OPERATION 1. Verify the power switch is in the off position. Plug your heaters & RTD into the rear connectors. Plug the provided line cord from the console into a standard 120V, 15A outlet.

TPC10064 Power Control Console User Manual

Technical

User Manual for TPC10064


File Info : application/pdf, 24 Pages, 3.91MB

PDF preview unavailable. Download the PDF instead.

TPC10064
USER MANUAL TPC10064 - Power Control Console with TEC-9400 (PID + Fuzzy Logic Process Controller)
DMR1ea3vni0us6iao.lTnTE6P-/C4202110·-04D601423-94204-405 Revision 2/22/2019

SPECIFICATIONS
Temperature Controller: Model TEC-9400, 1/16 DIN Dual Display with PID Auto-tuning Sensor Input: 3-Wire RTD PT100 Connector Body: White Power Cord/voltage Input: 120VAC, 50/60 HZ, 15A Heater Outputs: 12A Max, 1440 watts max Output Device: Solid State Relay Main Power Switch: Located on front panel Fuse Main Power: See replacement parts list on next page (located on back panel) Fuse Control Power: See replacement parts list on next page (located on back panel)
WARNINGS
1. Air vents located on top and bottom of console must not be blocked! To prevent an overheating condition the internal components must remain as close to room temperature (75ºF / 24ºC) as possible.
2. Dangerous voltage capable of causing injury or death is present within this console. Power to all equipment must be disconnected before installation or beginning any troubleshooting procedures. Heater output wiring and component replacement must be made by qualified personnel only.
3. To minimize the possibility of fire or shock, do not expose this console to rain or excessive moisture.
4. Do not use this console in areas where hazardous conditions exist such as excessive shock, vibration, dirt, corrosive gases, oil or where explosive gases or vapors are present.
5. It is strongly recommended that a process should incorporate a Limit Control like a Tempco TEC-910 which will shut down the equipment at a preset process condition in order to avoid possible damage to products or systems.
WIRING (For safety, disconnect all power sources prior to wiring)
1. Attach the leads from your 3-Wire RTD sensor to the mini-plug provided. The red lead attached to the (-) lead. When using a 2-Wire RTD, a jumper has to be placed between the (+) and (G) terminal.
2. The heater output current is sourced directly through the line cord. The rear console output receptacles and mating Hubbell plugs provide live controlled power for direct connection to your heater(s). Connect one lead from your heater to one prong of the Hubbell plug (not ground). Connect the other lead from your heater to the other prong. Connect heater ground (if applicable) to the ground connection (G) on the plug.
1

OPERATION
1. Verify the power switch is in the off position. Plug your heaters & RTD into the rear connectors. Plug the provided line cord from the console into a standard 120V, 15A outlet. Switch on the console.
2. Set your desired temperature setpoint by using the up and down arrow buttons on the TEC-9400 temperature controllers.
3. Refer to the following pages for complete operation and page 4 & 7 for auto-tuning of the TEC-9400 temperature controllers.

SPARE/REPLACEMENT PARTS
Tempco Part Number

Description

EHD-124-148 EHD-124-276 EHD-102-113 TCA-101-154

Fuse (1), rated 15 Amp/250V, ¼ x 1 ¼", fast acting BUSS ABC-15-R. Used for main control console power.
Fuse (1), rated 1 Amp/ 250V, ¼" x 1¼", fast acting, BUSS ABC-1-R. Used for TEC-9400 Controller.
Power output plug, Hubbell HBL4720C, 15A 125V Twist-Lock.
RTD mini plug, White, 3-P.

NOTE: For all fuses, use listed BUSS part numbers or equivaliant.

2

TEC-9400 Front Panel Keys and Display

KEYPAD OPERATION SCROLL KEY: This key is used to scroll through a menu to select a parameter to be viewed or adjusted. UP KEY: This key is used to increase the value of the selected parameter. DOWN KEY: This key is used to decrease the value of the selected parameter.

RESET KEY: This key is used to:
1. Revert the display to the home screen. 2. Reset a latching alarm once the alarm condition is removed. 3. Stop manual control mode, Auto-Tuning mode or calibration mode. 4. Clear an Auto-Tuning or communication error message. 5. Restart the dwell timer when the dwell timer has timed out. 6. Enter the manual control menu if failure mode occurs.

ENTER KEY: Press and hold for 5 seconds or longer to:

1. Enter the setup menu. The display will show

.

2. Enter manual control mode. Press and hold for 6.2 seconds, then let go, to select manual control

mode. The display will show

.

3. Enter Auto-Tuning mode. Press and hold for 7.4 seconds, then let go to select Auto-Tuning

mode. The display will show

.

4. Perform calibration of a selected parameter during the calibration procedure. Press and hold for

8.6 seconds, then let go to select calibration mode.

During power-up, the upper display will show PROG and the lower display will show

the Firmware version for 6 seconds.

3

1.1 Menu Flowchart
The Menu has been divided in to 5 groups. They are as follows: 1. User Menu - Below 2. Setup Menu - Page 5 3. Manual Mode Menu - Page 7 4. Auto-Tuning Mode Menu - Page 7 5. Calibration Mode Menu (not recommended, calibration section has been removed)

User Menu

Setup Menu

Manual Mode Auto-Tuning Mode Calibration Mode

5 Sec

6.2 Sec

7.4 Sec

8.6 Sec

9.8 Sec

To access
parameter
In the User Menu,
Refer to Section 1.1.1 Below

To access parameter in the Setup Menu, Refer to Section 1.1.2 Page 5

5 Sec

5 Sec

To start
Manual Control
Mode, Refer to Section 1.1.3 Page 7

To start

DO NOT ENTER

Auto-Tuning

Mode, Refer to

Section 1.1.4

Page 7

Press for the next parameter Press and key to return to the previous parameter.

1.1.1 User Menu

The below user menu parameters are available depending on user selection.

PV,SV

SP1 SP2 SP3 SP4 SP5 SP6 SP7 SFtR CT 1R CT 2R DT MR PASS RUN CYCR ST EP T IM R SEL1 SEL2 SEL3 SEL4 SEL5 SEL6 SEL7 SEL8

 See pJV 

4

1.1.2 Setup Menu

The setup menu has been categorized in to eight categories. They are listed below.

1. Basic Menu (Below) 2. Output Menu (pg. 6)
3. Alarm Menu 4. Event Input Menu

5. User Select Menu 6. Communication Menu
7. Current Transformer Menu 8. Profile Menu (Ramp and Soak)

1.1.2.1 Basic Menu (bASE)
In the setup menu, when the upper display says "SET", Use the or keys to get "bASE" in the lower display. Then, use the key to cycle through the "bASE" menu parameters. (Note chart on pg. 8)

or

SET

bASE

OFS1 OFS2 OFS3 INPT UNIT
DP INLO INHI SP1L SP1H FILT DISP PB
TI TD RAMP RR RET Y RELO REHI RMSP RINL RINH CODE OFST L OFST H CALO CAHI SFT SFL1 SFL2 SFtH

} Turn options ON or OFF- Not Used
Pgs. 8 & 9
- Pgs. 9 & 10 - Retransmit - Not Used
- Pg. 11 Security Code - Pg. 14 - Pg. 14 Offset Calibration

* Does not apply to the controller used in this console.
5

1.1.2.2 Output Menu (oUT)
In the setup menu, when the upper display says "SET", use the or key to get "oUT" in the lower display. Then, use the key to cycle through the "oUT" menu parameters.

or

SET

OUT

OUT 1 O1T Y O1FT O1HY CYC1 OFST OUT 2 O2T Y O2FT CYC2 CPB
DB PL1L PL1H PL2L PL2H

- Pg. 9
- Power Limit Pg. 10 - Power Limit Pg. 10
} Not Used

* Not Used in this console

6

1.1.3 Manual Mode Menu ­ (Use for Temporary Operation if Sensor Fails) (Also refer to pg. 18)

Press and hold the " " key for approx. 6sec until the "HAND" parameter is shown in the upper display. Then, press and hold the " " key for an additional 5 sec. until an "MANU" led starts to flash in the lower left of the display. Then, use the " " key to cycle through the available options. User is able to manually set the out output to be energized from 0-100% of the cycle time. "Hx.xx" is used to adjust output 1. "Cx.xx" is used to adjust output 2.

You are able to exit manual mode by pressing and holding the

key.

HANd 5 Sec

MV1 MV2 FILE

Press key 5 Sec To execute the selected default program
1.1.4 Auto-Tuning Mode ­ (Tunes PID Parameters to Your Application) (Also refer to pg. 15)

Press and hold the " " key for approx. 7sec until the "A-T" parameter is shown in the upper display. Press and hold the " " key for 5 seconds to activate Auto-Tuning Mode. Continue to hold the " " key for an additional 3 seconds, else the display will revert to a "User Menu" parameter.
Auto-tuning allows the controller to find its own optimal control parameters (PID) by measuring the speed of your thermal process.

7

1.2 Parameter Description
(*Parameters that are not applicable are not shown)

Register Address

Parameter Notation

Parameter Description

Range

Default Value

Basic Menu

0

SP1

Set Point 1 (Used for Output 1)

Low: SP1L High: SP1H

77.0° F (25.0° C)

0 J_tC: J type Thermocouple

1 K_tC: K type Thermocouple

2 T_tC: T type Thermocouple 3 E_tC: E type Thermocouple 4 B_tC: B type Thermocouple

5 R_tC: R type Thermocouple

6 S_tC: S type Thermocouple

7 N_tC: N type Thermocouple

8 L_tC: L type Thermocouple

8

INPT
(Set for console

Input sensor selection

9 U_tC: U type Thermocouple 10 P_tC: P type Thermocouple

13

Do Not Adjust)

11 C_tC: C type Thermocouple

12 D_tC: D type Thermocouple

13 Pt.dN: PT100 DIN curve

14 Pt.JS: PT100 JIS curve 15 4-20: 4-20mA linear current input 16 0-20: 0-20mA linear current input

17 0-5V: 0-5VDC linear voltage input

18 1-5V: 1-5VDC linear voltage input

19 0-10: 0-10VDC linear voltage input

0 oC:°C unit

9

UNIT

Input unit selection

1 oF:°F unit

1

2 Pu:Process unit

0 No.dP: No decimal point

10

DP

Decimal point selection

1 1-dP: 1 decimal digit 2 2-dP: 2 decimal digit

0

3 3-dP: 3 decimal digit

13

SP1L

Low limit of set point 1 (Span Value)

Low: -19999 High :SP1H

0.0° F (-18.0° C)

14

SP1H

High limit of set point 1 (Span Value)

Low: SP1L High: 45536

1000.0° F (538° C)

0 0: 0 second time constant

1 0.2: 0.2 second time constant

2 0.5: 0.5 second time constant

15

FILT

Filter damping time constant of PV Sensor

3 1: 1 second time constant 4 2: 2 second time constant 5 5: 5 second time constant

2

(See Pg. 14)

6 10: 10 second time constant

7 20: 20 second time constant

8 30: 30 second time constant

9 60: 60 second time constant

8

Basic Menu
Output Menu

(*Parameters that are not applicable are not shown)

Register Address
16
17

Parameter Notation
DISP PB

Parameter Description

Range

Secondary display selection
Proportional band value
(See Pg. 17)

0 None: No Display 1 MV1: Display MV1 2 MV2: Display MV2 3 tIMR: Display Dwell Time 4 PRoF: display Profile Status
Low: 0.0 High: 500.0°C (900.0°F)

18

TI

Integral time value
(See Pg. 17)

Low: 0 High: 3600 sec

19

TD

Derivative time value
(See Pg. 17)

Low: 0.0 High: 360.0 sec

20

OUT1

O1TY

21

FACTORY SET, DO

NOT

CHANGE

Output 1 function Output 1 signal type

0 REVR: Reverse (heating) control action
1 dIRt : Direct (cooling) control action
0 RELY: Relay output 1 SSrd: Solid state relay drive
output 2 4-20: 4-20mA linear current 3 0-20: 0-20mA linear current 4 0-5V: 0-5VDC linear voltage 5 1-5V: 1-5VDC linear voltage 6 0-10: 0-10VDC linear voltage

Select BPLS (Bumpless transfer), or

22

O1FT

Output 1 failure transfer mode
(See Pg. 15)

0.0 ~ 100.0 % to continue output 1 control function if the sensor fails, or select OFF (0) or ON (1) for ON-OFF

control

Default Value
0 18.0° F
(10.0° C)
100 25 0
1
0

23

O1HY

Output 1 ON-OFF control hysteresis. PB=0

Low: 0.1°C (0.2°F) High: 50.0°C (90.0°F)

0.2° F
(0.1° C)

24

CYC1

Output 1 cycle time

Low: 0.1 High: 90.0 sec.

1.0

Basic Menu

26

RAMP

Ramp function selection
(See Pg. 13)

0 NoNE: No Ramp Function 1 MINR: Use °/minute as Ramp Rate 2 HRR: Use °/hour as Ramp Rate

0

9

Basic Menu Output Menu User Menu

(*Parameters that are not applicable are not shown)

Register Address

Parameter Notation

Parameter Description

27

RR

Ramp rate
(See Pg. 13)

61

PL1L

Output 1 Low Power limit

62

PL1H

Output 1 High Power limit

94

PASS

Password entry
(See Next Page)

Range
Low: 0.0 High: 900.0°F
Low: 0 High:PL1H or 50%
Low: PL1L High: 100 %
Low: 0 High: 9999

Default Value
0 0 100 0

10

2 Programming
Press and hold for 5 seconds, then release to enter the setup menu. Press and release to cycle through the list of parameters. The upper display indicates the parameter symbol, and the lower display indicates the value of the selected parameter.

2.1 User Security

There are two parameters, PASS (password) and CODE (security code), which will control the lockout program.

CODE Value 0
1000
9999
Others

PASS Value* Any Value
=1000 1000 =9999 9999 =CODE CODE

Access Rights All parameters are changeable All parameters are changeable Only user menu parameters changeable All parameters are changeable Only SP1 to SP7 are changeable All parameters are changeable No parameters can be changed

2-1.User Access Rights
*Record this value

2.2 Signal Input
INPT: Select the desired sensor type or signal type for the signal input. Factory set. DO NOT CHANGE
UNIT: Select the desired process unit Options: °C, °F, PU (Process unit). If the unit is neither °C nor °F, then is set to PU.
DP: Select the desired resolution (decimal points) for the process value.

11

2.3 Control Output There are 4 kinds of control modes can be configured as shown below.
2.3.1 Heat Only ON-OFF Control ­ (Used for Solonoids and Valves) Select REVR for OUT1, Set PB to 0. O1HY is used to adjust the hysteresis for ON-OFF
control. The output 1 hysteresis (O1HY) setting is only available when PB = 0. The heat only ON-OFF control function is shown below.
2-1.Heat Only ON-OFF Control ON-OFF control may cause excessive process oscillations even if the hysteresis is set to the smallest value. If ON-OFF control is used (i.e. PB = 0), TI, TD, CYC1, OFST, CYC2, CPB, DB will no longer be applicable and will be hidden. Auto-Tuning mode and Bumpless transfer are not possible in on/off mode. 2.3.2 Heat only P or PD Control ­ (Used for Electric Heaters) Select REVR for OUT1, set TI = 0, OFST is used to adjust the control offset (manual reset). If PB 0 then O1HY will be hidden. OFST Function: OFST is measured in % with a range of 0 - 100.0 %. When the process is stable, let's say the process value is lower than the set point by 5°F. Let's also say that 20.0 is used for the PB setting. In this example, 5°F is 25% of the proportional band (PB). By increasing the OFST value by 25%, the control output will adjust itself, and the process value will eventually coincide with the set point. When using Proportional (P) control (TI = 0), Auto-Tuning will be unavailable. Refer to the "manual tuning" section for the adjustment of PB and TD. Manual reset (OFST) is usually not practical because the load may change from time to time; meaning the OFST setting would need to be constantly adjusted. PID control can avoid this problem.
12

2.3.3 Heat only PID Control ­ (Default for Electric Heaters) Select REVR for OUT1. PB and TI should not be zero. Perform Auto-Tuning for initial startup. If the control result is not satisfactory, use manual tuning or try Auto-Tuning a second time to improve the control performance.
2.3.4 Cool only Control ON-OFF control, Proportional control, and PID control can be used for cooling control. Set "OUT1" to DIRT (direct action). NOTE: ON-OFF control may result in excessive overshoot and undershoot in the process. Proportional control could result in a deviation of the process value from the set point. It is recommended to use PID control for Heating or Cooling control to produce a stable process value. When selecting parameters, all of the above parameters may not be available. The number of visible parameters depends on the configuration of the controller.
2.4 Ramp The ramping function is performed during power up or any time the set point is changed. Choose "MINR" (ramp in minutes) or "HRR" (ramp in hours) for the "RAMP" setting, and the controller will perform the ramping function. The ramp rate is programmed by adjusting the "RR" setting. The ramping function is disabled whenever the controller enters Failure mode, Manual control mode, Auto-Tuning mode or Calibration mode.
2.4.1 Ramping Example without Dwell Timer Set the "RAMP" setting to "MINR" to ramp in minutes. Set the ramp rate (RR) to 10. The starting temperature is 30°C. The setpoint is initially set to 200°C. After the process warms up, the user changed the setpoint to 100°C after 30 minutes. After power up, the process will behave as shown below.
2-2.Ramp Function Note: When the ramp function is used, the lower display will show the current ramping value. However, it will revert to show the set point value as soon as the up or down key is touched for adjustment. The ramp rate is initiated at power on and/or whenever the Set point is changed. Setting the "RR" setting to zero means no ramping function is used.
13

2.5 User Calibration - Display Offset

Each unit is calibrated in the factory before shipment. The user can still modify the calibration in the field.

The basic calibration of the controller is highly stable and set for life. User calibration allows the user to offset

the permanent factory calibration in order to:

! Calibrate the controller to meet a user reference standard. ! Match the calibration of the controller to that of a particular transducer or sensor input.

! Calibrate the controller to suit the characteristics of a particular installation. ! Remove long term drift in the factory set calibration.

There are two parameters: Offset Low (OFTL) and Offset High (OFTH) for adjustment to correct an error in

the process value. There are two parameters for the sensor input. These two signal values are CALO and CAHI. The input

signal low and high values are to be entered in the CALO and CAHI parameters respectively.

Refer to section 1.6 for key operation and section 1.7 for the operation flowchart. Press and

hold the key until the setup Menu page is obtained. Then, press and release the key to navigate to the calibration low parameter OFTL. Send your low signal to the sensor input of the controller, then press and release the key. If the process value (the upper display) is different from the input signal, the user can use and keys to change the OFTL value (the lower display) until the process value is equal to the value the user needs. Press and hold the key for 5 seconds to complete the low point calibration (the

display should blink once). The same procedure is applied for high scale calibration.

As shown below, the two points OFTL and OFTH construct a straight line. For the purpose of accuracy, it is best to calibrate with the two points as far apart as possible. After the user calibration is

complete, the input type will be stored in the memory. If the input type is changed, a calibration error will

occur and an error code

is displayed.

2-3.Two Point User Calibration
2.6 Digital Filter In certain applications the process value is too unstable to be read. To improve this, a
programmable low pass filter incorporated in the controller can be used. This is a first order filter with a time constant specified by the FILT parameter. A value of 0.5 seconds is used as a factory default. Adjust FILT to change the time constant from 0 to 60 seconds. 0 seconds represents no filter applied to the input signal. The filter is characterized by the following diagram.
14

Note: The Filter is available only for the process value (PV), and is performed for the displayed value only. The controller is designed to use an unfiltered signal for control even when a filter is applied. If a lagged (filtered) signal is used for control; it may produce an unstable process.
2-4.Filter Characteristics
2.7 Failure Transfer The controller will enter failure mode if one of the following conditions occurs: 1. An SBER error occurs due to an input sensor break, an input current below 1mA for 4-20mA, or an input voltage below 0.25V for 1-5 V. 2. An ADER error occurs due to the A-D converter failing.
Output 1 and Output 2 will perform the failure transfer (O1.ft & O2.ft) function as the controller enters failure mode. 2.7.1 Output 1 Failure Transfer
If Output 1 Failure Transfer is activated, it will perform as follows:
1. If output 1 is configured as proportional control (PB0), and BPLS is selected for O1FT, then output 1 will perform a Bumpless transfer. After that, the previous average value of of the output will be used for controlling output 1.
2. If output 1 is configured as proportional control (PB0), and a value of 0 to 100.0 % is set for O1FT, then output 1 will perform failure transfer. After that the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control (PB=0), then output 1 will transfer to an off state if OFF is set for O1FT, or it will transfer to an on state if ON is set for O1FT.
2.8 Auto-Tuning The Auto-Tuning process will be performed at the set point (SP1). The process will oscillate around the
set point during the tuning process. Set a set point to a lower value if overshooting beyond the normal process value will cause damage. It is usually best to perform Auto-Tuning at the Set point the machine is expected to be operated at, with the process running normally (i.e. material in the oven, etc.)
Auto-Tuning is generally applied in the following cases: ! Initial setup for a new process ! The set point is changed substantially from the previous Set point when Auto-Tuning was performed. ! The control result is unsatisfactory
15

2.8.1 Auto-Tuning Operation Steps

1. The system is set up to run under real-world conditions. 2. "PB and "TI" settings should not be set to zero. 3. The LOCK parameter should be set to NONE. 4. Set the set point to a normal operating value, or a lower value if overshooting beyond the
normal process value will cause damage.

5. Press and hold the key until

appears on the upper display. Continue to hold the

" " key for an additional 3 seconds, else the display will revert to a "User Menu"

parameter.

6. Press and hold the key until the TUNE indicator begins to flash.

7. The Auto-Tuning process has begun. NOTE:

During Auto-Tuning, the output will stay on until the Process Value reaches the setpoint. This is likely to

cause the temperature to exceed the setpoint.

Then, the output will remain off until the process value falls below the setpoint.

This will occur at least two times while the controller "learns" how to control your process.

Procedures: Auto-Tuning can be applied either as the process is warming up (Cold Start) or as the
process has been in steady state (Warm Start). After the Auto-Tuning process is completed, the TUNE indicator will stop flashing and the unit will revert to PID control by using its new PID values. The PID values obtained are stored in nonvolatile memory.
2.8.2 Auto-Tuning Error

If Auto-Tuning fails, an ATER cases.

message will appear on the upper display in any of the following

! If PB exceeds 9000 (9000 PU, 900.0°F or 500.0°C) ! If TI exceeds 1000 seconds ! If the set point is changed during the Auto-Tuning process

2.8.3 Solution for an Auto-Tuning Error

1. Try Auto-Tuning once again. 2. Avoid changing the set point value during the Auto-Tuning process. 3. Ensure PB and TI are not set to zero. 4. Use manual tuning.

5. Touch RESET key to reset the

message.

16

2.9 Manual Tuning
In certain applications, using Auto-Tuning may be inadequate for the control requirement, or, the process moves too slowly to Auto-tune accurately. If this is the case, the user can try manual tuning. If the control performance by using Auto-Tuning is still unsatisfactory, the following guidelines can be applied for further adjustment of PID values.

ADJUSTMENT SEQUENCE Proportional Band ( PB ) Integral Time ( TI ) Derivative Time ( TD )

SYMPTOM Slow Response High overshoot or Oscillations Slow Response Instability or Oscillations Slow Response or Oscillations High Overshoot
2-2.PID Parameter Adjustment Guide

SOLUTION Decrease PB Increase PB Decrease TI Increase TI Decrease TD Increase TD

2-5. Effects of PID Adjustment 17

2.10 Manual Control

To enable manual control, ensure the LOCK parameter is set to NONE.

Press and hold until

(Hand Control) appears on the display. Press and hold until

the "MANU" indicator begins to flash. The lower display will show

.

Indicates the output control variable for output 1, and

indicates the control variable for

output 2. The user can use the up-down keys to adjust the percentage values for the heating or cooling

output. This % value is based on the CYC1 and CYC2 settings, where the associated output will stay on for

the % of time the CYC1 & CYC2 values are set for.

Example: If CYC1 is set to 20seconds, and the controller is set to "H50.0", the output will be on for 10seconds, then turn off for 10 seconds.

The controller performs open loop control and ignores the input sensor as long as it stays in manual control mode

2.10.1 Exit Manual Control Pressing the key will revert the controller to its normal display mode.

2.11 Setting Controller to Factory Default

The controller's parameters can be loaded with default values listed in the parameter description table . In

certain situation it is desirable to retain these values after the parameters values has been changed. The

below procedure to be followed to reload the default values. 1. Ensure the LOCK parameter is set to NONE.

2. Press and hold until

(Hand Control) appears on the display.

3. Press and release the key to cycle through the manual mode menu to reach "FILE".

4. Press and hold for 5 seconds or until the upper display FILE flash for a moment.

18

6.4 Error Code

The description of the Error code is explained below

Error Code
4
10 11 14 15 16

Display Symbol
ER04
ER10 ER11 ER14 ER15 EIER

Description & Reason
Illegal setup values used: COOL is used for OUT2 when DIRT (cooling
action) is used for OUT1, or when PID mode is not used for
OUT1 (PB =0 and/or TI=0)
Communication error: bad function code
Communication error: register address out of range
Communication error: attempt to write a read-only data
Communication error: write a value which is
out of range to a register Event Input Error: Two or more event inputs are set to the same
function

Corrective Action
Check and correct setup values of OUT2, PB1, PB2, TI1, TI2 and OUT1. IF OUT2 is needed for cooling control, the controller should use PID mode (PB 0 and TI 0) and OUT1 should use reverse mode (heating action), otherwise, OUT2 cannot be used for
cooling control
Correct the communication software to meet the protocol requirements.
Do not issue an over-range address of the register to the secondary
Do not write read-only data or protected data to the secondary.
Do not write an over-range data to the secondary register
Do not set the same function in two or more Event Input Function parameters (E1FN through E6FN)

1. The PID values obtained after Auto-Tuning

process are out of range. Retry Auto-Tuning.

2. Do not change the setpoint value during Auto-

26

ATER

Auto-Tuning Error: Failed to perform Auto-Tuning function

Tuning process. 3. Use manual tuning instead of Auto-Tuning
process.

4. Do not set a zero value for TI.

5. Do not set a zero value for PB.

6. Touch RESET key

29

EEPR

EEPROM can't be written correctly

Return to factory for repair.

30

CJER

Cold junction compensation for Thermocouple malfunction

Return to factory for repair.

Input sensor break, or input

39

SBER

current below 1 mA if 4-20 mA is used, or input voltage below

Replace the input sensor.

0.25V if 1 - 5V is used

40

ADER

A to D converter or related component(s) malfunction

Return to factory for repair.

6.5 Mode

6-5.Error Code

The Value of the Mode Register is as below.
Value H'000X H'010X H'020X H'030X H'040X H'0X00 H'0x01

Mode Normal mode Calibration mode Auto-Tuning mode Manual control mode Failure mode Alarm status is off Alarm status is on

6-6.Operation Mode

19

RETURNS
NoproductreturnscanbeacceptedwithoutacompletedReturn MaterialAuthorization(RMA)form.
TECHNICAL SUPPORT
Technical questions and troubleshooting help is available from Tempco.Whencallingorwritingpleasegiveasmuchbackground informationontheapplicationorprocessaspossible. E-mail:techsupport@tempco.com Phone:630-350-2252
800-323-6859
Note: Informationinthismanualwasdeemedcorrectatthetimeofprinting. ThepolicyofTempcoisoneofcontinuousdevelopmentandproduct improvement,and we reserve the right to modify specifications and designs without priornotice.Notresponsiblefortypographicalerrors.
20

Custom Manufacturer Since 1972
ELECTRIC HEATING ELEMENTS · TEMPERATURE CONTROLS · SENSORS · PROCESS HEATING SYSTEMS

HEAT THINGS UP!
With Thousands of Design Variations We Make Everything You Need.

Band Heaters Cast-In Heaters Radiant Heaters Flexible Heaters Process Heaters Temperature Control

Cartridge Heaters Coil & Cable Heaters