iO-GRID M Modbus RTU Connection Operating Manual(FATEK-PLC) EN
2302EN V2.0.0
and FATEK PLC Modbus RTU Connection
Operating Manual

Table of Contents

1.

Remote I/O Module System Configuration List ....................................................................... 3

1.1 Product Description ................................................................................................. 3

2.

FATEK PLC Connection Setup ................................................................................................. 4

2.1 FATEK PLC Hardware Connection........................................................................... 4

2.2 FATEK PLC Connection Setup ................................................................................ 6

2

1. Remote I/O Module System Configuration List

Part No.

Specification

Description

GFMS-RM01S Master Modbus RTU, 1 Port

Main Controller

GFDI-RM01N Digital Input 16 Channel

Digital Input

GFDO-RM01N Digital Output 16 Channel / 0.5A

Digital Output

GFPS-0202 Power 24V / 48W

Power Supply

GFPS-0303 Power 5V / 20W

Power Supply

0170-0101

8 pin RJ45 female connector/RS-485 Interface

Interface Module

1.1 Product Description
I. The interface module is used externally to convert FATEK PLC RS485's communication port (Modbus RTU) to a RJ45 connector
II. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
III. The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.

3

2. FATEK PLC Connection Setup
This chapter explains how to use the WinProladder program to connect FATEK PLC with For detailed information, please refer to the Winproladder Manual
2.1 FATEK PLC Hardware Connection
I. The connection port is on the top of the machine. Take FBs-10MAR2-AC for example. It uses Port2(RS485 pin)
Connections for other communication modules
All FATEK's RS485 communication modules have the following pins on the terminal blocks (from top to bottom):
First pin: "+" Second pin: "-" Third pin: "Ground"
4

II. Connect Port2 (RS485 A/B) on the top of the machine to the interface module (1/2) to convert it into a RJ45 connector, which will be connected to the main controller
5

2.2 FATEK PLC Connection Setup
I. Launch WinProladder and set up the communication ports

This demonstration utilizes communication module CB55 RS485 with Port2 in its address

The communication parameter setting must be consistent with

to enable communication

6

II. Editing the program- Click on "Set up program block diagram", then from the dropdown menu, select "Communication Commands" and then select "M-BUS"
III. Function Commands
 Pt: The address of the port for selecting a Modbus communication module  SR: Starting register for the communication program  WR: The starting register running the commands will take up totally 8 registers In this example, we select "2", "R5000" and "R3000"
7

IV. Internal Related Relays

Internal Related Relays

Communication Port

Port Ready Indicating Relay

Port1

M1960

Port2

M1962

Port3

M1936

Port4

M1938

V. Establish a Communication Form

The form's starting address must be the same with that of the register from the SR command

8

VI. Setting the Communication Commands



station number

 From the drop-down menu, select "Read" or "Write" to PLC

 With double word data, select "2" for data length

 Read

's value to PLC R1's address



's register address

Note:



's first GFDI-RM01N has the register address at 1000(HEX) converted to

4096(DEC)+1, and the starting address at 404097



's first GFDO-RM01N has the register address at 2000(HEX) converted to

8192(DEC)+1, and the starting address at 408193

9

