User Manual for Intesis models including: Gateway integration Fujitsu General Limited Air

User Manual INKNXFGL001R000

Intesis, Fujitsu, RAC, and, VRF, KNX, INKNXFGL001R000, hms, AC, interfaces

HMS Networks S.L.U.

Gateway for integration of Fujitsu General Limited air ...

Gateway for integration of Fujitsu General Limited air conditioners into KNX TP-1 (EIB) control systems Application’s Program Version: 1.1 USER MANUAL

User Manual INKNXFGL001R000 - HMS Networks

Gateway for integration of Fujitsu General Limited air conditioners into KNX TP-1 (EIB) control systems. Application's Program Version: 1.1. USER MANUAL.


File Info : application/pdf, 68 Pages, 2.01MB

PDF preview unavailable. Download the PDF instead.

user-manual-inknxfgl001r000
Gateway for integration of Fujitsu General Limited air conditioners into KNX TP-1 (EIB) control systems
Application's Program Version: 1.1
USER MANUAL
Issue date: 07/2020 r1.7 ENGLISH

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Important User Information
Disclaimer
The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.
HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.
The data, examples and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
2 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Gateway for integration of Fujitsu General Limited air conditioners into KNX TP-1 (EIB) control systems.
Application's Program Version: 1.1

ORDER CODE

LEGACY ORDER CODE

INKNXFGL001R000 FJ-RC-KNX-1i

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
3 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

INDEX

1 Presentation ........................................................................................................ 6 2 Connection.......................................................................................................... 7
INKNXFGL001R000 with FGL Remote Controller ................................................ 7 3 Configuration and setup ........................................................................................ 7 4 ETS Parameters ................................................................................................... 8
General dialog .............................................................................................. 9 4.1.1 Address in Fujitsu Remote Controller bus (3 wire) ....................................... 9 4.1.2 Fujitsu Error Type ................................................................................... 9 4.1.3 Send READs for Control_ objects on bus recovery ....................................... 9 4.1.4 Scene to load on bus recovery / startup ................................................... 10 4.1.5 Disallow control from remote controller .................................................... 10 4.1.6 Enable func "Control_ Lock Control Obj"................................................... 11 4.1.7 Enable func "Operating Hours Counter" .................................................... 11 4.1.8 Enable object "Error Code [2byte]" .......................................................... 12 4.1.9 Enable object "Error Text Code [14byte]" ................................................. 12
Mode Configuration dialog ............................................................................ 12 4.2.1 Enable "Mode Cool/Heat" objects ............................................................ 13 4.2.2 Enable PID-Compat. Scaling Mode Objects (for Control) ............................. 13 4.2.3 Enable use of + / - object for Mode ......................................................... 14 4.2.4 Enable use of bit-type Mode objects (for control) ...................................... 15 4.2.5 Enable use of bit-type Mode objects (for status)........................................ 15 4.2.6 Enable use of Text object for Mode .......................................................... 15
Special Modes Configuration dialog ................................................................ 16 4.3.1 Enable use of ECONOMY mode (AC feature) ............................................. 17 4.3.2 Enable use of POWER mode.................................................................... 17 4.3.3 Enable use of ECONOMY mode ................................................................ 18 4.3.4 Enable use of ADDITIONAL HEATING mode .............................................. 19 4.3.5 Enable use of ADDITIONAL COOLING mode .............................................. 20
Fan Speed Configuration dialog ..................................................................... 20 4.4.1 Available fanspeeds in Indoor Unit........................................................... 21 4.4.2 DPT object type for fanspeed .................................................................. 21 4.4.3 Enable use of +/- object for Fan Speed .................................................... 22 4.4.4 Enable "Fan Speed Man/Auto" objects (for Control and Status) ................... 23 4.4.5 Enable use of bit-type Fan Speed objects (for Control)............................... 23 4.4.6 Enable use of bit-type Fan Speed objects (for Status) ................................ 24 4.4.7 Enable use of Text object for Fan Speed................................................... 24
Vanes Up-Down Configuration dialog ............................................................. 25 4.5.1 Indoor unit has U-D Vanes ..................................................................... 25 4.5.2 Type of Vanes Control............................................................................ 25 4.5.3 Available U-D positions in Indoor Unit ...................................................... 26 4.5.4 DPT object type for Vanes Up-Down ........................................................ 27 4.5.5 Enable use of +/- object for Vanes U-D .................................................... 28 4.5.6 Enable use of bit-type Vane U-D objects (for Control) ................................ 29 4.5.7 Enable use of bit-type Vane U-D objects (for Status) ................................. 29 4.5.8 Enable "Vanes U-D Swing" objects (for control and status) ......................... 29 4.5.9 Enable use of Text object for Vane U-D .................................................... 30
Vanes Left-Right Configuration dialog ............................................................ 30 4.6.1 Indoor unit has L-R Vanes ...................................................................... 31 4.6.2 Type of Vanes Control............................................................................ 31 4.6.3 Available L-R positions in Indoor Unit....................................................... 32 4.6.4 DPT object type for Vanes Left-Right ....................................................... 33 4.6.5 Enable use of +/- object for Vanes L-R .................................................... 34 4.6.6 Enable use of bit-type Vane L-R objects (for Control)................................. 35 4.6.7 Enable use of bit-type Vane L-R objects (for Status) .................................. 35 4.6.8 Enable "Vanes L-R Swing" objects (for control and status).......................... 35 4.6.9 Enable use of Text object for Vane L-R..................................................... 36

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
4 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Temperature Configuration dialog.................................................................. 36 4.7.1 Periodic sending of "Status_ AC Setp" ...................................................... 37 4.7.2 Transmission of "Status_ AC Ambient Ref Temp"....................................... 37 4.7.3 Enable use of +/- object for Setpoint Temp .............................................. 38 4.7.4 Enable limits on Control_ Setpoint obj ..................................................... 38 4.7.5 Ambient temp. ref. is provided from KNX ................................................. 39
Scene Configuration dialog ........................................................................... 39 4.8.1 Enable use of scenes ............................................................................. 39 4.8.2 Scenes can be stored from KNX bus ........................................................ 40 4.8.3 Enable use of bit objects for scene execution ............................................ 40 4.8.4 Scene "x" preset ................................................................................... 41
Switch-Off Timeouts Configuration dialog ....................................................... 42 4.9.1 Enable use of Open Window / Switch off timeout function .......................... 43 4.9.2 Enable use of Occupancy function ........................................................... 44 4.9.3 Enable use of SLEEP timeout .................................................................. 46
Binary Input "x" Configuration dialog ............................................................. 48 4.10.1 Enable use of Input "x" .......................................................................... 48 4.10.2 Contact type......................................................................................... 48 4.10.3 Debounce time ..................................................................................... 48 4.10.4 Disabling function.................................................................................. 48 4.10.5 Function............................................................................................... 49 5 Specifications .................................................................................................... 57 6 AC Unit Types compatibility ................................................................................. 58 7 Error Codes ....................................................................................................... 59
RAC and VRF J-II / V-II / VR-II series ............................................................ 59 VRF V / S / J series...................................................................................... 61 8 Appendix A ­ Communication Objects Table .......................................................... 62

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
5 / 68

IntesisTM INKNXFGL001R000 1 Presentation

User's manual r1.7 EN

INKNXFGL001R000 allows a complete and natural integration of Fujitsu General Limited (FGL from now on) air conditioners with KNX control systems.

Main features:
· Reduced dimensions and quick installation.
· Multiple objects for control and status (bit, byte, characters...) with KNX standard datapoint types.
· Status objects for every control available.
· Timeout for Open Window and Occupancy. Sleep function also available.
· Control of the AC unit based in the ambient temperature read by the own AC unit, or in the ambient temperature read by any KNX thermostat.
· AC unit can be controlled simultaneously by the wired remote control of the AC unit and by KNX.
· Total Control and Monitoring of the AC unit from KNX, including monitoring of AC unit's state of internal variables, running hours counter (for filter maintenance control), and error indication and error code.
· Up to 5 scenes can be saved and executed from KNX, fixing the desired combination of Operation Mode, Set Temperature, Fan Speed, Vane Position and Remote Controller Lock in any moment by using a simple switching.
· Four binary inputs for potential-free contacts provide the possibility to integrate many types of external devices. Also configurable from ETS, they can be used for switching, dimming, shutter/blind control, and more.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
6 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

2 Connection

Connection of the INKNXFGL001R000 to the AC indoor unit

The INKNXFGL001R000 can be connected directly to the RWB (1:Red, 2:White, 3:Black) bus of the indoor unit (No FGL remote controller -RC from Now on- connected in the RWB bus) or with the FGL RC. See connection diagram below.

Bus Remote Controller (BRC) (It is not mandatory to have it in the network)

Free potential binary inputs

AC Indoor Unit
GND (3) B Data (2) W Power (1) R Internal electronic control board

RW B

- Com - IN4 - IN3 - IN2 - IN1

R
AC Unit W
B

Fujitsu bus max length 500 m

KNX TP-1 (EIB) bus

Figure 2.1 INKNXFGL001R000 connection diagrams

INKNXFGL001R000 with FGL Remote Controller
Connection of the INKNXFGL001R000 to the KNX bus:
Disconnect power of the KNX bus. Connect the INKNXFGL001R000 to the KNX TP-1 (EIB) bus using the KNX standard connector (red/grey) of the INKNXFGL001R000, respect polarity.
Reconnect power of the KNX bus and mains power of the AC unit.
Important: Please, connect first the Intesis on the KNX bus and then to the AC unit. Afterwards, power the AC unit and wait 30 seconds for the unit and the Intesis to start communicating properly.

3 Configuration and setup
This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.
ETS database for this device can be downloaded from: https://intesis.com/products/ac-interfaces/fujitsu-gateways/fujitsu-knx-inputs-vrf-fj-rc-knx-1i
Please consult the README.txt file, located inside the downloaded zip file, to find instructions on how to install the database.
Important: Do not forget to select the correct settings of AC indoor unit being connected to the INKNXFGL001R000. This is in "Parameters" of the device in ETS.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
7 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

4 ETS Parameters

When imported to the ETS software for the first time, the gateway shows the following default parameter configuration:

Figure 4.1 Default parameter configuration
With this configuration it's possible to send On/Off (Control_ On/Off), change the AC Mode (Control_ Mode), the Fan Speed (Control_ Fan Speed) and also the Setpoint Temperature (Control_ Setpoint Temperature). The Status_ objects, for the mentioned Control_ objects, are also available to use if needed. Also objects Status_ AC Ambient Ref Temp and Status_ Error/Alarm are shown.

Figure 4.2 Default communication objects

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
8 / 68

IntesisTM INKNXFGL001R000
General dialog

User's manual r1.7 EN

Inside this parameter's dialog it is possible to activate or change the parameters shown in the Figure 4.1.
The first field shows the URL where to download the database and the user manual for the product. (Currently: https://www.intesis.com)

4.1.1 Address in Fujitsu Remote Controller bus (3 wire)
Fujitsu dual remote controller function setting. 0: master, 1: slave (default). This parameter is used to select the function our gateway will have in the RWB RC-bus. o If set to "0" the gateway will act as a master in the RC-bus. (No BRC present, or BRC
set as slave). o If set to "1" the gateway will act as a slave in the RC-bus. (BRC present set as master).

Figure 4.3 Parameter detail
Important: After changing this parameters value and downloading to the gateway, it is required to perform a power cycle of the FGL system to apply the changes in the systems active runtime memory.
4.1.2 Fujitsu Error Type
This parameter defines the type of FGL unit you have and the associated error codes. Please, check table below which value you have to use depending on the AC system type you have.

Figure 4.4 Parameter detail

AC System Type
RAC Non inverter models RAC inverter models
VRF V / S / J
RAC inverter model G* series VRF J-II / V-II / VR-II

Error Type
Type A Type A Type B

Table 4.1 Parameter detail

4.1.3 Send READs for Control_ objects on bus recovery

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
9 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

When this parameter is enabled, INKNXFGL001R000 will send READ telegrams for the group addresses associated on its Control_ objects on bus recovery or application reset/start-up.

o If set to "No" the gateway will not perform any action.

o If set to "Yes" all Control_ objects with both Transmit (T) and Update (U) flags enabled will send READs and their values will be updated with the response when received.

Figure 4.5 Parameter detail
 Delay before sending READs (sec): With this parameter, a delay can be configured between 0 and 30 seconds for the READs sent by the Control_ objects. This is to give time enough to other KNX devices on the bus to start-up before sending the READs.
4.1.4 Scene to load on bus recovery / startup
This parameter executes a selected scene on bus recovery or startup, only if the selected scene has an enabled preset or values previously saved from KNX bus (see 4.8 for more information). If the gateway is disconnected from the indoor unit the scene will not be applied, even when connecting to the indoor unit again.
Figure 4.6 Parameter detail
4.1.5 Disallow control from remote controller
This parameter allows: 1- Having the remote controller always locked, or 2- Decide through a new communication object if the RC is locked or not. (Default)
o If set to "Yes" all the actions performed through the remote controller will be disabled. o If set to "No" the remote controller will work as usually. It also appears a new parameter
and the communication object Control_ Lock Remote Control.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
10 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.7 Communication Object and parameter detail
 Enable comm obj "Ctrl_ Remote Lock": If set to "No" the object will not be shown. (Default). If set to "Yes" the Control_ Lock Remote Control object will appear. · When a "1" value is sent to this communication object, the remote controller is locked. To be unlocked a "0" value must be sent. The gateway remembers the last value received even if a KNX bus reset/failure happens. Important: If an initial scene is enabled and it has as Value for Remote Lock (unchanged) or unlocked, this would unlock the remote controller because the initial scene has priority over the Control_ Lock Remote Control communication object.
4.1.6 Enable func "Control_ Lock Control Obj"
This parameter shows/hide the Control_ Lock Control Obj communication object which, depending on the sent value, locks or unlocks ALL the Control_ communication objects except itself. It also shows/hide the Status_ Lock Control Obj.
43 104
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Lock Control Objects object will appear.
· When a "1" value is sent to this communication object, all the Control_ objects will be locked. To unlock a "0" value must be sent, as the gateway remembers the last value received even if a KNX bus reset/failure happens.
4.1.7 Enable func "Operating Hours Counter"
This parameter shows/hides the Status_ Operation Hour Counter communication object which counts the number of operating hours for the INKNXFGL001R000.
107
o If set to "No" the object will not be shown. o If set to "Yes" the Status_ Operation Hour Counter object will appear.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
11 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

· This object can be read and sends its status every time an hour is counted. The gateway keeps that count in memory and the status is sent also after a KNX bus reset/failure. Although this object is marked as a Status_ object it also can be written to update the counter when needed. To reset the counter should be written a "0" value.

Important: This object comes by default without the write (W) flag activated. If is necessary to write on it, this flag must be activated.

Important: This object will also return its status, every time a value is written, only if it's different from the existing one.

Important: If the stored value is 0 hours, the gateway will not send the status to KNX.

4.1.8 Enable object "Error Code [2byte]"
This parameter shows/hides the Status_ Error Code communication object which shows the indoor unit errors, if occurred, in numeric format.
99

o If set to "No" the object will not be shown.
o If set to "Yes" the Status_ Error Code [2byte] object will appear.
· This object can be read and also sends the indoor unit error, if occurred, in numeric format. If a "0" value is shown that means No error.

4.1.9 Enable object "Error Text Code [14byte]"
This parameter shows/hides the Status_ Error Text Code communication object which shows the indoor unit errors, if occurred, in text format.

100

FJ

o If set to "No" the object will not be shown.
o If set to "Yes" the Status_ Error Text Code object will appear.
· This object can be read and also sends the indoor unit error, if occurred, in text format. The errors shown have the same format as at the remote controller and at the error list from the indoor unit manufacturer. If the object's value is empty that means No error.

Mode Configuration dialog

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
12 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.8 Default Mode Configuration dialog
All the parameters in this section are related with the different mode properties and communication objects.
4.2.1 Enable "Mode Cool/Heat" objects
This parameter shows/hides the Control_ and Status_ Mode Cool/Heat communication objects.
3 67
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ and Status_ Mode Cool/Heat objects will appear.
· When a "1" value is sent to the Control_ communication object, Heat mode will be enabled in the indoor unit, and the Status_ object will return this value.
· When a "0" value is sent to the Control_ communication object, Cool mode will be enabled in the indoor unit, and the Status_ object will return this value.
4.2.2 Enable PID-Compat. Scaling Mode Objects (for Control)
This parameter shows/hides the Control_ Mode Cool & On and Control_ Mode Heat & On communication objects.
4 5
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Mode Cool & On and Control_ Mode Heat & On objects will
appear. · These objects provide compatibility with those KNX thermostats that control the demand of heating or cooling by using scaling (percentage) objects. In

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
13 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

these thermostats, the percentage demand is meant to be applied on a fluid valve of the heating / cooling system.

· INKNXFGL001R000 device does not provide individual control on the internal parts of the indoor unit (as can be its compressor, refrigerant valves, etc.). Rather, it provides the same level of control as a (user) remote controller.

· Objects "Control_ Mode Cool & On" and "Control_ Mode Heat & On" intend to bring compatibility between thermostats oriented to the control of custom heating / cooling systems and ready-made AC indoor units, by applying the following logic:

· Whenever a Non-zero value (>0%) is received at "Control_ Mode Cool & On", indoor unit will switch On in COOL mode.

· Whenever a Non-zero value (>0%) is received at "Control_ Mode Heat & On", indoor unit will switch On in HEAT mode.

· Latest updated object will define the operating mode

· Indoor unit will switch off only when both objects become zero (0%) ­ or when an OFF is requested at object "0. On/Off [DPT_1.001 - 1bit]"

* Important: These objects function is only to send On/Off and Cool/Heat to the indoor
unit. The PID (Inverter system) is calculated by the indoor unit itself. Please consider introducing an appropriate PID configuration to the external KNX thermostat to not interfere the indoor unit PID.

4.2.3 Enable use of + / - object for Mode
This parameter shows/hides the Control_ Mode +/- communication object which lets change the indoor unit mode by using two different datapoint types.
11
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Mode +/- object and a new parameter will appear.

Figure 4.9 Parameter detail

 DPT type for +/- Mode Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Mode +/- object.
The sequence followed when using this object is shown below:

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
14 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

AUTO

HEAT

COOL

FAN

 Up / Increase  Down / Decrease

DRY

Important: Read the documentation of your indoor unit to check if it has HEAT mode available.
4.2.4 Enable use of bit-type Mode objects (for control)
This parameter shows/hides the bit-type Control_ Mode objects.
6 7 8 9 10
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
To activate a mode by using these objects a "1" value has to be sent.
4.2.5 Enable use of bit-type Mode objects (for status)
This parameter shows/hides the bit-type Status_ Mode objects.
68 69 70 71 72
o If set to "No" the objects will not be shown. o If set to "Yes" the Status_ Mode objects for Auto, Heat, Cool, Fan and Dry will appear.
When enabled, a mode will return a "1" through its bit-type object.

4.2.6 Enable use of Text object for Mode
This parameter shows/hides the Status_ Mode Text communication object.
73
o If set to "No" the object will not be shown.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
15 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o If set to "Yes" the Status_ Mode Text object will appear. Also, in the parameters, will be shown five text fields, one for each mode, that will let modify the text string displayed by the Status_ Mode Text when changing mode.

Figure 4.10 Parameter detail
Special Modes Configuration dialog

Figure 4.11 Default Special Modes Configuration dialog
The Special Modes can be parameterized through the ETS parameters dialog and they can be used to give extra functionality.
Important: When executing any of the Special Modes the real state of the indoor unit will NOT be shown in KNX.
Important: When the predefined time for the Special Mode is finished or a "0" value is sent to stop it; the previous state will be recovered.
Important: If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is received from KNX while any Special Mode is running ("1"), the Special Mode will stop and the previous state will be recovered. The value received will be also applied then.
Important: If a value concerning On/Off, Mode, Fan Speed or Setpoint Temperature is modified through the remote controller, the Special Mode will stop WITHOUT recovering the previous state. Then the real indoor unit state will be shown in KNX including the new value received through the remote controller.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
16 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

4.3.1 Enable use of ECONOMY mode (AC feature)

This parameter shows/hides the Control_ Economy and Status_ Economy communication objects. This communication object is using the Economy function provided by the AC unit itself. Please refer to your user manual for more information on this function.

1 65
o If set to "No" the objects will not be shown.
o If set to "Yes" the Control_ Economy and Status_ Economy objects and new parameters will appear.
· When a "1" value is sent to the Control_ communication object, Economy will be enabled, and the Status_ object will return this value.
· When a "0" value is sent to the Control_ communication object, Economy will be disabled, and the Status_ object will return this value.
Important: This mode will ONLY work if the indoor unit is both turned on and in a Heat, Cool, Auto-Heat or Auto-Cool Mode.

4.3.2 Enable use of POWER mode
This parameter shows/hides the Control_ Power Mode and Status_ Power Mode communication objects. The Power Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.

44 103
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Power Mode and Status_ Power Mode objects and new
parameters will appear.

Figure 4.12 Parameter detail
· When a "1" value is sent to the Control_ communication object Power Mode will be enabled, and the Status_ object will return this value.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
17 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

· When a "0" value is sent to the Control_ communication object, Power Mode will be disabled, and the Status_ object will return this value.

Important: This mode will ONLY work if the indoor unit is both turned on and in a Heat, Cool, Auto-Heat or Auto-Cool Mode.

 Action time for this mode (minutes): Duration of Power Mode, in minutes, once started.

 Setpoint delta increase (HEAT) or decrease (COOL) ­ in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode, while in Power Mode.

 Fan Speed for this mode: Fan Speed that will be set in the unit while in Power Mode.

4.3.3 Enable use of ECONOMY mode
This parameter shows/hides the Control_ Econo Mode and Status_ Econo Mode communication objects. The Econo Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
45 104
o If set to "no" the objects will not be shown. o If set to "yes" the Control_ Econo Mode and Status_ Econo Mode objects and new
parameters will appear.
· When a "1" value is sent to the Control_ communication object, EconoMode will be enabled, and the Status_ object will return this value.
· When a "0" value is sent to the Control_ communication object, EconoMode will be disabled, and the Status_ object will return this value. Important: This mode will ONLY work if the indoor unit is both turned on and in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
 Action time for this mode (minutes): Duration of EconoMode, in minutes, once started.
 Setpoint delta increase (HEAT) or decrease (COOL) ­ in Celsius:

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
18 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode, while in EconoMode.
 Fan Speed for this mode: Fan Speed that will be set in the unit while in EconoMode.

4.3.4 Enable use of ADDITIONAL HEATING mode
This parameter shows/hides the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode communication objects. The Additional Heating Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
46 105

Figure 4.13 Communication object and parameter detail
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Start Additional Heat Mode and Status_ Additional Heat Mode
objects and new parameters will appear. · When a "1" value is sent to the Control_ communication object, Additional Heating Mode will be enabled, and the Status_ object will return this value. · When a "0" value is sent to the Control_ communication object, Additional Heating Mode will be disabled, and the Status_ object will return this value. Important: This mode will ALWAYS turn on the indoor unit in Heat mode.
 Action time for this mode (minutes): Duration of Additional Heating Mode, in minutes, once started.
 Setpoint temp for this mode (ºC): Setpoint temperature that will be applied while in Additional Heating Mode.
 Fan Speed for this mode: Fan Speed that will be set in the unit while in Additional Heating Mode.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
19 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

4.3.5 Enable use of ADDITIONAL COOLING mode
This parameter shows/hides the Control_ Start Additional Cool Mode and Status_ Additional Cool Mode communication objects. The Additional Heating Mode lets change the Setpoint Temperature and the Fan Speed within a given period of time.
47 106

Figure 4.14 Communication object and parameter detail
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Start Additional Cool Mode and Status_ Additional Cool Mode
objects and new parameters will appear. · When a "1" value is sent to the Control_ communication object, Additional Cooling Mode will be enabled, and the Status_ object will return this value. · When a "0" value is sent to the Control_ communication object, Additional Cooling Mode will be disabled, and the Status_ object will return this value. Important: This mode will ALWAYS turn on the indoor unit in Cool mode.
 Action time for this mode (minutes): Duration of Additional Cooling Mode, in minutes, once started.
 Setpoint temp for this mode (ºC): Setpoint temperature that will be applied while in Additional Cooling Mode.
 Fan Speed for this mode: Fan Speed that will be set in the unit while in Additional Cooling Mode.
Fan Speed Configuration dialog

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
20 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.15 Default Fan Speed Configuration dialog
All the parameters in this section are related with the Fan Speed properties and communication objects.
4.4.1 Available fanspeeds in Indoor Unit
This parameter needs to be fixed according to you indoor unit capacity. Please check your indoor unit user manual and introduce the right number of fanspeeds.

Figure 4.16 Parameter detail
4.4.2 DPT object type for fanspeed
With this parameter is possible to change de DPT for the Control_ Fan Speed and Status_ Fan Speed byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.
Important: The communication objects shown in this section may be different depending on the number of fan speeds available, although they all share the same communication object number. o When "Enumerated [DPT 5.010]" is selected, Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear.
12 74
12 74
The first fan speed will be selected if a "1" is sent to the Control_ object. The second one will be selected sending a "2"; the third one will be selected sending a "3"; the fourth one selecting "4"

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
21 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

The Status_ object will always return the value for the fan speed selected.
Important: If a "0" value is sent to the Control_ object, the minimum fan speed will be selected. If a value bigger than "4" is sent to the Control_ object, then the maximum fan speed will be selected.

o When "Scaling [DPT 5.001]" is selected, Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear.
12 74
12 74
Table next shows the range of values that can be sent through the Control_ object and the value returned by the Status_ object.

Control_ Status_

Fan Speed 1 0% - 49% 33%

Fan Speed 2 50% - 82%
67%

Fan Speed 3 83% - 100%
100%

Control_ Status_

Fan Speed 1 0% - 37% 25%

Fan Speed 2 38% - 62%
50%

Fan Speed 3 63% - 87%
75%

Fan Speed 4 88% - 100%
100%

Important: Read the documentation of your indoor unit to check how many fan speeds are available.
4.4.3 Enable use of +/- object for Fan Speed
This parameter shows/hides the Control_ Fan Speed +/- communication object which lets increase/decrease the indoor unit fan speed by using two different datapoint types.
18
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Fan Speed +/- object and a new parameter will appear.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
22 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.17 Parameter detail
 DPT type for +/- Fan Speed Object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Fan Speed +/- object.  Does +/- sequence include fan speed Auto?
This parameter includes or excludes the auto mode for the fan speed in the list of available speeds.  Roll-over Speed at upper/lower limit
This parameter lets choose if roll-over will be enabled ("Yes") or disabled ("No") for the Control_ Fan Speed +/- object.

AUTO

Only if Roll-over is enabled

FS 1

FS 2

FS 3

Only if Roll-over is enabled

 Up / Increase  Down / Decrease
* If available

FS 4*

4.4.4 Enable "Fan Speed Man/Auto" objects (for Control and Status)

This parameter shows/hides the bit-type Control_ Fan Speed Man/Auto and the Status_ Fan Speed Man/Auto objects.

13 75

4.4.5 Enable use of bit-type Fan Speed objects (for Control)

This parameter shows/hides the bit-type Control_ Fan Speed objects.

14

15

16

17

4

4*

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
23 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

* Only available if the AC unit has 4 fan speeds.

o If set to "No" the objects will not be shown.
o If set to "Yes" the Control_ Fan Speed objects for Speed 1, Speed 2 and Speed 3 will appear. To activate a Fan Speed by using these objects a "1" value has to be sent.

4.4.6 Enable use of bit-type Fan Speed objects (for Status)

This parameter shows/hides the bit-type Status_ Fan Speed objects.

76

77

78

79

4

4*

* Only available if the AC unit has 4 fan speeds.

o If set to "No" the objects will not be shown.
o If set to "Yes" the Status_ Fan Speed objects for Speed 1, Speed 2, Speed 3 and Speed 4 (if available) will appear. When a Fan Speed is enabled, a "1" value is returned through its bit-type object.

4.4.7 Enable use of Text object for Fan Speed
This parameter shows/hides the Status_ Fan Speed Text communication object.
80
o If set to "No" the object will not be shown. o If set to "Yes" the Status_ Fan Speed Text object will appear. Also, in the parameters,
will be shown five text fields, one for each Fan Speed, that will let modify the text string displayed by the Status_ Fan Speed Text when changing a fan speed.

Figure 4.18 Parameter detail
© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
24 / 68

IntesisTM INKNXFGL001R000
Vanes Up-Down Configuration dialog

User's manual r1.7 EN

Figure 4.19 Vanes Up-Down Configuration dialog
All the parameters in this section are related with the Vanes Up-Down properties and communication objects.
4.5.1 Indoor unit has U-D Vanes
This parameter lets choose if the unit has Up-Down Vanes available or not.

Figure 4.20 Parameter detail
o If set to "No" all the parameters and communication objects for the Up-Down Vanes will not be shown.
o If set to "Yes" all the parameters and communication objects (if enabled in the parameters dialog) for the Up-Down Vanes will be shown.
Important: Read the documentation of your indoor unit to check if Up-Down Vanes are available.
4.5.2 Type of Vanes Control
This parameter lets choose if the unit uses a step control no the vanes position or directly a position indication.

Figure 4.21 Parameter detail
o If set to "Step" only the communication objects only for SWING and STEP will be shown.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
25 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o If set to "Position" all the parameters and communication objects for the 4 Vanes positions and Swing will be shown.

Figure 4.22 Parameter detail
4.5.3 Available U-D positions in Indoor Unit
This parameter lets you choose between "0 (Only Swing)" and "4". o If set to "0 (Only Swing)" all the parameters and communication objects (if enabled in
the parameters dialog) for the swing positions will be shown.
24 86

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
26 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.23 Communication Object and parameter details
o If set to "4" all the parameters and communication objects (if enabled in the parameters dialog) for the 4 Vanes positions will be shown.
Important: Read the documentation of your indoor unit to check if Up-Down Vanes positions are available.
4.5.4 DPT object type for Vanes Up-Down
With this parameter is possible to change de DPT for the Control_ Vanes U-D and Status_ Vanes U-D byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.
Important: The communication objects shown in this section may be different depending on the number of vanes position available, although they all share the same communication object number.
o When "Enumerated [DPT 5.010]" is selected, Control_ Vanes U-D and Status_ Vanes U-D communication objects for this DPT will appear.
19 81
To choose a vanes position, values from "1" to "4" can be sent to the Control_ object. Each value will correspond to the position (i.e. Value "3" = Position 3). The Status_ object will always return the value for the vane position selected.
Important: If a "0" value is sent to the Control_ object, the Position 1 will be selected. If a value bigger than "4" is sent to the Control_ object, then the higher Position will be selected.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
27 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o When "Scaling [DPT 5.001]" is selected, Control_ Vane Up-Down and Status_ Vane UpDown communication objects for this DPT will appear.

19 81

The next table shows the range of values that can be sent through the Control_ object and the value returned by the Status_ object.

Control_ Status_

Vanes Pos.1 Vanes Pos.2 Vanes Pos.3 Vanes Pos.4

0% - 37% 38% - 62% 63% - 87% 88% - 100%

25%

50%

75%

100%

4.5.5 Enable use of +/- object for Vanes U-D

This parameter shows/hides the Control_ Vane Up-Down +/- communication object which lets change the indoor unit vane position by using two different datapoint types.

25

o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Vanes U-D +/- object and a new parameter will appear.

Figure 4.24 Parameter detail
 DPT type for +/- Vane Up-Down obj This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Vanes U-D +/- object.
 Does +/- sequence include SWING vanes Up-Down? This parameter lets choose if SWING function is included ("Yes") or not ("No") in the sequence when using Control_ Vanes U-D +/- object as shown in the discontinuous segment at the picture below.
 Roll over Vanes at upper/lower limit

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
28 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

This parameter lets choose if roll-over will be enabled ("Yes") or disabled ("No") for the Control_ Vanes U-D +/- object.

Only if Roll-over is enabled

P. 1

P. 2

P. 3

Only if Roll-over is enabled
 Up / Increase  Down / Decrease

P. 4

Swing

4.5.6 Enable use of bit-type Vane U-D objects (for Control)
This parameter shows/hides the bit-type Control_ Vanes U-D objects.
20 21 22 23
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Vanes U-D objects for each Position will appear. To activate
a Vanes Position by using these objects, a "1" value has to be sent.
4.5.7 Enable use of bit-type Vane U-D objects (for Status)
This parameter shows/hides the bit-type Status_ Vanes U-D objects.
82 83 84 85
o If set to "No" the objects will not be shown. o If set to "Yes" the Status_ Vanes U-D objects for each Position will appear. When a Vanes
Position is enabled, a "1" value is returned through its bit-type object.
4.5.8 Enable "Vanes U-D Swing" objects (for control and status)
This parameter will only be shown if the value "Position" is selected on the 4.5.2 section. It will show/hide Control_ Vanes U-D SWING y Status_ Vanes U-D SWING communication objects.
24 86
o If set to "No" the object will not be shown.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
29 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o If set to "Yes" the Control_ Vanes U-D Swing y Status_ Vanes U-D Swing objects will appear.
· When a "1" value is sent to the Control_ communication object, Vanes UpDown will be in Auto mode and the Status_ object will return this value.
· When a "0" value is sent to the Control_ communication object, Vanes UpDown will be in Manual mode and the Status_ object will return this value.
Important: When activating Auto Mode in the indoor unit, this one will choose the best position available for the Vanes Up-Down. This position will not be shown either in the KNX bus or in the remote controller.
Important: Read the documentation of your indoor unit to check how many vanes modes are available.

4.5.9 Enable use of Text object for Vane U-D
This parameter shows/hides the Status_ Vanes U-D Text communication object.
87
o If set to "No" the object will not be shown. o If set to "Yes" the Status_ Vanes U-D Text object will appear. Also, in the parameters will
be shown seven text fields, five for the Vane Position and one for the Swing function, that will let modify the text string displayed by the Status_ Vanes U-D Text when changing a vane position.

Figure 4.25 Parameter detail
Vanes Left-Right Configuration dialog

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
30 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.26 Vanes Left-Right Configuration dialog
All the parameters in this section are related with the Vanes Left-Right properties and communication objects.
4.6.1 Indoor unit has L-R Vanes
This parameter lets choose if the unit has Left-Right Vanes available or not.
Figure 4.27 Parameter detail
o If set to "No" all the parameters and communication objects for the Left-Right Vanes will not be shown.
o If set to "Yes" all the parameters and communication objects (if enabled in the parameters dialog) for the Left-Right Vanes will be shown. Important: Read the documentation of your indoor unit to check if Left-Right Vanes are available.
4.6.2 Type of Vanes Control
This parameter lets choose if the unit uses a step control no the vanes position or directly a position indication.
Figure 4.28 Parameter detail
o If set to "Step" only the communication objects only for SWING and STEP will be shown.
33 35

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
31 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o If set to "Position" all the parameters and communication objects for the 4 Vanes positions and Swing will be shown.

Figure 4.29 Parameter detail
4.6.3 Available L-R positions in Indoor Unit
This parameter lets you choose between "0 (Only Swing)" and "5". o If set to "0 (Only Swing)" all the parameters and communication objects (if enabled in
the parameters dialog) for the swing positions will be shown.
Figure 4.30 Parameter and objects detail
o If set to "5" all the parameters and communication objects (if enabled in the parameters dialog) for the 5 Vanes positions will be shown.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
32 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.31 Parameter and objects detail
Important: Read the documentation of your indoor unit to check if Left-Right Vanes positions are available.
4.6.4 DPT object type for Vanes Left-Right
With this parameter is possible to change de DPT for the Control_ Vanes L-R and Status_ Vanes L-R byte-type communication objects. Datapoints Scaling (DPT_5.001) and Enumerated (DPT_5.010) can be selected.
Important: The communication objects shown in this section may be different depending on the number of vanes position available, although they all share the same communication object number.
o When "Enumerated [DPT 5.010]" is selected, Control_ Vanes L-R and Status_ Vanes L-R communication objects for this DPT will appear.

To choose a vanes position, values from "1" to "5" can be sent to the Control_ object. Each value will correspond to the position (i.e. Value "3" = Position 3).
The Status_ object will always return the value for the vane position selected.
Important: If a "0" value is sent to the Control_ object, the Position 1 will be selected. If a value bigger than "5" is sent to the Control_ object, then the higher Position will be selected.
o When "Scaling [DPT 5.001]" is selected, Control_ Vane L-R and Status_ Vane L-R communication objects for this DPT will appear.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
33 / 68

IntesisTM INKNXFGL001R000
27 88

User's manual r1.7 EN

The next table shows the range of values that can be sent through the Control_ object and the value returned by the Status_ object.

Control_ Status_

Vanes Pos.1 Vanes Pos.2 Vanes Pos.3 Vanes Pos.4 Vanes Pos.5

0% - 29% 30% - 49% 50% - 69% 70% - 89% 90% - 100%

20%

40%

60%

80%

100%

4.6.5 Enable use of +/- object for Vanes L-R
This parameter shows/hides the Control_ Vane L-R +/- communication object which lets change the indoor unit vane position by using two different datapoint types. It is only present when "5" is selected on the "Available L-R position Indoor Unit" dropdown menu.
34
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Vanes L-R +/- object and a new parameter will appear.

Figure 4.32 Parameter detail
 DPT type for +/- Vane L-R obj
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Vanes L-R +/- object.
 Does +/- sequence include SWING vanes Left-Right?
This parameter lets choose if SWING function is included ("Yes") or not ("No") in the sequence when using Control_ Vanes L-R +/- object as shown in the discontinuous segment at the picture below.
 Roll over Vanes at upper/lower limit
This parameter lets choose if roll-over will be enabled ("Yes") or disabled ("No") for the Control_ Vanes L-R +/- object.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
34 / 68

IntesisTM INKNXFGL001R000

P. 1

Only if Roll-over is enabled

P. 2

P. 3

P. 4

Only if Roll-over is enabled
 Up / Increase  Down / Decrease

P. 5

User's manual r1.7 EN
Swing

4.6.6 Enable use of bit-type Vane L-R objects (for Control)
This parameter shows/hides the bit-type Control_ Vanes L-R objects.
28 29 30 31 32
o If set to "No" the objects will not be shown. o If set to "Yes" the Control_ Vanes L-R objects for each Position will appear. To activate a
Vanes Position by using these objects, a "1" value has to be sent.
4.6.7 Enable use of bit-type Vane L-R objects (for Status)
This parameter shows/hides the bit-type Status_ Vanes L-R objects.
89 90 91 92 93
o If set to "No" the objects will not be shown. o If set to "Yes" the Status_ Vanes L-R objects for each Position will appear. When a Vanes
Position is enabled, a "1" value is returned through its bit-type object.
4.6.8 Enable "Vanes L-R Swing" objects (for control and status)
This parameter will only be present if parameter on 4.6.2 is set to "Position". It will show/hide Control_ Vanes L-R SWING y Status_ Vanes L-R SWING communication objects.
33

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
35 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

94
o If set to "No" the object will not be shown.
o If set to "Yes" the Control_ Vanes L-R Swing y Status_ Vanes L-R Swing objects will appear.
· When a "1" value is sent to the Control_ communication object, Vanes LeftRight will be in Auto mode and the Status_ object will return this value.
· When a "0" value is sent to the Control_ communication object, Vanes LeftRight will be in Manual mode and the Status_ object will return this value.
Important: When activating Auto Mode in the indoor unit, this one will choose the best position available for the Vanes Left-Right. This position will not be shown either in the KNX bus or in the remote controller.
Important: Read the documentation of your indoor unit to check how many vanes modes are available.
4.6.9 Enable use of Text object for Vane L-R
This parameter shows/hides the Status_ Vanes L-R Text communication object.
95
o If set to "No" the object will not be shown.
o If set to "Yes" the Status_ Vanes L-R Text object will appear. Also, in the parameters will be shown seven text fields, five for the Vane Position and one for the Swing function, that will let modify the text string displayed by the Status_ Vanes L-R Text when changing a vane position.

Figure 4.33 Parameter detail
Temperature Configuration dialog

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
36 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.34 Default Temperature Configuration dialog
All the parameters in this section are related with the Temperature properties and communication objects.
4.7.1 Periodic sending of "Status_ AC Setp"
This parameter lets change the interval of time (in seconds, from 0 to 255) at the end of which the AC setpoint temperature is sent to the KNX bus. For a "0" value, the AC setpoint temperature will ONLY be sent on change. The AC setpoint temperature is sent through the communication object Status_ AC Setpoint Temp.
96
Figure 4.35 Communication object and parameter detail
Important: In case the ambient temperature is provided from KNX, the setpoint temperature returned from this object, will be the one resulting from the formula shown in the section "4.6.4 Ambient temp. ref. is provided from KNX".
4.7.2 Transmission of "Status_ AC Ambient Ref Temp"
This parameter lets to you choose if the AC return temperature will be sent "only cyclically", "only on change" or "cyclically and on change". The AC return temperature is sent through the communication object Status_ AC Ambient Ref Temp.
97:

Figure 4.36 Parameter detail
 "Status_ AC Ambient Ref Temp" periodic sending time (in sec)

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
37 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

This parameter will only be available for the "only cyclically" and "cyclically and on change" options, and lets you change the interval of time (in seconds, from 1 to 255) at the end of which the AC return temperature is sent to the KNX bus.

4.7.3 Enable use of +/- object for Setpoint Temp
This parameter shows/hides the Control_ Setpoint Temp +/- communication object which lets change the indoor unit setpoint temperature by using two different datapoint types.
37
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Setpoint Temp +/- object and a new parameter will appear.

Figure 4.37 Parameter detail
 DPT type for +/- Setp Temp object
This parameter lets choose between the datapoints 0-Up / 1-Down [DPT_1.008] and 0-Decrease / 1-Increase [DPT_1.007] for the Control_ Setpoint Temp +/object.

(Lower limit) 18ºC

19ºC

...

29ºC

 Up / Increase  Down / Decrease

30ºC (Upper limit)

4.7.4 Enable limits on Control_ Setpoint obj
This parameter enables to define temperature limits for the Control_ Setpoint Temperature object.

Figure 4.38 Parameter detail
o If set to "No" the setpoint temperature limits for the Control_ Setpoint Temperature object will be the default: 16ºC for the lower limit and 31ºC for the upper limit.
o If set to "Yes" it is possible to define temperature limits for the Control_ Setpoint Temperature object.
 Control_ Set Temp Lower limit (ºC)

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
38 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

This parameter lets to define the lower limit for the setpoint temperature.  Control_ Set Temp Upper limit (ºC)

This parameter lets to define the upper limit for the setpoint temperature.

Important: If a setpoint temperature above the upper defined limit (or below the lower defined limit) is sent through the Control_ Setpoint Temperature object, it will be ALWAYS applied the limit defined.
Important: When limits are enabled, any setpoint temperature sent to the AC (even through scenes, special modes, etc.) will be limited.

4.7.5 Ambient temp. ref. is provided from KNX
This parameter shows/hides the Control_ Ambient Temperature communication object which lets use an ambient temperature reference provided by a KNX device.
38
o If set to "No" the object will not be shown and the ambient temperature will never be send to the AC unit.
o If set to "Yes" the Control_ Ambient Temp object will appear. Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference ambient temperature for the air conditioner.
Scene Configuration dialog

Figure 4.39 Parameter detail
All the parameters in this section are related with the Scene properties and communication objects. A scene contains values of: On/Off, Mode, Fan speed, Vane position, Setpoint Temperature and Remote Controller Disablement.
4.8.1 Enable use of scenes
This parameter shows/hides the scene configuration parameters and communication objects.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
39 / 68

IntesisTM INKNXFGL001R000
48

User's manual r1.7 EN

Figure 4.40 Parameter detail
o If set to "No" the scene parameters and communication objects will not be shown. o If set to "Yes" the scene parameters and communication objects will be shown. To
execute a scene through the byte-type object, a value from "0" to "4" has to be sent, correponding each one to a different scene (i.e. "0" = Scene 1;... "4" = Scene 5).
4.8.2 Scenes can be stored from KNX bus
This parameter shows/hides the Control_ Save/Exec Scene and all the Control_ Store Scene (if enabled) communication objects.
48
o If set to "No" the communication objects will not be shown. o If set to "Yes" the communication objects and a new parameter will appear. To store a
scene through the byte-type object, a value from "128" to "132" has to be sent to the object, correponding each one to a different scene (i.e. "128" = Scene 1;... "132" = Scene 5).

Figure 4.41 Parameter detail
 Enable use of bit objects for storing scenes (from bus)
If set to "No" the objects will not be shown.
If set to "Yes" the Control_ Store Scene objects for storing scenes will appear. To store a scene by using these objects, a "1" value has to be sent to the scene's object we want to store (i.e. to store scene 4, a "1" has to be sent to the Control_ Store Scene 4 object).
49 50 51 52 53
4.8.3 Enable use of bit objects for scene execution
This parameter shows/hides the Control_ Execute Scene bit-type communication objects.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
40 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.42 Parameter detail
o If set to "No" the communication objects will not be shown. o If set to "Yes" the communication objects will appear. To execute a scene by using these
objects, a "1" value has to be sent to the scene's object we want to execute (i.e. to execute scene 4, a "1" has to be sent to the Control_ Execute Scene 4 object).
54 55 56 57 58
4.8.4 Scene "x" preset
This parameter lets define a preset for a scene (the following description is valid for all the scenes).
Figure 4.43 Parameter detail
o If set to "No" the preset for the scene "x" will be disabled. o If set to "Yes" the preset will be enabled. When a scene is executed the values configured
in the preset will be aplied.
Important: If a scene's preset is enabled, will not be possible to modify (store) the scene from the KNX bus.

Figure 4.44 Parameter detail
 Scene "x" / Value for On-Off This parameter lets choose the power of the indoor unit when the scene is executed. The following options are available: "ON", "OFF" or "(unchanged)".
 Scene "x" / Value for Mode

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
41 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

This parameter lets choose the mode of the indoor unit when the scene is executed.
The following options are available: "AUTO", "HEAT", "COOL", "FAN", "DRY", or "(unchanged)".

 Scene "x" / Value for Fan Speed
This parameter lets choose the fan speed of the indoor unit when the scene is executed. The following options are available: "FAN SPEED AUTO", "FAN SPEED 1", "FAN SPEED 2", "FAN SPEED 3", "FAN SPEED 4 (if available)" or "(unchanged)".

 Scene "x" / Value for Vane U-D (if available)
This parameter lets choose the vane position of the indoor unit when the scene is executed. The following options are available: "VANES U-D OFF", "VANES U-D POS 1(if available)", "VANES U-D POS 2(if available)", "VANES U-D POS 3(if available)", "VANES U-D POS 4(if available)", "VANES U-D SWING" or "(unchanged)".

 Scene "x" / Value for Vane L-R (if available)
This parameter lets choose the vane position of the indoor unit when the scene is executed. The following options are available: "VANES L-R OFF", "VANES L-R POS 1(if available)", "VANES L-R POS 2(if available)", "VANES L-R POS 3(if available)", "VANES L-R POS 4(if available)", "VANES L-R POS 5(if available)", "VANES L-R SWING" or "(unchanged)".
 Scene "x" / Value for Setpoint Temp (ºC)
This parameter lets choose the setpoint temperature of the indoor unit when the scene is executed. The following options are available: from "18ºC" to "30ºC" (both included) or "(unchanged)".
 Scene "x" / Value for Remote Lock
This parameter lets choose the remote controller status of the indoor unit when the scene is executed. The following options are available: "Locked (remote not allowed)", "unlocked (remote allowed)" or "(unchanged)".

Important: If any preset value is configured as "(unchanged)", the execution of this scene will not change current status of this feature in the AC unit.
Important: When a scene is executed, Status_ Current Scene object shows the number of this scene. Any change in previous items does Status_ Current Scene show "No Scene". Only changes on items marked as "(unchanged)" will not disable current scene.
Switch-Off Timeouts Configuration dialog

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
42 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.45 Default Switch-Off Timeouts Configuration dialog
All the parameters in this section are related with the timeout properties and communication objects.
4.9.1 Enable use of Open Window / Switch off timeout function
This parameter shows/hides the Control_ Switch Off Timeout communication object which lets Start/Stop a timeout to switch off the indoor unit.
39 39
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Switch Off Timeout object and new parameters will appear.
If a "1" value is sent to this object, and the indoor unit is already turned on, the switchoff timeout will begin. If a "0" value is sent to this object, the switch-off timeout will stop.

Figure 4.46 Parameter detail
 AC switch-off timeout (min) This parameter lets select how much time (in minutes) to wait before switching off the indoor unit.
 DPT for Window / Switch-off timeout This parameter lets choose between the datapoints 0-Open / 1-Closed Window [DPT_1.009] and 0-Stop / 1-Start Timeout [DPT_1.010] for the Control_ Switch Off Timeout.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
43 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

 Disallow On/Off operation while window is Open

If set to "No", On/Off commands while the window is open will be accepted.

· If a "1" value is sent to the Control_ Switch Off Timeout object the switch-off timeout period will begin again.

· If a "0" value is sent to the Control_ Switch Off Timeout object, No action will be performed.

If set to "Yes", On/Off commands, while the window is open, will be saved (but not applied). These commands will be used in the next parameter if set to "Yes".

 Reload last On/Off val once window is closed?
If set to "No", once the switch-off timeout is stopped, any value will be reloaded.
If set to "Yes", once the switch-off timeout is stopped, the last On/Off value sent will be reloaded.
· If a "1" value is sent to the Control_ Switch Off Timeout object after the timeout period, the indoor unit will turn on.
· If a "0" value is sent to the Control_ Switch Off Timeout after the timeout period, No action will be performed.

4.9.2 Enable use of Occupancy function
This parameter shows/hides the Control_ Occupancy communication object which lets apply different parameters to the indoor unit depending on the presence/No presence in the room.
40
o If set to "No" the object will not be shown. o If set to "Yes" the Control_ Occupancy object and new parameters will appear. If a "1"
value is sent to this object (No room occupancy), the timeout will begin. If a "0" value is sent to this object, the timeout will stop.

Figure 4.47 Parameter detail
 Timeout to apply action (minutes)

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
44 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

This parameter lets choose how much time to wait (in minutes) before executing the action specified in the next parameter ("Action after timeout elapsed").
 Action after timeout elapsed

When Switch-Off is selected, once the timeout has elapsed, the indoor unit will be turned off.

When Apply Preset Delta is selected, once the timeout has elapsed, a delta temperature will be applied to save energy (decreasing the setpoint when in Heat mode or increasing the setpoint when in Cool mode). Also new parameters will appear.

Figure 4.48 Parameter detail
 Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature (increase or decrease) that will be applied when the timeout has elapsed.
Important: When there is occupancy again after the application of a delta, the same delta will be applied inversely. (i.e. In a room with AC in cool mode and 25ºC setpoint temperature, a +2ºC delta is applied after the occupancy timeout, setting the setpoint at 27ºC because there is No occupancy in the room. If the setpoint is raised to 29ºC during that period, when the room is occupied again, a -2ºC delta will be applied and the final setpoint temperature will then be 27ºC).
 Enable secondary timeout
If set to "No" nothing will be applied.
If set to "Yes", a new timeout will be enabled and two new parameters will appear.

Figure 4.49 Parameter detail
 Timeout to apply action (minutes) This parameter lets choose how much time to wait (in minutes) before executing the action specified in the next parameter ("Action after timeout elapsed"). This time is considered as a part of the occupancy.
 Action after timeout elapsed

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
45 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

When Switch-Off is selected, once the timeout has elapsed, the indoor unit will turn off.

When Apply Preset Delta is selected, once the timeout configured is extinguished, a delta temperature will be applied (decreasing the setpoint when in Heat mode, or increasing the setpoint when in Cool mode). Also new parameters will appear.

 Temp delta decrease (HEAT) or increase (COOL) (ºC)
This parameter lets configure the delta temperature that will be applied when the timeout is extinguished.
Important: When there is occupancy again after the application of a delta, the same delta will be applied inversely as explained above.

 Disallow On/Off operation while not Occupied
If set to "No", On/Off commands while the window is open will be accepted.
If set to "yes", once Switch-Off action has been executed, On/Off commands will be saved (but not applied). These commands will be used in the next parameter if set to "yes".

Figure 4.50 Parameter detail
 Reload last On/Off value when Occupied If set to "No", once the switch-off timeout has elapsed, any value will be reloaded. If set to "Yes", once the switch-off timeout has elapsed, the last On/Off value will be reloaded. · If a "1" value is sent to the Control_ Occupancy object after the timeout period, the indoor unit will turn on. · If a "0" value is sent to the Control_ Occupancy after the timeout period No action will be performed.
4.9.3 Enable use of SLEEP timeout
This parameter shows/hides the Control_ Sleep Timeout communication object which lets start a timeout to automatically turn off the indoor unit.
41
o If set to "No" the object will not be shown.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
46 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o If set to "Yes" the Control_ Sleep Timeout object and a new parameter will appear. If a "1" value is sent to this object the switch-off timeout will begin. If a "0" value is sent to this object, the switch-off timeout will stop.

Figure 4.51 Parameter detail
 Timeout to apply action (minutes)
This parameter lets select how much time (in minutes) to wait before switching off the AC unit.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
47 / 68

IntesisTM INKNXFGL001R000
Binary Input "x" Configuration dialog

User's manual r1.7 EN

Figure 4.52 Parameter detail

All the parameters in this section are related with the binary inputs properties and communication objects.

4.10.1

Enable use of Input "x"

This parameter enables the use of the Input "x" and shows/hides the Status_ Inx communication object(s) which will act as configured in the "Function" parameter.

109 110 111 112

o If set to "No" the objects will not be shown. o If set to "Yes" the Status_ Inx object(s) and new parameters will appear.

4.10.2

Contact type

This parameter lets choose the behavior that will have the binary input depending on if the contact is Normally open or Normally closed.
o There are two possible options to configure the contact type: "NO: Normally Open" and "NC: Normally Closed".

4.10.3 Debounce time
This parameter lets choose a debounce time (in milliseconds) that will be applied to the contact.

4.10.4 Disabling function

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
48 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

This parameter shows/hides the Control_ Disable Input x communication object which will let disable/enable the input x.

59 59

o If set to "No" any object will be shown.
o When "DPT 1.003: 0-Disable; 1-Enable" is selected, the input can be disabled using the value "0" and enabled using the value "1".
o When "DPT 1.002: 1-True (Disable); 0-False (Enable)" is selected, the input can be disabled using the value "1" and enabled using the value "0".

4.10.5 Function
This parameter lets choose the function that will have the binary input. There are 7 different functions available: Switching, Dimming, Shutter/Blind, Value, Execute Scene (internal), Occupancy (internal) and Window Contact (internal).
o When "Switching" is selected the communication object and new parameters for the Input "x" will appear as shown below.
109

Figure 4.53 Parameter detail
 Send telegram after bus recovery
This parameter lets select if the Binary Input "x" will send a telegram, or not, after a bus recovery and the type of telegram sent (if enabled).
· When "No action" is selected, No telegram will be sent after a bus recovery.
· When "Current status" is selected, the binary input will send a telegram with its current status after a bus recovery. Also a new parameter will appear (see below).
· When "On" is selected, the binary input will send a telegram with a "1" value after a bus recovery. Also a new parameter will appear (see below).
· When "Off" is selected, the binary input will send a telegram with a "0" value after a bus recovery. Also a new parameter will appear (see below).

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
49 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

Figure 4.54 Parameter detail
 Sending delay after a bus recovery (seconds)
This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
 Value on rising edge
This parameter lets select the value that the Binary Input "x" will send on a rising edge (contact activated).
· When "On" is selected, the binary input will always send telegrams with a "1" value.
· When "Off" is selected, the binary input will always send telegrams with a "0" value.
· When "Toggle (On/Off)" is selected, the binary input will send a "1" value after a "0" value and viceversa.
· When "No action" is selected, the binary input will not perform any action.
 Value on falling edge
This parameter lets select the value that the Binary Input "x" will send on a falling edge (contact deactivated).
· When "On" is selected, the binary input will always send telegrams with a "1" value.
· When "Off" is selected, the binary input will always send telegrams with a "0" value.
· When "Toggle (On/Off)" is selected, the binary input will send a "1" value after a "0" value and viceversa.
· When "No action" is selected, the binary input will not perform any action.

 Cyclical sending
This parameter lets enable/disable cyclical sending when a determined condition is met.
· When "When output value is On" is selected, everytime a "1" value is sent, it will be sent cyclically. Also a new parameter will appear (see below).
· When "When output value is Off" is selected, everytime a "0" value is sent, it will be sent cyclically. Also a new parameter will appear (see below).

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
50 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

· When "Always" is selected, the binary input will send any value cyclically. Also a new parameter will appear (see below).
· When "Never" is selected, cyclical sending will be disabled.
 Period for cyclical sending (seconds) This parameter lets configure a time (in seconds) for the cyclical sending.

Figure 4.55 Parameter detail
o When "Dimming" is selected the communication objects and new parameters for the Input "x" will appear as shown below.
109 110

Figure 4.56 Parameter detail
 Send telegram after bus recovery
This parameter lets select if the Binary Input "x" will send a telegram, or not, after a bus recovery and the type of telegram sent (if enabled).
· When "No action" is selected, No telegram will be sent after a bus recovery. · When "On" is selected, the binary input will send a telegram with a "1" value
after a bus recovery. Also a new parameter will appear (see below).
· When "Off" is selected, the binary input will send a telegram with a "0" value after a bus recovery. Also a new parameter will appear (see below).

Figure 4.57 Parameter detail

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
51 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

 Sending delay after a bus recovery (seconds)

This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.

 Mode for short (long) operation
This parameter lets select the value that the Binary Input "x" will send on a rising edge (contact activated), for a short and a long operation.
· When "On (increase)" is selected, the binary input will always send telegrams with a "1" value for a short operation, and an "increase step" for a long operation.
· When "Off (decrease)" is selected, the binary input will always send telegrams with a "0" value for a short operation, and an "decrease step" for a long operation.
· When "Toggle: On/Off (increase/decrease)" is selected:
o For the short operation the binary input will send a "1" value after a "0" value and viceversa.
o For the long operation the binary input will send an "increase step" after a "decrease step" and viceversa.

Important: note that the first long operation in toggle depends on the last short operation, meaning that after a "1" value will be sent a "decrease step" and after a "0" value will be sent an "increase step".
Important: The time period between a short and a long operation is defined in the parameter "Short/long operation limit (x100ms)".
 Increasing step
This parameter lets select the increasing step value (in %) that will be sent for a long operation.

 Decreasing step
This parameter lets select the decreasing step value (in %) that will be sent for a long operation.
 Short/long operation limit (x100ms)
This parameter lets introduce the time period difference for the short and the long operation.

 Cycl. send. period in long oper. (x100ms)
This parameter lets configure a time (in seconds) for the cyclical sending of a long operation.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
52 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o When "Shutter/Blind" is selected the communication objects and new parameters for the Input "x" will appear as shown below.

109 110

Figure 4.58 Parameter detail
 Send telegram after bus recovery This parameter lets select if the Binary Input "x" will send a telegram, or not, after a bus recovery and the type of telegram sent (if enabled). · When "No action" is selected, No telegram will be sent after a bus recovery. · When "Move Up" is selected, the binary input will send a telegram with a "0" value after a bus recovery. Also a new parameter will appear (see below). · When "Move Down" is selected, the binary input will send a telegram with a "1" value after a bus recovery. Also a new parameter will appear (see below).
Figure 4.44 Parameter detail
 Sending delay after a bus recovery (seconds) This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
 Operation This parameter lets select the value that the Binary Input "x" will send on a rising edge (contact activated). · When "Up" is selected, the binary input will always send telegrams with a "0". · When "Down" is selected, the binary input will always send telegrams with a "1" value. · When "Toggle (Up/Down)" is selected the binary input will send a "0" value after a "1" value and viceversa.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
53 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

 Method
This parameter lets select the working method for the shutter/blind.
· When "Step-Move-Step" is selected: On a rising edge (contact activated) a step/stop telegram will be sent and will begin a time called T1. If a falling edge occurs (contact deactivated) during the T1, No action will be performed.
If the rising edge is maintained longer than T1, a move telegram will be sent and will start a time called T2. If a falling edge occurs during the T2, a step/stop telegram will be sent. If a falling edge occurs after T2 No action will be performed.
· When "Move-Step" is selected: On a rising edge a move telegram will be sent and will begin the T2 time. If a falling edge occurs during the T2, a step/stop telegram will be sent. If a falling edge occurs after T2 No action will be performed.
Important: The T1 time have to be defined in the "Short/long operation limit (x100ms)" parameter. Also the T2 time have to be defined in the "Vanes adjustment time (x100ms)" parameter.

 Short/long operation limit (x100ms)
This parameter lets introduce the time period difference for the short and the long operation (T1 time).

 Vanes adjustment time (x100ms)
This parameter lets introduce the time period for the vanes adjustment/blind movement (T2 time).

o When "Value" is selected the communication objects and new parameters for the Input "x" will appear as shown below.
110

Figure 4.59 Parameter detail
 Send telegram after bus recovery This parameter lets select if the Binary Input "x" will send a telegram, or not, after a bus recovery and the type of telegram sent (if enabled).

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
54 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

· When "No action" is selected, No telegram will be sent after a bus recovery.

· When "Fixed value" is selected, the binary input will send a telegram with the same value configured in the "Value on rising edge" parameter. Also a new parameter will appear (see below).

Figure 4.60 Parameter detail
 Sending delay after a bus recovery (seconds) This parameter lets configure a delay (in seconds) that will be applied after a bus recovery and, after which, a telegram will be sent.
 DPT to be sent This parameter lets select the DPT type for the value that will be defined in the next parameter. This value will be sent on a rising edge (contact activated).
Figure 4.61 Parameter detail
 Value on rising edge (when contact activated) This parameter lets define a value for the DTP type configured in the "DPT to be sent" parameter. This value will be sent on a rising edge (contact activated).
o When "Execute Scene (internal)" is selected, the binary input "x" will activate the scene defined in the next parameter, on a rising edge (contact activated).

Figure 4.62 Parameter detail
 Scene when contact is activated This parameter lets choose the scene that will be activated on a rising edge. This scene MUST be defined in the "Scene Configuration" dialog as a preset.
o When "Occupancy (internal)" is selected, the binary input "x" will have the same behavior as configured in the parameter "Enable use of Occupancy function" inside the "Switch-Off Timeouts Configuration" dialog.

Figure 4.63 Parameter detail
© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
55 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

o When "Window Contact (internal)" is selected, the binary input "x" will have the same behavior as configured in the parameter "Enable use of Open Window / Switch off timeout function" inside the "Switch-Off Timeouts Configuration" dialog.

Figure 4.64 Parameter detail

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
56 / 68

IntesisTM INKNXFGL001R000 5 Specifications

User's manual r1.7 EN

Enclosure

Plastic, type ABS (UL 94 V-0). 2,5 mm thickness White RAL 9010

Dimensions

71 X 71 X 27 mm

Weight

70g

Colour

Ivory white

Power supply

29V DC, 7mA Supplied through KNX bus.

AC Indoor Unit Bus

Voltage: 13-18V Current: 80mA

LED indicators

1 x KNX programming.

Push buttons

1 x KNX programming.

4 x Potential-free binary inputs.

Signal cable length: 5m unshielded, may be extended up to 20m with twisted.

Binary inputs

Compliant with the following standards: IEC61000-4-2 : level 4 - 15kV (air discharge) - 8kV (contact discharge)

MIL STD 883E-Method 3015-7 : class3B

Configuration

Configuration with ETS.

Operating Temperature

From -25ºC to 60ºC

Storage Temperature

From - 40ºC to 45ºC

Isolation Voltage 2500V

RoHS conformity Compliant with RoHS directive (2002/95/CE).

CE conformity to EMC directive (2004/108/EC) and Low-voltage directive (2006/95/EC)

Certifications

· EN 61000-6-2 · EN 61000-6-3 · EN 60950-1 · EN 50491-3 · EN 50090-2-2 · EN 50428 · EN 60669-1 · EN 60669-2-1

Binary inputs 71 mm

71 mm

KNX bus connection
Programming LED Programming button
AC Indoor unit RWB bus connection 27 mm

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
57 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

6 AC Unit Types compatibility
A list of FGL indoor unit model references compatible with INKNXFGL001R000 and their available features can be found in:
Fujitsu: https://www.intesis.com/docs/compatibilities/inxxxfgl001r000_compatibility
General: https://www.intesis.com/docs/compatibilities/inxxxfgl001r000_general_compatibility
Fuji Electric: https://www.intesis.com/docs/compatibilities/inxxxfgl001r000_fuji-electric_compatibility
Hiyasu: https://www.intesis.com/docs/compatibilities/inxxxfgl001r000_hiyasu_compatibility

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
58 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

7 Error Codes
In order to get the right values regarding AC error codes, remember that you have to select the proper AC system type. Please visit section 4.1.2 for more information on the AC system type selection.

AC System Type
RAC Non inverter models RAC inverter models

Error Type
Type A

Error section
7.1

VRF V / S / J

Type A

7.2

RAC inverter model G* series VRF J-II / V-II / VR-II

Type B

7.1

* G series stands for units that include a `G' just before the power number in its reference. E.g.: ASYG09LTCA

RAC and VRF J-II / V-II / VR-II series

Error in KNX -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 20 21 22 23 24
25
26 27 28 29 30 31 32 33 34 36 37 38 39 40 41 42 43 44 45
46
47 48 49 50 51 52

Error in Remote Controller NA 00 01 02 03 04 05 06 07 08 09 0A 0b 0C 0d 0E 0F 11 12 13 14 15 16 17 18
19
1A 1b 1C 1d 1E 1F 20 21 22 24 25 26 27 28 29 2A 2b 2C 2d
2E
2F 30 31 32 33 34

Error Description
Communication Error (Hex:FFFF, Dec:65535) Wired remote controller error Indoor signal error Indoor room temperature sensor error Indoor room temperature sensor error Indoor heat exchanger temperature sensor (middle) error Indoor heat exchanger temperature sensor (middle) error Outdoor heat exchanger temperature sensor (outlet) error Outdoor heat exchanger temperature sensor (outlet) error Power voltage error Float switch operated Outdoor temperature sensor error Outdoor temperature sensor error Outdoor discharge pipe temperature sensor error Outdoor discharge pipe temperature sensor error Heat sink thermistor (Inverter) error Discharge temperature error Indoor unit EEPROM error Indoor fan error Indoor signal error Outdoor EEPROM error Compressor temperature sensor error Pressure switch abnormal, Pressure sensor error IPM protection CT error Active filter error INV voltage protection Compressor location error Outdoor fan error Outdoor unit computer communication error 2-way valve temperature sensor error 3-way valve temperature sensor error Connected indoor unit error Indoor MANUAL AUTO switch error reverse VDD permanent stop protection VDD permanent stop protection Excessive high pressure protection on cooling P.F.C. circuit error Indoor signal error Indoor signal error Indoor heat exchanger temperature sensor (inlet) error Outdoor heat exchanger temperature sensor (middle) error Power supply frequency detection error Compressor temperature error 4-way valve error Heat sink thermistor P.F.C. error Indoor unit damper error Inverter error Low pressure error Refrigerant circuit address set-up error Master unit, Slave unit set-up error Connected the indoor number set-up error P.F.C. printed circuit board error Indoor fan 2 error

AC System Type
RAC Inverter and Non
Inverter

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
59 / 68

IntesisTM INKNXFGL001R000

User's manual r1.7 EN

53

35

Control box thermistor error

54

36

Indoor unit CT error

55

37

Indoor fan motor 1 driving circuit error

56

38

Indoor fan motor 2 driving circuit error

117

11

Serial communication error between indoor/outdoor units

118

12

Remote controller communication error

119

13

Communication error between outdoor units

120

14

Network communication error

121

15

Scan error

122

16

Peripheral unit communication error

123

17

Electricity charge apportionment error

133

21

Indoor unit initial setting error

134

22

Indoor unit capacity abnormal

135

23

Incompatible series connection error

136

24

Connection unit number error

137

25

Connection pipe length error

138

26

Indoor unit address setting error

139

27

Master/slave unit setting error

140

28

Other setting error

141

29

Connection unit number error in wired remote controller system

149

31

Indoor unit power supply abnormal

150

32

Indoor unit main PCB error

151

33

Indoor unit display PCB error

152

34

Power relay error

153

35

Indoor unit manual auto switch error

154

36

Heater relay error

155

37

Indoor unit transmission PCB error

156

38

Network convertor PCB error

157

39

Indoor unit power supply circuit error

158

3A

Indoor unit communication circuit (wired remote controller) error

165

41

Indoor unit room temp. thermistor error

166

42

Indoor unit heat ex. temp. thermistor error

167

43

Humidity sensor error

168

44

Light sensor error

169

45

Gas sensor error

170

46

Float sensor error

171

47

Water temperature sensor error

172

48

Warm water flow rate sensor error

173

49

Heater sensor error

181

51

Indoor unit fan motor 1 error

182

52

Indoor unit coil (expansion valve) error

RAC Inverter models G
series

183

53

Indoor unit water drain abnormal

184

54

Air cleaning function error

VRF

185

55

Filter cleaning function error

186

56

Water circulation pump error

J-II / V-II / VR-II Series

187

57

Indoor unit damper error

188

58

Indoor unit intake grille position error

189

59

Indoor unit fan motor 2 error

195

5U

Indoor unit miscellaneous error

197

61

Outdoor unit power supply abnormal

198

62

Outdoor unit main PCB error

199

63

Outdoor unit inverter PCB error

200

64

Outdoor unit active filter/PFC circuit error

201

65

Outdoor unit IPM error

202

66

Convertor distinction error

203

67

Outdoor unit power short interruption error (protective operation)

204

68

Outdoor unit magnetic relay error

205

69

Outdoor unit transmission PCB error

206

6A

Outdoor unit display PCB error

213

71

Outdoor unit discharge temp. thermistor error

214

72

Outdoor unit compressor temp. thermistor error

215

73

Outdoor unit heat ex. temp. thermistor error

216

74

Outside air temp. thermistor error

217

75

Outdoor unit suction gas temp. thermistor error

218

76

Outdoor unit operating valve thermistor error

219

77

Outdoor unit heat sink temp. thermistor error

220

78

Expansion valve temperature sensor error

229

81

Receiver liquid level detection sensor error

230

82

Outdoor unit sub-cool heat ex. gas temp. thermistor error

231

83

Outdoor unit liquid pipe temp. thermistor error

232

84

Outdoor unit current sensor error

233

85

Fan motor current sensor error

234

86

Outdoor unit pressure sensor error

235

87

Oil sensor error

245

91

Outdoor unit compressor 1 error

246

92

Outdoor unit compressor 2 error

247

93

Outdoor unit compressor start up error

248

94

Outdoor unit trip detection

249

95

Outdoor unit compressor motor control error

250

96

Open loop error(Field-weakening relevant)

RAC

251

97

Outdoor unit fan motor 1 error

Inverter models G

252

98

Outdoor unit fan motor 2 error

series

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
60 / 68

IntesisTM INKNXFGL001R000

253

99

Outdoor unit 4-way valve error

254

9A

Outdoor unit coil (expansion valve) error

259

9U

Outdoor unit miscellaneous error

261

A1

Outdoor unit discharge temperature 1 error

262

A2

Outdoor unit discharge temperature 2 error

263

A3

Outdoor unit compressor temperature error

264

A4

Outdoor unit pressure error 1

265

A5

Outdoor unit pressure error 2

266

A6

Outdoor unit heat exchanger temperature error

267

A7

Suction temperature abnormal

268

A8

Poor refrigerant circulation

269

A9

Current overload error

270

AA

Outdoor unit special operation error

271

AC

Ambient temperature error

272

AF

Out of the possible operation range

273

AJ

Freeze protection operated

277

C1

Peripheral unit main PCB error

278

C2

Peripheral unit transmission PCB error

279

C3

Peripheral unit PCB 1 error

280

C4

PCB 2 error

281

C5

PCB 3 error

282

C6

PCB 4 error

283

C7

PCB 5 error

284

C8

Peripheral unit input device error

285

C9

Display device error

286

CA

EEPROM error

287

CC

Peripheral unit sensor error

288

CF

Peripheral unit external connector error (USB memory)

289

CJ

Other parts error

293

F1

System tool software error

294

F2

System tool adaptor error

295

F3

System tool interface error

296

F4

System tool environment error

309

J1

RB unit error

310

J2

Branch boxes error

311

J3

Total heat exchanging, ventilation unit error

312

J4

Domestic hot water unit error

313

J5

Zone control interface error

User's manual r1.7 EN
VRF J-II / V-II / VR-II
Series

VRF V / S / J series

Error in KNX -1 0 2 4 6 7 9 10 11 12 13 17 18 19
20
31 32 33 34

Error in Remote Controller NA 00 02 04 06 07 09 0A 0b 0C 0d 11 12 13
18
1F 20 21 32

Error Description
Communication Error (Hex:FFFF, Dec:65535) No Error Model information Error Power frequency Error EEPROM access Error EEPROM deletion Error Room sensor Error Heat Ex. Middle Sensor Error Heat Ex. Inlet sensor Error Heat Ex. Outlet sensor Error Blower temperature thermistor Error Drain Error Room temperature Error Indoor fan motor Error Standard wired remote Error Standard wired token Error Network communication Error Node setting error Communication Error between Main PCB & Transmission PCB Outdoor unit Error

VRF V / S / J series

In case you detect an error code not listed in any of the different tables above, please contact your nearest FGL technical support service.

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
61 / 68

IntesisTM INKNXFGL001R000

User's manual r1.6 EN

8 Appendix A ­ Communication Objects Table

TOPIC

OBJECT NUMBER

NAME

On/Off Mode Fan Speed

0

Control_ On/Off

1

Control_ Economy

2

Control_ Mode

3

Control_ Mode Cool/Heat

4

Control_ Mode Cool & On

5

Control_ Mode Heat & On

6

Control_ Mode Auto

7

Control_ Mode Heat

8

Control_ Mode Cool

9

Control_ Mode Fan

10

Control_ Mode Dry

Control_ Mode +/11
Control_ Mode +/-

Control_ Fan Speed / 3 Speeds

Control_ Fan Speed / 3 Speeds 12
Control_ Fan Speed / 4 Speeds

Control_ Fan Speed / 4 Speeds

LENGTH 1 bit

DATAPOINT TYPE

FLAGS

DPT_NAME

DPT_I D

R W T U

DPT_Switch

1.001

W T 0 - Off; 1-On

FUNCTION

1 bit

DPT_Bool

1.002

1 byte DPT_HVACContrMode 20.105

1 bit

DPT_Heat/Cool

1.100

W T W T W T

1 ­ Set ECONOMY
0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 Dry
0 - Cool; 1 - Heat;

1 byte

DPT_Scaling

5.001

W T 0% - Off; 0.1%-100% - On + Cool

1 byte

DPT_Scaling

5.001

W T 0% - Off; 0.1%-100% - On + Heat

1 bit

DPT_Bool

1.002

W T 1 - Auto

1 bit

DPT_Bool

1.002

W T 1 - Heat

1 bit

DPT_Bool

1.002

W T 1 - Cool

1 bit

DPT_Bool

1.002

W T 1 - Fan

1 bit

DPT_Bool

1.002

W T 1 - Dry

1 bit

DPT_Step

1.007

W

0 - Decrease; 1 - Increase

1 bit

DPT_UpDown

1.008

W

0 - Up; 1 - Down

1 byte

DPT_Scaling

5.001

W T

0%-49% - Speed 1; 50%-82% - Speed 2; 83%-100% - Speed 3

1 byte 1 byte 1 byte

DPT_Enumerated DPT_Scaling
DPT_Enumerated

5.010 5.001 5.010

W T W T W T

1 - Speed 1; 2 - Speed 2; 3 Speed 3
0%-37% - Speed 1; 38%-62% - Speed 2; 63%-87% - Speed 3; 88%-100% - Speed 4 1 - Speed 1; 2 - Speed 2; 3 Speed 3; 4 Speed 4

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
62 / 68

IntesisTM INKNXFGL001R000

Fan Speed
Vanes Up-Down
Vanes Left-Right

13

Control_ Fan Speed Man/Auto

14

Control_ Fan Speed 1

15

Control_ Fan Speed 2

16

Control_ Fan Speed 3

17

Control_ Fan Speed 4

Control_ Fan Speed +/18
Control_ Fan Speed +/-

Control_ Vanes U-D / 4 pos 19
Control_ Vanes U-D / 4 pos

20

Control_ Vanes U-D Pos1

21

Control_ Vanes U-D Pos2

22

Control_ Vanes U-D Pos3

23

Control_ Vanes U-D Pos4

24

Control_ Vanes U-D Swing

Control_ Vanes U-D +/25
Control_ Vanes U-D +/-

26

Control_ Vanes U-D Move Pos

Control_ Vanes L-R / 5 pos 27
Control_ Vanes L-R / 5 pos

28

Control_ Vanes L-R Pos1

29

Control_ Vanes L-R Pos2

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

User's manual r1.6 EN

1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 byte
1 byte 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 byte
1 byte 1 bit 1 bit

DPT_Bool DPT_Bool DPT_Bool DPT_Bool DPT_Bool DPT_Step DPT_UpDown DPT_Scaling
DPT_Enumerated DPT_Bool DPT_Bool DPT_Bool DPT_Bool DPT_Bool DPT_Step
DPT_UpDown DPT_Step
DPT_Scaling
DPT_Enumerated DPT_Bool DPT_Bool

1.002 1.002 1.002 1.002 1.002 1.007 1.008 5.001
5.010 1.002 1.002 1.002 1.002 1.002 1.007 1.008 1.017 5.001
5.010 1.002 1.002

W T W T W T W T W T W W W T
W T W T W T W T W T W T W W W W T
W T W T W T

0 ­ Manual; 1 - Auto 1 ­ Set Fan Speed 1 1 ­ Set Fan Speed 2 1 ­ Set Fan Speed 3 1 ­ Set Fan Speed 4
0 - Decrease; 1 - Increase
0 - Up; 1 - Down 0%-37% - Pos1; 38%-62% - Pos2; 63%87% Pos3; 88%-100% - Pos4
1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4
1 ­ Set Position 1 1 ­ Set Position 2 1 ­ Set Position 3 1 ­ Set Position 4 0 - Off; 1 - Swing
0 - Decrease; 1 - Increase
0 - Up; 1 - Down
0 ­ Move position; 1 ­ Move position 0%-29% - Pos1; 30%-49% - Pos2; 50%69% Pos3; 70%-89% - Pos4; 90%-100% Pos5 1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4; 5 Pos5 1 ­ Set Position 1 1 ­ Set Position 2

URL https://www.intesis.com
63 / 68

IntesisTM INKNXFGL001R000

Temperature
Timeout
Locking Special Modes Scenes

30

Control_ Vanes L-R Pos3

31

Control_ Vanes L-R Pos4

32

Control_ Vanes L-R Pos5

33

Control_ Vanes L-R Swing

Control_ Vanes L-R +/34
Control_ Vanes L-R +/-

35

Control_ Vanes L-R Move Pos

36

Control_ Setpoint Temperature

Control_ Setpoint Temp +/37
Control_ Setpoint Temp +/-

38

Control_ Ambient Temp

Control_ Window Contact Status 39
Control_ Switch Off Timeout

40

Control_ Occupancy

41

Control_ Sleep Timeout

42

Control_ Lock Remote Control

43

Control_ Lock Control Objects

44

Control_ Power Mode

45

Control_ Econo Mode

46

Control_ Additional Heat

47

Control_ Additional Cool

48

Control_ Save

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

User's manual r1.6 EN

1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 2 byte 1 bit 1 bit 2 byte 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 byte

DPT_Bool DPT_Bool DPT_Bool DPT_Bool DPT_Step DPT_UpDown DPT_Step DPT_Value_Temp DPT_Step DPT_UpDown DPT_Value_Temp DPT_OpenClose DPT_Start DPT_Occupancy DPT_Start DPT_Bool DPT_Bool DPT_Start DPT_Start DPT_Start DPT_Start DPT_SceneControl

1.002 1.002 1.002 1.002 1.007 1.008 1.007 9.001 1.007 1.008 9.001 1.009 1.010 1.018 1.010 1.002 1.002 1.010 1.010 1.010 1.010 18.001

W T W T W T W T W W W W T W W W T W T W T W T W T W T W T W T W T W T W T W T

1 ­ Set Position 3 1 ­ Set Position 4 1 ­ Set Position 5 0 - Off; 1 - Swing 0 - Decrease; 1 - Increase 0 - Up; 1 - Down 0 ­ Move position; 1 ­ Move position (ºC) 0 - Decrease; 1 - Increase 0 - Up; 1 - Down (ºC) 0 - Open; 1 - Closed 0 - Stop; 1 - Start 0 - Not Occupied; 1 - Occupied 0 - Stop; 1 - Start 0 - Unlocked; 1 - Locked 0 - Unlocked; 1 - Locked 0 - Stop; 1 - Start 0 - Stop; 1 - Start 0 - Stop; 1 - Start 0 - Stop; 1 - Start 128 to 132 - Save Scene 1 to 5

URL https://www.intesis.com
64 / 68

IntesisTM INKNXFGL001R000

Disabling
On/Off Mode

Control_ Exec Scene

49

Control_ Store Scene1

50

Control_ Store Scene2

51

Control_ Store Scene3

52

Control_ Store Scene4

53

Control_ Store Scene5

54

Control_ Execute Scene1

55

Control_ Execute Scene2

56

Control_ Execute Scene3

57

Control_ Execute Scene4

58

Control_ Execute Scene5

Control_ Disable Input 1 59
Control_ Disable Input 1

Control_ Disable Input 2 60
Control_ Disable Input 2

Control_ Disable Input 3 61
Control_ Disable Input 3

Control_ Disable Input 4 62
Control_ Disable Input 4

64

Status_ On/Off

65

Status_ Economy

66

Status_ Mode

67

Status_ Mode Cool/Heat

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

User's manual r1.6 EN

1 byte DPT_SceneControl 18.001

W T

1 bit

DPT_Bool

1.002

W

1 bit

DPT_Bool

1.002

W

1 bit

DPT_Bool

1.002

W

1 bit

DPT_Bool

1.002

W

1 bit

DPT_Bool

1.002

W

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Enable

1.003

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Enable

1.003

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Enable

1.003

W T

1 bit

DPT_Bool

1.002

W T

1 bit

DPT_Enable

1.003

W T

1 bit

DPT_Switch

1.001 R T

1 bit

DPT_Bool

1.002 R T

1 byte DPT_HVACContrMode 20.105 R T

1 bit

DPT_Heat/Cool

1.100 R T

0 to 4 - Exec. Scene 1 to 5; 1 - Store Scene 1 - Store Scene 1 - Store Scene 1 - Store Scene 1 - Store Scene 1 - Execute Scene 1 - Execute Scene 1 - Execute Scene 1 - Execute Scene 1 - Execute Scene 0 - False; 1 - True 0 - Disable; 1 - Enable 0 - False; 1 - True 0 - Disable; 1 - Enable 0 - False; 1 - True 0 - Disable; 1 - Enable 0 - False; 1 - True 0 - Disable; 1 - Enable 0 - Off; 1-On 1 ­Economy is active 0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 Dry 0 - Cool; 1 - Heat

URL https://www.intesis.com
65 / 68

IntesisTM INKNXFGL001R000

Fan Speed
Vanes UP-Down

68

Status_ Mode Auto

69

Status_ Mode Heat

70

Status_ Mode Cool

71

Status_ Mode Fan

72

Status_ Mode Dry

73

Status_ Mode Text

Status_ Fan Speed / 3 Speeds

74

Status_ Fan Speed / 3 Speeds

Status_ Fan Speed / 4 Speeds

Status_ Fan Speed / 4 Speeds

75

Status_ Fan Speed Manual/Auto

76

Status_ Fan Speed 1

77

Status_ Fan Speed 2

78

Status_ Fan Speed 3

79

Status_ Fan Speed 4

80

Status_ Fan Speed Text

Status_ Vanes U-D / 4 pos 81
Status_ Vanes U-D / 4 pos

82

Status_ Vanes U-D Pos1

83

Status_ Vanes U-D Pos2

84

Status_ Vanes U-D Pos3

85

Status_ Vanes U-D Pos4

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

User's manual r1.6 EN

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

14 byte DPT_String_8859_1 16.001 R T

1 byte

DPT_Scaling

5.001

W T

1 byte

DPT_Enumerated

5.010

W T

1 byte

DPT_Scaling

5.001

W T

1 byte

DPT_Enumerated

5.010

W T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

14 byte DPT_String_8859_1 16.001 R T

1 byte

DPT_Scaling

5.001 R T

1 byte

DPT_Enumerated

5.010 R T

1 bit

DPT_Bool

1.002 R T

1 bit

DPT_Bool

1.002 R T

1 bit 1 bit

DPT_Bool DPT_Bool

1.002 R T 1.002 R T

1 - Auto 1 - Heat 1 - Cool 1 - Fan 1 - Dry ASCII String 33% - Speed 1; 67% - Speed 2; 100% - Speed 3; 1 - Speed 1; 2 - Speed 2; 3 Speed 3; 25% - Speed 1; 50% - Speed 2; 75% Speed 3; 100% - Speed 4 1 - Speed 1; 2 - Speed 2; 3 Speed 3; 4 Speed 4 0 ­ Manual; 1 - Auto
1 ­ Fan is in speed 1
1 ­ Fan is in speed 2
1 - Fan is in Speed 3
1 - Fan is in Speed 4
ASCII String 25% - Pos1; 50% - Pos2; 75% - Pos3; 100% - Pos4 1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4
1 - Position 1
1 - Position 2
1 - Position 3
1 - Position 4

URL https://www.intesis.com
66 / 68

IntesisTM INKNXFGL001R000

User's manual r1.6 EN

Vanes Left-Right
Temperature Error
Locking Special Modes

86

Status_ Vanes U-D Swing

87

Status_ Vanes U-D Text

Status_ Vanes L-R / 5 pos 88
Status_ Vanes L-R / 5 pos

1 bit

DPT_Bool

1.002 R T

14 byte DPT_String_8859_1 16.001 R T

1 byte

DPT_Scaling

5.001 R T

1 byte

DPT_Enumerated

5.010 R T

89

Status_ Vanes L-R Pos1

1 bit

DPT_Bool

1.002 R T

90

Status_ Vanes L-R Pos2

1 bit

DPT_Bool

1.002 R T

91

Status_ Vanes L-R Pos3

1 bit

DPT_Bool

1.002 R T

92

Status_ Vanes L-R Pos4

1 bit

DPT_Bool

1.002 R T

93

Status_ Vanes L-R Pos5

1 bit

DPT_Bool

1.002 R T

94

Status_ Vanes L-R Swing

1 bit

DPT_Bool

1.002 R T

95

Status_ Vanes L-R Text

14 byte DPT_String_8859_1 16.001 R T

96

Status_ AC Setpoint Temp

2 byte

DPT_Value_Temp

9.001 R T

97 98 99 100 101 102 103 104 105

Status_ AC Ambient Ref Temp

2 byte

DPT_Value_Temp

9.001 R T

Status_ Error/Alarm

1 bit

DTP_Alarm

1.005 R T

Status_ Error Code

2 byte

Enumerated

R T

Status_ Error Text code

14 byte DPT_String_8859_1 16.001 R T

Status_ Lock Remote Control

1 bit

DPT_Bool

1.002

W T

Status_ Lock Remote Control Objects

1 bit

DPT_Bool

1.002

W T

Status_ Power Mode

1 bit

DPT_Switch

1.001 R T

Status_ Econo Mode Status_ Additional Heat

1 bit 1 bit

DPT_Switch DPT_Switch

1.001 R T 1.001 R T

0 ­ Off; 1 - Swing ASCII String 20% - Pos1; 40% - Pos2; 60% - Pos3; 80% - Pos4; 100% - Pos5 1 - Pos1; 2 - Pos2; 3 - Pos3; 4 - Pos4; 5 Pos5 1 - Position 1
1 - Position 2
1 - Position 3
1 - Position 4
1 - Position 5
0 ­ Off; 1 - Swing
ASCII String
(ºC)
(ºC) 0 - No Alarm; 1 - Alarm 0 - No Error; Any other see user's manual 4 char FJ Error; Empty - None 0 - Unlocked; 1 - Locked 0 - Unlocked; 1 - Locked 0 - Off; 1-On 0 - Off; 1-On 0 - Off; 1-On

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
67 / 68

IntesisTM INKNXFGL001R000

User's manual r1.6 EN

Counter Scene
Binary Inputs

106 107 108 109 111 113 115
110 112 114 116

Status_ Additional Cool Status_ Operation Hour Counter Status_ Current Scene Status_ Inx - Switching Status_ Inx ­ Dimming - On/Off Status_ Inx ­ Shut/Blind - Step Status_ Inx ­ Value Status_ Inx ­ Value Status_ Inx ­ Value Status_ Inx ­ Value Status_ Inx ­ Value Status_ Inx ­ Dimming ­ Step(%) Status_ Inx - Shut/Blind -Move

1 bit

DPT_Switch

1.001 R T 0 - Off; 1-On

2 byte DPT_Value_2_Ucount 7.007 R T Number of operating hours

1 byte DPT_SceneNumber 17.001 R T 0 to 4 - Scene 1 to 5; 63 - No Scene

1 bit

DPT_Switch

1.001 R T 0 - Off; 1-On

1 bit

DPT_Switch

1.001 R T 0 - Off; 1 - On

1 bit

DPT_ShutterBlinds

1.023 R

T

0 ­ Step Up; 1 ­ Step Down

1 byte DPT_Value_1_Ucount 5.010 R T 1 byte unsigned value

2 byte DPT_Value_2_Ucount 7.001 R T 2 byte unsigned value

2 byte DPT_Value_2_Count 8.001 R T 2 byte signed value

2 byte

DPT_Value_Temp

9.001 R T Temperature (ºC)

4 byte DPT_Value_4_Ucount 12.001 R T 4 byte unsigned value

1 bit

DPT_Control_Dimm. 3.007 R

T

Dimming step

1 bit

DPT_ShutterBlinds

1.023 R

T

0 ­ Move Up; 1 ­ Move Down

© HMS Industrial Networks S.L.U. - All rights reserved This information is subject to change without notice

URL https://www.intesis.com
68 / 68



References

Microsoft Word para Office 365