User Manual: 1.0KW/1.5KW Inverter / MPPT SCC / AC Charger
Version: 1.0
1 About This Manual
1.1 Purpose
This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
2 Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION -- To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION - Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3 Introduction
This is a multi-function inverter/charger, combining functions of inverter, solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
3.1 Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible to mains voltage or generator power
- Auto restart while AC is recovering
- Overload/ Over temperature/ short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
3.2 Basic System Architecture
The following illustration shows the basic application for this inverter/charger. It also includes the following devices to have a complete running system:
- Generator or Utility.
- PV modules
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.
Figure 1 Hybrid Power System Diagram: The diagram illustrates a hybrid power system. On the left, inputs are shown: Solar Power, Generator, and Utility power. These connect to the central Inverter unit. The Inverter is also connected to an External Battery. On the right, the Inverter outputs power to Home Appliances.
Product Overview Diagram: The diagram shows the front and side views of the inverter unit. The front panel features:
- 1. LCD display
- 2. Status indicator LEDs (AC/INV, CHG, FAULT)
- 3. Charging indicator
- 4. Fault indicator
- 5. Function buttons (ESC, UP, DOWN, ENTER)
- 6. Power on/off switch
The rear panel shows:
- 7. AC input terminals
- 8. AC output terminals
- 9. PV input terminals
- 10. Battery input terminals
- 11. Circuit breaker
- 12. Output receptacles
4 Installation
4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
4.2 Preparation
Before connecting all wirings, please take off the bottom cover by removing two screws.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the sides and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
Mounting Clearance Diagram: Arrows indicate required clearances around the unit: 20cm to the left, 20cm to the right, 50cm above, and 50cm below.
NOTICE: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It is recommended to use M4 or M5 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be requested in some applications, however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below for required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.
Recommended battery cable size:
Model | Wire Size | Cable (mm²) | Torque value (max) |
---|---|---|---|
1.0 KW 12 V | 1 x 6 AWG | 14 | 5 Nm |
1.5 KW 24 V | 1 x 6 AWG | 14 | 5 Nm |
Battery Connection Steps:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- It is suggested to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the chart.
- Insert the battery wires flatly into the battery connectors of the inverter and make sure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected, and conductors are tightly screwed into the battery terminals.
Recommended tool: #2 Pozi Screwdriver
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).
Battery Wiring Diagram: Two diagrams illustrate battery connections for a 1.0KW 12V inverter and a 1.5KW 24V inverter, showing series connections of 12V batteries.
Terminal Connection Diagram: Illustrates connecting wires to the inverter's battery terminals.
4.5 AC Input/Output Connection
CAUTION!! Before connecting to the AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of the AC breaker is 20A for 1.0 KW and 20A for 1.5 KW.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires:
Model | Gauge | Torque Value |
---|---|---|
1.0 KW 12 V | 14 AWG | 2 Nm |
1.5 KW 24 V | 12 AWG | 2 Nm |
AC Input/Output Connection Steps:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10 mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (⊚) first.
WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
AC Wiring Diagram: Shows connection of Ground (yellow-green), Line (brown or black), and Neutral (blue) wires to the AC input terminals. Also shows the connection to an external circuit breaker.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws.
Wire Color Coding:
- PE: Ground (yellow-green)
- L: LINE (brown or black)
- N: Neutral (blue)
AC Output Connection Diagram: Shows connection of wires to the AC output terminals.
- Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioners are required to have at least a 2-3 minute delay before restarting to allow refrigerant gas inside the circuits to balance. If a power shortage occurs and recovers in a short time, it may cause damage to your connected appliances. To prevent this kind of damage, check with the appliance manufacturer if it is equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but this may still cause internal damage to the air conditioner.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install a separate DC circuit breaker between the inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model | Wire Size | Torque value (max) |
---|---|---|
1.0KW 12V 1.5KW 24V |
1 x 12 AWG | 2 Nm |
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL | 1.0 KW | 1.5 KW |
---|---|---|
Max. PV Array Open Circuit Voltage | 150 Vdc | |
PV Array MPPT Voltage Range | 20 ~ 150 Vdc | 30 ~ 150 Vdc |
PV Module Configuration Example (using 250Wp PV module):
Solar Panel Spec. (reference) - 250Wp - Vmp: 30.1Vdc - Imp: 8.3A - Voc: 37.7Vdc - Isc: 8.4A - Cells: 60 |
SOLAR INPUT (Min in serial: 4 pcs, max. in serial: 12 pcs) |
Q'ty of panels | Total input power | |
---|---|---|---|---|
2 pcs in serial | 2 pcs | 500 W | ||
3 pcs in serial | 3 pcs | 750 W | ||
4 pcs in serial | 4 pcs | 1000 W |
PV Module Wire Connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- It is suggested to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection wire to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection wire to the negative pole (-) of the PV input connector.
Recommended tool: 4 mm blade screwdriver
PV Input Terminal Connection Diagram: Shows connecting PV wires to the inverter's PV input terminals, emphasizing correct polarity.
4.7 Final Assembly
After connecting all wirings, please put the bottom cover back by screwing four screws.
5 Operation
5.1 Power ON/OFF
Side view of unit: Shows the location of the power switch on the bottom of the unit.
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
5.2 Operation and Display Panel
The operation and display panel, shown in the chart below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.
Display Panel Diagram: Shows the LCD screen with various icons and readouts, including input/output power, battery status, and system mode (BYPASS, ECO, CHARGING). Also shows the function buttons and indicator LEDs.
LED Indicator
LED Indicator | Color | Status | Messages |
---|---|---|---|
AC/ INV | Green | Solid On | Output is powered by utility in Line mode. |
Flashing | Output is powered by battery or PV in battery mode. | ||
CHG | Green | Solid On | Battery is fully charged. |
Flashing | Battery is charging. | ||
$ riangle$ FAULT | Red | Solid On | Fault occurs in the inverter. |
Flashing | Warning condition occurs in the inverter. |
Function Keys
Function Key | Description |
---|---|
ESC | To exit setting mode |
UP | To go to previous selection |
DOWN | To go to next selection |
ENTER | To confirm the selection in setting mode or enter setting mode |
5.3 LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the "UP" or "DOWN" button to select setting programs. Then, press the "ENTER" button to confirm the selection or the ESC button to exit.
Setting Programs:
Program | Description | Selectable option | ||
---|---|---|---|---|
00 | Exit setting mode | Escape (default) 0000 E | One-button restore setting options | |
0000 H | ||||
01 | Output source priority: To configure load power source priority | Utility first (default) 01 USB | Utility will provide power to the loads as the first priority. Solar and battery energy will provide power to the loads only when utility power is not available. | |
Solar first 015 U | Solar energy provides power to the loads as the first priority. If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time. Battery provides power to the loads only when any one condition happens: - Solar energy and utility is not available. - Solar energy is not sufficient and utility is not available. | |||
SBU priority 015 BU | Solar energy provides power to the loads as the first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12. | |||
MKS priority 01 n+5 | When solar is available, solar energy and battery energy will supply power to the loads; the utility only supplies energy to the load as a backup power. When solar is not available, utility energy will supply power to the loads, and the battery only supplies energy to the load as a backup power. | |||
02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) | 10A 02 10 |
20A 02 20 |
|
30A 02 30 |
40A (default) 02 40 |
|||
50A 02 50 |
60A 02 60 |
|||
70A 02 70 |
80A 02 80 |
|||
03 | AC input voltage range | Appliances (default) 03 APL |
If selected, acceptable AC input voltage range will be within 90-280VAC. | |
UPS 03 UPS |
If selected, acceptable AC input voltage range will be within 170-280VAC. | |||
05 | Battery type | AGM (default) 05 AǦn |
Flooded 05 FLd |
|
User-Defined 05 USE |
If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in programs 26, 27, and 29. | |||
06 | Auto restart when overload occurs | Restart disable (default) 06 Lfd |
Restart enable 06 LfE |
|
07 | Auto restart when over temperature occurs | Restart disable (default) 07 Lfd |
Restart enable 07 LfE |
|
09 | Output frequency | 50 Hz (default) 09 50 Hz |
60 Hz 09 60 Hz |
|
10 | Output voltage | 220 V 10 220 |
230V (default) 10 230 |
|
240 V 10 240 |
||||
11 | Setting voltage point back to utility source when selecting "MKS priority" in program 01 | 2A 11 2A |
10A 11 10A |
|
20A (default) 11 20A |
30A 11 30A |
|||
40A 11 40A |
||||
12 | Setting voltage point back to battery mode when selecting "MKS priority" in program 01 | 1.5KW 24V default setting: 23V 12 230v |
1.0KW 12V default setting: 11.5V 12 115v |
Setting range is from 21.0V to 26.2V for 1.5KW model and 10.5V to 13.1V for 1.0KW model. Increment of each click is 0.1V. |
13 | Battery fully charged voltage setting | 1.5KW 24V default setting: 27V 13 270v (default) |
1.0KW 12V default setting: 13.5V 13 135v (default) |
Setting range is from 24.0V to 29.2V for 1.5KW model and 12V to 14.6V for 1.0KW model. Increment of each click is 0.1V. |
14 | Maximum utility charging current | 10A 14 10 |
20A (default) 14 20 |
|
30A 14 30 |
40A 14 40 |
|||
15 | Charger source priority: To configure charger source priority | If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below: | ||
Solar first 15 50 | Solar energy will charge the battery as the first priority. Utility will charge the battery only when solar energy is not available. | |||
Solar and Utility (default) 15 50U | Solar energy and utility will charge the battery at the same time. | |||
Only Solar 15 050 | Solar energy will be the only charger source, no matter if utility is available or not. | |||
If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge the battery. Solar energy will charge the battery if it's available and sufficient. | ||||
18 | Alarm control | Alarm on (default) 18 60 | Alarm off 18 60F | |
19 | Auto return to default display screen | Return to default display screen (default) 19 ESP | If selected, no matter how users switch the display screen, it will automatically return to the default display screen (Input voltage / output voltage) after no button is pressed for 1 minute. | |
Stay at latest screen 19 FP | If selected, the display screen will stay at the latest screen the user finally switched to. | |||
20 | Backlight control | Backlight on (default) 20 10 | Backlight off 20 10F | |
22 | Beeps while primary source is interrupted | Alarm on (default) 22 AO | Alarm off 22 AOF | |
23 | Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode. | Bypass disable (default) 23 64d | Bypass enable 23 64E | |
25 | Record Fault code | Record enable (default) 25 FEN | Record disable 25 FdS | |
26 | Bulk charging voltage (C.V voltage) | 1.0KW 12V default setting: 14.1V 1.5KW 24V default setting: 28.2V If self-defined is selected in program 5, this program can be set up. Setting range is from 12V to 15V for 1.0 KW 12V model and 24V to 30V for 1.5KW 24V model. Increment of each click is 0.1V. |
||
27 | Floating charging voltage | 1.0KW 12V default setting: 13.5V 1.5KW 24V default setting: 27V If self-defined is selected in program 5, this program can be set up. Setting range is from 12V to 15V for 1.0 KW 12V model and 24V to 30V for 1.5KW 24V model. Increment of each click is 0.1V. |
||
29 | Low DC cut-off voltage | 1.0KW 12V default setting: 10.0V 1.5KW 24V default setting: 20.0V If self-defined is selected in program 5, this program can be set up. Setting range is from 10.0V to 15V for 1.0 KW 12V model and 24V to 30V for 1.5KW 24V model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to the setting value no matter what percentage of load is connected. |
||
30 | Battery equalization | Battery equalization 30 EEN | Battery equalization disable (default) 30 EdS | If "Flooded" or "User-Defined" is selected in program 05, this program can be set up. |
31 | Battery equalization voltage | 1.0KW 12V default setting: 14.6V EU 31 145 |
1.5KW 24V default setting: 29.2V EU 31 292 |
Setting range is from 12V to 15V for 1.0 KW 12V model and 24V to 30V for 1.5 KW 24V model. Increment of each click is 0.1V. |
33 | Battery equalized time | 60 min (default) | Setting range is from 5 min to 900 min. Increment of each click is 5 min. | |
34 | Battery equalized timeout | 120 min (default) | Setting range is from 5 min to 900 min. Increment of each click is 5 min. | |
35 | Equalization interval | 30 days (default) | Setting range is from 0 to 90 days. Increment of each click is 1 day. | |
36 | Equalization activated immediately | Enable 35 REП |
Disable (default) 35 AdS |
If equalization function is enabled in program 30, this program can be set up. If "Enable" is selected in this program, it activates battery equalization immediately and the LCD main page will show "E9". If "Disable" is selected, it cancels the equalization function until the next activated equalization time arrives based on program 35 setting. At this time, "E9" will not be shown in the LCD main page. |
5.4 Fault Reference Code
Fault Code | Fault Event | Icon on |
---|---|---|
01 | Fan is locked when inverter is off. | 01 |
02 | Over temperature | 02 |
03 | Battery voltage is too high | 03 |
04 | Battery voltage is too low | 04 |
05 | Output short-circuited or over temperature is detected by internal converter components. | 05 |
06 | Output voltage is too high. | 06 |
07 | Overload time out | 07 |
08 | Bus voltage is too high | 08 |
09 | Bus soft start failed | 09 |
51 | Over current or surge | 51 |
52 | Bus voltage is too low | 52 |
53 | Inverter soft start failed | 53 |
55 | Over DC voltage in AC output | 55 |
57 | Current sensor failed | 57 |
58 | Output voltage is too low | 58 |
59 | PV voltage is over limitation | 59 |
5.5 Warning Indicator
Warning Code | Warning Event | Audible Alarm | Icon flashing |
---|---|---|---|
01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
03 | Battery is over-charged | Beep once every second | 03 |
04 | Low battery | Beep once every second | 04 |
07 | Overload | Beep once every 0.5 second | 07 |
10 | Output power derating | Beep twice every 3 seconds | 10 |
15 | PV energy is low. | Beep twice every 3 seconds | 15 |
E9 | Battery equalization | None | E9 |
6 Clearance and Maintenance for Anti-Dust Kit (Optional)
6.1 Overview
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate the internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
6.2 Clearance and Maintenance (Option)
- Step 1: Please remove screws as shown in the diagram.
- Step 2: Then, the dustproof case can be removed, and the air filter foam can be taken out as shown in the chart below.
- Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
Dust Kit Removal Diagram: Shows the side of the inverter and arrows indicating where to remove screws to detach the dustproof case and access the air filter foam.
7 Specifications
Table 1 Line Mode Specifications
INVERTER MODEL | 1.0KW-12V | 1.5KW-24V | |
---|---|---|---|
Input Voltage Waveform | Sinusoidal (utility or generator) | ||
Nominal Input Voltage | 230Vac | ||
Low Voltage Range | 170Vac ± 10V (UPS); 90Vac ± 10V (Appliances) | ||
Low Voltage Return Voltage | 180Vac ± 10V (UPS); 100Vac ± 10V (Appliances) | ||
High Voltage Range | 280Vac ± 10V | ||
High Voltage Return Voltage | 270Vac ± 10V | ||
Max AC Input Voltage | 300Vac | ||
Nominal Input Frequency | 50 Hz / 60 Hz (Auto detection) | ||
Low Frequency Range | 40 ± 1 Hz | ||
Low Frequency Return Frequency | 42 ± 1 Hz | ||
High Frequency Range | 65 ± 1 Hz | ||
High Frequency Return Frequency | 63 ± 1 Hz | ||
Output Short Circuit Protection | Circuit Breaker | ||
Efficiency (Line Mode) | >95% (Rated R load, battery fully charged) | ||
Transfer Time | 10 ms | ||
Output power derating: When AC input voltage drops to 170V, the output power will be derated. |
Output Power Rated Power 50% Power |
Input Voltage |
Table 2 Inverter Mode Specifications
INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
---|---|---|
Rated Output Power | 1000VA/1000W | 1500VA/1500W |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac ± 5% | |
Output Frequency | 50 Hz | |
Peak Efficiency | 94% | |
Overload Protection | 3s@ >150% load; 5s@ 100%-150% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 12 Vdc | 24 Vdc |
Cold Start Voltage | 11.5 Vdc | 23.0 Vdc |
Low DC Warning Voltage @ load < 50% @ load >50% |
11.25 Vdc 11.0 Vdc |
22.5 Vdc 22 Vdc |
Low DC Warning Return Voltage @ load < 50% @ load >50% |
11.75 Vdc 11.5 Vdc |
23.5 Vdc 23 Vdc |
Low DC Cut-off Voltage @ load < 50% @ load >50% |
10.75 Vdc 10.5 Vdc |
21.5 Vdc 21 Vdc |
High DC Recovery Voltage | 15.5 Vdc | 31 Vdc |
High DC Cut-off Voltage | 16.0 Vdc | 32 Vdc |
No Load Power Consumption | <17 W | <27 W |
Table 3 Charge Mode Specifications
Utility Charging Mode | 1.0 KW-12V | 1.5KW-24V | |
---|---|---|---|
Charging Algorithm | 3-Step | ||
AC Charging Current (Max) | 40Amp (WL/P=230Vac) | 40Amp (WL/P=230Vac) | |
Bulk Charging Voltage | Flooded Battery | 14.6 | 29.2 |
AGM / Gel Battery | 14.1 | 28.2 | |
Floating Charging Voltage | 13.5 Vdc | 27 Vdc | |
Charging Curve | |||
MPPT Solar Charging Mode | 1.0KW-12V | 1.5KW-24V | |
Max. PV Array Power | 600 W | 1200 W | |
PV Array MPPT Voltage Range | 20 ~ 150 Vdc | 30 ~ 150 Vdc | |
Max. PV Array Open Circuit Voltage | 150 Vdc | ||
Max solar charging current | 40Amp | ||
Max(AC+Solar) Charging current | 80Amp |
Table 4 General Specifications
INVERTER MODEL | 1.0KW-12V | 1.5KW-24V |
---|---|---|
Safety Certification | CE | |
Operating Temperature Range | -10°C to 50°C | |
Storage temperature | -15°C - 60°C | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Dimension (D*W*H), mm | 286 x 240 x 91 | |
Net Weight, kg | 3 | 3.5 |
Related Documents
![]() |
User Manual for 4.5KW/6.5KW Inverter/Charger This user manual provides comprehensive instructions for the 4.5KW and 6.5KW Inverter/Charger, covering installation, operation, specifications, and troubleshooting. Learn about its features, system architecture, and how to use its advanced functions for reliable power support. |