Nyle ThermaCharge+ Energy Storing Water Tanks
Designed for use as a recovery heater having its own storage tank.
Key Features
- Glass-lined Tank: 119 gallon capacity. Tank interior is coated with glass specially designed for water heater use.
- Terminal Block: Factory-installed. Just bring the service to heater and connect to block.
- Elements: Zinc plated copper sheaths for longer life. Medium watt density means lower surface temperature to minimize scale build-up and more surface to heat water. Maximum input 12 kW.
- Controls: Temperature control (adjustable through a range of 130° - 170°F on single element and 120° - 181°F on dual element) and manual reset high temperature cutoff per element.
- Demand Response Compatible
Additional Features
- CSA Certified And ASME Rated T&P Relief Valve
- Simplified Circuitry, Color Coded For Ease Of Service
- Anode Rod For Maximum Corrosion Protection
- Cabinet Has Bonderized Undercoat With Baked Enamel Finish
- Top Inlet And Outlet Openings
- Drain Valve
- UL Approved Field Conversion Program
- Compliance: Meets The Standby Loss Requirements Of The U.S. Department Of Energy And Current Edition Of ASHRAE/IES 90.1.
Rough-in Dimensions
Number of Elements: 2
US Gal | Liters | |
---|---|---|
Tank Capacity | 119 | 450 |
A | 62 7/16 inches | 1586 mm |
B | 49 3/4 inches | 1264 mm |
C | 33 3/4 inches | 857 mm |
D | 11 3/4 inches | 451 mm |
E | 13 1/4 inches | 337 mm |
F 2" NPT Recirculation Fitting | 9 1/4 inches | 235 mm |
F 2" NPT Inlet | 29 3/8 inches | 746 mm |
G | 4 inches | 101.6 mm |
Shipping Weight | 326 lbs | 147.9 Kg. |
Diagram Description: A diagram shows the dimensions of the water heater tank with labels A through H indicating various measurements and connection points, including junction box, NPT inlets/outlets, and relief valve opening. The diagram also includes a scale reference.
Element Availability Chart: (Light-Duty Commercial Electric)
Voltage | Wiring | kW Input Available |
---|---|---|
240V | Simultaneous | 12** |
277V* | Simultaneous | 12 |
480V | Simultaneous | 12 |
* Single-Phase only for 277V
** Simultaneous only in 3ph
Electric Characteristics
Simultaneous Dual Element Operation (Single Phase Connection)
Element Wattage Upper / Lower |
Full Load Current in Amperes (Terminals - L1, L2) 240V |
Full Load Current in Amperes (Terminals - L1, L2) 480V |
---|---|---|
6000 | N/A | 25 |
Simultaneous Dual Element Operation (Unbalanced Three Phase Connection)
Element Wattage Upper / Lower |
Full Load Current in Amperes (Terminals - L1 / Terminals L2 & L3) 240V |
Full Load Current in Amperes (Terminals - L1 / Terminals L2 & L3) 480V |
---|---|---|
6000 | 43.3 / 25.0 | 21.6 / 12.5 |
Recovery Capacities: U.S. Gallons/Hr and Liters/Hr at Temperature Rise Indicated
Element Wattage Upper / Lower |
Input kW |
°F | 36 | 40 | 54 | 60 | 72 | 80 | 90 | 100 | 108 | 120 | 126 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
°C | 20 | 22.2 | 30 | 33.3 | 40 | 44.4 | 50 | 55.5 | 60 | 66.6 | 70 | ||
GPH 135 | 122 | 90 | 81 | 68 | 61 | 54 | 49 | 45 | 41 | 39 | |||
6000/6000 | 12 | LPH 511 | 460 | 341 | 307 | 256 | 230 | 205 | 184 | 170 | 153 | 146 |
Recovery capacities at 100° F rise equal: for non-simultaneous element operation = 4.1 gal. x kW of one element; for simultaneous element operation = 4.1 gal. x 2/3 kW of both elements. For other rises multiply element kW as previously explained by 410 and divide by temperature rise. Full load current for single phase = total watts/voltage.