Job Name/Location: Date: PO No.: Architect: Engr: Rep:
(Company)
KUM XB181A
R32 M ult i F Out door Unit
Out door Unit (ODU) - KUM XB181A

For: File

Resubmit

Approval Other

GC: Mech:

(Project Manager)

Tag No:

Performance:

Cooling Capacity (Min.-Rated-Max., Btu/h) 8,400~18,000~21,600

Heating Capacity (Min.-Rated-Max., Btu/h) 10,080~22,000~25,000

Max. Heating Capacity at 17°F (Btu/h) Max. Heating Capacity at 5°F (Btu/h) Max. Heating Capacity at -4°F (Btu/h) Cooling COP @95°F (Rated) Heating COP @47°F (Rated)

20,200 17,700 14,800
3.97 3.60

Cooling Nominal Test Conditions: Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB / 75°F WB

Heating Nominal Test Conditions: Indoor: 70°F DB / 60°F WB Outdoor: 47°F DB / 43°F WB

Electrical: Power Supply (V/Hz/Ø)1,2 MOP (A)
MCA (A)
Cooling Rated Amps (A) Heating Rated Amps (A) Compressor (A) Fan Motor (A) Locked Rotor Amps (A)
MOP - Maximum Overcurrent Protection

208-230V, 60, 1
20 16.1 12.33 12.33
12 0.33 16.0
MCA - Minimum Circuit Ampacity

Piping:

Refrigerant Charge (lbs.)

Liquid Line Connection (in., O.D.) Vapor Line Connection (in., O.D.) Maximum Total Piping3 (ft.) Min. / Max. ODU to IDU Piping (ft.) Piping Length (no add'l refrigerant, ft.) Additional Refrigerant Charge (oz. / ft.) Maximum Elevation between ODU and IDU (ft.) Maximum Elevation between IDU and IDU (ft.)

ODU = Outdoor Unit

IDU = Indoor Unit

3.08
1/ 4 x 2
3/ 8 x 2
164
9.8 / 82.0
98.4
0.22 49.2 24.6

Features:

· Auto operation / Auto restart

· Restart delay (three [3] minutes)

· Inverter (variable speed

· Self diagnosis

compressor)

· Soft start

· Integrated central control connection · Low ambient cooling down to 14°F

· Defrost / Deicing

(-4°F with Wind Baffle Kit)

Operating Range: Cooling (°F DB) Heating (°F WB)
Unit Data: Refrigerant Type Refrigerant Control Sound Pressure (Cool / Heat) ±1 dB(A)4 Net / Shipping Weight (lbs.) Power Wiring from ODU to IDU (No x AWG)2 Communication Wiring from ODU to IDU (No x AWG)2 Heat Exchanger Coating Minimum No. of Indoor Units Maximum No. of Indoor Units
Compressor: Type Quantity Oil / Type

14 to 118 -4 to +64
R32 EEV
49 / 54 102.7 / 111.6
3 x 14 2 x 18 Gold FinTM
2
2
Twin Rotary 1
FW68D

Fan: Type
Quantity Motor / Drive Max. Airflow Rate (CFM)

Axial 1
Brushless Digitally Controlled/Direct
1,766

Notes:
1. Acceptable operating voltage: 187V - 253V. 2. All power supply wiring to the outdoor unit is field supplied, solid or stranded. The power wiring and the communication wiring from the outdoor unit to the indoor unit is field supplied and must be stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only). All wiring must comply with applicable local and national codes. a. Power Supply Wiring to Outdoor Unit (No. x AWG): 3 x 14 for 18k and 24k; 3 x 12 for 30k and 36k. b. Power Wiring and Communication Wiring from Outdoor Unit to Indoor Unit (No. x AWG) 3 x 14 / 2 x 18.
3. Piping lengths are equivalent.
4. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745. 5. This data is rated 0 ft. above sea level, with 0 ft. level difference between outdoor and indoor units, and the following refrigerant pipe lengths: KUMXB181A: 16.4 ft. x 2 = 32.8 ft. KUMXB241A: 16.4 ft. x 3 = 49.2 ft. KUMXB301A: 16.4 ft. x 4 = 65.6 ft. KUMXB361A: 16.4 ft. x 4 = 65.6 ft. 6. All capacities are net with a combination ratio between 95 - 105%. 7. Must follow installation instructions in the applicable LG installation manual. 8. Refer to the Combintion Data Manual for combination capacity tables. 9. See the Performance Data Manual for sensible and latent capacities.

Optional Accessories:  Power Distribution Indicator (PDI) Premium - PQNUD1S41  Mobile LGMV for Android® Smartphones / Tablets or for iOS® Tablets - PLGMVW100
(Android is a registered trademark of Google LLC. iOS is a registered trademark of Cisco Systems, Inc.)

 LG Monitoring View (LGMV) for Computers - PRCTIL0  Drain Pan Heater -PQSH1203  Low Ambient Wind Baffle Kit -
ZLABGP03A

Controller Options:  MultiSITE Communication Mgr.  AC Smart 5  ACP 5

 ACP 5 BACnet® Gateway  LonWorks® Gateway
BACnet® is a registered trademark of ASHRAE. Lon- Works is a registered trademark of Echelon Corp.

Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps (excluding ductless systems) must be matched with appropriate coil components to meet ENERGY STAR® criteria. Ask your contractor for details or visit www.energystar.gov. (ENERGY STAR and the ENERGY STAR mark are registered trademarks owned by the U.S. Environmental Protection Agency.)

For a complete list of available accessories, contact your LG representative. For continual product development, LG reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com

SB_M ult i_F_ODU_R32_KUM XB181A_2025_01_07_193346
Page 1 of 2

Job Name/Location:
KUM XB181A
R32 M ult i F Out door Unit
Out door Unit (ODU) - KUM XB181A

Tag No.: Date: PO No.:

For continual product development, LG reserves the right to change specifications without notice. © LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com

SB_M ult i_F_ODU_R32_KUM XB181A_2025_01_07_193346
Page 2 of 2

