AKO Temperature Controller Up To Three Relays and Two Probes

1- Versions and References

MODELRELAYSPOWER SUPPLY, 50/60 Hz
AKO-14212Cool: 16 A, 250 V, cos φ=1, SPST
R2: 8 A, 250 V, cos φ=1, SPDT
12 V ±20%
AKO-14220Cool: 16 A, 250 V, cos φ=1, SPST
R2: 8 A, 250 V, cos φ=1, SPDT
120 V ~+8%-12%
AKO-14223Cool: 16 A, 250 V, cos φ=1, SPST
R2: 8 A, 250 V, cos φ=1, SPDT
230 V ~±10%
AKO-14312Cool: 16 A, 250 V, cos φ=1, SPST
Def: 8 A, 250 V, cos φ=1, SPDT
Fan: 6 A, 250 V, cos φ=1, SPST
12 V ±20%
AKO-14320Cool: 16 A, 250 V, cos φ=1, SPST
Def: 8 A, 250 V, cos φ=1, SPDT
Fan: 6 A, 250 V, cos φ=1, SPST
120 V ~+8%-12%
AKO-14323Cool: 16 A, 250 V, cos φ=1, SPST
Def: 8 A, 250 V, cos φ=1, SPDT
Fan: 6 A, 250 V, cos φ=1, SPST
230 V ~±10%

2- Technical Data

3- Installation

The controller should be installed in a place protected from vibrations, water and corrosive gases, and where ambient temperature does not surpass the value specified in the technical data.

In order for the controllers to have IP65 protection, the gasket should be properly installed between the apparatus and the perimeter of the panel cut-out where it is to be fitted.

In order to give a correct reading, the probe should be installed in a place without heat influences other than the temperature that is to be measured or controlled.

3.1 Fastening units for panel mounting:

To fix the unit, place the fasteners 1 over the sliders 2 as shown in the figure. Move the fasteners in the direction of the arrow. By pressing tab 3 fasteners may be moved in the opposite direction of the arrow.

PANEL CUT-OUT

max. 18 mm

3.2 Connection:

The probe and its lead should NEVER be installed in ducting along with power, control or power supply wiring.

The power supply circuit should be connected with a minimum 2 A, 230 V, switch located close to the unit. Power supply cables should be H05VV-F 2x0,5 mm² or H05V-K 2x0,5 mm². Section of connecting wires for relays contacts should be 2,5 mm².

POWER SUPPLY S1-TEM

POWER SUPPLY S2-DEF S1-TEM

C R2 COOL FAN C DEF COOL

AKO-14212

AKO-14220

AKO-14223

AKO-14312

AKO-14320

AKO-14323

4- Front Panel Functions

5- Adjustment and Configuration

It should only be programmed or modified by personnel who are fully conversant with the equipment operation and possibilities.

5.1 Set Point temperature

The factory SET POINT default value is 0.0°C.

Press UP KEY for at least 5 seconds to DISPLAY SET POINT. It displays the CURRENT SET POINT value and LED °C or °F starts flashing.

Press UP or DOWN keys to CHANGE SET POINT into the required value.

Pressing UP and DOWN keys simultaneously to ACCEPT THE NEW SET POINT. The display returns to the CURRENT TEMPERATURE display status and LED °C or °F stops flashing.

When PA is displayed, PASSWORD programmed in L5 parameter of tid menu should be entered to access the CURRENT SET POINT.

Press UP and DOWN keys simultaneously. 0 will be displayed to ENTER PASSWORD.

Press UP or DOWN keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.

Press UP and DOWN keys simultaneously to ACCEPT PASSWORD. The CURRENT SET POINT value will be displayed and it can be already modified.

5.2 Parameters Configuration

Level 1 Menus

Press UP and DOWN keys simultaneously for at least 10 seconds. LED °C or °F will be flashing, we are in the programming LEVEL 1 MENUS and the first menu "rE" is displayed.

Press UP key to access the next menu and DOWN key to return to previous one.

Pressing UP keys in the last menu EP, the controller returns to the CURRENT TEMPERATURE display status and LED °C or °F will stop flashing.

When PA is displayed, PASSWORD programmed in L5 of "tid" menu should be entered to access programming LEVEL 1 MENUS.

Press UP and DOWN keys. 0 will be displayed to ENTER PASSWORD.

Press UP or DOWN keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.

Press UP and DOWN keys simultaneously to ACCEPT PASSWORD. The first menu "rE" will be displayed.

Level 2 Parameters

In the desired menu of LEVEL 1 MENUS, press UP and DOWN keys simultaneously. LEVEL 2 PARAMETERS programming is accessed. The first parameter of the selected menu is displayed on the screen.

Press UP key to access the next parameter and DOWN key to return to the previous one.

Pressing UP and DOWN keys simultaneously in the last parameter EP, the controller returns to the LEVEL 1 MENUS.

Level 3 Values

To DISPLAY the CURRENT VALUE of any parameter, select the required one and press UP and DOWN keys simultaneously. Once it is displayed, you can CHANGE VALUE, pressing UP or DOWN key.

Press UP and DOWN keys simultaneously to ACCEPT THE NEW. The programming returns to LEVEL 2 PARAMETERS.

REMARK: If no key is pressed for 25 seconds in either of the previous steps, the controller will automatically return to the CURRENT TEMPERATURE display status without modifying any of the parameters values.

LevelMenuDescriptionValuesMin.Def.Max.
ALLevel 2 ALARM control (Visual)
A0Configuration of temperature alarms (0 = Relative to SP) (1 = Absolute)001
A1Maximum alarm in sensor 1 (°C/°F)-50.0A299.9
A2Minimum alarm in sensor 1 (°C/°F) (If programmed in A1, A2)-50.0A199.9
A3Temperature alarm delay in the start-up (min.)00120
A4Temperature alarm delay from the end of a defrost (min.)0099
A5Temperature alarm delay from the moment at which they should operate due to temperature (min.)03099
A8Signals if defrost ends due to maximum time: (0=Led DT OFF) (1=Led DT ON)001
A10Differential Alarms Temperature A1 and A2007
EPExit to Level 1
CnFLevel 2 GENERAL STATUS
P1Delay of all functions on power supply switch on(min.)0099
P2Allocation of password to Set Point: (0=Without allocation) (1=With allocation of L5 password)001
P3Initial parameters: (1=YES, configure to "Def" and exit programming)001
P4Connected sensors: (1=Sensor 1) (2=Sensor 1 + Sensor 2)112
P5Address for units with communication00126
P6Relay 2 (F2) function in 2 relay versions: (0=Defrost) (1=Fans control)001
P7Temperature display mode: (0=Integers in °C) (1=One decimal in °C) (2=Integers in °F) (3=One decimal in °F)013
P8Sensor to be displayed: (1=Sensor 1) (2=Sensor 2)112
EPExit to Level 1
tidLevel 2 ACCESS AND INFORMATION control
L5Access password to parameters and information0099
L6Parameters transfer: (0=Disabled) (1=Send) (2=Receive)002
EPExit to Level 1

6- Description of Parameters and Messages

Values in the Def. column are factory-set.

Level 1 Menus and Description

rE Level 2 REFRIGERATION control (Compressor)

LevelDescriptionValuesMin.Def.Max.
C0Sensor 1 calibration (Offset)(°C/°F)-20.00.020.0
C1Sensor 1 differential (Hysteresis)(°C/°F)0.12.020.0
C2Set Point upper limit (It cannot be set above this value)(°C/°F)C399.999.9
C3Set Point lower limit (It cannot be set below this value)(°C/°F)-50.0-50.0C2
C4Compressor protection delay type: 0=OFF/ON ((From the last switch-off) 1=ON (At switch-on)001
C5Protection delay time (Value for the option selected in parameter C4)(min.)0099
C7"COOL" (Compressor) relay time in ON in case of faulty sensor 1 (min.) (If C7=0 and C8≠0, the relay will always be OFF disconnected)(min.)01099
C8"COOL" (Compressor) relay time in OFF in case of faulty sensor 1 (min.) (If C8=0 and C7≠0, the relay will always be ON connected)(min.)0599
EPExit to Level 1

dEF Level 2 DEFROST control

LevelDescriptionValuesMin.Def.Max.
d0Defrost frequency (Elapsed time between 2 starts)(h.)0699
d1Defrost maximum duration(min.)03099
d2Type of message during defrost: (0=Current temperature display) (1=Defrost start temperature display) (2=Display dEF message)022
d3Message maximum duration (Time added at the end of defrost)(min.)0599
d4Defrost final temperature by sensor 2 (If programmed in P4)(°C/°F)-50.08.099.9
d5Defrost start-up on equipment switch-on: (0=NO, first defrost according to d0) (1=YES, first defrost according to d6)001
d6Defrost start-up delay on equipment switch-on(min.)0099
d7Defrost type: (0=Electric heat) (1=Hot gas by-pass)001
d8To defrost by air in 2 relays, parameters P6 and F3 should be programmed
d9Time calculation between defrost periods: (0=Total real time) (1=Compressor operation sum)001
EPExit to Level 1

FAn Level 2 FANS control (Evaporator)

LevelDescriptionValuesMin.Def.Max.
F0Fans stop temperature by sensor 2 (If programmed in P4)(°C/°F)-50.04.099.9
F1Sensor 2 differential(°C/°F)0.12.020.0
F2Stop fans, when compressor stops?: In 2 relays versions, R2 operates if P6=1001
F3Fans status during defrost: (0=Off) (1=On)001
F4Start-up delay after defrost (Operates if it is higher than d9)(min.)0399
EPExit to Level 1

7- Parameters Transfer

AKO-14918 portable server, with no power supply, in which parameters programmed in a powered controller can be copied by transfer. Parameters can be transferred again from the server to other identical powered controllers.

To transfer parameters, other servers are available for controllers that should be programmed identically in high quantity without power supply.

Power supply

Programming

Transfer

AKO-14918

8- Maintenance

Clean the controller surface with a soft cloth, soap and water. Do not use abrasive detergents, petrol, alcohol or solvents.

9- Warnings

The use of the unit without observing the manufacturer's instructions may alter its safety qualification.

To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should be used.

Between -40 °C and +20 °C, when the probe is extended up to 1.000 m with minimum 0,5 mm² cable, deviation will be less than 0.25 °C (Probe extension cable ref. AKO-15586).

(*) The intensity specified for each relay is its maximum individual value; if more than one is connected, the intensity of the addition (COMPRESSOR + DEFROST + FAN) must not exceed the total maximum intensity specified in the rating plate.

PDF preview unavailable. Download the PDF instead.

351422302 1 QuarkXPress(R) 7.3 QuarkXPress(R) 7.3

Related Documents

Preview AKO D141xx/D101xx & D140xx Series Temperature Controllers: Programming and Parameter Guide
Comprehensive guide to programming and understanding parameters for AKO D141xx/D101xx and D140xx series temperature controllers, detailing menu navigation, settings, and error messages.
Preview AKO D142H232 Digital Thermostat Installation and Operation Manual
Installation and operation instructions for the AKO D142H232 digital thermostat, covering wiring, setup, parameters, and technical specifications.
Preview AKO Temperature Controller User Manual (AKO-16523, AKO-16520 Series)
Comprehensive user manual for AKO temperature controllers, including installation, configuration, operation, and troubleshooting for models like AKO-16523, AKO-16520, AKO-16523P, AKO-16520P, AKO-16523D, AKO-16523-V. Covers features, parameters, alarms, and connectivity.
Preview AKO Gas Leak and Trapped Person Alarm System User Manual
Comprehensive user manual for AKO gas leak detection and trapped person alarm systems, covering installation, operation, configuration, technical specifications, and connectivity for models like AKO-555241, AKO-558241, AKO-555242, and AKO-558242.
Preview AKO Trapped Person Alarm Push-Button Quick Guide
A quick guide for the AKO trapped person alarm push-button, covering installation, wiring, configuration, operation, and technical specifications.
Preview AKO Thermometers and Temperature Controllers User Manual
User manual for AKO's range of thermometers and temperature controllers, detailing features, operation, wiring, and technical specifications.
Preview AKO Serie 16523: Controladores de Temperatura para Cámaras Frigoríficas - Manual Técnico
Manual técnico completo para los controladores de temperatura AKO serie 16523 (AKO-16523, AKO-16523P, AKO-16523L, AKO-16520, AKO-16520P, AKO-16523D, AKO-16523-V) para cámaras frigoríficas. Incluye configuración, operación, advertencias, especificaciones y mantenimiento.
Preview AKO-16523 Temperature Controller for Cold Rooms User Manual
This user manual provides comprehensive instructions for the AKO-16523 series of temperature controllers for cold rooms. It covers installation, wiring, configuration, operation, maintenance, and troubleshooting, ensuring optimal performance and longevity of the device.