22-1904-1M-EN

https://www.trane.com/content/dam/Trane/Commercial/global/products-systems/equipment/unitary/split-systems/split-systems-1-1-2-to-5-tons/22-1904-1M-EN

Trane 2twb3048a1000aa Manual

4TTR4 (22-1904-*)

Split System Air Conditioners and Heat Pumps

PDF preview unavailable. Download the PDF instead.

22-1904-1M-EN
Product Data
Split System Cooling
4TTR4018L1000A 4TTR4024L1000B 4TTR4025L1000B 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000B

Note: "Graphics in this document are for representation only. Actual model may differ in appearance."

April 2020

22-1904-1M-EN

Product Specifications

Model No. (a)

4TTR4018L1000A

4TTR4024L1000B/ 4TTR4025L1000B

4TTR4030L1000A/ 4TTR4031L1000A

4TTR4036L1000A/ 4TTR4037L1000A

POWER CONNS. -- V/PH/HZ (b) 208/230/1/60

208/230/1/60

208/230/1/60

208/230/1/60

MIN. BRCH. CIR. AMPACITY

12

14

17

18

BR. CIR. PROT. RTG. -- MAX.

(AMPS)

20

20

25

30

COMPRESSOR

CLIMATUFF®SCROLL

CLIMATUFF®SCROLL

CLIMATUFF®SCROLL

CLIMATAUFF®SCROLL

RL AMPS -- LR AMPS

9 -- 63

10.1 -- 52

12.8-- 68

14.1-- 72

Outdoor Fan FL AMPS

0.60

0.90

0.77/.64

0.77/.64

Fan HP

1/15

1/8

1/8

1/8

Fan Dia (inches)

18.2

18.2

23.0

23.0

Coil

SPINE FINTM

SPINE FINTM

SPINE FINTM

SPINE FINTM

Refrigerant R-410A

4 LBS., 2 OZ

4 LBS., 11 OZ / 4 LBS., 2 OZ

4 LBS., 11 OZ

5 LBS., 8 OZ / 5 LBS., 3 OZ

LINE SIZE -- IN. O.D. GAS (c)

3/4

3/4

3/4

3/4

LINE SIZE -- IN. O.D. LIQ. (c)

3/8

3/8

3/8

3/8

Charge Spec. Subcooling

10°F

10°F

10°F

10°F / ( 8°F on 037)

Dimensions H x W X D Crated (IN.)

30.1 x 26.7 x 30 30.1 x 26.7 x 30

34 x 30.1 x 33

38 x 30.1 x 33

Weight -- Shipping (lbs.)

153

153

183

183

Weight -- Net (lbs.)

133

133

156

156

Optional Accessories:

Anti-short Cycle Timer

TAYASCT501A

TAYASCT501A

TAYASCT501A

TAYASCT501A

Evaporator Defrost Control

AY28X079

AY28X079

AY28X079

AY28X079

Rubber Isolator Kit

BAYISLT101

BAYISLT101

BAYISLT101

BAYISLT101

Extreme Condition Mount Kit Start Kit

BAYECMT023 BAYKSKT263

BAYECMT023 --

BAYECMT023 BAYKSKT263

BAYECMT023 BAYKSKT263

Crankcase Heater Kit Seacoast Kit

BAYCCHT302 BAYSEAC001

BAYCCHT302 BAYSEAC001

BAYCCHT302 BAYSEAC001

BAYCCHT302 BAYSEAC001

Low Ambient Kit Service Valve Panel Cover

BAYLOAM103
TAYSVPANL0022AA

BAYLOAM103

BAYLOAM103

BAYLOAM103

TAYSVPANL0022AA TAYSVPANL0032AA TAYSVPANL3343AA

Refrigerant Lineset (d)
(a) Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard 210/240.
(b) Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. (c) Standard line lengths -- 60', Standard lift -- 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant
piping software Pub#32­3312­0* (* denotes latest revision). (d) 25, 30, 35 and 50 foot linesets available. For a complete listing of lineset options available from equipment or supply stores,
refer to the Trane Residential and Light Commercial Product Handbook.

2

22-1904-1M-EN

Product Specifications

Model No. (a) POWER CONNS. -- V/PH/HZ (b)

4TTR4042L1000A/ 4TTR4043L1000A
280/230/1/60

4TTR4048L1000A 280/230/1/60

4TTR4060L1000B 280/230/1/60

MIN. BRCH. CIR. AMPACITY

22

24

27

BR. CIR. PROT. RTG. -- MAX. (AMPS)

35

40

45

COMPRESSOR

CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL

RL AMPS -- LR AMPS Outdoor Fan FL AMPS

16.7 -- 109 1.05

18.5 -- 124 1.05

20.8 -- 127.1 1.05

Fan HP

1/5

1/5

1/5

Fan Dia (inches)

27.5

27.5

27.5

Coil

SPINE FINTM

SPINE FINTM

SPINE FINTM

Refrigerant R-410A

6 LBS., 2 OZ / 5 LBS., 5 OZ

5 LBS., 3 OZ

7 LBS., 10 OZ

LINE SIZE -- IN. O.D. GAS (c)

7/8

7/8

7/8

LINE SIZE -- IN. O.D. LIQ. (c)

3/8

3/8

3/8

Charge Spec. Subcooling

12°F

10°F

10°F

Dimensions H x W X D Crated (IN.)

34.4 x 35.1 x 38.7

34.4 x 35.1 x 38.7

42.4 x 35.1 x 38.7

Weight -- Shipping (lbs.)

216

212

246

Weight -- Net (lbs.)

184

189

211

Optional Accessories:

Anti-short Cycle Timer

TAYASCT501A

TAYASCT501A

TAYASCT501A

Evaporator Defrost Control

AY28X079

AY28X079

AY28X079

Rubber Isolator Kit

BAYISLT101

BAYISLT101

BAYISLT101

Extreme Condition Mount Kit Start Kit Crankcase Heater Kit Seacoast Kit Low Ambient Kit

BAYECMT004 BAYKSKT263 BAYCCHT301 BAYSEAC001 BAYLOAM103

BAYECMT004 BAYKSKT263 BAYCCHT301 BAYSEAC001 BAYLOAM103

BAYECMT004 BAYKSKT263 BAYCCHT301 BAYSEAC001 BAYLOAM103

Service Valve Panel Cover Refrigerant Lineset (d)

TAYSVPANL0044AA

(a) Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard 210/240.
(b) Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. (c) Standard line lengths -- 60', Standard lift -- 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant
piping software Pub#32­3312­0* (* denotes latest revision). (d) 25, 30, 35 and 50 foot linesets available. For a complete listing of lineset options available from equipment or supply stores,
refer to the Trane Residential and Light Commercial Product Handbook.

22-1904-1M-EN

3

Product Specifications

Sound Power Level

MODEL
4TTR4018L1 4TTR4024L1 4TTR4025L1 4TTR4030L1 4TTR4031L1 4TTR4036L1 4TTR4037L1 4TTR4042L1 4TTR4043L1 4TTR4048L1

A-Weighted Sound Power Level [dB(A)]
71 71 71 71 71 71

Sound Power Level

Full Octave Sound Power(dB)

63 125 250

Hz* Hz

Hz

74

71

65

74

71

65

73

73

72

73

73

72

81

72

69

81

72

69

500 1000 2000

Hz

Hz

Hz

68

67

63

68

67

63

69

68

60

69

68

60

69

66

60

69

66

60

4000 Hz 56 56
52
52
57 57

4TTR4060L1

71

81

72

69

69

66

60

57

Note: Rated in accordance with AHRI Standard 270­2008 *For Reference Only

8000 Hz 50 50
45
45
54 54 54

4

22-1904-1M-EN

Accessory Description and Usage
Anti-Short Cycle Timer -- Solid state timing device that prevents compressor recycling until five (5) minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power delivery, commercial applications, long lineset, etc.
Evaporation Defrost Control -- SPST Temperature actuated switch that cycles the condenser off as indoor coil reaches freeze-up conditions. Used for low ambient cooling to 30°F with TXV.
Rubber Isolators -- Five (5) large rubber donuts to isolate condensing unit from transmitting energy into mounting frame or pad. Use on any application where sound transmission needs to be minimized.
Hard Start Kit -- Start capacitor and relay to assist compressor motor startup. Use in areas with marginal power supply, on long linesets, low ambient conditions, etc.
Extreme Condition Mount Kit -- Bracket kits to securely mount condensing unit to a frame or pad without removing any panels. Use in areas with high winds, or on commercial roof tops, etc.

AHRI Standard Capacity Rating Conditions AHRI Standard 210/240 Rating Conditions 1. Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. 2. High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering
indoor coil. 3. Low Temperature Heating 17°F DB air entering indoor coil. 4. Rated indoor airflow for heating is the same as for cooling. AHRI Standard 270 Rating Conditions -- (Noise rating numbers are determiend with the unit in cooling operations.) Standard Noise Rating number is at 95°F outdoor air.

Model Nomenclature
Outdoor Units

4TWV 0 0 3 6 A 1 0 0 0A A

Refrigerant Type 2 = R-22 4 = R-410A

TRANE

Product Type W = Split Heat Pump T = Split Cooling

Product Family V = Variable Speed Z = Leadership ­ Two Stage X = Leadership R = Replacement/Retail

M or B = Basic A = Light Commercial L = Side Discharge

Family SEER 3 = 13 6 = 16 4 = 14 8 = 18 5 = 15 9 = 19

0 = 20

Split System Connections 1-6 Tons 0 = Brazed

Nominal Capacity in 000s of BTUs

Major Design Modifications

Power Supply 1 = 200-230/1/60 or 208-230/1/60 3 = 200-230/3/60 4 = 460/3/60

Secondary Function

Minor Design Modifications

Unit Parts Identifier

22-1904-1M-EN

5

Schematic Diagrams
Figure 1. 1.5­4.0 Ton Models

6

22-1904-1M-EN

Figure 2. 5.0 Ton Models

Schematic Diagrams

22-1904-1M-EN

7

Schematic Diagrams

Figure 3. 5.0 Ton Models

8

22-1904-1M-EN

Outline Drawing

Model

Base

A

B

C

D

4TTR4018L

730

724

651

2 (28­3/4) (28­1/2) (25­5/8)

3/4

4TTR4024L 4TTR4025L

730

724

651

2 (28­3/4) (28­1/2) (25­5/8)

3/4

4TTR4030L 4TTR4031L

730

829

756

3 (28­3/4) (32­5/8) (29­3/4)

3/4

4TTR4036L 4TTR4037L

832

829

756

3 (32­3/4) (32­5/8) (29­3/4)

3/4

4TTR4042L 4TTR4043L

741

946

870

4 (29­1/8) (37­1/4) (34­1/4)

7/8

4TTR4048L

741

946

870

4 (29­1/8) (37­1/4) (34­1/4)

7/8

4TTR4060L

4

943

946

870

(37­1/8) (37­1/4) (34­1/4)

7/8

E

F

G

H

J

3/8

127 (5)

57 (2­1/4)

194 (7­5/8)

38 (1­1/2)

3/8

127 (5)

57 (2­1/4)

194 (7­5/8)

38 (1­1/2)

3/8

127 (5)

76

197

60

(3)

(7­3/4) (2­3/8)

3/8

127 (5)

76

197

60

(3)

(7­3/4) (2­3/8)

3/8

143 (5­5/8)

83 (3­1­4)

206 (8­1/8)

70 (2­3/4)

3/8

143 (5­5/8)

83 (3­1­4)

206 (8­1/8)

70 (2­3/4)

3/8

152 (6)

98 (3­7/8)

219 (8­5/8)

86 (3­3/8)

K
457 (18)
457 (18)
508 (20)
508 (20)
508 (20)
508 (20)
508 (20)

22-1904-1M-EN

9

Mechanical Specification Options
General
The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.
Casing
Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint finish. The corner panels are prepainted. All panels are subjected to our 1,000 hour salt spray test.
Refrigerant Controls
Refrigeration system controls include condenser fan, compressor contactor and low and high pressure switches. A factory supplied, field installed liquid line drier is standard.
Compressor
The compressor features internal over temperature and pressure protection. Other features include: Centrifugal oil pump and low vibration and noise.
Condenser Coil
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.
Low Ambient Cooling
As manufactured, this system has a cooling capacity to 55°F. The addition of an evaporator defrost control permits operation to 40°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F.
The addition of the BAYLOAM107A low ambient kit permits ambient cooling to 20°F.
Thermostats--Cooling only and heat/cooling (manual and automatic change over). Sub-base to match thermostat and locking thermostat cover.

10

22-1904-1M-EN

Notes

22-1904-1M-EN

11

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane. com or tranetechnologies.com.

The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory. org.

Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

22-1904-1M-EN 24 Apr 2020 Supersedes 22-1904-1L-EN (October 2019)

©2020 Trane


PTC Arbortext Publishing Engine PDFlib PDI 9.0.6 (C /Win64); modified using iText 2.1.7 by 1T3XT