RS website

2

Follow the on-screen instructions.

Accessing the Settings Menu

Configuration settings are password protected. To access the Settings menu, go to the Unlock screen and enter the password. The default password is 1234.
8

EN
Grounding
The sensor is tested for electromagnetic compatibility (EMC) as shown in Specifications. For maximum protection against electromagnetic interference, the sensor must be connected to earth at one point, either the cable shield termination or the metal sensor housing, but not both. To minimise electromagnetic interference or "noise", the sensor should be mounted away from sources of electromagnetic interference such as motors and generators.
Operation
Once the sensor is in position and the appropriate power, air, water and cable connections are secure, the system is ready for continuous operation by completing the following simple steps:
1. Turn on the power supply 2. Turn on the connected measurement instrument 3. Read or monitor the temperature
IMPORTANT
 If the sensor is exposed to significant changes in ambient temperature (hot to cold, or cold to hot), allow 20 minutes for the sensor body temperature to stabilise before taking or recording measurements.
 Do not operate the sensor near strong electromagnetic fields (e.g. around arc welders or induction heaters). Electromagnetic interference can cause measurement errors.
 Wires must be connected only to the correct terminals. Check all connections before applying power.
 Do not damage the cable, as this could provide a path for moisture and vapour into the sensor.
 Always turn off the power before modifying electrical connections.  Do not attempt to open the sensor. There are no user-serviceable parts inside. This will
damage the sensor and invalidate the warranty.
9

EN

Modbus over Serial Line
Interface

Modbus address Baud rate Format Reply delay (ms)

1 9600 8 data, No parity, 1 stop 20

Supported functions

Read register Write single register Write multiple register Read write multiple registers

0x03, 0x04 0x06 0x10 0x17

The list below includes all available addresses. R = Read; W = Write

Address
0x00 0x01 0x02 0x04 0x05 0x06 0x07 0x08

Length (words) 1 1 2 1 1 1 1 1

0x09

1

0x0A

1

0x0B

1

0x0C

1

0x0D

1

10

Description

R/W

Sensor Type (31 for RSPro-UART)

R

Field of view (0 for 15:1)

R

Serial number

R

Modbus slave address (1)

R

Output type (0 for Voltage)

R

Reflected Energy Compensation (0 for Off; 1 for On) R/W

Reflected Temperature

R/W

Emissivity Setting (1 LSB = 0.0001)

R/W

Minimum 0.2000, Maximum 1.0000

Transmissivity Setting (1 LSB = 0.0001)

R/W

Minimum 0.2000, Maximum 1.0000

Output range low (Temperature @ 0 V)

R/W

Output range high (Temperature @ 5 V)

R/W

Alarm setpoint

R/W

Alarm hysteresis

R/W

EN

Address Length

Description

R/W

(words)

0x0E

1

Alarm settings

R/W

0/1 for Off; 2 for Low alarm; 3 for High alarm

0x0F -

-

Not used

-

0x11

0x12

1

Hold Mode

R/W

0 for Off; 1 for Peak; 2 for Valley

0x13

1

Hold Period (1 LSB = 0.1 seconds)

R/W

Minimum 0.1 seconds, Maximum 1200.0 seconds

0x14

1

Average Period (1 LSB = 0.1 seconds)

R/W

Minimum 0.1 seconds, Maximum 60.0 seconds

0x15

1

Average Temperature

R

0x16

1

Minimum Temperature

R

0x17

1

Maximum Temperature

R

0x18

1

Filtered Temperature

R

0x19

1

Unfiltered Temperature

R

0x1A

1

Sensor Temperature

R

0x1C

1

Status (bits active high)

R

Bit 0: Measurement error

Bit 1: Sensor temperature low

Bit 2: Sensor temperature high

Bit 3: Object temperature low

Bit 4: Object temperature high

0x27

1

Reflected Temperature (not saved to non-volatile

R/W

memory)

0x28

1

Emissivity (not saved to non-volatile memory)

R/W

Notes:
1. All temperature are in tenths of degrees C 2. With the exception of addresses 0x27 and 0x28, all write operations are saved to nonvolatile memory 3. For further information please refer to http://www.modbus.org/specs.php

11

EN

Configurable Settings

Emissivity Setting

Enter the emissivity setting (between 0.2 and 1.0). The emissivity setting should match the emissivity of the target surface. This can be determined experimentally by comparing measurements with a trusted contact probe, or estimated using an emissivity table.

Non-reflective non-metals, such as rubber, foods, thick plastics, organic materials and painted surfaces, generally have a high emissivity, around 0.95. This is the default setting.

Transmissivity Setting
Reflected Energy Compensation / Reflected Temperature
Average Period
Hold Mode / Hold Period
Output Range Low/High
Average Temperature Minimum/Maximum Temperature Filtered Temperature

Bare, clean metal surfaces can have a very low emissivity, and are often difficult to measure accurately. If possible, a measurable area of the surface should be painted or coated to reduce reflections and increase the emissivity.
When aiming the sensor through an IR-transmissive window, this setting should be adjusted to compensate for the presence of the window. Enter the transmissivity of the window (Enter "1" if no window is present.
In most applications, the target surface has the same surroundings as the sensor (for example, it is in the same room). In this case, Reflected Energy Compensation should remain OFF for an accurate measurement.
However, if the sensor is positioned outside an oven or furnace, with the target object inside, the reflection of the hot furnace interior can affect the measurement. In this case, Reflected Energy Compensation should be ON and Reflected Temperature should be set to the temperature inside the oven or furnace.
To slow the response time of the sensor, or to reduce fluctuations or noise on the measurement, enter an averaging period (in seconds) here.
If required, hold processing can be applied by setting Hold Mode to "Peak" or "Valley" and setting the hold period (in seconds). This is useful if the temperature reading is interrupted by gaps between moving objects, or by an obstruction.
Set the lower and upper temperature range limits for the voltage output. The relationship between the measured temperature and output voltage is linear.
Measured temperature including averaging only (excluding hold processing).
Highest and lowest temperatures measured during the hold period.
Measured temperature including averaging and hold processing.

12

EN

Unfiltered Temperature Sensor Temperature Alarm Set Point Alarm Hysteresis
Alarm Settings

Measured temperature without averaging or hold processing.
The temperature inside the housing of the sensor.
The temperature at which the alarm will be triggered.
The temperature difference between the Set Point and the reset level. The alarm will be reset automatically when the temperature passes the reset level.
3 (High): The alarm is triggered if the temperature is higher than the Set Point.
2 (Low): The alarm is triggered if the temperature is lower than the Set Point.
0 or 1 (Off): The alarm function is disabled.

Calibration
Every sensor is calibrated to within the published specification at the time of manufacturing.

Maintenance
Our customer service representatives are available for application assistance, calibration, repair, and solutions to specific problems. Contact our Service Department before returning any equipment. In many cases, problems can be solved over the telephone. If the sensor is not performing as it should, try to match the symptom below to the problem. If the table does not help, call RS for further advice.

13

EN

Troubleshooting

Symptom No output or display Inaccurate measured temperature
Voltage output does not match displayed temperature No alarm output

Probable Cause

Solution

No power to the sensor Check the power supply and wiring

Target too small for sensor's field of view

Ensure the sensor's view is completely filled by the target. Position the sensor closer to the target to measure a smaller area.

Incorrect emissivity setting Choose the correct emissivity setting
for the target material. See "Emissivity" for more information

Target is a reflective metal Try using a low emissivity setting, or

surface

paint or coat a measurable area of the

target to make it non-reflective

Field of view obstruction

Remove obstruction; ensure sensor has a clear view of target

Dust or condensation on lens

Ensure lens is clean and dry. Clean gently with a soft lens cloth and water. If problem recurs, consider using an air purge collar.

Output temperature scale mismatch

Check if the output temperature range has been adjusted via UART, ensure the output scale matches the input range of the measurement instrument

Incorrect wiring or configuration

Check electrical connections (see Installation) and Alarm Output settings