Liebert® IntelliSlot™ Unity Card

Version 7.8.0.0_00083 Firmware Release Notes

December 20th, 2019

1. Version and Compatibility Information

This document outlines:

  1. Version and Compatibility Information
  2. What's New
  3. Security Issues Addressed
  4. Upgrade Instructions
  5. Known Issues

1. Version and Compatibility

This release contains the following firmware version:

IS-UNITY_7.8.0.0_00083

This release is compatible with the following Liebert IntelliSlot communication cards:

This release is compatible with the following power and thermal management equipment:

*iCOM Firmware PA1.04.033.STD versions or later

This release is compatible with the following sensors:

Supported Features

Communication CardLIFE™ ServicesCommunication ProtocolThird-Party Protocols
SupportSensor SupportHTTP/ HTTPSVelocity ProtocolEmailSMSSNMP v1,v2c,v3BACnet IP/MSTPModbus TCP/RTUYDN23
IS-UNITY-DPNXL, EXS S1 & PeX
IS-UNITY-LIFE----
IS-UNITY-SNMP----
Sensor Support----

Supported Browsers

2. What's New

This release contains the following enhancements, updates and corrections:

3. Security Issues Addressed

The following highly publicized security vulnerabilities have already been addressed in a previous release:

NameDescription
"ShellShock"Updated bash version to fix this in release 4.2
"Poodle"SSLv3 was disabled in release 5.0
Cross-ScriptingCross-Scripting entries via the Web user Interface were restricted in release 5.1
CVE-2016-0734 "Clickjacking"Resolved in the 6.2 release.
"Beast” and “Logjam”The "Beast” and “Logjam” vulnerabilities have been addressed in the 6.3 release.
TLS 1.0 accessTLS 1.0 has been disabled so only newer versions are used. This was addressed in the 6.3 release.
"Sweet 32 Birthday Attack"Vulnerability Birthday attacks against TLS ciphers with 64bit block size vulnerability (Sweet32) resolved in the 7.0 release.
TLS 1.1 accessTLS 1.1 has been disabled. TLS 1.2 is the minimum version used. This was addressed in the 7.6 release.
CVE-2004-0583This vulnerability could allow a brute force ID/Password attack. This was addressed in the 7.8 release.
Lack of Account LockoutUser must now configure unique administrator credential to access the card. This was addressed in the 7.8 release.
California IoT Security Law; SB-327User must now configure unique administrator credential to access the card. This was addressed in the 7.8 release.

4. Update Instructions

The Unity cards may be updated to this firmware version using the web-based Firmware Upload feature.

Please refer to the Firmware Updates section of the Liebert IntelliSlot Unity Card User Manual (SL-52645).

5. Known Issues

ComponentDescription
Device SettingsWhen temperature settings are made on some thermal devices, there may be some 'round-off' error of one tenth of a degree between what was requested and what the device shows after the change. This is a known limitation of some thermal device firmware versions and will be corrected in future versions of the device controller firmware.
Liebert GXT3/4 UPS SupportThe IP address of the Unity card may be displayed on the local display of the Liebert GXT4 UPS unit. The IP address is pushed to the GXT4 when the card starts up. If the address changes (for example, if it is changed by the DHCP server when the DHCP lease runs out), the local GXT4 display will continue to show the old address until the card is restarted.
Sensor SupportWhile the SNMP OIDS for the GXT are backward compatible with those from the IS-WEBCARD, the text values in some SNMP varbinds and email/SMS notifications have changed slightly to use the Unity card equivalent.
SNMPThe preferred way to change the display order for multiple sensors is through the Web user interface. If the order is changed using one of the supported protocols then the entire list of sensors should be set in the correct order (including slots that should become blank) to ensure all sensors are still included.
Firmware UpdateSNMP getnext requests may fail on some tables if there are multiple varbinds in the request. If this occurs, use single-varbind requests.
Firmware UpdateWhen using the Microsoft Edge browser to upgrade firmware from a 7.5.0.0 or 7.5.1.0 to another release, the web page will become blank and display an authorization error. To recover, enter the IP address of the card followed by <Enter> after the firmware upgrade completes (this typically takes 5 – 6 minutes).
Firmware UpdateAn update from version 4.3 or older will fail when updating to the v7.7 release or newer. An intermediated (two step) process is required - update to V7.6, then update to v7.7 or newer. Please contact Monitoring Application support to obtain the 7.6 firmware version.

PDF preview unavailable. Download the PDF instead.

unityreleasenotes 7.8.0.0 00083 Acrobat Distiller 17.0 (Windows)

Related Documents

Preview Vertiv Liebert HPM: High-Performance Data Center Cooling Solutions (4-30 kW)
Explore the Vertiv Liebert HPM series, offering efficient and reliable air conditioning solutions for data centers and critical environments. Discover technical specifications, key features, and applications for cooling capacities from 4 to 30 kW.
Preview Vertiv Liebert TFX Installer/User Guide: Power Conditioning & Distribution System
Explore the Vertiv Liebert® TFX Installer/User Guide for detailed instructions on installing, operating, and maintaining this advanced 3-phase power conditioning and distribution system. Learn about its modular design, cabinet options, and technical specifications for reliable data center power solutions.
Preview Liebert XDH 50 & 60 Hz User Manual - Vertiv
Comprehensive user manual for Vertiv's Liebert XDH 50 & 60 Hz data center cooling modules. Covers installation, operation, maintenance, safety, and technical specifications.
Preview Liebert DS Thermal Management System: System Design Catalog
Explore the Vertiv Liebert DS Thermal Management System with this comprehensive design catalog. Details include capacities from 35 to 105 kW, various cooling configurations (air-cooled, water/glycol-cooled, GLYCOOL Economizer), and blower options. Find technical specifications, electrical data, and planning guidelines for data center cooling solutions.
Preview Liebert® iCOM™ Installer/User Guide
Comprehensive Installer and User Guide for the Vertiv Liebert® iCOM™ system, detailing intelligent communication and monitoring for Liebert XDU thermal management units. Covers setup, operation, diagnostics, and BMS integration.
Preview Liebert iCOM Installer/User Guide: Intelligent Communication and Monitoring for Liebert CRV
This comprehensive guide details the installation, operation, and service of the Liebert iCOM system for Liebert CRV thermal management units, covering setup, diagnostics, customization, and networking.
Preview Liebert Air-cooled Drycooler Installer/User Guide | Vertiv
This comprehensive guide from Vertiv provides essential information for the installation, operation, and maintenance of the Liebert Air-cooled, Direct-drive Drycooler. It covers safety, components, site preparation, piping, electrical connections, and troubleshooting for qualified personnel.
Preview Vertiv Liebert GXT5 UPS: Installer and User Guide
Comprehensive guide for the Vertiv Liebert GXT5 Uninterruptible Power System (UPS). Covers installation, operation, maintenance, troubleshooting, and specifications for reliable power protection.