Installation Guide for Schneider models including: Schneider, Galaxy VS
6/2021 www.schneider-electric.com. Legal Information ... Read all instructions in the installation manual before installing or working on this UPS system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
6/ 2021 www.schneider-electric.com. Legal Information ... Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric ...
File Info : application/pdf, 88 Pages, 7.88MB
DocumentDocumentGalaxy VS UPS for External Batteries Installation 20-150 kW 400/480 V 10-75 kW 208 V Latest updates are available on the Schneider Electric website 6/2021 www.schneider-electric.com Legal Information The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners. This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric. Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel. As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice. To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein. Go to IEC: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_iec/ or UL: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_ul/ or scan the QR code above for digital experience and translated manuals. Table of Contents UPS for External Batteries 990-91111F-001 Important Safety Instructions -- SAVE THESE INSTRUCTIONS .........................................................................................5 FCC Statement ..........................................................................................6 Electromagnetic Compatibility .....................................................................6 Safety Precautions .....................................................................................6 Electrical Safety .........................................................................................9 Battery Safety ............................................................................................9 Symbols Used .......................................................................................... 11 ENERGY STAR Qualification.....................................................................13 Specifications ............................................................................................14 Specifications for 400 V Systems ...............................................................14 Input Specifications 400 V ...................................................................14 Bypass Specifications 400 V................................................................15 Output Specifications 400 V.................................................................16 Battery Specifications 400 V ................................................................17 Recommended Cable Sizes 400 V .......................................................18 Recommended Upstream Protection 400 V ..........................................20 Specifications for 480 V Systems ...............................................................21 Input Specifications 480 V ...................................................................21 Bypass Specifications 480 V................................................................22 Output Specifications 480 V.................................................................23 Battery Specifications 480 V ................................................................24 Recommended Cable Sizes 480 V .......................................................25 Recommended Upstream Protection 480 V ..........................................27 Specifications for 208 V Systems ...............................................................28 Input Specifications 208 V ...................................................................28 Bypass Specifications 208 V................................................................29 Output Specifications 208 V.................................................................30 Battery Specifications 208 V ................................................................31 Recommended Cable Sizes 208 V .......................................................32 Recommended Upstream Protection 208 V ..........................................34 Recommended Bolt and Lug Sizes ............................................................36 Torque Specifications................................................................................37 Requirements for a Third Party Battery Solution..........................................38 Third Party Battery Breaker Requirements ............................................38 Guidance for Organizing Battery Cables ...............................................39 Environment............................................................................................. 39 UPS Weights and Dimensions ...................................................................40 Clearance ................................................................................................41 Single System Overview ..........................................................................42 Parallel System Overview........................................................................43 Overview of Installation Kits ....................................................................46 Optional Seismic Kit GVSOPT002 .............................................................47 Optional NEMA 2 Hole Kit GVSOPT005 .....................................................47 Optional Parallel Kit GVSOPT006 ..............................................................48 Optional Kit GVSOPT030 ..........................................................................49 Installation Procedure for Single Systems ............................................50 3 UPS for External Batteries Installation Procedure for Parallel Systems ..........................................51 Prepare for Installation .............................................................................52 Install the Power Module(s).....................................................................56 Install the Seismic Anchoring (Option) ..................................................57 Prepare the UPS for TN-C/480 V Solid-Grounded System ................58 Connect the Power Cables......................................................................59 Connect the Power Cables with NEMA 2 Hole Plates ........................63 Connect the Signal Cables ......................................................................67 Connect the Signal Cables from a Modular Battery Cabinet..............69 Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products .....................................................................................71 Connect the IMB Signal Cables in a Simplified 1+1 Parallel System........................................................................................................ 75 Connect the PBUS Cables ......................................................................79 Connect the External Communication Cables......................................80 Connect the Modbus Cables .....................................................................81 Add Translated Safety Labels to Your Product.....................................82 Final Installation ........................................................................................83 4 990-91111F-001 Important Safety Instructions -- SAVE THESE INSTRUCTIONS UPS for External Batteries Important Safety Instructions -- SAVE THESE INSTRUCTIONS Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a "Danger" or "Warning" safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death. DANGER DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury. WARNING WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage. NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage. Please Note Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. 990-91111F-001 5 UPS for External Batteries FCC Statement Important Safety Instructions -- SAVE THESE INSTRUCTIONS NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Electromagnetic Compatibility NOTICE RISK OF ELECTROMAGNETIC DISTURBANCE This is a product category C2 UPS product. In a residential environment, this product may cause radio inference, in which case the user may be required to take additional measures. Failure to follow these instructions can result in equipment damage. Safety Precautions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the installation manual before installing or working on this UPS system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not install the UPS system until all construction work has been completed and the installation room has been cleaned. If additional construction work is needed in the installation room after the UPS has been installed, turn off the UPS and cover the UPS with the protective packaging bag the UPS was delivered in. Failure to follow these instructions will result in death or serious injury. 6 990-91111F-001 Important Safety Instructions -- SAVE THESE INSTRUCTIONS UPS for External Batteries DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · The product must be installed according to the specifications and requirements as defined by Schneider Electric. It concerns in particular the external and internal protections (upstream breakers, battery breakers, cabling, etc.) and environmental requirements. No responsibility is assumed by Schneider Electric if these requirements are not respected. · After the UPS system has been electrically wired, do not start up the system. Start-up must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The UPS system must be installed according to local and national regulations. Install the UPS according to: · IEC 60364 (including 60364-4-41 protection against electric shock, 603644-42 protection against thermal effect, and 60364-4-43 protection against overcurrent), or · NEC NFPA 70, or · Canadian Electrical Code (C22.1, Part 1) depending on which one of the standards apply in your local area. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Install the UPS system in a temperature controlled indoor environment free of conductive contaminants and humidity. · Install the UPS system on a non-flammable, level and solid surface (e.g. concrete) that can support the weight of the system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The UPS is not designed for and must therefore not be installed in the following unusual operating environments: · Damaging fumes · Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant heat from other sources · Moisture, abrasive dust, steam or in an excessively damp environment · Fungus, insects, vermin · Salt-laden air or contaminated cooling refrigerant · Pollution degree higher than 2 according to IEC 60664-1 · Exposure to abnormal vibrations, shocks, and tilting · Exposure to direct sunlight, heat sources, or strong electromagnetic fields Failure to follow these instructions will result in death or serious injury. 990-91111F-001 7 UPS for External Batteries Important Safety Instructions -- SAVE THESE INSTRUCTIONS DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or cut holes for cables or conduits with the gland plates installed and do not drill or cut holes in close proximity to the UPS. Failure to follow these instructions will result in death or serious injury. WARNING HAZARD OF ARC FLASH Do not make mechanical changes to the product (including removal of cabinet parts or drilling/cutting of holes) that are not described in the installation manual. Failure to follow these instructions can result in death, serious injury, or equipment damage. NOTICE RISK OF OVERHEATING Respect the space requirements around the UPS system and do not cover the UPS ventilation openings when the UPS system is in operation. Failure to follow these instructions can result in equipment damage. NOTICE RISK OF EQUIPMENT DAMAGE Do not connect the UPS output to regenerative load systems including photovoltaic systems and speed drives. Failure to follow these instructions can result in equipment damage. 8 990-91111F-001 Important Safety Instructions -- SAVE THESE INSTRUCTIONS Electrical Safety UPS for External Batteries DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH · Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. · Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. · Turn off all power supplying the UPS system before working on or inside the equipment. · Before working on the UPS system, check for hazardous voltage between all terminals including the protective earth. · The UPS contains an internal energy source. Hazardous voltage can be present even when disconnected from the utility/mains supply. Before installing or servicing the UPS system, ensure that the units are OFF and that utility/mains and batteries are disconnected. Wait five minutes before opening the UPS to allow the capacitors to discharge. · A disconnection device (e.g. disconnection circuit breaker or switch) must be installed to enable isolation of the system from upstream power sources in accordance with local regulations. This disconnection device must be easily accessible and visible. · The UPS must be properly earthed/grounded and due to a high leakage current, the earthing/grounding conductor must be connected first. Failure to follow these instructions will result in death or serious injury. Battery Safety DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Battery circuit breakers must be installed according to the specifications and requirements as defined by Schneider Electric. · Servicing of batteries must only be performed or supervised by qualified personnel knowledgeable of batteries and the required precautions. Keep unqualified personnel away from batteries. · Disconnect charging source prior to connecting or disconnecting battery terminals. · Do not dispose of batteries in a fire as they can explode. · Do not open, alter, or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Failure to follow these instructions will result in death or serious injury. 990-91111F-001 9 UPS for External Batteries Important Safety Instructions -- SAVE THESE INSTRUCTIONS DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Batteries can present a risk of electric shock and high short-circuit current. The following precautions must be observed when working on batteries · Remove watches, rings, or other metal objects. · Use tools with insulated handles. · Wear protective glasses, gloves and boots. · Do not lay tools or metal parts on top of batteries. · Disconnect the charging source prior to connecting or disconnecting battery terminals. · Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electric shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit). Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH When replacing batteries, always replace with the same type and number of batteries or battery packs. Failure to follow these instructions will result in death or serious injury. CAUTION RISK OF EQUIPMENT DAMAGE · Mount the batteries in the UPS system, but do not connect the batteries until the UPS system is ready to be powered up. The time duration from battery connection until the UPS system is powered up must not exceed 72 hours or 3 days. · Batteries must not be stored more than six months due to the requirement of recharging. If the UPS system remains de-energized for a long period, we recommend that you energize the UPS system for a period of 24 hours at least once every month. This charges the batteries, thus avoiding irreversible damage. Failure to follow these instructions can result in injury or equipment damage. 10 990-91111F-001 Important Safety Instructions -- SAVE THESE INSTRUCTIONS Symbols Used Earthing/ground symbol. UPS for External Batteries Protective earth (PE)/equipment grounding conductor (EGC) symbol. Direct current (DC) symbol. Alternating current (AC) symbol. Positive polarity symbol. It is used to identify the positive terminal(s) of equipment which is used with, or generates direct current. Negative polarity symbol. It is used to identify the negative terminal(s) of equipment which is used with, or generates direct current. Battery symbol. Static switch symbol. It is used to indicate switches that are designed to connect or disconnect the load to or from the supply respectively without the existence of moving parts. AC/DC converter (rectifier) symbol. It is used to identify an AC/DC converter (rectifier) and, in case of plug-in devices, to identify the relevant receptacles. DC/AC converter (inverter) symbol. It is used to identify an DC/AC converter (inverter) and, in case of plug-in devices, to identify the relevant receptacles. 990-91111F-001 11 UPS for External Batteries Important Safety Instructions -- SAVE THESE INSTRUCTIONS Fuse symbol. It is used to identify fuse boxes or their locations. Transformer symbol. Input symbol. It is used to identify an input terminal when it is necessary to distinguish between inputs and outputs. Output symbol. It is used to identify an output terminal when it is necessary to distinguish between inputs and outputs. Switch disconnector symbol. It is used to identify the disconnecting device in the form of switch that protects the equipment from short circuit or heavy load current. It opens the circuits once the current flow crosses its maximum limit. Circuit breaker symbol. It is used to identify the disconnecting device in the form of circuit breaker that protects the equipment from short circuit or heavy load current. It opens the circuits once the current flow crosses its maximum limit. Disconnection device symbol. It is used to identify the disconnecting device in the form of circuit breaker or switch that protects the equipment from short circuit or heavy load current. It opens the circuits once the current flow crosses its maximum limit. Neutral symbol. It is used to identify the neutral conductors or their locations. Phase conductor symbol. It is used to identify the phase conductors or their locations. 12 990-91111F-001 Important Safety Instructions -- SAVE THESE INSTRUCTIONS ENERGY STAR Qualification UPS for External Batteries Select models are ENERGY STAR® qualified. For more information on your specific model go to www.se. com. 990-91111F-001 13 UPS for External Batteries Specifications Specifications Specifications for 400 V Systems Input Specifications 400 V UPS rating Voltage (V) Connections Input voltage range (V) Frequency range (Hz) Nominal input current (A) Maximum input current (A) Input current limitation (A) Input power factor Total harmonic distortion (THDI) Maximum short circuit rating Protection Ramp-in 20 kW 30 kW 40 kW 50 kW 380/400/415 4-wire (L1, L2, L3, N, PE) WYE (single mains) 3-wire (L1, L2, L3, PE) WYE (dual mains)1 2 380 V: 331-437 400 V: 340-460 415 V: 353-477 40-70 60 kW 80 kW 100 kW 120 kW 150 kW 32/30/29 47/45/43 63/60/58 38/36/35 57/54/52 76/72/69 39/37/36 59/56/54 78/74/72 0.99 for load greater than 50% 0.95 for load greater than 25% <5% at 100% load <3% at 100% load 65 kA RMS 79/75/72 91/90/87 91/91/90 95/90/87 114/108/ 104 117/111/ 107 126/120/ 116 151/144/ 139 156/148/ 143 158/150/ 144 182/180/ 173 182/182/ 179 189/180/ 173 227/216/ 208 234/222/ 214 237/225/ 217 273/270/ 260 273/273/ 268 Built-in backfeed protection and fuses Programmable and adaptive 1-40 seconds NOTE: For a UPS with N+1 power module, the input power factor is 0.99 at 100% load and the total harmonic distortion (THDI) is <6% at full linear load (symmetrical). 1. TN and TT power distribution systems are supported. Corner (line) grounding is not supported. 2. Only for dual mains system with upstream 4-pole breakers: Install an N connection with the input cables (L1, L2, L3, N, PE). Refer to earthing schematics for TN-S dual mains 4-pole circuit breaker. 14 990-91111F-001 Specifications UPS for External Batteries Bypass Specifications 400 V UPS rating Voltage (V) Connections Bypass voltage range (V) Frequency range (Hz) Nominal bypass current (A) Nominal neutral current (A)3 Maximum short circuit rating Protection 20 kW 30 kW 40 kW 50 kW 60 kW 380/400/415 4-wire (L1, L2, L3, N, PE) WYE 380 V: 342-418 400 V: 360-440 415 V: 374-457 50/60 ± 1, 50/60 ± 3, 50/60 ± 10 (user selectable) 80 kW 100 kW 120 kW 150 kW 31/29/28 46/44/42 53/50/48 79/75/72 65 kA RMS 61/58/56 105/100/ 96 77/73/70 131/125/ 120 92/87/84 158/150/ 144 123/117/ 112 210/200/ 193 153/146/ 141 263/250/ 241 184/175/ 169 263/250/ 241 230/219/ 211 263/250/ 241 Built-in backfeed protection and fuses Internal fuse specifications: Rated 400 A, prearcing 33 kA2s Built-in backfeed protection and fuses Internal fuse specifications: Rated 550 A, prearcing 52 kA2s 3. Harmonic currents in neutral are only considered to be 1.73 x nominal up till 100 kW. Above 100 kW only resistive load is considered. 990-91111F-001 15 UPS for External Batteries Specifications Output Specifications 400 V UPS rating 20 kW 30 kW 40 kW 50 kW 60 kW 80 kW Voltage (V) 380/400/415 Connections 4-wire (L1, L2, L3, N, PE) Output voltage regulation Symmetrical load ± 1% Asymmetrical load ± 3% Overload capacity 150% for 1 minute (in normal operation) 125% for 10 minutes (in normal operation) 125% for 1 minute (in battery operation) 110% continuous (bypass operation) 1000% for 100 milliseconds (bypass operation) Dynamic load response ± 5% after 2 milliseconds ± 1% after 50 milliseconds Output power factor 1 Nominal output current (A) 30/29/28 46/43/42 61/58/56 76/72/70 91/87/83 122/115/ 111 Frequency regulation 50/60 Hz bypass synchronized 50/60 Hz ± 0.1% free-running (Hz) Synchronized slew rate (Hz/sec) Programmable to 0.25, 0.5, 1, 2, 4, 6 Output performance classification (according to IEC 62040-3:2021) VFI-SS-11 Total harmonic distortion (THDU) <1% for linear load <5% for non-linear load Load crest factor Load power factor 2.5 From 0.7 leading to 0.7 lagging without any derating 100 kW 152/144/ 139 120 kW 182/173/ 167 150 kW 228/217/ 209 16 990-91111F-001 Specifications UPS for External Batteries Battery Specifications 400 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Protection of the energy storage device: An overcurrent protective device must be located in close proximity to the energy storage device. · Trip delay must be set to zero on all battery breakers. Failure to follow these instructions will result in death or serious injury. UPS rating Charging power in % of output power at 040% load4 Charging power in % of output power at 100% load Maximum charging power (at 0-40% load) (kW)4 Maximum charging power (at 100% load) (kW) Nominal battery voltage (VDC) Nominal float voltage (VDC) Maximum boost voltage (VDC) Temperature compensation (per cell) End of discharge voltage (full load) (VDC) Battery current at full load and nominal battery voltage (A)6 Battery current at full load and minimum battery voltage (A)6 Ripple current Battery test Maximum short circuit rating 20 kW 80% 30 kW 40 kW 50 kW 20%5 16 24 32 40 4 6 8 10 32-48 blocks: 384-576 32-48 blocks: 436-654 720 for 48 blocks 40-48 blocks: 480-576 40-48 blocks: 545-654 -3.3mV/°C, for T 25 °C 0mV/°C, for T < 25 °C 32 blocks: 307 54 81 40 blocks: 384 109 109 68 102 136 136 < 5% C20 (5 minute runtime) Manual/automatic (selectable) 10 kA 60 kW 80 kW 48 64 12 16 35-48 blocks: 420-576 35-48 blocks: 477-654 32-48 blocks: 384-576 32-48 blocks: 436-654 35 blocks: 32 336 blocks: 307 130 174 163 217 100 kW 120 kW 150 kW 80 96 120 20 24 30 40-48 blocks: 480-576 40-48 blocks: 545-654 40 blocks: 384 217 260 326 271 326 407 4. Values based on 48 blocks. 5. At 380 V only 15% for 50 kW, 100 kW, and 150 kW. 6. Values based on 20-40 kW: 32 blocks; 50-150 kW: 40 blocks. 990-91111F-001 17 UPS for External Batteries Specifications Recommended Cable Sizes 400 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 150 mm2. Failure to follow these instructions will result in death or serious injury. Copper UPS rating Input phases (mm2) Input PE (mm2) Bypass/output phases (mm2) Bypass PE/output PE (mm2) Neutral (mm2) DC+/DC- (mm2)7 DC PE (mm2) 20 kW 6 6 6 6 10 10 10 Aluminum UPS rating Input phases (mm2) Input PE (mm2) Bypass/output phases (mm2) 20 kW 6 6 6 The maximum number of cable connections per busbar: Two on input/output/ bypass busbars; Four on DC+/DC- busbars; Six on N/PE busbars. NOTE: Overcurrent protection is to be provided by others. Cable sizes in this manual are based on table B.52.3 and table B.52.5 of IEC 60364-5-52 with the following assertions: · 90 °C conductors · An ambient temperature of 30 °C · Use of copper or aluminum conductors · Installation method C PE cable size is based on table 54.2 of IEC 60364-4-54. If the ambient temperature is greater than 30 °C, larger conductors are to be selected in accordance with the correction factors of the IEC. NOTE: Recommended cable sizes and maximum allowable cable size may vary for the auxiliary products. Not all auxiliary products support aluminum cables. Refer to the installation manual provided with the auxiliary product. NOTE: The DC cable sizes given here are recommendations Always follow the specific instructions in the battery solution documentation for DC cable sizes and DC PE cable sizes and ensure that the DC cable sizes match the battery breaker rating. NOTE: Neutral conductor is sized to handle 1.73 times phase current in case of high harmonic content from non-linear loads. If non or less harmonic currents are expected, neutral conductor can be sized accordingly but not less than the phase conductor. 30 kW 10 10 6 6 16 25 16 40 kW 16 16 10 10 25 35 16 50 kW 25 16 16 16 35 35 16 60 kW 35 16 25 16 50 50 25 80 kW 50 25 35 16 70 70 35 100 kW 70 35 50 120 kW 95 50 70 150 kW 120 70 95 25 35 50 95 95 95 95 95 120 50 50 70 30 kW 16 16 10 40 kW 25 16 16 50 kW 35 16 25 60 kW 50 25 35 80 kW 70 35 50 100 kW 95 50 70 120 kW 120 70 95 150 kW 150 95 150 7. 20-40 kW: DC cables are sized according to 32 blocks. 50-100 kW: DC cables are sized according to 40 blocks. 18 990-91111F-001 Specifications Aluminum (Continued) UPS rating Bypass PE/output PE (mm2) Neutral (mm2) DC+/DC- (mm2)8 DC PE (mm2) 20 kW 6 10 16 16 30 kW 10 25 35 16 40 kW 16 35 50 25 50 kW 16 50 50 25 60 kW 16 70 70 35 80 kW 25 95 95 50 UPS for External Batteries 100 kW 35 120 kW 50 150 kW 95 2 x 70 2 x 70 70 2 x 70 2 x 70 70 2 x 70 2 x 95 95 8. 20-40 kW: DC cables are sized according to 32 blocks. 50-100 kW: DC cables are sized according to 40 blocks. 990-91111F-001 19 UPS for External Batteries Specifications Recommended Upstream Protection 400 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · For parallel systems, instantaneous override (Ii) values must not be set higher than 1250 A. Place the label 885-92556 adjacent to the upstream circuit breaker to inform about the hazard. · For UPS rating 20-120 kW: In parallel systems with three or more UPSs, a circuit breaker must be installed on the output of each UPS. The unit output breaker (UOB) instantaneous override (Ii) values must not be set higher than 1250 A. · For UPS rating 150 kW: In parallel systems with two or more UPSs, a circuit breaker must be installed on the output of each UPS. The unit output breaker (UOB) instantaneous override (Ii) values must not be set higher than 1250 A. Failure to follow these instructions will result in death or serious injury. UPS rating Breaker type In Ir Im 20 kW Input NSX100H TM40D (LV429674) 40 40 500 (fixed) NOTE: For local directives which require 4-pole circuit breakers: If neutral conductor is expected to carry a high current, due to line-neutral non-linear load, the circuit breaker must be rated according to expected neutral current. NOTE: For the scalable UPS (GVSUPS50K150HS), always size the upstream protection for a UPS rating of 150 kW. Bypass NSX100H TM32D (LV429675) 32 32 400 (fixed) 30 kW Input NSX100H TM63D (LV429672) 63 63 500 (fixed) Bypass NSX100H TM50D (LV429673) 50 50 500 (fixed) 40 kW Input NSX100H TM80D (LV429671) 80 80 640 (fixed) Bypass NSX100H TM63D (LV429672) 63 63 500 (fixed) UPS rating Breaker type In Ir Im 50 kW 60 kW 80 kW 100 kW Input Bypass Input Bypass Input Bypass Input Bypass NSX100H NSX100H NSX160H NSX100H NSX160H NSX160H NSX250H NSX160H TM100D TM80D TM125D TM100D TM160D TM125D TM200D TM160D (LV429670) (LV429671) (LV430671) (LV429670) (LV430670) (LV430671) (LV431671) (LV430670) 100 80 125 100 160 125 200 160 100 80 125 100 160 125 200 160 800 (fixed) 640 (fixed) 1250 (fixed) 800 (fixed) 1250 (fixed) 1250 (fixed) 6 x In 1250 (fixed) UPS rating Breaker type In/Io Ir tr Im/Isd tsd li 120 kW Input NSX250H TM250D (LV431670) 250 250 -- 5 x In -- -- Bypass NSX250H TM200 (LV431671) 200 200 -- 6 x In -- -- 150 kW Input NSX400H Mic.L5 (LV432701) 280 -- 0.5 10 0 4.5 x In Bypass NSX250H TM250 (LV431670) 250 250 -- 5 x In -- -- 20 990-91111F-001 Specifications UPS for External Batteries Specifications for 480 V Systems The supply for input and bypass must be solid-grounded WYE transformers. Delta input supply for either input or bypass is not permitted. The UPS system must be installed as a separately derived system. Leakage currents will occur in the bonding jumper and the technical/system earth. Input Specifications 480 V UPS rating Connections Input voltage range (V) Frequency range (Hz) Nominal input current (A) Maximum input current (A) Input current limitation (A) Input power factor Total harmonic distortion (THDI) Maximum short circuit rating Protection Ramp-in 20 kW 30 kW 40 kW 50 kW 60 kW 80 kW 3-wire (L1, L2, L3, G) WYE or 4-wire (L1, L2, L3, N, G) WYE (single mains) 3-wire (L1, L2, L3, G) WYE (dual mains) 408-552 100 kW 40-70 25 37 50 62 74 99 124 30 45 60 74 89 119 149 31 47 62 77 93 124 154 0.99 for load greater than 50% 0.95 for load greater than 25% <5% at 100% load 65 kA RMS <3% at 100% load <5% at 100% load <3% at 100% load Built-in backfeed protection and fuses Programmable and adaptive 1-40 seconds 120 kW 149 179 185 <5% at 100% load 150 kW 186 223 231 <3% at 100% load NOTE: For a UPS with N+1 power module, the input power factor is 0.99 at 100% load and the total harmonic distortion (THDI) is <6% at full linear load (symmetrical). 990-91111F-001 21 UPS for External Batteries Bypass Specifications 480 V UPS rating Connections Bypass voltage range (V) Frequency range (Hz) Nominal bypass current (A) Nominal neutral current (A)9 Maximum short circuit rating Protection 20 kW 30 kW 40 kW 50 kW 60 kW 3-wire (L1, L2, L3, G) WYE or 4-wire (L1, L2, L3, N, G) WYE 432-528 80 kW 50/60 ± 1, 50/60 ± 3, 50/60 ± 10 (user selectable) 24 36 49 61 73 97 42 62 83 104 125 166 65 kA RMS Built-in backfeed protection and fuses Internal fuse specifications: Rated 400 A, prearcing 33 kA2s Specifications 100 kW 120 kW 150 kW 121 146 182 208 208 208 Built-in backfeed protection and fuses Internal fuse specifications: Rated 550 A, prearcing 52 kA2s 9. Harmonic currents in neutral are only considered to be 1.73 x nominal up till 100 kW. Above 100 kW only resistive load is considered. 22 990-91111F-001 Specifications UPS for External Batteries Output Specifications 480 V NOTE: The number of output connections must match the number of input wires in a single mains system or bypass wires in a dual mains system. UPS rating 20 kW 30 kW 40 kW 50 kW 60 kW 80 kW Connections 3-wire (L1, L2, L3, G, GEC10) or 4-wire (L1, L2, L3, N, G) Output voltage regulation Symmetrical load ± 1% Asymmetrical load ± 3% Overload capacity 150% for 1 minute (in normal operation) 125% for 10 minutes (in normal operation) 125% for 1 minute (in battery operation) 125% continuous (bypass operation) 1000% for 100 milliseconds (bypass operation) Dynamic load response ± 5% after 2 milliseconds ± 1% after 50 milliseconds Output power factor 1 Nominal output 24 36 48 60 72 96 current (A) Frequency regulation 50/60 Hz bypass synchronized 50/60 Hz ± 0.1% free-running (Hz) Synchronized slew rate (Hz/sec) Programmable to 0.25, 0.5, 1, 2, 4, 6 Total harmonic distortion (THDU) <1% for linear load <5% for non-linear load Load crest factor Load power factor 2.5 From 0.7 leading to 0.7 lagging without any derating 100 kW 120 kW 150 kW 120 144 180 10. Per NEC 250.30. 990-91111F-001 23 UPS for External Batteries Specifications Battery Specifications 480 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Protection of the energy storage device: An overcurrent protective device must be located in close proximity to the energy storage device. · Trip delay must be set to zero on all battery breakers. Failure to follow these instructions will result in death or serious injury. UPS rating Charging power in % of output power at 040% load11 Charging power in % of output power at 100% load Maximum charging power (at 0-40% load) (kW)11 Maximum charging power (at 100% load) (kW) Nominal battery voltage (VDC) Nominal float voltage (VDC) Maximum boost voltage (VDC) Temperature compensation (per cell) End of discharge voltage (full load) (VDC) Battery current at full load and nominal battery voltage (A)12 Battery current at full load and minimum battery voltage (A)12 Ripple current Battery test Maximum short circuit rating 20 kW 80% 30 kW 40 kW 50 kW 20% 16 24 32 40 4 6 8 10 32-48 blocks: 384-576 32-48 blocks: 436-654 720 for 48 blocks 40-48 blocks: 480-576 40-48 blocks: 545-654 -3.3mV/°C, for T 25 °C 0mV/°C, for T < 25 °C 32 blocks: 307 54 81 40 blocks: 384 108 108 68 101 135 135 < 5% C20 (5 minute runtime) Manual/automatic (selectable) 10 kA 60 kW 80 kW 48 64 12 16 35-48 blocks: 420-576 35-48 blocks: 477-654 32-48 blocks: 384-576 32-48 blocks: 436-654 35 blocks: 32 336 blocks: 307 130 173 162 216 100 kW 120 kW 150 kW 80 96 120 20 24 30 40-48 blocks: 480-576 40-48 blocks: 545-654 40 blocks: 384 216 260 326 270 325 406 11. Values based on 48 blocks. 12. Values based on 20-40 kW: 32 blocks; 50-150 kW: 40 blocks. 24 990-91111F-001 Specifications UPS for External Batteries Recommended Cable Sizes 480 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 300 kcmil. Failure to follow these instructions will result in death or serious injury. Copper UPS rating Input phases (AWG/ kcmil) Input EGC (AWG/ kcmil) Bypass/output phases (AWG/kcmil) Bypass EGC/output EGC (AWG/kcmil) Neutral (AWG/kcmil) DC+/DC-(AWG/ kcmil)13 DC EGC (AWG/ kcmil) 20 kW 8 10 10 10 6 4 8 The maximum number of cable connections per busbar: Two on input/output/ bypass busbars; Four on DC+/DC- busbars; Six on N/G busbars. NOTE: Overcurrent protection is to be provided by others. Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions: · 90 °C (194 °F) conductors (75 °C (167 °F) termination) · An ambient temperature of 30 °C (86 °F) · Use of copper or aluminum conductors If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC. Equipment grounding conductors (EGC) are sized in accordance with NEC Article 250.122 and Table 250.122. NOTE: Recommended cable sizes and maximum allowable cable size may vary for the auxiliary products. Not all auxiliary products support aluminum cables. Refer to the installation manual provided with the auxiliary product. NOTE: The DC cable sizes given here are recommendations Always follow the specific instructions in the battery solution documentation for DC cable sizes and DC EGC cable sizes and ensure that the DC cable sizes match the battery breaker rating. NOTE: Neutral conductor is sized to handle 1.73 times phase current in case of high harmonic content from non-linear loads. If non or less harmonic currents are expected, neutral conductor can be sized accordingly but not less than the phase conductor. 30 kW 6 8 8 10 4 2 6 40 kW 4 8 6 8 2 1/0 6 50 kW 3 6 4 8 1/0 1/0 6 60 kW 1 6 3 8 2/0 2/0 6 80 kW 2/0 6 1 6 4/0 4/0 4 100 kW 3/0 120 kW 4/0 150 kW 300 4 4 4 2/0 3/0 4/0 6 6 4 2 x 1/0 2 x 1/0 2 x 1/0 2 x 3/0 2 x 1/0 2 x 4/0 4 3 2 13. 20-40 kW: DC cables are sized according to 32 blocks. 50-100 kW: DC cables are sized according to 40 blocks. 990-91111F-001 25 UPS for External Batteries Specifications Aluminum UPS rating Input phases (AWG/ kcmil) Input EGC (AWG/ kcmil) Bypass/output phases (AWG/kcmil) Bypass EGC/output EGC (AWG/kcmil) Neutral (AWG/kcmil) DC+/DC-(AWG/ kcmil)14 DC EGC (AWG/ kcmil) 20 kW 6 6 6 6 4 3 6 30 kW 4 6 6 6 2 1/0 4 40 kW 2 6 4 6 1/0 2/0 4 50 kW 1 4 2 6 2/0 2/0 4 60 kW 1/0 4 1 6 4/0 4/0 4 80 kW 3/0 4 2/0 4 2 x 1/0 2 x 1/0 2 100 kW 250 120 kW 300 150 kW 2 x 3/0 2 2 2x2 3/0 250 300 4 4 2 2 x 2/0 2 x 3/0 2 x 250 1 2 x 2/0 2 x 250 2 2x1 2 x 1/0 NOTE: For DC EGC aluminum cables used in parallel conduits, EGC must be full-sized in order to prevent overload or burnout of cables. NOTE: 80% rated circuit breakers for UIB, UOB, MBB, SSIB. 14. 20-40 kW: DC cables are sized according to 32 blocks. 50-100 kW: DC cables are sized according to 40 blocks. 26 990-91111F-001 Specifications UPS for External Batteries Recommended Upstream Protection 480 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · For parallel systems, instantaneous override (Ii) values must not be set higher than 1250 A. Place the label 885-92556 adjacent to the upstream circuit breaker to inform about the hazard. · For UPS rating 20-120 kW: In parallel systems with three or more UPSs, a circuit breaker must be installed on the output of each UPS. The unit output breaker (UOB) instantaneous override (Ii) values must not be set higher than 1250 A. · For UPS rating 150 kW: In parallel systems with two or more UPSs, a circuit breaker must be installed on the output of each UPS. The unit output breaker (UOB) instantaneous override (Ii) values must not be set higher than 1250 A. Failure to follow these instructions will result in death or serious injury. CAUTION HAZARD OF FIRE · Connect only to a circuit with the below specifications. · Connect to a circuit provided with a 250 A branch circuit overcurrent protection maximum in accordance with the National Electrical Code, ANSI/ NFPA70, and the Canadian Electrical Code, Part I, C22.1. Failure to follow these instructions can result in injury or equipment damage. UPS rating Breaker type Ir tr @ 6 Ir li (x In) NOTE: For the scalable UPS (GVSUPS50K150GS), always size the upstream protection for a UPS rating of 150 kW. NOTE: Overcurrent protection is to be provided by others and marked with its function. 20 kW Input Bypass HJF36100U31X 40 35 0.5-16 8 30 kW Input 60 Bypass 40 kW Input 50 80 Bypass 50 kW Input 70 100 Bypass 80 UPS rating Breaker type Ir tr @ 6 Ir li (x In) 60 kW 80 kW Input Bypass Input HJF36150U31X HJF36100U31X JJF36250U31X 125 100 175 0.5-16 10 12 5 Bypass HJF36150U31X 125 100 kW Input JJF36250U31X 200 8 5 Bypass 175 UPS rating Breaker type Ir tr @ 6 Ir li (x In) 120 kW Input JJF36250CU31X 250 0.5-16 5 Bypass JJF36250CU31X 200 150 kW Input LJF36400U31X 300 3 Bypass JJF36250U31X 250 5 990-91111F-001 27 UPS for External Batteries Specifications Specifications for 208 V Systems Input Specifications 208 V UPS rating Voltage (V) Connections Input voltage range (V) Frequency range (Hz) Nominal input current (A) Maximum input current (A) Input current limitation (A) Input power factor Total harmonic distortion (THDI) Maximum short circuit rating Protection Ramp-in 10 kW 15 kW 20 kW 25 kW 200/208/220 4-wire (L1, L2, L3, N, G) WYE (single mains) 3-wire (L1, L2, L3, G) WYE (dual mains) 200 V: 170-230 208 V: 177-239 220 V: 187-253 40-70 30 kW 40 kW 50 kW 60 kW 75 kW 31/30/28 47/45/42 62/60/56 37/36/34 56/54/51 74/72/68 39/37/35 58/55/52 77/74/70 0.99 for load greater than 50% 0.95 for load greater than 25% <5% at 100% load <3% at 100% load 65 kA RMS 78/75/71 91/90/85 91/91/87 93/90/85 112/107/ 102 115/110/ 104 124/119/ 113 149/143/ 135 153/147/ 139 155/149/ 141 182/179/ 169 182/182/ 174 186/179/ 169 223/215/ 203 229/220/ 208 <5% at 100% load 233/224/ 212 273/269/ 254 273/273/ 260 <3% at 100% load Built-in backfeed protection and fuses Programmable and adaptive 1-40 seconds NOTE: For a UPS with N+1 power module, the input power factor is 0.99 at 100% load and the total harmonic distortion (THDI) is <6% at full linear load (symmetrical). 28 990-91111F-001 Specifications UPS for External Batteries Bypass Specifications 208 V UPS rating Voltage (V) Connections Bypass voltage range (V) Frequency range (Hz) Nominal bypass current (A) Nominal neutral current (A)15 Maximum short circuit rating Protection 10 kW 15 kW 20 kW 25 kW 30 kW 200/208/220 4-wire (L1, L2, L3, N, G) WYE 200 V: 180-220 208 V: 187-229 220 V: 198-242 50/60 ± 1, 50/60 ± 3, 50/60 ± 10 (user selectable) 40 kW 50 kW 60 kW 75 kW 29/28/27 44/42/40 50/48/45 75/72/68 65 kA RMS 58/56/53 73/70/66 100/96/91 125/120/ 114 87/84/80 150/144/ 136 117/112/ 106 200/192/ 182 146/140/ 133 250/240/ 227 175/168/ 159 250/240/ 227 219/210/ 199 250/240/ 227 Built-in backfeed protection and fuses Internal fuse specifications: Rated 400 A, prearcing 33 kA2s Built-in backfeed protection and fuses Internal fuse specifications: Rated 550 A, prearcing 52 kA2s 15. Harmonic currents in neutral are only considered to be 1.73 x nominal up till 50 kW. Above 50 kW only resistive load is considered. 990-91111F-001 29 UPS for External Batteries Specifications Output Specifications 208 V UPS rating 10 kW 15 kW 20 kW 25 kW 30 kW 40 kW Voltage (V) 200/208/220 Connections 4-wire (L1, L2, L3, N, G) Output voltage regulation Symmetrical load ± 1% Asymmetrical load ± 3% Overload capacity 150% for 1 minute (in normal operation) 125% for 10 minutes (in normal operation) 125% for 1 minute (in battery operation) 125% continuous (bypass operation) 1000% for 100 milliseconds (bypass operation) Dynamic load response ± 5% after 2 milliseconds ± 1% after 50 milliseconds Output power factor 1 Nominal output current (A) 29/28/26 43/42/39 58/56/52 73/70/66 87/83/79 115/111/ 105 Frequency regulation 50/60 Hz bypass synchronized 50/60 Hz ± 0.1% free-running (Hz) Synchronized slew rate (Hz/sec) Programmable to 0.25, 0.5, 1, 2, 4, 6 Total harmonic distortion (THDU) <2% Load crest factor Load power factor 2.5 From 0.7 leading to 0.7 lagging without any derating 50 kW 144/139/ 131 60 kW 173/167/ 157 75 kW 217/208/ 197 30 990-91111F-001 Specifications UPS for External Batteries Battery Specifications 208 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · Protection of the energy storage device: An overcurrent protective device must be located in close proximity to the energy storage device. · Trip delay must be set to zero on all battery breakers. Failure to follow these instructions will result in death or serious injury. UPS rating Charging power in % of output power at 040% load16 Charging power in % of output power at 100% load Maximum charging power (at 0-40% load) (kW)16 Maximum charging power (at 100% load) (kW) Nominal battery voltage (VDC) Nominal float voltage (VDC) Maximum boost voltage (VDC) Temperature compensation (per cell) End of discharge voltage (full load) (VDC) Battery current at full load and nominal battery voltage (A)17 Battery current at full load and minimum battery voltage (A)17 Ripple current Battery test Maximum short circuit rating 10 kW 80% 15 kW 20 kW 25 kW 20% 8 12 16 20 2 3 4 5 32-40 blocks: 384-480 32-40 blocks: 436-545 600 for 40 blocks -3.3mV/°C, for T 25 °C 0mV/°C, for T < 25 °C 32 blocks: 307 27 41 55 68 34 51 68 85 < 5% C20 (5 minute runtime) Manual/automatic (selectable) 10 kA 30 kW 24 6 82 102 40 kW 32 8 109 136 50 kW 40 10 136 170 60 kW 48 12 164 204 75 kW 60 15 205 254 16. Values based on 40 blocks. 17. Values based on 32 blocks. 990-91111F-001 31 UPS for External Batteries Specifications Recommended Cable Sizes 208 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. The maximum allowable cable size is 300 kcmil. Failure to follow these instructions will result in death or serious injury. Copper UPS rating Input phases (AWG/ kcmil) Input EGC (AWG/ kcmil) Bypass/output phases (AWG/kcmil) Bypass EGC/output EGC (AWG/kcmil) Neutral (AWG/kcmil) DC+/DC-(AWG/ kcmil) DC EGC (AWG/ kcmil) 10 kW 8 10 8 10 6 10 10 Aluminum UPS rating Input phases (AWG/ kcmil) Input EGC (AWG/ kcmil) 10 kW 6 6 The maximum number of cable connections per busbar: Two on input/output/ bypass busbars; Four on DC+/DC- busbars; Six on N/G busbars. NOTE: Overcurrent protection is to be provided by others. Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions: · 90 °C (194 °F) conductors (75 °C (167 °F) termination) · An ambient temperature of 30 °C (86 °F) · Use of copper or aluminum conductors If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC. Equipment grounding conductors (EGC) are sized in accordance with NEC Article 250.122 and Table 250.122. NOTE: Recommended cable sizes and maximum allowable cable size may vary for the auxiliary products. Not all auxiliary products support aluminum cables. Refer to the installation manual provided with the auxiliary product. NOTE: The DC cable sizes given here are recommendations Always follow the specific instructions in the battery solution documentation for DC cable sizes and DC EGC cable sizes and ensure that the DC cable sizes match the battery breaker rating. NOTE: Neutral conductor is sized to handle 1.73 times phase current in case of high harmonic content from non-linear loads. If non or less harmonic currents are expected, neutral conductor can be sized accordingly but not less than the phase conductor. 15 kW 4 8 6 10 3 6 10 20 kW 3 8 4 8 1 4 8 25 kW 2 6 3 8 2/0 4 8 30 kW 1/0 6 2 6 3/0 2 6 40 kW 3/0 6 1/0 6 2 x 1/0 1/0 6 50 kW 4/0 4 3/0 6 2 x 2/0 2/0 6 60 kW 300 4 4/0 4 2 x 2/0 4/0 4 75 kW 2 x 2/0 3 300 4 2 x 2/0 250 4 15 kW 3 6 20 kW 1 6 25 kW 1/0 4 30 kW 3/0 4 40 kW 250 4 50 kW 300 2 60 kW 2 x 3/0 2x2 75 kW 4/0 1 32 990-91111F-001 Specifications UPS for External Batteries Aluminum (Continued) UPS rating Bypass/output phases (AWG/kcmil) Bypass EGC/output EGC (AWG/kcmil) Neutral (AWG/kcmil) DC+/DC-(AWG/ kcmil) DC EGC (AWG/ kcmil) 10 kW 6 6 4 8 6 15 kW 4 6 1 4 6 20 kW 3 6 2/0 3 6 25 kW 1 6 4/0 2 6 30 kW 1/0 4 2 x 1/0 1/0 4 40 kW 3/0 4 2 x 2/0 3/0 4 50 kW 250 4 2 x 4/0 4/0 4 60 kW 300 2 2 x 4/0 250 2 75 kW 2 x 3/0 2 2 x 4/0 2 x 3/0 2 NOTE: For DC EGC aluminum cables used in parallel conduits, EGC must be full-sized in order to prevent overload or burnout of cables. NOTE: 80% rated circuit breakers for UIB, UOB, MBB, SSIB. 990-91111F-001 33 UPS for External Batteries Specifications Recommended Upstream Protection 208 V DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH · For parallel systems, instantaneous override (Ii) values must not be set higher than 1250 A. Place the label 885-92556 adjacent to the upstream circuit breaker to inform about the hazard. · For UPS rating 10-60 kW: In parallel systems with three or more UPSs, a circuit breaker must be installed on the output of each UPS. The unit output breaker (UOB) instantaneous override (Ii) values must not be set higher than 1250 A. · For UPS rating 75 kW: In parallel systems with two or more UPSs, a circuit breaker must be installed on the output of each UPS. The unit output breaker (UOB) instantaneous override (Ii) values must not be set higher than 1250 A. Failure to follow these instructions will result in death or serious injury. CAUTION HAZARD OF FIRE · Connect only to a circuit with the below specifications. · Connect to a circuit provided with a 250 A branch circuit overcurrent protection maximum in accordance with the National Electrical Code, ANSI/ NFPA70, and the Canadian Electrical Code, Part I, C22.1. Failure to follow these instructions can result in injury or equipment damage. UPS rating Breaker type Ir tr @ 6 Ir li (x In) NOTE: For the scalable UPS (GVSUPS25K75FS), always size the upstream protection for a UPS rating of 75 kW. NOTE: Overcurrent protection is to be provided by others and marked with its function. 10 kW Input Bypass HJF36100U31X 50 40 0.5-16 8 15 kW Input 80 Bypass 20 kW Input 60 100 Bypass 80 25 kW Input HJF36150U31X 125 Bypass HJF36100U31X 100 5 8 UPS rating Breaker type Ir tr @ 6 Ir li (x In) 30 kW Input Bypass HJF36150U31X 150 110 0.5-16 10 12 40 kW Input JJF36250U31X 200 Bypass HJF36150U31X 150 50 kW Input JJF36250U31X 250 Bypass 200 5 8 5 UPS rating Breaker type Ir 60 kW Input LJF36400U31X 300 Bypass JJF36250U31X 225 75 kW Input LJF36400U31X 350 Bypass LJF36400U31X 300 34 990-91111F-001 Specifications UPS rating tr @ 6 Ir li (x In) 60 kW Input 0.5-16 5 Bypass 75 kW Input 3 UPS for External Batteries Bypass 5 990-91111F-001 35 UPS for External Batteries Recommended Bolt and Lug Sizes Specifications NOTICE RISK OF EQUIPMENT DAMAGE Use only UL approved compression cable lugs. Failure to follow these instructions can result in equipment damage. Copper -- One Hole Cable Lugs Cable size 10 AWG 8 AWG 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil Bolt size M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm Copper -- Two Hole Cable Lugs Cable lug type LCA10-56-L LCA8-56-L LCA6-56-L LCA4-56-L LCA4-56-L LCA2-56-Q LCA1-56-E LCA1/0-56-X LCA2/0-56-X LCA3/0-56-X LCA4/0-56-X LCA250-56-X LCA300-56-X Crimping tool NA CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 Die NA CD-720-1 Red P21 CD-720-1 Blue P24 CD-720-1 Gray P29 CD-720-1 Gray P29 CD-720-1 Brown P33 CD-720-2 Green P37 CD-720-2 Pink P42 CD-720-2 Black P45 CD-720-2 Orange P50 CD-720-3 Purple P54 CD-720-3 Yellow P62 CD-720-4 White P66 Cable size 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil Bolt size M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm Aluminum -- One Hole Cable Lugs Cable lug type LCC6-12-L LCC4-12-L LCC2-12-Q LCC1-12-E LCC1/0-12-X LCC2/0-12-X LCC3/0-12-X LCC4/0-12-X LCC250-12-X LCC300-12-X Crimping tool CT-930 CT-930 CT-930 CT-930 CT-930 CT-930 CT-930 CT-930 CT-930 CT-930 Die CD-920-6 Blue P24 CD-920-4 Gray P29 CD-920-2 Brown P33 CD-920-1 Green P37 CD-920-1/0 Pink P42 CD-920-2/0 Black P45 CD-920-3/0 Orange P50 CD-920-4/0 Purple P54 CD-920-250 Yellow P62 CD-920-300 White P66 Cable size 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG Bolt size M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm Cable lug type LAA6-56-X LAA4-56-X LAA3-56-X LAA2-56-X LAA1-56-X LAA1/0-56-X Crimping tool CT-720 CT-720 CT-720 CT-720 CT-720 CT-720 Die CD-720-1 Gray P29 CD-720-2 Green P37 CD-720-2 Green P37 CD-720-2 Pink P42 CD-720-2 Gold P45 CD-720-2 Tan P50 36 990-91111F-001 Specifications Aluminum -- One Hole Cable Lugs (Continued) Cable size 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil Bolt size M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm Cable lug type LAA2/0-56-5 LAA3/0-56-5 LAA4/0-56-5 LAA250-56-5 LAA300-56-5 Aluminum -- Two Hole Cable Lugs Cable size 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil Bolt size M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm M8 x 25 mm Cable lug type LAB2/0-12-5 LAB3/0-12-5 LAB4/0-12-5 LAB250-12-2 LAB300-12-2 UPS for External Batteries Crimping tool CT-720 CT-720 CT-720 CT-720 CT-720 Crimping tool CT-720 CT-720 CT-720 CT-720 CT-720 Die CD-720-3 Olive P54 CD-720-3 Ruby P60 CD-720-4 White P66 CD-720-5 Red P71 CD-720-6 Blue P76 Die CD-720-3 Olive P54 CD-720-3 Ruby P60 CD-720-4 White P66 CD-720-5 Red P71 CD-720-6 Blue P76 Torque Specifications Bolt size M4 M5 M6 M8 M10 M12 Torque 1.7 Nm (1.25 lb-ft / 15 lb-in) 2.2 Nm (1.62 lb-ft / 19.5 lb-in) 5 Nm (3.69 lb-ft / 44.3 lb-in) 17.5 Nm (12.91 lb-ft / 154.9 lb-in) 30 Nm (22 lb-ft / 194.7 lb-in) 50 Nm (36.87 lb-ft / 442.5 lb-in) 990-91111F-001 37 UPS for External Batteries Specifications Requirements for a Third Party Battery Solution Battery breaker boxes from Schneider Electric are recommended for the battery interface. Please contact Schneider Electric for more information. Third Party Battery Breaker Requirements DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All selected battery breakers must be equipped with instantaneous trip functionality with an undervoltage release coil or a shunt trip release coil. Failure to follow these instructions will result in death or serious injury. NOTE: There are more factors to consider when selecting a battery breaker than the requirements listed below. Please contact Schneider Electric for more information. Design Requirements for Battery Breaker Battery breaker rated DC voltage > Normal battery voltage Battery breaker rated DC current > Rated discharge battery current DC landings AUX switches for monitoring Short-circuit breaking capability Minimum trip current The normal voltage of the battery configuration is defined as the highest nominal occurring battery voltage. This can be equivalent to the float voltage which may be defined as number of battery blocks x number of cells x cell float voltage. This current is controlled by the UPS and must include maximum discharge current. This will typically be the current at the end of discharge (minimum operation DC voltage or in overload condition or a combination). Two DC landings for DC cables are required. One AUX switch must be installed in each battery breaker and connected to the UPS. The UPS can monitor up to two battery breakers. The short-circuit breaking capability must be higher than the short-circuit DC current of the (largest) battery configuration. The minimum short-circuit current to trip the battery breaker must match the (smallest) battery configuration, to make the breaker trip in case of a short circuit, up to the end of its life time. 38 990-91111F-001 Specifications UPS for External Batteries Guidance for Organizing Battery Cables NOTE: For 3rd party batteries, use only high rate batteries for UPS applications. NOTE: When the battery bank is placed remotely, the organizing of the cables is important to reduce voltage drop and inductance. The distance between the battery bank and the UPS must not exceed 200 m (656 ft). Contact Schneider Electric for installations with a longer distance. NOTE: To minimize the risk of electromagnetic radiation, it is highly recommended to follow the below guidance and to use grounded metallic tray supports. Cable Length <30 m 3175 m 76150 m 151200 m Not recommended Not recommended Not recommended Not recommended Acceptable Not recommended Not recommended Not recommended Recommended Acceptable Acceptable Not recommended Recommended Recommended Recommended Recommended Environment Temperature Relative humidity Elevation Audible noise one meter (three feet) from unit Protection class Color Operating Storage 0 °C to 50 °C (32 °F to 122 °F) with load derating above 40 °C (104 °F).18 -15 °C to 40 °C (5 °F to 104 °F) for systems with batteries. -25 °C to 55 °C (-13 °F to 131 °F) for systems without batteries. 0-95% non-condensing 10-80% non-condensing Designed for operation in 0-3000 m (0- 10000 feet) elevation. Derating required from 1000-3000 m (330010000 feet): Up to 1000 m (3300 feet): 1.000 Up to 1500 m (5000 feet) : 0.975 Up to 2000 m (6600 feet): 0.950 Up to 2500 m (8300 feet): 0.925 Up to 3000 m (10000 feet): 0.900 400 V: 60 dB at 70% load, 68 dB at 100% load 480 V: 57 dB at 70% load, 64 dB at 100% load 208 V: 60 dB at 70% load, 68 dB at 100% load IP21 RAL 9003, gloss level 85% 18. For temperatures between 40 °C (104 °F) and 50 °C (122 °F), derate the load power rating with 2.5% per °C. 990-91111F-001 39 UPS for External Batteries UPS Weights and Dimensions 20-50 kW UPS 400 V 20-50 kW UPS with N+1 power module 400 V 60 kW UPS 400 V 60-100 kW UPS with N +1 power module 400 V 80-100 kW UPS 400 V 120 kW UPS 400 V 150 kW UPS 400 V 20-50 kW UPS 480 V 20-50 kW UPS with N+1 power module 480 V 60 kW UPS 480 V 60-100 kW UPS with N +1 power module 480 V 80-100 kW UPS 480 V 120 kW UPS 480 V 150 kW UPS 480 V 10-25 kW UPS 208 V 10-25 kW UPS with N+1 power module 208 V 30 kW UPS 208 V 30-50 kW UPS with N+1 power module 208 V 40-50 kW UPS 208 V 60 kW UPS 208 V 75 kW UPS 208 V Weight kg (lbs) 206 (454) 250 (551) 238 (525) 290 (639) 250 (551) 278 (613) 290 (639) 206 (454) 250 (551) 238 (525) 290 (639) 250 (551) 278 (613) 290 (639) 206 (454) 250 (551) 238 (525) 290 (639) 250 (551) 278 (613) 290 (639) Height mm (in) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) 1485 (58.46) Width mm (in) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) 521 (20.51) Specifications Depth mm (in) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 847 (33.35) 40 990-91111F-001 Specifications Clearance UPS for External Batteries NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in your local area. NOTE: The required minimum rear clearance is 150 mm (5.91 in). Front View of the UPS 990-91111F-001 41 UPS for External Batteries Single System Overview UIB SSIB IMB UOB BB Single System Overview Unit input breaker Static switch input breaker Internal maintenance breaker Unit output breaker Battery breaker Single System Single Mains Single System Dual Mains 42 990-91111F-001 Parallel System Overview Parallel System Overview UIB SSIB IMB UOB SIB BB MBB UPS for External Batteries Unit input breaker Static switch input breaker Internal maintenance breaker Unit output breaker System isolation breaker Battery breaker External maintenance bypass breaker Simplified 1+1 Parallel System Galaxy VS can support 2 UPSs in a simplified 1+1 parallel system for redundancy with shared unit input breaker UIB and static switch input breaker SSIB. Simplified 1+1 Parallel System Single Mains Simplified 1+1 Parallel System Dual Mains 990-91111F-001 43 UPS for External Batteries Parallel System Overview Parallel System with Individual Unit Input Breaker UIB and Static Switch Input Breaker SSIB Galaxy VS can support up to 4 UPSs in parallel for capacity and up to 3+1 UPSs in parallel for redundancy with individual unit input breaker UIB and static switch input breaker SSIB. NOTE: The internal maintenance breaker IMB can only be used in a simplified 1+1 parallel system. In any other parallel system, an external maintenance bypass breaker MBB must be provided and the internal maintenance breaker IMB* must be padlocked in the open position. Parallel System Single Mains Parallel System Dual Mains 44 990-91111F-001 Parallel System Overview UPS for External Batteries Parallel System with Shared Unit Input Breaker UIB and Static Switch Input Breaker SSIB Galaxy VS can support up to 4 UPSs in parallel for capacity and up to 3+1 UPSs in parallel for redundancy with shared unit input breaker UIB and static switch input breaker SSIB. NOTE: The internal maintenance breaker IMB can only be used in a simplified 1+1 parallel system. In any other parallel system, an external maintenance bypass breaker MBB must be provided and the internal maintenance breaker IMB* must be padlocked in the open position. Parallel System Single Mains Parallel System Dual Mains 990-91111F-001 45 UPS for External Batteries Overview of Installation Kits Installation Kit 0M-100883 Part Spring washer Used in Connect the Power Cables, page 59. Overview of Installation Kits Number of units 40 Installation Kit 0M-100917 Part M8 nut with washer Used in Prepare the UPS for TN-C/480 V Solid-Grounded System, page 58. Bonding busbar Number of units 2 1 Installation Kit 0M-88357 Part USB cable 150 Ohm resistor Terminal connector Used in Connect the Modbus Cables, page 81. Number of units 1 10 2 Installation Kit 0J-0M-1160 Part Temperature sensor Used in For third-party battery solution, see Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products, page 71. Refer to the installation manual for your specific battery solution for information on how to install and connect the temperature sensor. Number of units 1 46 990-91111F-001 Overview of Installation Kits Optional Seismic Kit GVSOPT002 UPS for External Batteries Part M8 x 20 mm bolt with washer Used in Install the Seismic Anchoring (Option), page 57 and Final Installation, page 83. Number of units 12 Rear anchor 1 Rear anchoring bracket 1 Front anchoring bracket 1 Rear connection plate Used for installation with an adjacent product. Follow 1 instructions in the installation manual for the adjacent product. Optional NEMA 2 Hole Kit GVSOPT005 Part NEMA 2 hole plate (output, DC+, N) Used in Connect the Power Cables with NEMA 2 Hole Plates, page 63. Number of units 7 NEMA 2 hole plate (input, bypass, DC-) 8 M8 nut with washer 30 Spring washer 30 M8x24 mm flat washer 60 990-91111F-001 47 UPS for External Batteries Optional Parallel Kit GVSOPT006 Part PBUS1 cable 0W6268 Used in Connect the PBUS Cables, page 79. Overview of Installation Kits Number of units 1 PBUS2 cable 0W6267 1 AUX switch Connect the IMB Signal Cables in a Simplified 1+1 2 Parallel System, page 75. This kit contains parts for use with other UPS models which are not relevant for this installation. 48 990-91111F-001 Overview of Installation Kits UPS for External Batteries Optional Kit GVSOPT030 Part Interconnection clamp Only for installation with adjacent modular battery cabinet(s). Follow the modular battery cabinet installation manual. Used in For interconnection. Number of units 3 M6 x 16 mm screw with washer 3 M6 nut with washer 3 M8 x 25 mm bolt with washer For power cable connection. 9 M8 nut with washer 9 PE cable 0W13065 (for modular battery cabinet 1) DC cable 0W13071 (for modular battery cabinet 1) For power cable connection for modular battery cabinet 1. 1 1 DC cable 0W13066 (for modular battery cabinet 2) DC cable 0W13068 (for modular battery cabinet 3) Only for power cable connection for modular battery 1 cabinet 2,3,4 for a UPS rated over 50 kW. For a UPS rated for maximum 50 kW, use the provided DC cables. 1 DC cable 0W13067 (for modular battery cabinet 4) 1 Signal cable 0W13070 Signal cable 0W13069 Cable tie Cable tie For signal cable connection for modular battery cabinet 1. 1 1 For power cable fastening. 18 30 990-91111F-001 49 UPS for External Batteries Installation Procedure for Single Systems Installation Procedure for Single Systems 1. Prepare for Installation, page 52. 2. For UPS without preinstalled power modules: Install the Power Module(s), page 56. 3. Install the Seismic Anchoring (Option), page 57. 4. Only for TN-C/480 V solid-grounded earthing system (no neutral connection): Prepare the UPS for TN-C/480 V Solid-Grounded System, page 58. 5. Perform one of the following: Connect the Power Cables, page 59, or Connect the Power Cables with NEMA 2 Hole Plates, page 63. 6. Connect the Signal Cables, page 67. 7. Connect the Signal Cables from a Modular Battery Cabinet, page 69. 8. Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products, page 71. 9. Connect the External Communication Cables, page 80. 10. Add Translated Safety Labels to Your Product, page 82. 11. Final Installation, page 83. 50 990-91111F-001 Installation Procedure for Parallel Systems UPS for External Batteries Installation Procedure for Parallel Systems Simplified 1+1 Parallel System Parallel System 990-91111F-001 1. Prepare for Installation, page 52. 2. For UPS without preinstalled power modules: Install the Power Module(s), page 56. 3. Install the Seismic Anchoring (Option), page 57. 4. Only for TN-C/480 V solid-grounded earthing system (no neutral connection): Prepare the UPS for TN-C/480 V Solid-Grounded System, page 58. 5. Perform one of the following: Connect the Power Cables, page 59, or Connect the Power Cables with NEMA 2 Hole Plates, page 63. 6. Connect the Signal Cables, page 67. 7. Connect the Signal Cables from a Modular Battery Cabinet, page 69. 8. Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products, page 71. 9. Perform one of the following: For simplified 1+1 parallel system: Connect the IMB Signal Cables in a Simplified 1+1 Parallel System, page 75. For parallel system: Install a padlock on the internal maintenance breaker IMB in the open position on all UPSs in the parallel system. 10. Connect the PBUS Cables, page 79. 11. Connect the External Communication Cables, page 80. 12. Add Translated Safety Labels to Your Product, page 82. 13. Final Installation, page 83. 51 UPS for External Batteries Prepare for Installation Prepare for Installation DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or punch holes for cables or conduits with the gland plate installed and do not drill or punch holes in close proximity to the UPS. Failure to follow these instructions will result in death or serious injury. NOTE: Route the signal cables separately from the power cables and route the Class 2/SELV cables separately from the non-Class 2/non-SELV cables. 1. Remove the front panel. 2. Remove the lower front plate. 3. Remove the transparent cover. 4. Remove the top cover: a. Remove the screws and tilt the front of the top cover upwards. b. Slide the top cover towards the rear to remove it. Tabs in the rear of the top cover must disconnect from the slots in the rear of the UPS. 5. For installation with adjacent battery cabinet: Remove the left side panel. 52 990-91111F-001 Prepare for Installation UPS for External Batteries 6. For installation with adjacent battery cabinet: Remove the lower left side plate for internal DC cabling between the UPS and the adjacent battery cabinet. Front View of the UPS 7. For installation with maintenance bypass cabinet: Remove the right side panel. The side panel will be reinstalled on the maintenance bypass cabinet. 8. For installation with maintenance bypass cabinet: Remove the lower right side plate for internal power cabling between the UPS and the maintenance bypass cabinet. Front View of the UPS 990-91111F-001 53 UPS for External Batteries Prepare for Installation 9. For bottom cable entry: Remove the gland plate in the bottom of the UPS. Front View of the UPS 10. For rear cable entry: Remove the gland plate in the rear of the UPS. Front View of the UPS 11. Drill/punch holes for power cables/conduits in the gland plate. Install conduits (not provided), if applicable. 12. Install the gland plate in the bottom or rear of the UPS. 54 990-91111F-001 Prepare for Installation UPS for External Batteries 13. Remove the rear gland plates and the rear brush plates from the UPS. Rear View of the UPS 14. Perform one of the following: For installation without conduits: Reinstall the brush plates. For installation with conduits: Drill a hole in the gland plates for conduits, install conduits, and reinstall the gland plates. Rear View of the UPS without Conduits Rear View of the UPS with Conduits 15. Route the non-Class 2/non-SELV signal cables through the left rear brush/ gland plate and into the left side of the UPS. 16. Route the external cables that connect to the controller box through the right rear brush/gland plate and through the cable channel to the front of the UPS. 17. Route the Class 2/SELV signal cables through the right rear brush/gland plate and into the right side of the UPS. 990-91111F-001 55 UPS for External Batteries Install the Power Module(s) Install the Power Module(s) CAUTION HEAVY LOAD Power modules are heavy and require two persons to lift. · 20 kW power module weighs 25 kg (55 lbs). · 50 kW power module weighs 38 kg (84 lbs). Failure to follow these instructions can result in injury or equipment damage. NOTE: Always install power modules starting with the bottom position and upwards. 1. Remove the screw in each side of the empty power module slot. Remove filler plate, if present. 2. Push the power module into the slot. 3. Reinstall the screw in each side of the slot. 56 990-91111F-001 Install the Seismic Anchoring (Option) Install the Seismic Anchoring (Option) UPS for External Batteries 1. Mount the rear anchor(s) to the floor. Use appropriate hardware for the floor type the hole diameter in the rear anchor is ø14 mm. 2. Install the rear anchoring bracket on the UPS with the provided M8 bolts. Rear View of the UPS 3. Push the UPS into position so the rear anchoring bracket connects to the rear anchor. The front anchoring bracket is installed in the final installation steps. Rear View of the UPS 990-91111F-001 57 UPS for External Batteries Prepare the UPS for TN-C/480 V Solid-Grounded System Prepare the UPS for TN-C/480 V Solid-Grounded System NOTE: The UPS is preconfigured for TNS earthing system. NOTE: 480 V solid-grounded system (no neutral connection) using a bonding busbar will result in a higher leakage current. 1. Only for TN-C/480 V solid-grounded system (no neutral connection): Install the supplied bonding busbar. Front View of the UPS TN-C/480 V Solid-Grounded System (No Neutral Connection) 58 990-91111F-001 Connect the Power Cables Connect the Power Cables UPS for External Batteries DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH In single mains systems where power cables are split due to the cable size restriction, use the bypass busbars for the second input cable set. There is not enough space to land two input cable sets on the input busbars due to the single mains jumper busbars. Failure to follow these instructions will result in death or serious injury. NOTICE RISK OF EQUIPMENT DAMAGE To ensure correct load sharing in bypass operation in a parallel system: · All bypass cables must be the same length for all UPSs. · All output cables must be the same length for all UPSs. · All input cables must be the same length for all UPSs (only required in single mains system). Failure to follow these instructions can result in equipment damage. 1. Only for 480 V solid-grounded systems (no neutral cable connection): a. Remove the RFI bracket. Save the two screws. b. Remove the screw in the left side and save it. c. Install the RFI bracket in the left side with the three screws. Front View of the UPS 990-91111F-001 59 UPS for External Batteries Connect the Power Cables 2. Only for dual mains system: Remove the three single mains jumper busbars. Front View of the UPS 60 990-91111F-001 Connect the Power Cables UPS for External Batteries 3. Connect the power cables as shown in the described order: *Provided in kit. a. Connect the equipment grounding conductor/PE cables. b. Connect the N cables. Connect battery midpoint (if present in battery solution). c. Connect the DC+ cables. d. Connect the output cables. e. Connect the DC- cables. f. Only for dual mains system: Connect the bypass cables. g. Connect the input cables. NOTE: Ensure to connect the input cables to the correct input busbars in the top left side of the UPS. Front View of the UPS Single Mains System Front View of the UPS Dual Mains System 990-91111F-001 61 UPS for External Batteries Connect the Power Cables CAUTION RISK OF EQUIPMENT DAMAGE Check the fastening of the cable lugs. If the cable lugs move due to pulling on cables, the bolt can become loose. Failure to follow these instructions can result in injury or equipment damage. 62 990-91111F-001 Connect the Power Cables with NEMA 2 Hole Plates UPS for External Batteries Connect the Power Cables with NEMA 2 Hole Plates DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH In single mains systems where power cables are split due to the cable size restriction, use the bypass busbars for the second input cable set. There is not enough space to land two input cable sets on the input busbars due to the single mains jumper busbars. Failure to follow these instructions will result in death or serious injury. NOTICE RISK OF EQUIPMENT DAMAGE To ensure correct load sharing in bypass operation in a parallel system: · All bypass cables must be the same length for all UPSs. · All output cables must be the same length for all UPSs. · All input cables must be the same length for all UPSs (only required in single mains system). Failure to follow these instructions can result in equipment damage. 1. Only for 480 V solid-grounded systems (no neutral cable connection): a. Remove the RFI bracket. Save the two screws. b. Remove the screw in the left side and save it. c. Install the RFI bracket in the left side with the three screws. Front View of the UPS 990-91111F-001 63 UPS for External Batteries Connect the Power Cables with NEMA 2 Hole Plates 2. Perform one of the following: Only for single mains system: Remove the indicated L3 jumper busbar in the left side of the UPS. Save the L3 jumper busbar for reinstallation later. Only for dual mains system: Remove the three single mains jumper busbars in the left side of the UPS. Front View of the UPS 64 990-91111F-001 Connect the Power Cables with NEMA 2 Hole Plates UPS for External Batteries 3. Install the NEMA 2 hole plates and connect the power cables as shown in the described order: *Provided in kit. Front View of the UPS -- Single Mains System Front View of the UPS -- Dual Mains System 990-91111F-001 a. Connect the equipment grounding conductor/PE cables. b. Connect the N cables. Connect battery midpoint (if present in battery solution). c. Connect the DC+ cables. 65 UPS for External Batteries Connect the Power Cables with NEMA 2 Hole Plates d. Connect the output cables. e. Connect the DC- cables. f. Only for dual mains system: Connect the bypass cables. g. Connect the input cables. NOTE: Ensure to connect the input cables to the correct input busbars in the top left side of the UPS. 4. Only for single mains system: Reinstall the L3 jumper busbar in its original position with two M8 nuts. Front Right View of the UPS 66 990-91111F-001 Connect the Signal Cables Connect the Signal Cables UPS for External Batteries NOTE: Route the signal cables separately from the power cables and route the Class 2/SELV cables separately from the non-Class 2/non-SELV cables. 1. Connect the Class 2/SELV signal cables from the building EPO to board 640 4864 terminal J6600 in the UPS according to one of the options below. The EPO circuit is considered Class 2/SELV. Class 2/SELV circuits must be isolated from the primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2/SELV. EPO Configurations (6404864 terminal J6600, 19) The EPO input supports 24 VDC. NOTE: The default setting for the EPO activation is to turn off the inverter. If you want the EPO activation to transfer the UPS into forced static bypass operation instead, please contact Schneider Electric. 2. Connect the Class 2/SELV signal cables from the auxiliary products to board 6404864 in the UPS. Follow the instructions in the auxiliary product manuals. 990-91111F-001 67 UPS for External Batteries Connect the Signal Cables 3. Connect the Class 2/SELV signal cables to the input contacts and output relays on board 6404864 in the UPS. Do not connect any circuit to the input contacts unless it can be confirmed that the circuit is Class 2/SELV. The input contacts support 24 VDC 10 mA. All circuits connected must have the same 0 V reference. Name IN _1 (input contact 1) IN _2 (input contact 2) IN _3 (input contact 3) IN _4 (input contact 4) Description Configurable input contact Configurable input contact Configurable input contact Configurable input contact Location 640-4864 terminal J6616, 12 640-4864 terminal J6616, 34 640-4864 terminal J6616, 56 640-4864 terminal J6616, 78 The output relays support 24 VAC/VDC 1 A. All external circuitry must be fused with maximum 1 A fast acting fuses. Name OUT _1 (output relay 1) OUT _2 (output relay 2) OUT _3 (output relay 3) OUT _4 (output relay 4) Description Configurable output relay Configurable output relay Configurable output relay Configurable output relay Location 6404864 terminal J6617, 13 6404864 terminal J6617, 46 6404864 terminal J6617, 79 6404864 terminal J6617, 1012 4. Connect the non-Class 2/non-SELV signal cables from the auxiliary products to board 6404843 in the UPS. Follow the instructions in the auxiliary product manuals. 68 990-91111F-001 Connect the Signal Cables from a Modular Battery Cabinet UPS for External Batteries Connect the Signal Cables from a Modular Battery Cabinet For installation with adjacent modular battery cabinet, use the signal cables provided in optional installation kit GVSOPT030. For installation with remote modular battery cabinets, signal cables are not provided. Follow the modular battery cabinet installation manual to prepare for installation. 1. For a remote modular battery cabinet: Route the signal cables from modular battery cabinet 1 through the rear of the UPS. 2. For an adjacent modular battery cabinet: Route the signal cables from modular battery cabinet 1 to the UPS as shown. a. Route the signal cables from modular battery cabinet 1 into the UPS through the opening. b. Route the signal cables up through the cable channel in the UPS. Front View of Adjacent Modular Battery Cabinet 1 and the UPS 990-91111F-001 69 UPS for External Batteries Connect the Signal Cables from a Modular Battery Cabinet 3. Connect the signal cables from modular battery cabinet 1 to the UPS: a. Mount a termination plug in J8008 on board 640-7552 in the last modular battery cabinet (T). b. Connect the signal cable from J8011 on board 640-7552 in modular battery cabinet 1 to J6619 and J6604 on board 640-4843 in the UPS. c. Connect the signal cable from J8007 on board 640-7552 in modular battery cabinet 1 to J6608 on board 640-4864 in the UPS. Signal Cable Connections between Four Modular Battery Cabinets and the UPS 70 990-91111F-001 Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products UPS for External Batteries Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products NOTE: Route the signal cables separately from the power cables and route the Class 2/SELV cables separately from the non-Class 2/non-SELV cables. Example of Single System with Third-Party Switchgear NOTE: The internal maintenance breaker IMB* cannot be used in a system with an external maintenance bypass breaker MBB and the internal maintenance breaker IMB* must be padlocked in the open position. 1. Install the temperature sensor provided with the UPS in the battery solution. In battery cabinets, install the temperature sensor in the top corner of the battery cabinet. WARNING HAZARD OF FIRE Position the temperature sensor as described to ensure correct temperature measurements. Failure to follow these instructions can result in death, serious injury, or equipment damage. 2. Route the battery temperature sensor cables from the battery solution to the UPS and connect on board 640-4864 in the top of the UPS as shown. NOTE: One temperature sensor is provided with the UPS. Contact Schneider Electric if you want to buy an additional temperature sensor. NOTE: The battery temperature sensor cables are considered Class 2/ SELV. Class 2/SELV circuits must be isolated from the primary circuitry. 990-91111F-001 71 UPS for External Batteries Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products 3. Connect signal cables from the breaker indicator lights in your switchgear to board 640-4864 terminal J6618 in the top of the UPS. If an external supply is used, remove jumper from J6618 pin 8 and 9. NOTE: The breaker indicator light circuit is considered Class 2/SELV. Class 2/SELV circuits must be isolated from the primary circuitry. Do not connect any circuit to the breaker indicator light terminals unless it can be confirmed that the circuit is Class 2/SELV. 72 990-91111F-001 Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products UPS for External Batteries 4. Connect the signal cables from battery breaker 1 in your battery solution for shunt trip or undervoltage (UV) trip connection to board 640-4843 terminal J6603. Follow the illustration for connection with internal or external 24 VDC supply. Battery Breaker Trip Connection with Internal 24 VDC Supply Battery Breaker Trip Connection with External 24 VDC Supply Supported Shunt Current (A) 1.6 10 20 30 Time (ms) Continuous 1300 200 60 Temperature 20 °C (68 °F) 20 °C (68 °F) 20 °C (68 °F) 20 °C (68 °F) 5. Connect the signal cables from battery breaker 2 (if present) in your battery solution for shunt trip or undervoltage (UV) trip connection to board 640-4843 terminal J6604. The connection principle is the same as for battery breaker 1. 990-91111F-001 73 UPS for External Batteries Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products 6. Connect signal cables from AUX switches in your switchgear to board 6404843 in the top of the UPS. Terminal number J6601 J6602 J6603 J6604 J6609 J6614 Function Connection UOB_RED (redundant AUX Connect to redundant AUX switch in unit output breaker UOB. switch in unit output breaker) SIB (system isolation breaker) BB2 (battery breaker 2) BB1 (battery breaker 1) Connect to normally open (NO) AUX switch in system isolation breaker SIB for parallel system. SIB must contain an AUX switch for each connected UPS. Connect to normally open (NO) AUX switch in battery breaker number 219 Connect to normally open (NO) AUX switch in battery breaker number 119 BB1_TRIP (battery breaker 1) Connect to shunt trip or UV trip in battery breaker number 119 BB2_TRIP (battery breaker 2) Connect to shunt trip or UV trip in battery breaker number 219 UOB (unit output breaker) SSIB (static switch input breaker) Connect to normally open (NO) AUX switch in unit output breaker UOB. Connect to normally open (NO) AUX switch in static switch input breaker SSIB. SSIB must contain an AUX switch for each connected UPS. UIB (unit input breaker) MBB (maintenance bypass breaker) Connect to normally open (NO) AUX switch in unit input breaker UIB. UIB must contain an AUX switch for each connected UPS. Connect to normally closed (NC) AUX switch in maintenance bypass breaker MBB. MBB must contain an AUX switch for each connected UPS. 19. The UPS can connect to and monitor up to two battery breakers. 74 990-91111F-001 Connect the IMB Signal Cables in a Simplified 1+1 Parallel System UPS for External Batteries Connect the IMB Signal Cables in a Simplified 1+1 Parallel System NOTE: Route the signal cables separately from the power cables to ensure sufficient isolation. 1. Remove the static switch module from both UPSs. Front View of the UPS 2. Remove the cover from both UPSs. Front View of the UPS 3. Disconnect the signal cables from the internal maintenance breaker IMB indicator light on both UPSs. 990-91111F-001 75 UPS for External Batteries Connect the IMB Signal Cables in a Simplified 1+1 Parallel System 4. Remove the shelf from both UPSs. Front View of the UPS 5. Remove the front cover from the internal maintenance breaker IMB on both UPSs. Front View of the UPS 6. Install an additional AUX switch (provided) in the OF2 position in the internal maintenance breaker IMB on both UPSs. 76 990-91111F-001 Connect the IMB Signal Cables in a Simplified 1+1 Parallel System UPS for External Batteries 7. Connect the non-Class 2/non-SELV signal cables between the two UPSs: a. Connect the non-Class 2/non-SELV signal cables (not provided) from the AUX switch terminal 1 and 2 in the internal maintenance breaker IMB in UPS 1 to J6614-5 and J6614-6 on board 640-4843 in UPS 2 as shown. b. Connect the non-Class 2/non-SELV signal cables (not provided) from the AUX switch terminal 1 and 2 in the internal maintenance breaker IMB in UPS 2 to J6614-5 and J6614-6 on board 640-4843 in UPS 1 as shown. Front View of Internal Maintenance Breaker IMB 990-91111F-001 77 UPS for External Batteries Front View of Simplified 1+1 Parallel System Connect the IMB Signal Cables in a Simplified 1+1 Parallel System 8. Reinstall the front cover on the internal maintenance breaker IMB on both UPSs. 9. Reinstall the shelf on both UPSs. 10. Reconnect the signal cables from the internal maintenance breaker IMB to the indicator light on both UPSs. Front View of the UPS 11. Reinstall the cover on both UPSs. 12. Reinstall the static switch module on both UPSs. 78 990-91111F-001 Connect the PBUS Cables Connect the PBUS Cables UPS for External Batteries 1. Connect the provided PBUS 1 (white) and PBUS 2 (red) cables to the PBUS ports in the UPS controller boxes. Route the PBUS cables through the cable channel in the UPSs. Front View of Controller Box 2. Mount termination plugs (T) in the unused connectors. Example of System with Three UPSs in Parallel 990-91111F-001 79 UPS for External Batteries Connect the External Communication Cables Connect the External Communication Cables 1. Connect the external communication cables to the ports in the UPS controller box. Front View of the Controller Box A. Universal I/O port for built-in network management card. B. Modbus port for built-in network management card. C. Network port for built-in network management card. Use a shielded network cable. NOTE: Check that you are connecting to the correct port to avoid network communication conflicts. 80 990-91111F-001 Connect the External Communication Cables Connect the Modbus Cables UPS for External Batteries 1. Connect the Modbus cables to the UPS(s). Use either 2-wire or 4-wire connection. · Shielded twisted pair cables must be used for Modbus connections. The shield connection to the ground must be as short as possible (ideally below 1 cm). The cable shield must be connected to the Ch Gnd pin on each device. · Wiring should be done in accordance with local wiring codes. · Route signal cables separately from power cables to ensure sufficient isolation. · The Modbus port is galvanically isolated with the Com pin as ground reference. Example: 2-Wire Connection with Two UPSs Example: 4-Wire Connection with Two UPSs 990-91111F-001 2. Install 150 Ohm termination resistors at each end of each bus if the buses are very long and operate at high data rates. Busses under 610 meters (2000 feet) at 9600 baud or under 305 meters (1000 feet) at 19.200 baud should not require termination resistors. 81 UPS for External Batteries Add Translated Safety Labels to Your Product Add Translated Safety Labels to Your Product The safety labels on your product are in English and French. Sheets with translated safety labels are provided with your product. 1. Find the sheets with translated safety labels provided with your product. 2. Check which 885-XXX numbers are on the sheet with translated safety labels. 3. Locate the safety labels on your product that match the translated safety labels on the sheet look for the 885-XXX numbers. 4. Add the replacement safety label in your preferred language to your product on top of the existing French safety label. 82 990-91111F-001 Final Installation Final Installation UPS for External Batteries 1. Reinstall the top cover: a. Tilt the top cover and slide it onto the UPS from the rear. Tabs in the rear of the top cover must connect to the slots in the rear of the UPS. b. Push the top cover down in the front. Rear View of the UPS c. Reinstall the screws. Front View of the UPS 2. Check the fastening of the cable lugs. CAUTION RISK OF EQUIPMENT DAMAGE Check the fastening of the cable lugs. If the cable lugs move due to pulling on cables, the bolt can become loose. Failure to follow these instructions can result in injury or equipment damage. 990-91111F-001 83 UPS for External Batteries 3. Reinstall the transparent cover. Front View of the UPS Final Installation 4. Reinstall the lower front plate. Front View of the UPS 84 990-91111F-001 Final Installation UPS for External Batteries 5. Only for seismic anchoring: a. Install the seismic front anchoring bracket on the UPS with the provided M8 bolts. b. Mount the seismic front anchoring bracket on the UPS to the floor. Use appropriate hardware for the floor type the hole diameter in the front anchoring bracket is ø18 mm. Front View of the UPS 6. Lower the front and rear leveling feet on the UPS with a wrench until they connect with the floor. Use a bubble-leveler to check that the UPS is level. This step is not necessary for a UPS with seismic anchoring. Front View of the UPS CAUTION TIP HAZARD Do not move the cabinet after the leveling feet have been lowered. Failure to follow these instructions can result in injury or equipment damage. 7. Only for UL 924 and CSA C22.2 NO. 141-15 solutions: Fill out the label on the lower front plate with the UPS output rating in kW. 990-91111F-001 85 UPS for External Batteries Final Installation 8. Reinstall the front panel on the UPS: a. Insert the two tabs in the bottom of the front panel in the UPS at a tilted angle. b. Reconnect the front panel strap to the UPS. c. Close the front panel and lock with the two locking knobs. 86 990-91111F-001 Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) 1 41 29 70 00 *990-91111F-001* As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication. © 2018 2021 Schneider Electric. All rights reserved. 990-91111F-001