COMBINATION FAN AND LIMIT CONTROLS
The L4017 Combination Fan and Limit Control provides fan and high limit switching for all types of forced air heating systems.
- The fan switch makes and the limit switch breaks on temperature rise.
- The control may be used in line voltage, low voltage, or millivolt systems.
- The sensing element is installed directly in the plenum duct.
- The liquid-filled element operates independently of changes in pressure.
- Electrical circuits are switched by reliable snap switches.
- Temperature settings are adjustable.
- Fast response sensing elements.
- The sensing element may be bent away from an obstruction if necessary.
- Models available with a manual fan switch.
Form Number: 60-2259
SPECIFICATIONS
TRADELINE MODELS
Tradeline models are selected and packaged to provide ease of stocking, ease of handling, and maximum replacement value. Tradeline model specifications are the same as those of standard models except as noted below.
TRADELINE MODELS AVAILABLE:
L4017B Combination Fan and Limit Control. MANUAL-AUTO fan switch, 60 inch [1524 mm] capillary sensing element. Includes limit stop adjusting tool and element support bracket.
L4017B Combination Fan and Limit Control. MANUAL-AUTO fan switch and 10 inch [254 mm] self-supporting element. Includes limit stop adjusting tool.
ADDITIONAL FEATURES: Tradeline pack with cross reference label and special instruction sheet.
STANDARD MODELS
MODELS:
L4017A Combination Fan and Limit Control. Unit has adjustable fan-on and high limit set points with fixed limit and adjustable fan differentials. With case and cover.
L4017B Combination Fan and Limit Control. Unit has adjustable fan-on and high limit set points with fixed limit and adjustable fan differentials - with MANUAL-AUTO fan switch. With case and cover.
ELECTRICAL RATING (amperes):
FAN | LIMIT | |||
120V AC | 240V AC | 120V AC | 240V AC | |
Full Load | 14 | 7 | 8 | 4 |
Locked Rotor | 84 | 42 | 48 | 24 |
0.25 amp at 0.25 to 12V dc (limit only).
Maximum connected load: 2000 VA.
MAXIMUM AMBIENT TEMPERATURE: 190 F [88 C] at switches and 300 F [149 C] at sensing element.
LIMIT DIFFERENTIAL: Fixed at 25 F [14 C].
SWITCH ACTION: Fan switch makes at set point (adjustable differential model) and limit switch breaks at set point on temperature rise. Fan switch breaks at set point on model with fixed differential on temperature fall.
Figure 1 illustrates the dimensions of the L4017A and B models in inches, with millimeters provided in brackets. It details the overall size and the specific location for mounting holes and the sensing element insertion point (a 7/8 inch [22.2 mm] diameter hole).
ORDERING INFORMATION
When purchasing replacement and modernization products from your Tradeline wholesaler or distributor, refer to the Tradeline catalog or price sheets for complete ordering number.
SPECIFY:
- Model number, Tradeline if desired.
- Self-supporting element or capillary.
- Capillary length (capillary models only).
- Optional specification, if desired.
- Fahrenheit or Celsius scaleplate and ranges, if desired.
- Accessory, if desired.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
- Your local Honeywell Residential Division Sales Office (check white pages of phone directory).
- Residential Division Customer Service, HONEYWELL INC., 1885 Douglas Drive North, Minneapolis, Minnesota 55422 (612) 542-7500.
- (In Canada - HONEYWELL CONTROLS LIMITED, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9).
- International Sales and Service Offices in all principal cities of the world.
ELEMENT SPECIFICATIONS
LENGTH OF ELEMENT (in inches) [millimeters]:
Self-supporting model: 10 inches [254 mm] (total length of element).
Capillary models: 24 inches [609.6 mm], 36 inches [914.4 mm], and 54 inches [1371.6 mm] (flexible capillary length). Add 6 inches [152.4 mm] for total length including sensing element.
SENSING ELEMENT: Liquid-filled.
ADJUSTMENT MEANS: Indicators are inside cover.
MOUNTING MEANS: Two holes in backplate.
DIMENSIONS: See Figure 1.
FINISH: Gray.
Certifications: Underwriters Laboratories Inc. Component Recognized: File No. MP466, Guide No. MBPR-2. Canadian Standards Association Certified: File No. LR1620, Guide No. 400-E-0.
OPTIONAL SPECIFICATION
L4017A Combination Fan and Limit Control with fan-off scale. Unit has fixed fan and limit differentials. Fan-on setting is fixed at 33 F [19 C] above fan-off setting. With case and cover.
ACCESSORY
Adapter plate bag assembly, Part No. 21136E, to match mounting holes of competitive devices.
INSTALLATION
CAUTION
- Installer must be a trained, experienced serviceman.
- Disconnect electricity before connecting wiring to prevent electrical shock or equipment damage.
- Conduct a thorough checkout after the installation is complete.
LOCATION
Locate the control on a solid area of the furnace casing or jacket or on the discharge plenum. The stand-off plate furnishes a heat barrier, and a 1/4 inch [6.4 mm] thick asbestos washer (Part No. 106638) is provided to slip over the capillary for air seal between the element clearance hole and the diaphragm power head (see Figure 4). Since the ambient temperature rating is 190 F [88 C] at the switches, this heat barrier should be adequate for all normal applications.
Locate element where it will be exposed to rapid temperature changes in the furnace. After the fan starts, the element temperature should be affected as much as practicable by the changing temperature of the outlet air and receive only enough radiant heat to reduce element temperature lag. The element should not touch any internal part of the furnace. When provided, use the furnace manufacturer's recommendations to determine the exact location (Figure 3).
Figure 3 illustrates proper and improper locations for the sensing element. The 'RIGHT' example shows the element in airflow at average discharge temperature. The 'WRONG' examples show the element too far from the heat source, in dead air, or touching the heat exchanger.
Figure 2 shows proper positioning of the sensing element, emphasizing gradual bends away from joints to avoid rupture, and warning against sharp bends or bends next to joints.
MOUNTING
- Make a 7/8 inch [22.2 mm] diameter hole where the element is to be inserted.
- Loosen the cover screw and remove the cover from the L4017.
- Use the control as a template to mark the location of the 2 mounting holes (see Figure 1).
- Punch or drill the holes for the mounting screws.
- Insert the element into the element opening and slip the asbestos washer over the capillary (Figure 4). With the 2 screws provided, securely fasten the control to the furnace casing.
- Position the element as described in Location above, bending as necessary. Avoid sharp bends or repeated flexing with the self-supporting model (Figure 2).
FLEXIBLE CAPILLARY MODEL
The element must be firmly held in position by use of capillary support, Part No. 107324A, or similar support (Figure 5).
Figure 5 illustrates the capillary support (Part No. 107324A) used to hold the flexible capillary element firmly in position.
REPLACEMENT OF SIMILAR DEVICE BY THE L4017
Adapter plate bag assembly, Part No. 21136E, is available to fit mounting holes of similar controls (Figure 6).
Figure 6 shows the adapter plate (Part No. 21136E) and its dimensions in inches and millimeters, used to fit mounting holes of similar controls.
WIRING
CAUTION
Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
All wiring must comply with applicable local codes and ordinances. Follow the system wiring diagrams furnished with the burner. Figures 7 and 8 illustrate the connections to the L4017. For ease in wiring, 2 conduit knockouts are furnished at the bottom, and 1 at the top of the case.
CAUTION
A jumper is provided between the fan and the limit terminals. This jumper is used when both the fan and the limit switches are switching line voltage circuits. When the high limit switch is used in the low voltage circuit, remove this jumper.
Figure 7 illustrates wiring connections for the L4017 with the limit switch in a line voltage circuit. It shows a jumper between fan and limit terminals, a normally open fan switch, and a normally closed limit switch. Connections are shown for Line 1 (hot), Line 2, Fan Motor, and Power Supply. A warning advises adding disconnect means and overload protection.
Figure 8 illustrates wiring connections for the L4017 with the limit switch in a low voltage circuit. The jumper is removed. It shows a normally open fan switch and a normally closed limit switch. Connections are shown for Line 1 (hot), Line 2, Fan Motor, and Power Supply. A warning advises adding disconnect means and overload protection.
SETTINGS
LIMIT SETTING
To set the cutout point for the high limit switch, move the high limit indicator (Figure 9) to the desired set point. Follow setting instructions furnished by the furnace manufacturer whenever possible. The limit differential is fixed at 25 F [14 C]. The switch breaks at the setting and remakes 25 F [14 C] below the set point.
IMPORTANT: The high limit setting is provided with a stop to limit the maximum temperature setting. Do not force indicator above this point.
FAN SETTING (ADJUSTABLE DIFFERENTIAL)
The fan differential is adjustable from 15 to 50 F [8 to 28 C]. The fan switch makes at the set point and breaks 15 to 50 F [8 to 28 C] below the fan-on setting, depending on the position of the fan adjustment dial. To change the setting, move the fan-on indicator (Figure 9) to the desired temperature. Set the fan differential adjustment dial (Figure 9) to the desired differential. For constant fan operation (L4017B only), set the MANUAL-AUTO switch in the manual position.
FAN SETTING (FIXED DIFFERENTIAL)
Set the fan indicator to the desired fan-off temperature. The fan will come on 35 F [19 C] above that setting.
Figure 9 shows the L4017B with its cover removed, illustrating components such as the conduit knockout, mounting holes, high limit indicator, sensing element, capillary tubing, fan-on indicator, manual-auto fan switch, fan terminal screws, high limit terminal screws, jumper, stand-off plate, and fan differential adjustment dial. The L4017A is similar but lacks the manual fan switch.
CHECKOUT AND TROUBLESHOOTING
CHECKOUT
- Follow the furnace manufacturer's instructions for placing the furnace in operation. If a manual reset Pilotstat control is used, make sure that it is holding in.
- Set the thermostat and limit control to call for heat. The main burner should light.
- To check the high limit control, disconnect the fan motor and close all dampers. Set thermostat to call for heat. Main burner should light. When plenum temperature reaches limit control setting, main burner should shut off. When checkout is complete, connect fan motor and open all dampers.
- Make sure that the fan operates when the furnace temperature rises to the setting and shuts off when temperature drops below set point and through the desired differential. On fixed differential models, the fan should operate when furnace temperature rises to setting plus differential and shut off when temperature drops to setting.
OVERHEATING FURNACE (LIMIT SWITCH FREQUENTLY CUTS OUT)
- Make sure fan is operating by jumpering across the fan terminals. If fan does not operate, check the wiring.
- Make sure that fan setting is low enough so that the hot air is circulated from the furnace before the plenum temperature nears the high limit setting.
- If limit switch continues to cut out, check for obstruction to airflow through furnace. Inspect for clogged air filters and improperly adjusted dampers.