WellZone 3-Wire Pressure Controller – Installation and Operation Manual

WellZone 3-Wire Pressure Controller - CSI Controls

1106426A-3-WIRE WellZone Literature CSI ...

PDF preview unavailable. Download the PDF instead.

1106426A-3-WIRE-WellZone-Literature-CSI-8.5x11
WellZoneTM Pressure Controller
Single Phase 3-Wire Well Pump Control Panel Installation and Operation Manual
Parts Included

Specifications
Input Voltage: 230 VAC, 60Hz
Operating Temperature: 14°to 122° (-10° to 50°)
Pump Ratings: Single phase, 3-wire (4~17FLA)

Enclosure: 10 x 8 x 4 inch (25.4 x 20.3 x 10.2 cm) NEMA 4X thermoplastic Includes liquid tight cable strain relief fittings: · 1 x 1/2" + 1 x 3/4" UF cable
· 1 x 1/2" round cable

Pressure Transducer: 0-150 PSI (included) 1/4" NPT Male, NSF 61 rated, 4-20mA, with 16.4 ft (5m) cable Auxiliary Alarm Contacts: N.O. 1 amp, 120 VAC Max

Part # Description

1105505 1105506 1105507 1105508 1105509 1105510

WELLZONE 3W-050 WELLZONE 3W-075 WELLZONE 3W-100 WELLZONE 3W-150 WELLZONE 3W-200 WELLZONE 3W-300

3-WIRE MOTOR RUN CAP START CAP CB

HP Volts SFA Mfd

Mfd

1/2 230 4.3 15

43-53

15A

3/4 230 5.7 23

59-71

20A

1 230 7.1 23

86-103

20A

1 1/2 230 11.5 15

105-126 20A

2 230 13.2 20

105-126 25A

3 230 17.0 45

208-250 30A

This digital controller does not provide Variable Speed Pump Control or constant pressure operation. This control panel must be installed and serviced by a licensed electrician in accordance with the National Electric Code NFPA-70, state and local electrical codes. UL Type 4X enclosures are for indoor or outdoor use.
Warranty void if panel is modified.

?

For information regarding operation, available options, or servicing

questions, please call CSI Controls

Technical Support.

CSI Controls offers a five-year limited warranty. For complete terms and conditions, please visit www.sjerhombus.com.
Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in
handling said material. All applicable laws and regulations shall apply.

Manufactured by: CSI Controls

Technical Support: +1-800-746-6287 techsupport@sjeinc.com www.csicontrols.com
Technical Support Hours: Monday-Friday, 7:00 AM to 6:00 PM Central Time

PN 1106426A 03/2024 ©2024 SJE, Inc. All Rights Reserved. CSI Controls is a trademark of SJE, Inc
1

Features
The WellZoneTM 3W digital controller provides pressure control for single phase 3-wire submersible well pump applications. It uses a 0-150 PSI pressure transducer to monitor the discharge pressure and turns the pump ON and OFF according to adjustable Start and Stop setpoints. The LCD display allows for quick view of the system pressure, run status, hours run and pump cycles. The rotary button provides the user with a simple navigation method through the menu and program settings. It features built in pump protection including rapid cycling and dry run. It is preprogrammed to run the pump as the pressure drops below 40 PSI and stop as the pressure rises above 60 PSI. High & Low pressure settings are available with an auxiliary alarm relay.

Start Relay:

Circuit Breaker:
The pump circuit has a thermal-magnetic circuit breaker that provides pump disconnect and branch circuit protection.

LCD Display:
LCD display shows pressure reading, pump amp reading, pump on indicator.

75

L1

L2

50

RUN
T TEST

25
PUMP T1 T2

ESC 0 +12V AI C DI AUX

Pump Run Light
Pump Test Switch:
Run pump manually.
Rotary Encoder Push Button:
Rotate to scroll menu settings. Press to select the desired setting.
ESC Button:
Exit without saving or jump to previous display.
Start Capacitor
(Varies with model)

Run Capacitor
(Varies with model)

Pump Connection 230V, 1-phase, 3 wire 3/4" UF strain relief

Incoming Power 230V, 1-phase 1/2" UF strain relief

Pressure transducer 0-150 PSI / 4-20mA 1/2" round strain relief

2

L1 L2 GND

INFEED POWER 230 VAC
1 PHASE, 60 HZ

CB108 L1
L2 PUMP
CIRCUIT BREAKER

WELLZONE CONTROLLER

ORA 1 2 5
BLK YEL

RED

START RUN COMMON

RED

BLK

240VAC

MOT 1 PHASE, 3 WIRE

YEL

BRN BLU +-
AN118

CSI P/N 1105505 1105506 1105507 1105508

WELLZONE PANELS

DESCRIPTION
WELLZONE 3W-050 (230V,1/2 HP,4.0 SFA)

START CAPACITOR

RUN CAPACITOR

43-56 MFD/250V 15 MFD/370V

WELLZONE 3W-075 (230V,3/4 HP,5.2 SFA)
WELLZONE 3W-0100 (230V,1.0 HP,6.2 SFA)

59-71 MFD/250V 25 MFD/370V 88-108 MFD/250V 25 MFD/370V

WELLZONE 3W-150 (230V,1.5 HP,11.2 SFA)

108-130 MFD/250V 15 MFD/370V

CIRCUIT BREAKER
15 AMP
20 AMP 20 AMP
20 AMP

3

L1 L2 GND

INFEED POWER 230 VAC
1 PHASE, 60 HZ

CB108 L1
L2 PUMP
CIRCUIT BREAKER

WELLZONE CONTROLLER

ORA 1 2
1 5
3
BLK YEL

RED

START RUN COMMON

RED

BLK

240VAC

PUMP 1 PHASE, 3 WIRE

YEL

BRN BLU +-
AN118

CSI P/N 1105509 1105510

WELLZONE PANELS WITH KLIXON START OVERLOAD

DESCRIPTION

START CAPACITOR

RUN CAPACITOR

WELLZONE 3W-200 (230V,2 HP,11.9 SFA) 108-130 MFD/250V 20 MFD/370V

WELLZONE 3W-300 (230V,3 HP,14.3 SFA) 216-259 MFD/250V 45 MFD/370V

CIRCUIT BREAKER
25 AMP
30 AMP

4

Mounting the Control Panel 1 Drill and fasten top of the enclosure using appropriate anchor.
2 Drill and fasten bottom of the enclosure using appropriate anchors.
5

Wiring the Control Panel
CAUTION!
Disconnect all power to the control panel before wiring. Ensure that the incoming supply power voltage is the same as the rating of the pump motor being installed. Ensure that the rated Amps of the motor does not exceed the rating of the control panel. Ensure the HP rating and Capacitor values of the control panel are correct for the pump used.
1 Connect the following wires to the proper terminal
positions: · Incoming power to the circuit breaker · Motor/Pump power to Motor · Pressure transducer See wiring label on inside the control panel for details.
2 Verify correct operation of control panel after
the installation is complete.

3 Maximum motor cable lengths.

Vac 230V

Motor
HP 1/2HP 3/4HP 1.0HP 1.5HP 2.0HP 3.0HP

Amps2 4.3 5.7 7.10 11.5 13.2 17

14 AWG 400 300 250 175 150 120

Feet - Motor Cable (75C)1

12 AWG 650 450 400 300 250 200

10 AWG 1000 750 60 450 400 300

1 Cable length is measured from the motor to the main panelboard (Service Entrance) 75C Insulation - AWG Copper Wire only. Do not use aluminum conductors. Use with 2-wire motor only with internal thermal protection. 2 Typical S.F.A. (Service Factor Amps). Check motor nameplate for actual data.

6

8 AWG 1600 1200 1000 750 600 450

Operation Guide - PRESSURE CONTROL

Enter Enter

75 50
25 0
Rotate
75 50
25 0
Rotate
75 50

25 0

Main screen Pump runtimes and cycles Filter remaining life

75 50
25
Esc
0
Rotate

Start pressure Enter pump start pressure setting
Enter Esc

75 50
25 0

Save and return to main screen
Enter

SEE PARAMETER TABLE BELOW FOR COMPLETE LIST

Rotate
75 50
Esc
25

Fault History

75

Select to view last 10

faults

50

Enter Esc
25

Enter

0

0

FLT1

...

Rotate

FLT8

75

50

25 0
Notes : A. If there is no operation for 20 sec, the display will return to the main screen. B. The service function is used for alerting the user when it is time to change a filter
or to serivce the equipment after the accumulated run time is reached. The icon will flash on main screen when the timer is done (Filter at 0%).
Push and hold ESC button 4 seconds to reset the filter or service time.

7

Pressure transducer = 0-150 psi

Digital input = Floor sensor (stop pump) or low level float (stop pump)

PARAMETER

Description

Default Range Min Range Max

Unit Function

START

Start Pressure

40.0

STOP HIGH LOW

Stop Pressure High Pressure Low Pressure

60.0 70.0 20.0

LOW TMR Low Pressure Timer

30

OVERLOAD

SS..FF..AL SAeStteintgting

12.0

DRY RUN

Dry Run Amps

0.0

DRY TMR

Dry Run Timer

30

RECHARGE

Recharge Timer

20

STRT/MIN

Starts Per Minute

2

MAX RUN Max Run Time per cycle

0

NO AMPS

No Amps detect

ON

FILTER

Filter Life Timer

OFF

The pump will RUN when the pressure drops below the

1.0

140.0

PSI "START" pressure value and continue to RUN until the pressure

rises above the "STOP" value. Set START<STOP. The "STOP"

value should be at least 10 PSI over the "START" value.

The pump will RUN when the pressure drop below the "START"

10.0

150.0

PSI pressure value and continue to RUN until the pressure rises

above the "STOP" value.

10.0

150.0

PSI

High Pressure alarm. The pump will stop if the pressure rises above this value

Low Pressure alarm. If the pressure drop below this value, the

0.0

150.0

PSI "LOW TMR" timer will start. The pump will stop when the timer

is done and a "LOW PRESS" alarm will be displayed.

Low pressure timer. This delay timer needs to be long enough

0

3599s(59m:59s)

second

to allow the pump to pressurize the system on start up. It can be used to detect a broken discharge pipe or signi cant leak.

Value is in Seconds (s).

Set to the motor Service Factor Amps (SFA) value as listed on

the motor nameplate. The pump will stop if it is pulling excessive

4.0

17.0

Amps

amps and the "OVERLOAD" alarm will be displayed. The controller will reset the fault automatically after a cooling period.

The controller will reset this fault 4 times automatically before

requiring a manual reset.

Pump DRY RUN protection. Set this value lower than the

normal pump operating amps. 30% lower than the motor

0.0

17.0

Amps Service Factor Amps is common. Adjust up or down as this

function is tested. Example: Motor SFA = 10.0A. Set the Dry

Run Amps = 7.0A. Set to "0.0" to disable this function (Default)

Time delay before stopping the pump on "DRY RUN" as the

0

3599s(59m:59s) Seconds amps are lower than the "DRY RUN" Amps value. Timer value is

in seconds (s).

Automatic reset timer after a "DRY RUN" trip, allowing for

0

3599m(59h:59m) Minutes enough time for the well to recharge. Timer value is in minutes

(m). Set to "0" to disable.

Rapid cycle protection. Enter the maximum allowable pump

1

10

Cycles

starts per minute. If the number of starts is exceed, the display will show "RPD CYCL" and a manual reset is required for the

pump to start again.

Set the maximum cycle time. The pump will stop and the a

0

3599m(59h:59m) Minutes "MAX RUN" alarm will be displayed if the cycle time is greater

than this value. Set to "0" to disable (default)

The No amps detection function informs the user of thermal

ON

ON, OFF

NA

switch trip internal to the motor. Allow the motor to cool and it will start again automatically. This detection function is disabled

when set to "OFF".

Set the estimated pump run time between lter replacements.

0

9999

hours

The time is set in hours (h) and corresponds to pump running hours. A ashing wrench will appear on the screen when this

timer is done. This function is disabled by default.

CAUTION: The DY RUN protection is disabled by default. It must be set according to your pump HP and normal running Amps during start up.

8

ALARM

Fault

Pump

LOW PRES LOW PRESSURE ALARM STOP

HIGH PRES HIGH PRESSURE ALARM STOP

DRY RUN PUMP RUNNING DRY

STOP

Auxilary CLOSED CLOSED

Auto/Manual Reset
Auto reset when PSI is back to
normal
Auto reset when PSI is back to
normal

Description LOW PRESSURE ALARM Pressure below the Low Pressure set point for longer than the Low Pressure Timer. HIGH PRESSURE ALARM Pressure greater than the High Pressure set point.

Action
Check for leaks, broken pipes. Check the pump and motor.
Check pump, piping and pressure tank.

CLOSED

PUMP DRY RUN ALARM

Pump DRY RUN protection. Set this

Manual reset or by recharge if disabled

reset not

value lower than the normal pump operating amps. 30% lower than the motor Service Factor Amps is common. Example: Motor SFA = 10.0A.

Set the Dry Run Amps = 7.0A. Set to

If the pump is tripping on DRY RUN but there is water in the well, decrease this setting. If the pump is NOT tripping on DRY RUN, then increase this value.

"0.0" to disable this function (Default).

RAPID CYCLE PUMP RAPID CYCLING

STOP CLOSED

Manual reset

Check the pressure tank for

damage or incorrect pre-charge

RAPID CYCLING ALARM

pressure. These commonly result

This is the maximum allowable pump in the pump rapid cycling. Correct

starts per minute. If the number of or replace pressure tank.

cycles per minute is exceeded, the Increase the number starts per

pump will not start and the RDP CYCL minute for systems with small

alarm will be displayed.

pressure tanks. Contact the

pump/motor manufacturer for

the max allowable starts/minutes.

MAX RUN MAXIMUM RUN TIME

STOP

NO AMPS NO AMPS DETECTED

NONE

OVERLOAD MOTOR OVERLOAD

STOP

WATER SW WATER SWITCH ACTIVE STOP

XDR OPEN TRANSDUCER OPEN

STOP

CLOSED CLOSED CLOSED CLOSED CLOSED

Manual reset Auto reset

Check for pipe leaks or faucet

MAXIMIM RUN TIME ALARM

left open. Increase time if

Maximum runtime allowed in one cycle. necessary

NO AMPS DETECTED

No amps are detected which implies If it is a motor thermal trip, then

that the thermal switch internal to the allow the motor to cool and it will

motor has tripped or that the pump is start again automatically.

not connected.

Investigate the cause of the

When the "NO AMPS" function is

motor internal trip. If the motor is

enabled, it will ignore the Low

not connected, check the motor

Pressure and Dry Run conditions and wiring. The NO AMPS function

maintained the RUN command to the can be disabled when set to

pump unitl the motor has cooled down "OFF".

and restarts automatically.

Class10 overload protection, calculated

based on the motor S.F.A. load.

Auto reset / Manual The overload will automatically reset Check the pump for clogging or

reset

after a cooling period. It must be

locked rotor condition.

manually reset after four consecutive

times trips.

Auto reset

Digital input from the optional oor sensor or oat switch. If the input of water sensor is ON for more than 5 sec, shut down the pump and display "WATER SW". This alarm will auto reset when the switch opens.

Check the water sensor or oat switch. Correct the cause of water leakage or water supply prior to resetting the fault.

Auto reset

PRESSURE TRANSDUCER OPEN CONNECTION Active when the 4-20mA signal input value is < 3.0mA

Check the transducer cable connection to the pressure sensor. Make sure it is connected properly and hand tightened. Check the transducer cable for damage. Replace cable if damaged. Check the transducer cable connections to the controller. Make sure there is a good connection.

XDR SHORT TRANSDUCER SHORT RECHARGE WELL IS RECHARGING CHNG FILTER CHANGE FILTER

STOP STOP NONE

CLOSED

Auto reset

PRESSURE TRANSDUCER SHORT CIRCUIT Active when the 4-20mA signal input value is > 21mA

Same as above. In addition, check the pressure transducer. Remove it and inspect for damage. Replace if is it damaged.

CLOSED

Hold ESC for 4 sec if WELL IS RECHARGING - PLEASE

Wait for the recharge timer to

you want to cancel STAND BY

complete.

the timer and re-start This is the waiting time after the pump Increase or decrease this timer

the pump

as tripped on "Dry Run" fault, before value as needed to match the

immediately

performing an automatic reset.

recovery time of your well.

NONE

Hold ESC for 4 sec to reset the lter capacity to 100%

CHNG FILTER & Wrench Icon is displayed for 2 second every 7 seconds when the pump has run for the time listed in the users lter setting.

Replace or clean the lter regularly to keep the pumping system running at optimal e iciency.

9

Start Circuitry Overload Protector (For 2HP & 3HP only)
There is an additional overload (OL) protection device on 2HP and 3HP control panels. This OL device is for the protection of the START Circuitry and is located below the terminal blocks. Press the red button to reset. Q: What are symptoms when the start overload is tripped? A: There is a short in the start circuitry or a locked rotor situation. The pump will not start when this overload protector has tripped. Press the red button to reset. The digital display may also display "OVERLOAD" and must be reset (Press ESC button for 4 sec). Q: How to check the circuit with a multimeter? A: If the pump does not start after a reset. To verify that OL has reset, measure the resistance (ohm) from T1 and the black wires in the cap kit. It should measure continuity (<10 ohms). Check the start relay and capacitors as well. Q: How to reset? A: To reset, wait at least 10 minutes after the trip to allow for the unit to cool down and press the red button. Q: What do you do if the start overload keeps tripping? A: Check the capacitors and start relay. Check the motor if locked. Check ambient temperature in the control panel. The overload module will trip sooner if hot. Protect the control panel from direct sunlight.
10

REPLACEMENT PART NUMBERS

Part# 1105505 1105506 1105507

WellZone 3W-050

WellZone 3W-075

WellZone 3W-100

HP 1/2

3/4

1

1105508

1105509

1105510

WellZone 3W- WellZone 3W- WellZone

150

200

3W-300

1 1/2

2

3

SFA 4.3

5.7

7.1

11.5

13.2

17.0

Volts 230

230

230

230

230

230

RUN CAP 15mF

23mF

23mF

15mF

20mF

45mF

Part# 1036323

1004023 1004023

1036323

1003706

1003829

12210 Mars
370V

12215 370V

12215 370V

12210 370V

12214 370V

12223 370V

START CAP 43-56mF 59-71mF 88-108mF 108-130mF 108-130mF 216-59mF

Part# 1098476

1098478 6001275

1027120

1027120

1002979

Volt 250

250

250

250

250

250

Mars 11942

11943

11945

11946

11946

11952

Start Relay

HLR38002AL3D

HLR3800- HR3800-

2AL3D

2AL3D

HR3800-2AL3D

HR38002AL3D

HR38002AL3D

Part# 1098479 Start OL
Par# CB 15A

1098479 1098479

20A

20A

1098479

1098479

1098479

GA3VPA7421 GA3VRA0021

1104244

1104245

20A

25A

30A

NOTES: _______________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________
? Technical support, service questions: +1-800-746-6287 techsupport@sjeinc.com Monday - Friday 7:00 AM to 6:00 PM Central Time