General Notes
This chapter provides important advice on using this documentation. The documentation contains information that must be applied if the product is to be used safely and efficiently. Please read this documentation through carefully and familiarise yourself with the operation of the product before putting it to use. Keep this document to hand so that you can refer to it when necessary.
Identification
Representation | Meaning | Comments |
---|---|---|
? | Note | Offers helpful tips and information. |
[Objective] | Objective | Denotes the objective that is to be achieved via the steps described. Where steps are numbered, you must always follow the order given! |
✔️ | Condition | A condition that must be met if an action is to be carried out as described. |
[Step] | Step | Carry out steps. Where steps are numbered, you must always follow the order given! |
[Display Text] | Display text | Text appears on the instrument display. |
[Control Button] | Control button | Press the button. |
➡️ | Result | Denotes the result of a previous step. |
[See also] | Cross-reference | Refers to more extensive or detailed information. |
Safety Advice
Avoid Personal Injury/Damage to Equipment
- Do not use the measuring instrument and probes to measure on or near live parts.
- Never store the measuring instrument/probes together with solvents and do not use any desiccants.
Product Safety/Preserving Warranty Claims
- Operate the measuring instrument only within the parameters specified in the Technical data.
- Always use the measuring instrument properly and for its intended purpose. Do not use force.
- Do not expose handles and feed lines to temperatures in excess of 70 °C unless they are expressly permitted for higher temperatures.
- Temperatures given on probes / sensors relate only to the measuring range of the sensors.
- Open the instrument only when this is expressly described in the documentation for maintenance and repair purposes.
- Carry out only the maintenance and repair work that is described in the documentation. Follow the prescribed steps when doing so. For safety reasons, use only original spare parts from Testo.
Ensure Correct Disposal
- Take faulty rechargeable batteries/spent batteries to the collection points provided for them.
- Send the product back to Testo at the end of its useful life. Testo will ensure that it is disposed of in an environmentally friendly manner.
Intended Purpose
This chapter gives the areas of application for which the product is intended. Use the product only for those applications for which it was designed. Ask Testo if you are in any doubt.
The testo 417 is a compact measuring instrument for measuring flow velocities and temperatures by means of an integrated 100mm vane with temperature probe.
The product was designed for the following tasks/applications:
- Measuring volumetric flow rates at inlets/outlets
- Measuring the temperature of flows
The product should not be used in the following areas:
- Areas at risk of explosion.
- Diagnostic measurements for medical purposes
Product Description
Display and Control Elements
Overview
- 1 Probe
- 2 Display
- 3 Control buttons
- 4 Battery compartment (rear)
- 5 Service compartment (rear)
Button Functions
Button | Functions |
---|---|
⏻ [Power] | Switch instrument on; switch instrument off (press and hold) |
? [Light] | Switch display light on / off |
[Hold/Max/Min] | Keep reading, display maximum/minimum value |
⚙️ [Config/Confirm] | Open/leave configuration mode (press and hold); In configuration mode: Confirm input |
⬆️ [Increase] | In configuration mode: Increase value, select option |
⬇️ [Decrease] | In configuration mode: Reduce value, select option |
[Mean] | Multi-point and timed mean calculation |
[Vol] | Volumetric flow |
Important Displays
Display | Meaning |
---|---|
? | Battery capacity (bottom right in display):
|
Voltage Supply
Voltage is supplied by means of a 9V monobloc battery (included in delivery) or rechargeable battery. It is not possible to run the instrument from the mains supply or charge a rechargeable battery in the instrument.
Commissioning
Inserting a Battery/Rechargeable Battery
- To open the battery compartment on the rear of the instrument, push the lid of the battery compartment in the direction of the arrow and remove it.
- Insert a battery/rechargeable battery (9V monobloc). Observe the polarity!
- To close the battery compartment, replace the lid of the battery compartment in position and push it against the direction of the arrow.
Operation
Connecting a Probe
The necessary probes are permanently connected or integrated. It is not possible to connect any additional probes.
Switching the Instrument On / Off
Switching the instrument on:
- Press ⏻ [Power].
- Measurement view is opened: The current reading is displayed, or ----- lights up if no reading is available.
Switching the instrument off:
- Press and hold ⏻ [Power] (for approx. 2s) until the display goes out.
Switching the Display Light On / Off
Switching the display light on/off:
- The instrument is switched on.
- Press ? [Light].
Performing Settings
- To open configuration mode: The instrument is switched on and is in measurement view. Hold, Max or Min are not activated. Press and hold ⚙️ [Config/Confirm] (for approx. 2s) until the display changes. The instrument is now in configuration mode. You can change to the next function with ⚙️ [Config/Confirm]. You can leave configuration mode at any time. To do so, press and hold ⚙️ [Config/Confirm] (for approx. 2s) until the instrument has changed to measurement view. Any changes that have already been made in configuration mode will be saved.
- To set funnel factor F.FACT: For measurements at ventilation outlets with a funnel, the parameter F.FACT must be activated. The funnel set (order no. 0563 4170) consists of a funnel for measurements at plate outlets (200 x 200mm) and a funnel for measurements at ventilation outlets (330 x 330mm). Configuration mode is opened, F.FACT is lit. Activate (on) or deactivate (oFF) the factor with ⬆️ [Increase] / ⬇️ [Decrease] and confirm with ⚙️ [Config/Confirm].
- To set the area (only if F.FACT oFF): Configuration mode is opened, AREA is lit. Set the cross-sectional area with ⬆️ [Increase] / ⬇️ [Decrease] and confirm with ⚙️ [Config/Confirm].
Measuring
Taking a Measurement
- The instrument is switched on and is in measurement view.
- Put the probe in position and read off the readings.
Changing the Measurement Channel Display
- To change between displaying the temperature (°C, °F) and the calculated volumetric flow rate (m³/h, l/s, cfm): Press [Vol].
Holding the Reading, Displaying the Maximum/Minimum Value
The current reading can be recorded. The maximum and minimum values (since the instrument was last switched on) can be displayed.
- Press [Hold/Max/Min] several times until the desired value is displayed. The following are displayed in turn:
- Hold: the recorded reading
- Max: Maximum value
- Min: Minimum value
- The current reading
Resetting the Maximum/Minimum Values
The maximum/minimum values of all channels can be reset to the current reading.
- Press [Hold/Max/Min] several times until Max or Min lights up.
- Press and hold [Hold/Max/Min] (approx. 2s). All maximum or minimum values are reset to the current reading.
Performing a Multi-Point Mean Calculation
- Hold, Max or Min are not activated.
- Press [Mean]. Mean is lit. The number of readings recorded is displayed in the upper line, while the current reading is displayed in the lower line.
Option:
- To change between displaying the temperature (°C, °F), flow velocity (m/s, fpm) and calculated volumetric flow rate (m³/h, l/s, cfm): Press [Vol].
- To include readings (in the desired quantity): Press [Mean] (several times).
- To end measurement and calculate the mean value: Press [Mean]. Mean flashes. The calculated spot mean value is displayed.
- To return to measurement view: Press [Mean].
Performing a Mean Calculation in Time
- Hold, Max or Min are not activated.
- Press [Mean] twice. Mean is lit. The elapsed measuring time (mm:ss) is displayed in the upper line, while the current reading is displayed in the lower line.
Option:
- To change between displaying the temperature (°C, °F), flow velocity (m/s, fpm), and calculated volumetric flow rate (m³/h, l/s, cfm): Press [Vol].
- To start measurement: Press ⚙️ [Config/Confirm].
- To interrupt/continue measurement: Press ⚙️ [Config/Confirm] each time.
- To end measurement and calculate the mean value: Press [Mean]. Mean flashes. The calculated mean value in time is displayed.
- To return to measurement view: Press [Mean].
Care and Maintenance
Cleaning the Housing
- Clean the housing with a moist cloth (soap suds) if it is dirty. Do not use aggressive cleaning agents or solvents!
Changing the Battery/Rechargeable Battery
- The instrument is switched off.
- To open the battery compartment on the rear of the instrument, push the lid of the battery compartment in the direction of the arrow and remove it.
- Remove the spent battery/rechargeable battery and insert a new battery/rechargeable battery (9 V monobloc). Observe the polarity!
- To close the battery compartment, replace the lid of the battery compartment in position and push it against the direction of the arrow.
Note for Fine Adjustment
The production of vanes is subject to specified tolerances. All vanes are tested in a 100% quality control and finely adjusted once more. This fine adjustment may include applying acrylic drops. Once fine adjustments are complete, every testo 417 undergoes a final test. The results are recorded in a calibration protocol supplied with the respective testo 417. This confirms that the testo 417 meets specifications.
Questions and Answers
Question | Possible Causes | Possible Solution |
---|---|---|
? is lit (bottom right in display). | Instrument battery is almost spent. | Replace instrument battery. |
Instrument switches itself off automatically. | Auto Off function is switched on. Residual capacity of battery is too low. |
Switch function off. Replace battery. |
Display: ----- | Probe break. | Please contact your dealer or Testo Customer Service. |
Display reacts slowly | Ambient temperature is very low. | Raise ambient temperature. |
Display: uuuuu | Permitted measuring range was undershot. | Keep to permitted measuring range. |
Display: 00000 | Permitted measuring range was exceeded. | Keep to permitted measuring range. |
If we are unable to answer your question, please contact your dealer or Testo Customer Service. For contact data, see back of this document or web page www.testo.com/service-contact.
Technical Data
Characteristic | Value |
---|---|
Parameters | Flow velocity (m/s, fpm), temperature (°C / °F) |
Calculated variables | Volumetric flow rate (m³/h, l/s, cfm) |
Measuring range | +0.3...+20 m/s 0...+50 °C / +32...+122 °F 0...+99 999 m³/h 0...+440 m³/h (testo 417 in conjunction with funnel set (0563 4140)) 0,1...+200 m³/h, preferred 0,1...100 m³/h (testo 417 in conjunction with funnel & rectifier (0554 4174)) |
Resolution | 0.01 m/s 0.1 °C / 0.1 °F 0,1 m³/h (0...+99,9 m³/h) 1 m³/h (+100...+99 999 m³/h) |
Accuracy (± 1 Digit) | ±0.1m/s+1.5% of reading ±0.5 °C / ±0.9 °F |
Probe | Vane probe 100 mm, NTC temperature probe (integrated) |
Measuring rate | 2/s |
Operating temperature range | 0...+50 °C / +32...+122 °F |
Storage temperature | -40...+70 °C / -40...+158°F |
Voltage supply | 1x 9 V monobloc battery/rech. battery |
Battery life | approx. 50 h |
EC Directive | 2014/30/EC |
Accessories/Spare Parts
Name | Part no. |
---|---|
Funnel set consisting of funnel for disc valves (200 x 200mm) and funnel for ventilator (330 x 330mm) | 0563 4170 |
For a complete list of all accessories and spare parts, please refer to the product catalogues and brochures or look up our website: www.testo.com