User Manual for Lab Gruppen models including: D Series High Power Installation Platform, D Series, High Power Installation Platform, Power Installation Platform, Installation Platform, Platform

دفترچه راهنما

آمپلی فایر Lab Gruppen مدل D 20:4L - Proavl


File Info : application/pdf, 57 Pages, 9.70MB

PDF preview unavailable. Download the PDF instead.

Lab-Gruppen-D-204L-Operating-Manual
Rev. 3.0.1
Item no. OM­DSERIES­LAKE

D SERIES
High­Power installation platform

Lake Variants: D 200:4L D 120:4L D 80:4L D 40:4L D 20:4L D 10:4L
Incorporating technologies from
Operation Manual

1. Important safety instructions

1. Important safety instructions

Before using the device, be sure to carefully read the Safety Instructions. Keep this document with the device at all times.

1. Read these instructions. 2. Keep these instructions 3. Heed all warnings. 4. Follow all instructions. 5. Do not use this apparatus near water. 6. Clean only with a dry cloth. 7. Do not block any ventilation openings. Install in accordance
with the manufacturer's instructions. 8. Do not install near any heat sources such as radiators, heat
registers, stoves, or other apparatus (including amplifiers) that produce heat. 9. Do not defeat the safety purpose of the polarized or grounding-type plug. A polarized plug has two blades with one wider than the other. A grounding-type plug has two blades and a third grounding prong. The wide blade or the third prong is provided for your safety. If the provided plug does not fit into your outlet, consult an electrician for replacement of the obsolete outlet.
10. Protect the power cord from being walked on or pinched, particularly at plugs, convenience receptacles, and the point where they exit from the apparatus.
11. Only use attachments/accessories specified by the manufacturer.
12. Use only with a cart, stand, tripod, bracket, or table specified by the manufacturer, or sold with the apparatus. When a cart is used, use caution when moving the cart/apparatus combination to avoid injury from tip-over.
13. Unplug this apparatus during lightning storms or when unused for long periods of time.
14. Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way, such as power-supply cord or plug is damaged, liquid has been spilled or objects have fallen into the apparatus, the apparatus has been exposed to rain or moisture, does not operate normally, or has been dropped.
15. Use the mains plug to disconnect the appartus from the mains.
16. WARNING: To reduce the risk of fire or electric shock, do not expose this apparatus to rain or moisture.
17. Do not expose this equipment to dripping or splashing and ensure that no objects filled with liquids, such as vases, are placed on the equipment.
18. The mains plug of the power supply cord shall remain readily operable.
19. Do not connect the unit's output to any other voltage source such as battery, mains source, or power supply, regardless of whether the unit is turned on or off.
20. Do not remove the top (or bottom) cover. Removal of the cover will expose hazardous voltages. There are no user serviceable parts inside and removal may void the warranty.
21. An experienced user shall always supervise this professional audio equipment, especially if inexperienced adults or minors are using the equipment.
22. The US National Differences clause 16.3 requires that network cables must be flame rated VW-1.

2. Approvals
This equipment conforms to the requirements of the EMC Directive 2014/30/EU and the requirements of the Low Voltage Directive 2014/35/EU.
Standards applied: EMC Emission EN55103-1, E4 EMC Immunity EN55103-2, E5, with S/N below 1% at normal operation level. Electrical Safety EN60065, Class I
This equipment is tested and listed according to the U.S. safety standard ANSI/ UL 60065 and Canadian safety standard CSA C22.2 NO. 60065. Intertek made the tests and they are a Nationally Recognized Testing Laboratory (NRTL).
3. Warnings
3.1. Explanation of warning symbols
The lightning bolt triangle is used to alert the user to the presence of un-insulated "dangerous voltages" within the unit's chassis that may be of sufficient magnitude to constitute a risk of electric shock to humans.
The exclamation point triangle is used to alert the user to presence of important operating and service instructions in the literature accompanying the product.
3.2. Warnings
To prevent electric shock do not remove top or bottom covers. No user serviceable parts inside, refer servicing to qualified service personnel. Français: À prévenir le choc électrique n'enlevez pas les couvercles. Il n'y a pas des parties serviceable à l'intérieur, tous reparations doit etre faire par personnel qualifié seulment.

2 D SERIES Lake Operation Manual rev 3.0.1

3. Warnings

To completely disconnect this equipment from the AC mains, disconnect the power supply cord plug from the AC receptacle. The mains plug of the power supply cord shall remain readily operable. Français: Pour démonter complètement l'équipement de l'alimentation générale, démonter le câble d'alimentation de son réceptacle. La prise d'alimentation restera aisément fonctionnelle.
To reduce risk of fire or electric shock, do not expose this apparatus to rain or moisture. Français: Pour réduire les risques d'incendie ou de choc électrique, n'exposez pas l'appareil à la pluie ou à l'humidité.
Do not expose this system/apparatus to dripping or splashing and ensure that no objects filled with liquids, such as vases, are placed on the apparatus. Français: N'exposez pas ce système/appareil au ruissellement ni aux éclaboussures et assurez-vous qu'aucun objet contenant du liquide tel qu'un vase n'est placé sur l'appareil.
This apparatus must be connected to a mains socket outlet with a protective earthing connection. Français: Cet appareil doit être raccordé à une prise secteur avec terre de protection.
The mains plug is used as a disconnect device and shall remain readily operable. Français: Lorsque la prise du réseau d'alimentation est utilisés comme dispositif de déconnexion, ce dispositif doit demeuré aisément accessible.
3.3. Caution
To reduce the risk of fire or electric shock, do not remove screws. No user-serviceable parts inside. Refer servicing to qualified service personnel. Français: Pour réduire le risque d'incendie ou de choc électrique, ne pas retirer les vis. Aucune pièce réparable par l'utilisateur. Confier l'entretien àpersonnel qualifié.
3.4. User responsibility
3.4.1. Mains connection grounding
Your amplifier must be connected to a grounded socket outlet.
3.4.2. Speaker output hazard on amplifiers
Amplifiers are capable of producing hazardous output voltages. To avoid electrical shock, do not touch any exposed speaker wiring while the amplifier is operating. The external wiring connected to the speaker terminals shall be installed by a qualified person, or ready-made leads or cords of appropriate capacity shall be used.
As the power output channels on amplifiers produce high voltage, do not connect or disconnect speaker cables when the mains power is on.

3.4.3. Radio interference
A sample of this product has been tested and complies with the limits for the European Electro Magnetic Compatibility (EMC) directive. This equipment has also been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference from electrical equipment. This product uses radio frequency energy and if not used or installed in accordance with these operating instructions, may cause interference to other equipment, such as radio receivers.
This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures:
· Reorient or relocate the antenna. · Increase the separation between the equipment and
receiver. · Connect the equipment to an outlet on a circuit different
from that to which the receiver is connected. · Check if the affected unit complies with the EMC limits for
immunity, (CE-labeled). If not, address the problem with the manufacturer or supplier. All electrical products sold in the EC must be approved for immunity against electromagnetic fields, high voltage flashes, and radio interference. · Consult the dealer or an experienced radio/TV technician for help.
3.4.4. Speaker damage
Amplifier apparatus is very powerful and can be potentially dangerous to both loudspeakers and humans alike. Many loudspeakers can be easily damaged or destroyed by overpowering them. Always check the speaker's continuous and peak power capabilities. Although the amplifiers attenuators can be used to reduce the overall gain, an increase of the input signal can result in full output power, which may cause damage to connected speakers.
3.4.5. Maintenance
For safe and reliable operation, the dust filters on both sides of the front panel, behind the grilles, should be removed and cleaned regularly to ensure maximum airflow through the device.
If the dust filters are not maintained there will be safety risks; for example, high internal temperatures could ignite the dust and start a fire. There is also a risk that the unit will malfunction since it is dependent on constant airflow from front to rear. If the dust filters are not clean and the unit malfunctions, any resulting problems will not be covered by the warranty.

D SERIES Lake Operation Manual rev 3.0.1

3

4. Table of Contents

4. Table of Contents

1. Important safety instructions

2

2. Approvals

2

3. Warnings

2

3.1. Explanation of warning symbols

2

3.2. Warnings

2

3.3. Caution

3

3.4. User responsibility

3

5. Introduction

6

5.1. Welcome

6

5.2. D Series: Two versions available

6

5.3. Feature summary

7

6. Installation

8

6.1. Unpacking

8

6.2. Mounting

9

6.3. Cooling and fan operation

10

6.4. Operating voltage

10

6.5. Grounding

11

7. Product overview

12

7.1. Front panel

12

7.2. Rear panel

13

14 14

8.2. Level Adjustments & Mute Points

14

9. Front panel interface

15

9.1. Frame status and control

15

9.2. Channel status and control

15

9.3. Frame select and ID

16

9.4. Additional front panel operations and indications

17

4 D SERIES Lake Operation Manual rev 3.0.1

10. Rear panel interface 11. Operation and performance
11.1. Operation precautions 11.2. Power output performance
11.4. Power Supply 11.5. Auto power down 11.6. LoadPilot Load Monitoring 12. Lake Processing and Lake Controller 12.1. Introduction 12.2. Modules and Frames 12.3. Lake LoadLibraryTM and Fingerprints 12.4. Loudspeaker Processor Overview
12.6. Frame and System Presets
13.1. Network setup
13.3. System setup 13.4. Additional Software Reference Material 14. Appendix 14.1. Faults and warnings 14.2. Current draw and thermal dissipation 14.3. Maintenance
16. Warranty and support 16.1. General 16.2. Technical assistance and service

4. Table of Contents

18 19 19 19 21 28 29 30 32 32 32 33 33 33 33 34 34 35 36 39 40 40 42 48 49 53 53 53

D SERIES Lake Operation Manual rev 3.0.1

5

5. Introduction
5. Introduction
5.1. Welcome
Thank you for choosing the Lab.gruppen D Series for your sound reinforcement needs. We are confident that you will be pleased with the performance, unique features, configuration flexibility, reliability, and long­term durability offered by this product. For fast installation and use of this product, your welcome package includes a printed copy of the D Series Quick Start Guide (QSG). It provides a brief introduction to the features and functionality of the D Series and it also contains the information required to safely install the product and place it in service. Please read through the QSG thoroughly to become acquainted with the basic configuration and control options available. It is recommended that you also review all other product documentation to ensure familiarity with the various configuration and control options. Thank you again for placing your confidence in Lab.gruppen products.
5.2. D Series: Two versions available
D Series is an advanced, high­power installation amplifier platform designed for demanding applications, primarily in performance venues. For the utmost flexibility in processing and networking, the D Series is available in two versions: the Lake version, with a full slate of Lake processing algorithms and Dante networking; and the Tesira by Biamp version for full integration in a Tesira system and with Ethernet AVB audio transport. D-series Tesira versions are available in three output power levels, whereas the D-series lake versions are available in six output models. The six Lake power output models come in two form factors. Three high power models in a standard form factor and three lower powered models in a slimline, single rack unit, form factor. This operation manual is for use with Lake processing versions only, and applies to models at all six output power levels. The models D 200:4L, D 120:4L, D 80:4L, D 40:4L, D 20:4L and D 10:4L will further on only be referred to as D200, D120, D80, D40, D20 and D10.
6 D SERIES Lake Operation Manual rev 3.0.1

5. Introduction

5.3. Feature summary
5.3.1. Features common to both D Series variants
· Four channels with six levels of total available frame power output: 20000 W, 12000 W, 8000 W, 4000 W, 2000 W and 1000 W · Rational Power Management (RPM)
· True flexibility in allocating power output across each channel to match requirements, for more efficient use of amplifier inventory
· Any channel is capable of being significantly scaled up to match power requirements. · Dedicated on­board surveillance and load monitoring for voice alarm applications · Advanced universal power supply
· Regulated Switch­Mode Power Supply (R.SMPSTM) maintains stability through fluctuations in mains voltage · Best­in­class Power Factor Correction (PFC) · Current Draw Modeling (CDMTM) reduces peak mains draw · Breaker Emulation Limiter (BELTM) responds to available mains distribution · Under­Voltage Limiting (UVLTM) allows continued operation through mains voltage drop · CAFÉ (Configuring Amplifiers For the Environment) software incorporates ESPTM (Equipment Specification Predictor) to assist in design, equipment specification and commissioning · Features controlled by on­board DSP · Amplifier gain is set in the digital domain and controlled via the Lake Controller software. · ISVPLTM ­ The Inter­Sample Voltage Peak Limiter (ISVPL) tailors each channel's power output to the
characteristics of the connected load · Load Verification & Performance Monitoring ­ A comprehensive set of proprietary DSP­based tools
enables load verification and real­time performance monitoring

NOTE: The D200, D120 and D80 models have the possibility to bridge two power outputs to further increase scalability. This feature is not available on the D40, D20 and D10 models.
5.3.2. Features unique to Lake variant
· Lake's exclusive classic/linear­phase/FIR speaker processing platform with four throughputs · Group control with Raised CosineTM MESA EQTM asymmetric filters · LimiterMaxTM peak and RMS limiters · Extensive loudspeaker preset database (Lake LoadLibraryTM) · Comprehensive clocking management system with low latency sample rate conversion · Full support for Dante Controller · Multiple and redundant inputs with programmable failover
· Four "Lake Class" analog inputs with Iso­FloatTM ground isolation · Two AES3 digital inputs (4 audio channels) · Eight dual­redundant Dante network audio inputs · Comprehensive 3rd party protocol for integration potential with third party matrix systems via purpose­ developed middleware

D SERIES Lake Operation Manual rev 3.0.1

7

6. Installation
5.3.3. Other Documentation
This Operation Manual is intended to serve as a guide and reference to the operation and maintenance of the D Series Lake hardware platform. Comprehensive information is given regarding installation, connection and operation of the front panel interface.
D Series Lake amplifiers are designed for configuration and operation using the Lake Controller and CAFÉ software programs. This manual includes a brief tutorial on how to put an amplifier into service using Lake Controller, and it also includes an overview of some features that are implemented via CAFÉ.
For complete information on DSP configuration and operation using Lake Controller, please refer to the Lake Controller Manual, available online at www.labgruppen.com/support.
For detailed information on configuration and operation of the power platform using CAFÉ, please refer to the guide embedded in the software or to the CAFÉ Coach video series available on the Lab.gruppen YouTube channel or via a link on the Lab.gruppen web site.
6. Installation
6.1. Unpacking
Carefully open the shipping carton and check for any damage to the device or the supplied accessories. Every Lab.gruppen product is tested and inspected before leaving the factory and should arrive in perfect condition. If any damage is discovered, please notify the shipping company immediately. Only the consignee may initiate a claim with the carrier or their insurers for damage incurred during shipping. Save the carton and packing materials for the carrier's inspection.
6.1.1. Included in the box
In addition to the D Series device, the shipping carton includes the following items:
· D Series Lake Quick Start Guide · AC mains lead (power cable) with Neutrik powerCON connector (D200, D120 and D80) or IEC connector
(D40, D20 and D10) and AC socket plug according to ordering selection · Rear brackets for additional rear rack support (pair) along with associated mounting hardware · Connector kit including all needed connectors · Front grille and dust filter assembly
NOTE: Depending on the model, the connector kit might include more connectors than applicable for the product you have. Select those connectors required for your unit and application.
Please keep the original carton and associated packaging to facilitate shipping of the device should the need arise.
8 D SERIES Lake Operation Manual rev 3.0.1

6. Installation
6.2. Mounting
D Series is made for mounting in 19 inch racks. Four screw holes are available for attachment of the amplifier to the racks front rack rail. This device has no top or bottom vents; therefore, units may be stacked directly on top of one another. Sufficient space should be available at the rear to accommodate connectors and cables. In addition, allowance must be made for cable or loom bends within a rack.
6.2.1. Rear Mounting
Two rear support brackets, along with associated mounting hardware, are included with the D Series device. It is strongly recommended that these are used wherever possible. Fit the brackets to the vertical rails at the rear of the rack. The following diagrams show the fitting options for fixed and removable installation. The support brackets are reversible and may be fitted to point either to the front or rear of the rack; the proper orientation depends on the rack depth and position of the rear rack rails.
Figure 6.1: Rear support bracket with mounting hardware

Figure 6.2: Rear support bracket mounted for fixed installation and bracket pointing forward

Figure 6.3: Rear support bracket mounted for removable installation and bracket pointing towards rear

D SERIES Lake Operation Manual rev 3.0.1

9

6. Installation
6.2.2. Mounting front grille
The front grille is shipped on top of the amplifier inside the box to protect it during shipping. The front grille adheres to the amplifier with magnets. Hold the front grille with your fingers in each of the side cutouts and slide it gently into place straight from the front.
NOTE: Always ensure the dust filters behind the detachable front panel are clean to ensure maximum possible airflow. The exterior front panel is held in place by powerful magnets but is easy to detach by using your fingers in the openings at the each side. To clean the foam filter, detach it from the exterior front and gently use a vacuum cleaner or gently shake it. Remount with the opposite procedure. Never operate the amplifier without the dust filter installed.
6.3. Cooling and fan operation
D Series devices use a forced­air cooling system with airflow from front to rear, allowing high continuous power levels without thermal problems. To facilitate maximum air flow, ensure that no objects such as rack doors or lids are placed at the front or rear of the rack. Never attempt to reverse the airflow. Make sure an adequate air supply is provided in front of the D Series device, and that the rear of the device has sufficient space to allow air to escape. It is recommended to keep the ambient temperature around the device as cool as possible. An increased temperature can have a significant negative impact on the expected lifetime on the components inside the D Series device.
NOTE: Fit solid blanks (not ventilation blanks) to unused rack spaces to ensure effective air circulation. Leaving gaps in between items of equipment degrades the effectiveness of forced­air cooling.
If installing one or more D Series devices in a rack with other fan­cooled equipment, confirm that all other equipment also uses front­to­rear airflow for cooling. If this precaution is not observed, there is a risk of overheating, as units with the reverse airflow will be drawing in air which has already been heated by the D Series devices.
The D Series device is equipped with a sophisticated temperature sensing system which protects it from any overheating which may occur as a result of inadequate ventilation.
6.4. Operating voltage
D Series has a universal power supply and its mains nominal and operating voltages are specified in the Technical Specifications. D Series can be ordered with a variety of mains plugs. If the mains plug (AC plug) fitted to the mains cable (AC cord) is not appropriate for your country it can be removed and a locally­sourced one fitted instead. If you are not 100% confident of your competence to replace the mains plug (AC plug), the task should be carried out by qualified personnel.
NOTE: In­rush current is controlled and limited during the soft­start sequence. This enables multiple D Series Devices on the same AC mains circuit to be turned on simultaneously.
10 D SERIES Lake Operation Manual rev 3.0.1

6. Installation

6.4.1. Low voltage country considerations
Although the D Series has a wide range of operating mains voltage, some considerations can be applicable for low voltage regions. D Series performs well throughout the specified nominal voltage range but has slightly better efficiency at higher voltages. For regions with nominal voltage below 140 V, one could consider connecting the amplifier in a three phase delta or two phase split-phase configuration, especially applicable for the bigger models, (D200, D120 and D80).

NOTE: Following connections applicable only for resulting voltage inside the amplifiers nominal voltage range.

Connecting the amplifier in three phase delta configuration In three­phase configuration where the phases are 120 degrees apart, one can connect three balanced loads in a delta configuration. The connection is made between the phases instead of between the neutral and a phase.

120V
L1
Amp
N

L2
Amp
120V

208V

L1

Amp

L2

N

120V 208V
Amp
208V

Amp Amp

L3 L3

3 phase Y 120V

3 phase delta 208V

Figure 6:4: Three phase delta configuration

Connecting the amplifier in a split phase configuration In two phase split­phase configuration there are two phases separated by 180 degrees. Connecting between the phases gives double the line voltage.

100V

100V

200V

L1

Amp

N

Amp

L2

Split phase 100V

L1

Amp

L2

N

Split phase 200V

Figure 6.5: Two phase split­phase configuration

6.5. Grounding
D Series must be grounded (earthed) with the safety ground pin to the mains distribution system. NEVER disconnect the earth (ground) pin on the mains cable (AC power cord). Use correctly-shielded balanced audio input connections to minimize hum and interference.

11 D SERIES Lake Operation Manual rev 3.0.1

7. Product overview
7. Product overview
7.1. Front panel
1
1
The front panel consists of an outer front with air intake and a centered user interface. The user interface has LEDs for monitoring and six recessed touch buttons for control. 1 Rack ears for 19 inch rack mount 2 Exterior front grille (also air intake and dust filter holder)
3
3 Touch and LED panel ­ See section 9.1 for further information.
12 D SERIES Lake Operation Manual rev 3.0.1

7.2. Rear panel
1

2

3

4

7. Product overview
5

2

3

4

1

5

1
marked hot (+) and cold (-) terminal 2 Analog Inputs - Analog inputs are available on terminal block connectors with clearly marked hot (+), cold (-) and ground terminals 3 AES3 Inputs - AES3 inputs are available on terminal block connectors with clearly marked hot (+), cold (-) and ground terminals 4 RJ-45 Ethernet connectors for control and Dante digital audio network 5 Mains connector - Detachable Neutrik powerCON (for D 200, D 120 and D 80) or locking IEC connector

13 D SERIES Lake Operation Manual rev 3.0.1

7. Product overview

8. Signal flow, routing and mute points
8.1. Signal flow

device provides seven points in the signal chain where the signal level can be adjusted, muted or disconnected.

Module Data stored in Module FIles (Speaker Presets) Frame Data stored in System Files and Frame Presets

INPUTS Dante Receivers 1-8
AES 1-4 Analog 1-4
AES/Analog pass through
to Dante
OUTPUTS Dante 1-8 (no mutes)

Input Mixer A

Lake Contour Module A

Input Routers
1-4
WITH INPUT MUTES

Input Mixer B

Lake Contour Module B

Input Mixer C

Lake Contour Module C*

Input Mixer D

Lake Contour Module D*

Output Routing

Attenuator Mute
Phase Rev Custom RPM
Attenuator Mute
Phase Rev Custom RPM
Attenuator Mute
Phase Rev Custom RPM
Attenuator Mute
Phase Rev Custom RPM

ISVPL Auto RPM
ISVPL Auto RPM
ISVPL Auto RPM
ISVPL Auto RPM

Amp Gain Amp Gain Amp Gain Amp Gain

LoadSmart LoadSmart LoadSmart LoadSmart

LoadPilot LoadPilot LoadPilot LoadPilot

AMP AMP AMP AMP

1

2

3

4

5

Figure 8.1: D Series Lake Signal Flow Diagram
1 The input section (inputs, input router and input mixer) allows for mixing capabilities as well as redundant and prioritized inputs with automatic switch-over in case of signal failure
2 Up to four Lake Processing modules provide user EQ and loudspeaker processing, including LimiterMax limiting 3 The Output router allows free routing between module outputs and power output channels 4 Each power output channel provides individual channel processing, including ISVPL limiter, RPM and
load monitoring
5

8.2. Level Adjustments & Mute Points

the signal:

1 Input Router Stage 2 Input Mixer Stage 3 Module Input Stage 4 Module Output Stage 5 Output Router Stage 6 Attenuation Stage 7 Amp Gain Stage

Input selection and MUTE Router on /off connection to mixer and gain settings Mute and gain settings Mute and gain settings Output on /off routing connections Power output channel mute and attenuation settings

NOTE: If the required audio signal is not passing correctly, verify the connection, mute and gain settings at all seven stages.

14 D SERIES Lake Operation Manual rev 3.0.1

9. Front panel interface
9.1. Frame status and control

1

25

6

9. Front panel interface

34

7

8

9

NOTE: General status indication shown in Table 9.1. For detailed information on warning and fault indication, please refer to the Faults and Warnings table in Section 14.1.
1 FRAME LED ­ Provides status indication for a number functions affecting the amplifier frame 2 TEMP LED ­ Provides status indication for internal temperatures sensed at multiple points, including power
supply, DSP and output channels 3 PSU LED ­ Provides status indication on functionality of Power Supply Unit and mains supply, including under­
and over­voltage, power supply faults, and unstable mains supply 4 POWER LED and TOUCH BUTTON ­ Provides power state indication and control. Press and hold button to
toggle the amplifier between ON and STANDBY state. LED indication given in Table 9.1.

9.2. Channel status and control
5 LOAD LED ­ Provides load related status indication for monitoring functionality of LoadSmart and LoadPilot. Warnings and faults indicate problems or anomalies detected in the connected loudspeakers and/or cabling
6 AMP LED ­ Provides amplifier related status indication, including faults and warnings related to temperature, over­current, clipping and very high frequency
7 SIGNAL LED ­ Provides signal related status indication, including no signal and input signal clipping 8 MUTE LED and TOUCH BUTTON ­ Provides mute status indication and control. The LED is indicating
both Lake mutes and power channel mute. A single touch on the mute button toggles the power channel mute between mute and unmuted states
9 SELECT LED and TOUCH BUTTON ­ for selection and indication control between computer software and unit

15 D SERIES Lake Operation Manual rev 3.0.1

9. Front panel interface

OFF

Frame

N/A

Green
Frame OK

Amber
Frame warning

Temp PSU Power Load Amp Signal Mute Select

N/A

Temp OK

Temp warning

N/A No mains power No LoadPilot active

PSU OK
Fixed:ON Blinking: Turning ON
LoadPilot active and LoadOK

Power supply/ Mains warning
Button pressed. Hold for transition
Load warning

N/A

Power channel OK

Power channel warning

Output below signal present threshold (­60 dB)
Inactive channel in bridge operation

Output above signal present threshold (­60 dB)
Unmuted

Input signal approaching input clip (­2 dB)
Lake module is muting the signal chain at either input
router, module input or module output

Frame not selected

Frame selected

Waiting for more touches

Table 9.1: LED/category chart

Red
Frame fault
Temp fault
Power supply/ Mains fault
Fixed: STANDBY Blinking: Turning to
STANDBY Load fault
Power channel fault
Input signal clip or limit/fault active
Power channel muted
N/A

9.3. Frame select and ID
9 SELECT LED and TOUCH BUTTON ­ Selects mode and indicates control between computer software and unit. A single touch on the button will select the unit in supported computer software views. Multiple consecutive touches will select the corresponding Lake module (one touch for module A, 2 for module B etc.). In the other direction, when selecting the unit in a supported computer software view, the LED will indicate the unit is selected with steady green illumination.
NOTE: The touch buttons use capacitive touch technology and might be sensitive to large temperature and humidity variations.

16 D SERIES Lake Operation Manual rev 3.0.1

9. Front panel interface
9.4. Additional front panel operations and indications
9.4.1. Frame reset
A factory reset and soft reset can be performed from the front panel. A factory reset will restore all settings to original defaults, including network settings, frame presets and current settings. A soft reset reverts only the current settings to default. Network settings and frame presets are not changed with a soft reset. 6. Place the frame in standby mode. 7. Press and hold Select and channel 3 mute button. Then press the power button. 8. User interface will illuminate available options. Choose from the options below
a. Press channel 1 mute button (red LED) to initiate the factory reset sequence. b. Press channel 2 mute button (amber LED) to initiate the soft reset sequence. c. To cancel, press channel 4 mute button (green LED). 9. Wait state indication is present while either reset is performed. 10. To complete the factory reset process, cycle the mains power by completely removing the power plug and reinserting it.
9.4.2. Wait indication
Wait indication is displayed when the frame is performing an operation. All LEDs except power are unlit and a circling amber light is displayed on channels 1 and 2.
9.4.3. Power cycle required indication
After an operation that requires a subsequent power cycle to complete, the power LED blinks alternately red and green. A Power cycle requires that the mains is completely removed from the device and not connected again until the device has powered off.
9.4.4. Front panel lock
The front panel can be disabled from the Lake Controller. When the front panel is disabled, LEDs 4, 8 and 9 (all buttons on the lowest row) flash in amber when hitting any touch button.
17 D SERIES Lake Operation Manual rev 3.0.1

10. Rear panel interface

10. Rear panel interface

1

2

3

4

5

2

3

4

1

5

For electrical specifications on inputs and outputs, please refer to Technical Specifications in Section 15.
1 Amplifier Outputs ­ The amplifier outputs utilize mating Phoenix­type connectors. Connect loudspeaker cables to the mating plug­in connectors observing polarity (including bridge mode option for D200, D120 and D80) as marked on the rear panel
2 Analog Inputs ­ Analog inputs are available on terminal block connectors with clearly marked hot (+), cold (­) and ground terminals. The inputs are electronically balanced and feature Lake Iso­Float circuitry
3 AES3 Inputs ­ AES3 inputs are available on terminal block connectors with clearly marked hot (+), cold (­) and ground terminals
4 RJ­45 Ethernet connectors for control and Dante digital audio network. Neutrik etherCON connectors accept either mating etherCON connector or a standard RJ­45 connector.
Primary Network Connector ­ The primary connection provides integration into an Ethernet control network which may include other Lake Processors and the Lake Controller software. Network connection permits full control of all functions along with real­time metering from a remote position.
This device supports the Dante audio networking protocol, which allows transmission of multichannel, high­ definition digital audio over the same Ethernet connection.
Use the primary connector when using a star network topology, consisting of individual Cat­5e connections between the devices and an Ethernet switch. Alternatively this connection can be used to daisy chain directly to another Lake Processor. The daisy chain topology should not be used with Dante.
Additional information is also available in the Lake Network Configuration Guide.
NOTE: The Ethernet ports operate at the Ethernet data rate of up to 1 Gbps and allow straight or crossed network cables. LEDs above each port indicate network activity (ACT) and Gigabit network connections (Gbps). If Gbps LED is unlit, speed is 100 Mbps.
18 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
Secondary Connector ­ The secondary network connector can be used to create a Dante dual­network topology by connecting all secondary network connectors to a separate Ethernet switch, ensuring full redundancy in the event of a network component failure. Alternatively, the secondary network connector can be used to daisy­chain multiple Lake devices (LM, PLM, PLM+ or D Series), if Dual Redundancy is Disabled from the Lake Controller. When the device is in Dual Redundancy , it is possible to connect a Lake Controller to the Secondary Connector as long as the IP address on the computer is on the 172.31.x.x subnet.
ed via Lake Controller. See the Lake Controller Operation Manual for further details.
NOTE: When connecting multiple devices to an Ethernet network, care must be taken NOT to create a closed loop which causes network malfunction.
5 Mains connector ­ Detachable Neutrik powerCON (for D 200/120/80) or locking IEC connector (D 40/20/10). For more information, please refer to Section 6.4.
11. Operation and performance
11.1. Operation precautions
Make sure that the Standby button on the unit's front panel is either unlit (OFF), or red (STANDBY), before making any input or output connections. Ensure the AC voltage is within the range printed on the label adjacent to the AC mains connector. Ensure no input signal is present when powering on the unit to reduce the risk of any inadvertent bursts of high level audio.
11.2. Power output performance
The standard form factor D Series units (D200, D120 and D80) uses Lab.gruppen's patented Class TD purity of Class A/B designs. The slimline D Series units (D40,:D20 and D10) uses a newly developed Class D perfectly under all load conditions and the output maintains it with very low nominal impedances. Reliability is very high, and there is no interference with nearby RF equipment.
19 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance

11.2.1. Symmetrical power
D Series models can deliver power as shown in Table 11.1 when all channels are driven equally.

Load Impedance (ohms)
D 200:4L D 120:4L D 80:4L D 40:4L D 20:4L D 10:4L

2 ohms 2.67 ohms 4 ohms

(per channel)

(per channel)

(per channel)

4400 W

5000 W

4400 W

3000 W

3000 W

3000 W

2000 W

2000 W

2000 W

800 W

1000 W

1000 W

500 W

500 W

500 W

250 W

250 W

250 W

8 ohms
(per channel) 2300 W 1900 W 1500 W 1000 W 500 W 250 W

16 ohms
(per channel)

Hi-Z 70 V Hi-Z 100 V

(per channel)

(per channel)

1150 W

3300 W

4700 W

950 W

3000 W

3000 W

750 W

2000 W

2000 W

700 W

1000 W

1000 W

425 W

500 W

250 W

250 W

250 W

175 W

Table 11.1: Symmetrical Load Power Ratings

11.2.2. Rational Power ManagementTM
Rational Power ManagementTM (RPM) is a unique Lab.gruppen feature that allows for flexible allocation of power across channels of a D Series unit. Power that is not used by one output channel is free for use by another output channel with greater demands. Unique to this series is that all models in the range have amplifier channels that can produce higher outputs than the average 25% of the total power, see the Technical Specifications for the maximum single channel power capacity. RPM automatically allocates power up to the total limits of the specific amplifier model and helps minimize unused power in the installation.

Via the CAFÉ Software, desired

er; peak and

RMS voltage; and also the speaker's AES power rating. By specifying the nominal impedance of the load, the RPM

algorithms have all input data required to calculate resulting RPM settings. If the desired RPM settings results in a

total power output higher

reduction in dB. Once applied, the RPM functionality will ensure that all channels are capable

of delivering the

is performed with the ISVPL limiter algorithm. As default the R

the channels at a voltage (default voltage limitation) given in

in two modes.

20 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance

2000 W

SUB

LOW

MID

HIGH

FDigSeurriees -1A1m.2p:chAanmneplscphowaenr nadejulsstepdotowmeartcahdthjue slotueddspetoakemr raeqtcuihremthenetsloudspeaker requirements on a D 80:4
Auto RPM: The frame will automatically allocate power per output channel according to the ISVPL settings in the speaker preset (per module output) in Lake Controller. Auto RPM assumes a nominal impedance of the Load and applies an approximate power allocation. Auto RPM is default for D Series Lake.

Custom RPM: The CAFÉ software allows users to create an advanced custom power allocation scheme. Switching to Custom mode disables the Automatic mode. Additional information is available in documentation supplied with the CAFÉ software download.
Custom RPM using CAFÈ with ESP: CAFÉ (Configuring Amplifiers For the Environment) is a dedicated software application for Windows and OSX that provides tools for system planning, specification and commissioning. CAFÉ incorporates the Equipment Specification Predictor (ESP), a software module that examines SPL and speaker requirements for a project and generates requirements for output power on an amplifier and system level. ESP will generate a custom RPM configuration optimizing the power allocation within the frame. For more information on CAFÉ and ESP, please consult the documentation supplied with the CAFÉ software download.
11.3. Amplifier and Load Protection Systems
The D Series is equipped with a comprehensive set of protection circuits. If operating conditions become sufficiently extreme that any of these circuits become active, indication is provided by amber or red LEDs on the front panel, and by text notifications in the Lake Controller and CAFÉ software. Refer to Section 14.1 for more information on warnings and faults.
21 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
11.3.1. Inter­Sample Voltage Peak Limiter (ISVPL)
The ISVPL is a high quality voltage limiter that can deliver seamless limitation to any desired level. It ensures that the voltage at the output terminals never exceeds the defined threshold. It operates on these principles: · The signal is delayed slightly to allow the ISVPL to look­ahead and reduce the gain before voltage in excess
of the threshold can appear at the output. This results in zero voltage overshoot at the output with a rounded limitation up to the threshold. · The amplitude of the output signal between digital samples is predicted which permits the ISVPL to respond to analog peaks that may occur at the digital to analog converter. · The release time of gain reduction is adaptive depending on the dynamics of the signal. It is possible to select different ISVPL profiles for limiting optimization for a specific frequency band and personal preference. The profiles are divided into two categories, with one category optimized for low distortion and the other focusing on producing high sound pressure level (SPL). Within each category there are profiles optimized for the different frequency bands.
11.3.1.1. Low Distortion Profiles
· Universal ­ The universal profile is a soft limiter that can be used for all frequencies and is conservative in its action upon VCL and CPL.
· Sub/LF ­ The Sub/LF profile is tuned for frequency bands below 600 Hz. It has longer attack and release times and is less conservative when it comes to acting upon VCL and CPL.
11.3.1.2. High SPL Profiles
High SPL profiles do not use the adaptive release time feature. High SPL profiles optimized for high frequencies use less of the look­ahead delay peak­rounding feature; this feature is used most in the Sub profile and least the HF profile.
· Sub ­ The Sub profile is optimized for frequencies between 20 ­ 200 Hz · LF ­ The LF profile is optimized for frequencies between 20 ­ 1200 Hz · MF ­ The MF profile is optimized for frequencies between 300 ­ 6000 Hz · HF ­ The HF profile is optimized for frequencies above 1 kHz
11.3.1.3. ISVPL Voltage Settings
The ISVPL threshold may be set at any level between 17.8 V and 600 V in the Lake Controller software. For further details, please refer to the Lake Controller User Manual.
Lake­enabled amplifier devices (D Series Lake, PLM+, PLM) that have a smaller peak output voltage capability still allow ISVPL speaker threshold settings up to 600 V. When a threshold is set above the current maximum capability of a power output channel, the actual ISVPL will automatically be set to the maximum ISVPL for that channel. Therefore, the ISVPL threshold can be set at the Module for the speaker's maximum capability, and the Module file remains cross­compatible with all Lake­enabled amplifier devices.
Table 11.3 shows the theoretical maximum output power based on only the load impedance and the ISVPL setting. See the Technical Specifications, or use CAFÉ, to find the available power for a specific amplifier and load.
22 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance

Max. Sinewave Burst Power (Watts)

LLoad Impedance (ohms)
LISVPL SETTING (V peak)
194 193 181 167 153 121 101 83 70 56 47 38 17.8

2

2.67

4

8

16

4489 4489 4489 4489 4489 3660 2550 1722 1225 784 552 361
79

5993 5993 5993 5223 4384 2742 1910 1290 918 587 414 270
59

4705 4656 4095 3486 2926 1830 1275 861 613 392 276 181
40

2352 2328 2048 1743 1463 915 638 431 306 196 138
90 20

1176 1164 1024 872 732 458 319 215 153
98 69 45 10

Table 11.3: ISVPL­to­output examples

11.3.2. Current Peak Limiter (CPL)
The output Current Peak Limiter (CPL) ensures that the power output section will not be damaged by forcing it to deliver current levels at the outputs that exceed the maximum current ratings of the output transistors. The CPL keeps the output transistors within their Safe Operating Area (SOA). The CPL is non­adjustable.
This condition indicates an attempt to draw excessive current at the output. The output is attenuated until the output current falls below the maximum current rating. Limiting is performed by the ISVPL limiter in conjunction with the selected ISVPL profile.
CPL activity is shown by amber or red indication on Amp LED of the affected output channel and a corresponding text description in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults.

NOTE: If excessive current is indicated, check the output cables and examine the loudspeaker. If impedance appears normal, you may rectify the condition by altering the ISVPL settings or lowering input levels. CPL indication can be triggered by excessively low load impedance, possibly the result of too many loudspeaker cabinets connected in parallel.
11.3.3. Power Average Limiter (PAL)
The Power Average Limiter Active warning (PAL Active) will be displayed when the power supply is operating at the maximum average input power allowed for the PSU design. When this warning is displayed, gain limiting is being applied to the signal by a lowering of the ISVPL threshold.

23 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance

PAL activity is shown by PSU amber LED indication and a corresponding text description in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults.

11.3.4. Breaker Emulation Limiter (BELTM)
The BEL models the temperature in the external breaker and limits the mains current to prevent the breaker

be selected for Frame Replace support). The desired nominal current value can be set from 1 to 32 Arms. The

resulting

models

is set above, or bellow, the model's capabilities, the actual current is automatically adjusted into

the

:

· ·
allows current above the threshold to pass for a short time, leading to an increased modeled temperature. For the limiter to disengage, the current must reduce below the threshold to enable the breaker to cool down. · momentarily allows current above the threshold for a longer time, leading to an increased modeled temperature.
ed current for the breaker to cool down.

predict the current consumption, with the exact speaker requirements, and propose a safeguarding

11.3.5. Under Voltage Limiter (UVLTM)
The larger D Series devices (not D 20:4L and D 10:4L) are equipped with an under voltage limiter. With multiple, powerful devices on a mains distribution line, heavy current loads risk the reduction of voltage below that required for devices to function. The UVL reduces the mains current draw when voltage drops below 80 V. The amount of reduction applied increases as mains voltage drops towards 65 V; at 65 V the power supply is
automatically restarts.
11.3.6. Current Average Limiter (CALTM)
The Current Average Limiter (CAL) monitors the RMS current drawn from each power output channel to ensure that the power output stages are not overloaded. When activated, it regulates the current to a safe level to protect the channel. The CAL should not be activated in normal usage. If activated, this is shown by amber or red indication on the Amp LED of the affected output channel and a corresponding text description in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults

24 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
NOTE: For Slimeline models, to optimize the CAL's behavior when playing into a low impedance load, manually set the desired ISVPL to reflect the real peak voltage output to allow for a higher average current.
11.3.7. Voltage Clip Limiter (VCL)
If current draw from the unit's power supply is too high, the PSU's regulation capability may be exceeded and the internal voltage rails may drop and cause clipping. If this occurs, the VCL acts rapidly to prevent clipping on the subsequent peaks. Limiting is performed by the ISVPL limite Indication of this condition is shown on the output LEDs. Refer to Section 14.1 for more information on warnings and faults.
11.3.8. Temperature Protection
D Series devices are equipped with a sophisticated temperature sensing system that provides protection from overheating which may occur as a result of inadequate ventilation or excessive power output. Thermal measurements are made at several points within each power output channel along with measurements in operate continuously, with the highest possible output, and prevent shutting down. If temperature in any area reaches a critical level, a warning is displayed. The warning is issued at approximately 80% of the maximum allowable temperature. If the temperature continues to increase, a limiter (ATL or PTL) is engaged that limits signal peaks to reduce further heat accumulation. Limiting is accomplished by gradual reduction of the ISVPL thresholds. In the extreme case where the limiter cannot reduce heat accumulation and temperature reaches a dangerous level, a fault is displayed and audio is muted. Each power output channel, the power supply, and DSP area have separate indications. For all temperature faults, temperature monitoring will continue at 0.5 second intervals, with the output remaining muted. When the area has cooled below the dangerous threshold, the fault condition is cleared and audio is restored.
11.3.8.1. Power Output Channels
A power output channel temperature warning or fault is indicated by the Amp LED for that channel and the Temp LED for the frame. · A warning is indicated by a static amber LED · · A fault is indicated with a static red LED An event report is sent to the Lake Controller software for both the warning and the fault. If a temperature fault condition arises on a power channel, the output of that channel will be muted.
25 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
If the amplifier output channel temperature keeps rising after reaching the temperature warning threshold, the Amp channel Temperature Limiter (ATL) will engage at approximately 95% of the maximum allowable temperature. When ATL is engaged, it will try to reduce the power output to avoid that the amp channel goes into temp fault, i.e. muting. Limiting is removed when temperature falls below the ATL threshold.
11.3.8.2. Power Supply / DSP
A power supply (PSU) or DSP temperature warning or fault is indicated by the Temp LED. · A warning is indicated by static amber LEDs · Power supply Temperature Limit (PTL) is indicated by an amber LED · A fault is indicated with static red LEDs
If the power supply temperature keeps rising after reaching the temperature warning threshold, the Power supply Temperature Limiter (PTL) will engage at approximately 95% of the maximum allowable temperature. When PTL is engaged, it will try to reduce the total amplifier output power to avoid that the power supply goes into temp fault, i.e. muting of all channels. Limiting is removed when the temperature falls below the PTL threshold.
11.3.9. DC Protection
The DC protection is implemented, individually, on each power output to prevent damage to connected loudspeakers or any D Series components. DC present at the output will cause the unit's power output module breaker to blow, causing a permanent hardware fault that prevents signal throughput. In this instance the channel's Amp LED will illuminate red and a service channel fault will be registered in the Lake Controller and CAFÉ status views (D200, D120, D80 only). For the D40, D20 and D10, no audio will be heard from the outputs.
NOTE: A blown breaker in the power output module is not a user serviceable fault condition and the unit should be returned for repair.
11.3.10. VHF Protection
The D Series includes protection circuits that detect Very High Frequency (VHF) content in the input signal. The detection is amplitude­, frequency­ and time­dependent. It is initiated from 10 kHz upwards and, if continuous VHF signals are detected above the threshold for more than the attack time, the output for a D200, D120 and D80 will attenuate the gain until the signal is below the VHF threshold. When this is done, VHF Warning is displayed. If the signal is above the VHF threshold and the maximum of -12 dB of gain reduction is not enough to take the signal below the VHF threshold, the signal will mute after 15 seconds, and retest the signal after 6 seconds. Note that the D40, D20 and D10 will go directly to mute upon VHF detection.
normal operation.
This protection system recognizes only continuous VHF signals at high levels that will not appear in speech or music. Any such content can therefore be considered as a fault condition. VHF protection is essential to avoid damage to HF drivers. VHF protection is dependent on a combination of output power level and frequency. Figure 11.4 shows a decreasing power threshold, from approximately 10 kHz upwards, which illustrates increasing sensitivity of the protection system with frequency. When continuous output power above the threshold line is detected, VHF protection becomes active.
26 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance

Voltage [Vrms]

100 90 80 70 60 50 40 30 20 10 0 0

Trigger voltage

5

10

15

20

25

30

Frequency [kHz]

Fig 11.4: VHF Protection Frequency Sensitivity

The attack time of the VHF protection circuitry also changes with frequency, becoming shorter at higher frequencies. This is shown in Figure 11.5.

Time [ms]

1400
1200
1000 800
600
400 20
200
0 0

Full output voltage

5

10

15

20

25

30

Frequency [kHz]

Fig 11.5: VHF Protection Attack Time Variations

The VHF pr

solely to detect

continuous VHF content. HF content of normal music or speech signals at peak levels will be passed in full.

Operation of the VHF protection circuits is indicated by the channel's AMP LED that will illuminate yellow and

display VHF Warning when the max of -12 dB of gain reduction is applied (only applicable for D200, D120

and D80) and light red for a VHF FAULT. Both of these will be registered in the Lake Controller and CAFÉ

status views.

11.3.11. Short Circuit Protection
A low impedance or short circuit at the power output terminals is detected when the output current is high (Current Peak Limiter is active) and, simultaneously, the peak output voltage is below a predetermined threshold. When this situation occurs, the output stage is muted to protect it from damage.

Operation of the short circuit protection system is indicated by Amp channel LED showing steady red and a corresponding text description will register in Lake Controller and CAFÉ software programs. Refer to Section 14.1 for more information on warnings and faults.

27 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
The presence of a short circuit (or low impedance) is re­tested every six seconds, and the output remains muted until the fault clears.
11.3.12. Power supply protection
The power supply is very advanced and has several internal control and monitoring functions. Should any of these fail, the power supply will shut down to prevent damage or limit severity of the failure. If the power supply shuts down audio will be muted. Power supply faults, or power supply needs service faults, are indicated by a red LED and associated error messages registered in Lake Controller and CAFÉ software programs. In the extreme event of simultaneous low mains voltage supply and high power demand, the amount of incoming
supply will then be forced to shut down. This condition is a power protect fault, indicated with a red LED and associated error messages registered in Lake Controller and CAFÉ software programs.
11.3.12.1. Mains anomaly protection
mains service. Over­voltage ­ If the power supply detects mains voltage above 400 V peak or 270 V RMS, it will enter protective associated error messages will register in Lake Controller and CAFÉ software programs. Under­voltage ­ If the power supply detects mains voltage of less than 65 V (not available on D10 and D20), it will enter protective shut down mode. The amplifier will auto­restart if the condition clears. Will be indicated by a red LED and associated error messages will register in Lake Controller and CAFÉ software programs.
Mains instability ­ If the power supply detects protracted instability in the AC mains, it will enter protective shut down mode (D 200:4L, D 120:4L and D 80:4L only). The ampli Will be indicated by a red LED and associated error messages will register in Lake Controller and CAFÉ software programs. Mains glitch ­ If the power supply detects a momentary mains glitch (missing cycles) at the AC inlet, a warning indication will be reported with a yellow LED and associated error messages will register in Lake Controller and CAFÉ software programs (D 200:4L, D 120:4L and D 80:4L only). The powers supply and product continue operation throughout a mains glitch.
11.4. Power Supply
The R.SMPS (Regulated Switch Mode Power Supply) is designed to keep supply voltage rails at optimum levels. Thus the R.SMPS can deliver full rail voltage to the output sta consistent transient response and a clean LF response.
28 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
D Series features a universal power supply with power factor correction (PFC). The device can accept any mains voltage, from 65 V to 265 V, allowing it to function worldwide in many different configurations. The PFC reduces current peaks on the lines and reduces the requirements placed on the mains distribution system. D Series units offer an unparalleled power factor extremely close to one.
11.4.1. Low Inrush Current
High power amplifiers with inadequate inrush current limiting can draw considerable current from the mains at turn­on, sometimes tripping a fast­acting mains breaker. The D Series, however, has very low inrush current to prevent tripping of breakers. Several units can, under normal conditions, be powered up simultaneously. If you do experience problems powering up multiple units simultaneously, they must either be turned on manually in an ordered manner, or sequenced remotely using the Lake Controller software's Global Control feature. Alternatively, the capacity of the mains supply should be increased.
NOTE: If insufficient power is available to allow simultaneous power­up, then there is probably insufficient capacity for full power output during operation. It is recommended that additional capacity is added to the mains power distribution system.
11.4.2. Adaptive rail control
The D Series slimline models have Adaptive rail control available in Performance (default) and Green mode. In Green mode, this feature further increase the slimline models green credentials by lowering the idle consumption. This is achieved by lowering power supply's supply voltage, to the
raised, to allow for full power outtake, as soon as the signal returns. This feature is user controlled via the Lake Controller, where it can be turned on or off.
11.5. Auto power down
The D Series models have been equipped with a Auto Power Down function. If Auto Power Down is enabled, user-defined
audio passing and there is no user interaction via the Lake Controller, CAFÉ or 3rd party controllers. When the
the frame will turn on again.
NOTE: There is no Auto Power On feature on the return of signal, the device will need to be actively turned on after entering the standby mode via the Auto Power Down feature. This can be done from the network via the Lake Controller or the 3rd party protocol or via the front panel button.
29 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
11.6. LoadPilot Load Monitoring
11.6.1. Introduction
LoadPilot is a feature in D Series amplifiers that can continually monitor the integrity of loudspeakers and cables connected to the outputs to ensure that they are functioning properly and free from major anomalies or faults. By implementing LoadPilot, systems incorporating D Series amplifiers can be certified in compliance with voice evacuation standards such as EN54­16 and NFPA72.
LoadPilot functions by automatically superimposing low­level pilot tones on the input signal (if any present) to the amplifier. One tone is below the range of human hearing (approximately 10­20 Hz) and the other above (24 kHz), so the activity of LoadPilot is inaudible regardless of whether the system is currently reproducing program content. High­resolution current sensing on the outputs can calculate the impedance of the load at the frequency of the tones. Hence a stable measurement of the impedance of the load can be obtained and potential anomalies or faults can be detected that would indicate impaired loudspeaker function or total inoperability due to failure of the loudspeaker or faults in connected wiring. The superimposition of pilot tones and analysis is interleaved across the amplifier's output channels with a maximum total cycle time of around 20 seconds.
LoadPilot is implemented and configured in the CAFÉ software. Monitoring status and fault indication are displayed on the front panel and both in CAFÉ and Lake Controller.
LoadPilot may be configured with the automatic calibration or through a manual advanced mode, depending on monitoring requirements and characteristics of the connected loudspeaker loads.
11.6.2. Automatic calibration 11.6.2.1. Functional description
Automatic calibration is suitable for the following applications and requirements for error detection: · If one or two low­impedance loudspeakers are connected; if two in parallel is default, it will warn if one is
missing. · If there are one or two "spurs" with 70V loudspeakers connected; if two in parallel is default, it will warn if one
is missing. · If there is a short circuit in the load. · If there is an open circuit (all loudspeakers missing). · For passive 2­ and 3­way loudspeakers, if one or two LF drivers are connected and working; if two in parallel
is default, it will warn if one is missing. · For some passive 2­way designs, if one HF driver is disconnected. (However, with some loudspeakers the
HF impedance is dominated by a passive component i.e. crossover filter and the anomaly will not be detected.)
NOTE: LoadPilot is enabled only when the amplifier is On. It does not function while the amplifier is in Standby.
30 D SERIES Lake Operation Manual rev 3.0.1

11. Operation and performance
11.6.3. Manual configuration 11.6.3.1. Functional description
Manual configuration can be used in special cases where proper functioning requires setting of custom measurement frequencies, custom measurement levels, custom warning thresholds, or combinations of the three. Manual configuration addresses the following issues:
Speakers with non stable impedance ­ For the LoadPilot feature to function the load itself needs to have a stable impedance at the frequency of the tone. Resonances in the speaker or other non linear phenomenons can make the impedance at a certain frequency unstable. Stability needs to be verified by examining the impedance response to make sure it is relatively flat at the tone frequencies and by verifying LoadPilot readings when playing signal through the speaker at the most extreme expected level. The frequency of the pilot tones can be changed within certain ranges and a tone can be disabled. If a frequency where the speaker is stable can not be found one tone can be disabled and LoadPilot relies solely on the remaining tone.
High noise levels ­ To obtain accurate impedance measurements, it is necessary to drive a current sufficiently above the noise floor. However, it is important to keep the level low in order to prevent audible artifacts from cone travel. At very high impedances, the drive current may be insufficient. In the automatic mode, level is set around 60 mV which produces usable results for impedance up to 660 ohms.
Inductance in loudspeaker cables ­ Loudspeaker cable inductance at higher frequencies is very high relative to passive resistance, and the inductance increases linearly with length. Consequently, monitoring at the 24 kHz pilot tone frequency can be problematic with very long cables. The automatic mode will estimate cable impedance for 24 kHz and allow it to be used as long as it is less than 33% of total impedance presented by the load and as long as the total impedance is below about 440 ohms.
DC blocking capacitors in loudspeakers ­ Some loudspeakers incorporate a capacitor designed to block damaging voltages at very low frequencies. This may inhibit accurate measurements when using the 10 Hz pilot tone. In automatic mode, LoadPilot will disable the 10 Hz tone if total impedance is above about 440 ohms.
Constant voltage loudspeakers ­ Loudspeakers driven via transformers in 70V/100V solutions are more likely to exhibit wide variations in measured impedance as music and/or pilot tones are reproduced by the system. Also, most constant voltage systems operate more than two loudspeakers in parallel. Therefore, in addition to manual configuration of LoadPilot, additional step may be required. These include:
· Insertion of a series capacitor in each loudspeaker to block the 10 Hz LF tone ­ This will defeat measuring the loudspeakers with the LF tone, but will allow the LF tone to propagate through the entire cable run.
· Insertion of EOL (end­of­line) resistors ­ This enables LoadPilot to detect cable faults in a spur of the system. · Insertion of EOL (end­of­line) inductor ­ This is not mandatory, but it will avoid the loss of level at mid and high
frequencies due to the EOL resistor.
NOTE: Manual configuration of LoadPilot is implemented in CAFÉ versions 1.1.0. and later. For detailed information on manual configuration of LoadPilot, please refer to the integrated guide in the software program and to the CAFÉ Coach videos posted on the Lab.gruppen web site and on the Lab.gruppen channel on YouTube.
31 D SERIES Lake Operation Manual rev 3.0.1

12. Lake Processing and Lake Controller
11.6.4. Indication
The LoadPilot feature constantly monitors the impedances at the two given pilot tone frequencies and compares to the measured thresholds. The following faults and warnings can be triggered.
· Speaker shorted warning ­ Both tones below lower threshold. Corresponds to a distant short circuit that can either be in the cabling or in the speaker.
· Speaker damaged warning ­ One of the tones is below or above thresholds. Corresponds to an unexpected impedance deviation of one of the tones, most likely a damage to the speaker.
· Under speaker count warning ­ Both tones above upper threshold. Corresponds to an impedance increase across the impedance response and most likely a loss of speaker(s) in a parallel speaker connection.
· No load fault ­ At least one tone above measurable area or significantly above upper threshold. Most likely corresponding to loss of the load.
· Short circuit fault ­ LoadPilot analysis below short circuit threshold.
12. Lake Processing and Lake Controller
12.1. Introduction
D Series Lake integrates seamlessly into the Lake Processing environment, providing all features, functionality and connectivity associated with all Lake Processors. The internal Lake Processing, which includes programmable crossovers, EQ, dynamics and other functions, is fully controllable via Lake Controller software with a version number of v6.3 for D 200:4L, D 120:4L and D 80:4L, v6.5.0 for D 20:4L and D 10:4L and v6.5.1 for D 40:4L. All models are compatible with newer versions of the Lake Controller. Additional information is available in the Lake Controller Operation Manual and Lake Network Configuration Guide, both available on www.labgruppen.com. Also, additional documentation is available from the Start Menu after software installation.
Visit http://labgruppen.com to download the latest software, firmware and documentation for your devices.
12.2. Modules and Frames
A Frame represents one physical Lake Processor device (e.g. a D 200:4L). A maximum of four Modules are contained within each Frame; these are referred to as Module A, B, C and D. The number of Modules shown in a given Frame is dependent upon the signal processing configuration of that Frame.
ed as a Classic Crossover (Bessel, Butterworth, Linkwitz­Riley), as a Linear Phase
Contour Classic 1 Way (CL1­Way) Output Modules, providing a total of four Module outputs that can be routed to any of the four power outputs, but default is one to one (input 1 -> output 1 etc.). Please refer to the Lake Controller Operation Manual for further information.
32 D SERIES Lake Operation Manual rev 3.0.1

12. Lake Processing and Lake Controller

12.3. Lake LoadLibraryTM and Fingerprints
are available in the Lake LoadLibrary,

as SpeakerPresets

Additionally, Lake LoadLibrary loudspeaker types may also include data relating to the electrical characteristics of a on the device. This data set is termed a Fingerprint. When a sp

12.4. Loudspeaker Processor Overview
The Lake Processing system within D Series Lake devices may be configured with up to four processing Modules containing a total of up to twelve processing Module outputs that can be routed to any of the four power output channels. Each set of processing elements is referred to as a Module and can be configured as crossovers, full bandwidth auxiliary outputs, or a combination of the two. The relationship between inputs and outputs is defined via the Lake Controller.
The Lake Processing system provides two distinct categories of crossovers: · Infinite Impulse Response filters (IIR) such as the classic Bessel, Butterworth or Linkwitz­Riley types; these are
available with slopes ranging from 6 dB/octave to 48 dB/octave. · Finite Impulse Response filters (FIR) providing zero phase shift with steep transition slopes at the crossover
frequencies. These are also referred to as Linear Phase Crossovers.

12.5. Module, System and Sub­System Configuration Files

in Red and Frame data in Blue. ·

See Figure 8.1 where Module data is highlighted

possible to store a Module File directly on the hardware device. ·

12.6. Frame and System Presets
The entire processor configuration can be stored as a Frame Preset on this hardware device. Presets can be recalled) via the Lake Controller software or Preset Manager utility; presets can be stored using the Lake Controller software or Preset Manager utility. A maximum of 100 Frame Presets can be stored on this device. The data within a Frame Preset encompasses the configurations of all Modules in the Frame, including levels, crossover, EQ, input mixer, routing, and all other parameters. As Frame Presets are stored in the hardware device, recall is available without using a PC.
33 D SERIES Lake Operation Manual rev 3.0.1

13. System configuration tutorial
Using the System Presets function in the Lake Controller, entire system configurations can be stored and recalled across a network of Lake devices, including D Series Lake, LM, PLM and PLM+ Series devices. This enables fast retrieval and switching of entire system configurations as minimal data is being sent between the Controller and Processors.
13. System configuration tutorial
This section will describe how to get started with associated software and set up a basic system for operation.
13.1. Network setup
13.1.1. Network connections/topology
Each frame has two network ports; a primary and a secondary. See the below diagram for a typical network topology using the primary ports. By default, the secondary ports are configured in dual redundancy mode to support a second redundant network. The alternate configuration for the two ports is a switch mode which allows daisy­chaining devices in a single network. Daisy chain mode is not recommended for more than a few devices, and for not more than two if running Dante audio along with control data.

Computer

Switch

D Series Lake D Series Lake D Series Lake D Series Lake D Series Lake D Series Lake

Wireless Access Point

Switch

D Series Lake D Series Lake D Series Lake D Series Lake D Series Lake D Series Lake

NOTE: If using Dante audio in the network, the audio traffic needs to be filtered from reaching the wireless links.
13.1.2. Network configuration
Frames are configured by default to obtain IP addresses automatically. The frame will assign itself an IP address in the link local range (169.254.1.0 through 169.254.254.255). If a computer is configured the same way
34 D SERIES Lake Operation Manual rev 3.0.1

13. System configuration tutorial
(which should be default on modern operating systems), it will reside in the same subnet as the devices and communication can be established. Alternate configurations would be DHCP for a managed network or fixed IP. To connect to the secondary network in dual redundancy mode the computer shall be configured with an IP address in the 172.31.0.0 ­ 172.31.255.255.
13.2. Software installation and firmware update
13.2.1. Lake Controller software suite
1. The Lake controller software suite includes the Lake controller and accompanying utilities: Lake LoadLibrary, Dante discovery services and documentation. Download the Lake Controller installation from www.labgruppen.com.
2. Execute the installer and follow the on­screen instructions. This is a typical software installation where the default settings are acceptable for the vast majority of users.
13.2.2. CAFÉ software
1. The CAFÉ software is available as a separate installer on www.labgruppen.com. 2. Execute the installer and follow the on­screen instructions. This is a typical software installation where the
default settings are acceptable for the vast majority of users.
13.2.3. Firmware update
The latest firmware for the product is included in the Lake controller installation. It is likely that firmware installed on the new product is older and requires updating.
1. Make sure all frames are powered on and connected through a wired network. 2. Launch the Lake firmware update utility LakeUpdate.exe. 3. Select the appropriate product range. 4. If more than one network adapter is enabled, a prompt will appear requiring selection of the adapter connected
to the frames. 5. If prompted, allow the application access through the Firewall. 6. Latest firmware is preselected. 7. Discovered frames are listed. Tap Select Old and Update to initiate firmware update of all outdated frames.
Frames already up to date will not be selected. 8. Read warning message and tap OK. 9. Wait for all updates to be completed. A wait indication will display on the unit(s) during updating. 10. Follow the on screen instructions. Amplifiers with firmware associated with Lake Controller 6.5.0 or later will
automatically power cycle the mains power, whereas amplifiers with older firmware will display a message that a manual power cycle is required. (Note: A manual power cycle requires the mains plug to be completely removed, the standby button does not complete the firmware update.) 11. If internal updates are needed, these will be performed by the frame after the power cycle. A wait indication is displayed. 12. Tap Exit to close the update utility.
35 D SERIES Lake Operation Manual rev 3.0.1

13. System configuration tutorial
13.3. System setup
This tutorial provides a step­by­step guide for configuration of a typical professional loudspeaker system and provides an overview of the basic features and operation of the frame. This tutorial describes how to configure 4­channel frame for use with a generic 3­way loudspeaker system (with separate HF, MF and LF drivers), plus a separate subwoofer. It assumes that the system is fed with analog outputs from a mixing console with one fullrange main output and a separate sub feed.
1. Connect the loudspeakers to the four power output channels: a. Channel 1 ­ Low Frequency Driver b. Channel 2 ­ Mid Range Driver c. Channel 3 ­ High Frequency Driver d. Channel 4 ­ Subwoofer
2. Connect the main output of the mixing console to analog input 1 of the frame and the sub feed to input 2. While configuring, it is a good practice to make sure the volume is turned down on the console.
3. Ensure the frame is powered on and is in its default state, and that the computer has established an active Ethernet connection.
4. On the Tablet PC, launch the Lake Controller software application. Select the appropriate network adapter if more than one is enabled, and tap NO to the dialog asking whether to load the previous configuration.
5. Tap MODULES button on the menu bar at the bottom of the screen to access the Module Menu and scroll bar.
6. On the Module scroll bar, the frame is represented with a frame containing four discs. These are labeled A, B, C and D, each representing one of the four Lake processing modules.
7. Tap the frame to select it, then tap again in the MAIN area of the screen to place all modules of the frame in the current system configuration. The Lake Controller uploads settings from the frame.
8. Tap the icon for Module A; its border will turn yellow to confirm selection and an LED on the front panel of the associated device will illuminate.
9. Tap the Module Store/Recall button on the Modules Menu; the menu will change to show additional options. 10. Double­tap the Default Modules folder, then double­tap the Contour Classic Crossovers folder. A set of
loudspeaker symbols will be displayed. 11. Tap CL3way, and then tap the RECALL button. This configures the DSP for the Module A as a 3­way
crossover for the 3 way speaker. 12. Tap Yes when asked to confirm that all data will be overwritten. 13. An Output configuration dialog will pop up to allow for routing of module outputs to power channels. Tap the
orange number buttons in the matrix to un­route, freeing up a power channel. Tap a blue number button at the intersection of the appropriate module output and power channel, routing the module output to the power channel. Proceed until you have routing according to the picture below and tap the bottom right return button to exit the dialog.
36 D SERIES Lake Operation Manual rev 3.0.1

13. System configuration tutorial
14. The B module is already a CL1way as default and can be used to drive the sub. 15. Tap Store/Recall EXIT to return to the Modules Menu. 16. Ensuring Module A (or any other module that you want to control) is selected (yellow border), tap I/O Config.
17. The right side of the I/O CONFIG screen displays a block diagram for the Modules. Tapping the different blue blocks will access the configuration screens for Input mixer, Levels, Input EQ, Delay and Output EQ/Crossover respectively. The magnifying glass at the far right end accesses the output configuration. (NOTE: Tapping the blue return button (left arrow), or the EQ/Levels EXIT button in the menu bar returns to the I/O Config screen from the various configuration screens.)
Input Mixer Configuration ­ Drag sliders and tap ON/OFF buttons to control input mixer settings.
37 D SERIES Lake Operation Manual rev 3.0.1

13. System configuration tutorial

Levels Control ­ Drag sliders and tap mute buttons for module input and output channels.

Parametric EQ control ­ Select filter on the top squares and adjust filter properties by dragging the controls. Sliders at the bottom control center frequency and Q (bandwidth). Gain is controlled in the main window area. Additional filters can be added by tapping the top filter objects and placing new filters on the main area.

Delay Control ­ Drag sliders to control input and output delay

Crossover control ­ Select filters and drag on the bottom frequency bar to adjust crossover frequency. Crossover types may be changed by selecting the Crossover Functions button.

18. Tap the Input Gain button in the block diagram and unmute the Module Input Mute. Tap EQ/Levels Exit to return to IO Config.
19. The left side of the IO config screen holds frame configuration and summary for Clock configuration, Input configuration, Dante configuration, Breaker Emulation Limiter configuration and Analog Iso­Float & AES Termination configuration. All these configurations should be correct by default for this example.
20. From I/O config, tap Amplifier Events & Control and navigate to the Status tab. Unmute the power channels and
slowly increase the volume on the appropriate feed from the mixing console. Audio should now be active at the outputs and heard through the loudspeakers. Close the Amplifier Events & Control dialog with the return button
and return to the main area by tapping the I/O Config EXIT button.

Amplifier Events & Control, Status tab ­ Drag sliders to adjust power channel attenuation and tap mute buttons to control power channel mute. Metering and Status monitoring is available for each power channel.
38 D SERIES Lake Operation Manual rev 3.0.1

13. System configuration tutorial
21. Repeat step 16 and 20 for the B module. On the Output EQ/Crossover, tap the Aux Output Functions button on the menu bar and then tap LPF Enable button. Drag the Low pass filter control object on the frequency slider just above the menu bar to an appropriate crossover frequency for the sub, e.g. 100 Hz.
22. Use the control options mentioned in 17 to tune your loudspeakers. For larger systems, modules can be placed in groups (Groups menu from the MAIN page) for control of multiple units.
23. Some features like RPM can only be configured from within CAFÉ software. Return to AMPLIFIER EVENTS & CONTROL; from the main area hit MODULES button, select a module (e.g. Module A), tap I/O Config, tap AMPLIFIER EVENTS & CONTROL, and navigate to the Control tab. The CAFÉ button (next to bottom) opens the CAFÉ application and imports and highlights the current amplifier and its RPM view.
CAFÉ, RPM view ­ Enter power requirements and impedances for the channels to configure RPM.
13.4. Additional Software Reference Material
Additional information regarding configuration of Lake Controller for specific loudspeaker systems is available in the Lake Controller Operation Manual, available for download in PDF format at www.labgruppen.com/support. Additional information on configuration of CAFÉ software is available in an integrated guide in the software program and in the CAFÉ Coach videos posted on the Lab.gruppen web site and on the Lab.gruppen channel on YouTube.
39 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

14. Appendix

14.1. Faults and warnings

Category/Type
FRAME Warning

Name
Lake Controller offline

Warning Warning Warning Warning Warning

AES / Dante clock slipping
Dante device name conflict
Dante module not detected Dante module with
incompatible firmware Dante module disabled

Warning

Sense fault DSP

Warning Fault Fault
TEMP Warning

A/D converter power supply fault Audio Fault
DICO communication fault
Temperature warning power supply

Warning Warning Warning

Temperature warning DSP area
Power supply Temperature Limit
Amp channel Temperature Limit

On screen text

Description

Action

CTRL OFFLINE
CLOCK SLIPPING NAME CONFLICT
DANTE NEEDS SERVICE
DANTE FW INVALID DANTE DISABLED

Frame unable to find Lake controller on the network

Check network cabling/ network if controller
expected on the network

Frame not able to lock to incoming AES stream or Dante clock slipping.

Check AES sender and
clock configuration or Dante clock settings

Two or more devices on the network with the same Dante name

Review Dante configuration

Lake cannot detect a functioning Dante module

Restart device; if not cleared it needs service
to operate Dante

Dante module not loaded with correct FW

Retry updating the firmware with LakeUpdate

Dante module not communicated correctly or other internal configuration fault

Restart device; if not cleared it needs service

SENS FLT:DSP

Voltage and current sensing on amplifier output faulty. Audio continues but protection might be compromised. No load monitoring

Restart device; if not cleared it needs service

A/D PSU FAULT AUDIO FAULT DICO COMM FAULT

Voltage supply to the analog input converters faulty
Internal audio interface not functioning
Communication fault between host and amplifier platform

Restart device; if not cleared it needs service for
analog input to work
Restart device; if not cleared it needs service
Restart device; if not cleared it needs service

TEMP WARN:PSU TEMP WARN:DSP
PTL ACTIVE ATL ACTIVE

Power supply temperature approaching critical levels

Improve cooling or reduce output power to avoid temperature becoming critical

DSP area temperature approaching critical levels
Amplifier is reducing output power to avoid power supply temp fault protection
Amplifier channel is reducing output power to avoid amplifier channel temp fault protection

Improve cooling or reduce output power to avoid temperature becoming critical
Improve cooling or reduce output power to avoid limiting
Improve cooling or reduce output power to avoid limiting

40

D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

Category/Type
Warning

Name
Under speaker count

Warning Warning

More speakers Uncertain about load

Fault

No load

On screen text
UNDER SPKR CNT OVR SPKR COUNT UNCERTAIN LOAD
NO LOAD

Fault

Wrong load

WRONG LOAD

Fault

Short circuit

SHORT CIRCUIT

AMP

Warning

channel

Warning

Very high frequency warning

(D200, D120, D80 only)

Fault

TEMP WARN VHF WARNING TEMP FAULT

Fault Fault Fault Clip Clip Clip SIGNAL Fault Clip

Service channel Very high frequency fault Current average limiter
Current clip Voltage clip Module clip

SERVICE CH. VHF FAULT CAL ACTIVE
CURRENT CLIP VOLTAGE CLIP
MOD. CLIP

No input source Analog/AES input clip

NO INPUT INPUT CLIP

Description
Both LoadPilot tones above thresholds or LoadSmart detected
fewer speakers than expected
LoadSmart detected more speakers than expected
LoadSmart uncertain about load

Action
Check load, cabling and calibration
Check load and
Check load and

At least one LoadPilot tone above above thresholds

Check load or calibration

LoadSmart detected impedance response output model

Check load and

LoadPilot or full frequency analysis below short threshold or hardware
short protection

Check load and cabling

critical temperature Amplifier channel gain reduction due to VHF content internal protection limit
above safe operating level current limit
Module output signal clipped

Improve cooling or reduce output power to avoid temperature becoming critical Check input signal
Automatically unmutes when cooled down
Restart device; if not cleared it needs service
Check input signal
Reduce output power to avoid limiting
Reduce output power to avoid limiting
Reduce output power to avoid limiting
Review gain structure. Module gain vs AmpGain

Input router has no valid input source
The signal on the analog/AES input is above inputs capability

Review input router settings/connections
Lower the signal on the

41 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

14.2. Current draw and thermal dissipation

Level

Load

Rated power per channel

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

250 x 4 250 x 4 250 x 4 250 x 4 175 x 4 250 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

250 x 4 250 x 4 250 x 4 250 x 4 175 x 4 250 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

250 x 4 250 x 4 250 x 4 250 x 4 175 x 4 250 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

250 x 4 250 x 4 250 x 4 250 x 4 175 x 4 250 x 4

D SERIES 10:4

Line Current

Measured Power (W)

(A)

In

Out

Mains Voltage 100 VAC

0.1

7

0

0.5

45

0

0.7

71

0

2.3

229

125

2.4

240

125

2.6

254

125

2.8

279

125

1.8

179

88

2.3

230

125

Mains Voltage 120 VAC

0.1

7

0

0.4

44

0

0.6

70

0

1.9

228

125

2.0

238

125

2.1

252

125

2.3

277

125

1.5

179

88

1.9

229

125

Mains Voltage 208 VAC

0.1

7

0

0.3

42

0

0.4

66

0

1.1

221

125

1.1

228

125

1.2

245

125

1.3

269

125

0.9

174

88

1.1

222

125

Mains Voltage 230 VAC

0.1

7

0

0.3

41

0

0.3

65

0

1.0

218

125

1.0

225

125

1.1

238

125

1.2

263

125

0.8

168

88

1.0

216

125

Dissipated
7 45 71 104 115 129 154 92 105
7 44 70 103 113 127 152 91 103
7 42 66 96 103 120 144 86 97
7 41 65 93 100 113 138 81 91

Thermal Dissipation

BTU/hr

kCal/hr

24

6

153

38

241

61

355

89

391

98

439

111

527

133

313

79

358

90

24

6

152

38

238

60

350

88

386

97

433

109

519

131

311

78

353

89

24

6

142

36

225

57

328

83

353

89

408

103

493

124

294

74

332

84

25

6

141

36

222

56

317

80

342

86

387

97

472

119

275

69

311

78

42 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

Level

Load

Rated power per channel

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

425 x 4 500 x 4 500 x 4 500 x 4 250 x 4 500 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

425 x 4 500 x 4 500 x 4 500 x 4 250 x 4 500 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

425 x 4 500 x 4 500 x 4 500 x 4 250 x 4 500 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

425 x 4 500 x 4 500 x 4 500 x 4 250 x 4 500 x 4

D SERIES 20:4

Line Current

Measured Power (W)

(A)

In

Out

Mains Voltage 100 VAC

0.2

7

0

0.5

46

0

0.7

71

0

2.9

348

213

3.5

418

250

3.7

444

250

4.1

492

250

1.9

230

125

3.5

410

250

Mains Voltage 120 VAC

0.1

7

0

0.4

45

0

0.6

71

0

2.9

346

213

3.5

411

250

3.7

441

250

4.1

487

250

2.0

231

125

3.4

408

250

Mains Voltage 208 VAC

0.1

7

0

0.3

43

0

0.4

67

0

1.5

336

213

1.8

398

250

1.9

426

250

2.1

471

250

1.0

224

125

1.8

395

250

Mains Voltage 230 VAC

0.2

7

0

0.3

43

0

0.4

67

0

1.5

333

213

1.8

394

250

1.9

419

250

2.1

467

250

1.0

222

125

1.8

392

250

Dissipated
7 46 71 136 168 194 242 105 160
7 45 71 134 161 190 237 106 158
7 43 67 124 148 176 221 99 145
7 43 67 120 144 169 217 97 142

Thermal Dissipation

BTU/hr

kCal/hr

24

6

157

39

243

61

463

117

573

144

662

167

825

208

360

91

546

138

23

6

155

39

241

61

457

115

550

139

650

164

810

204

361

91

540

136

24

6

147

37

229

58

422

106

506

127

600

151

753

190

339

85

496

125

24

6

146

37

227

57

411

104

493

124

577

145

741

187

331

83

484

122

43 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

Level

Load

Rated power per channel

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

700 x 4 1000 x 4 1000 x 4 800 x 4 1000 x 4 1000 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

700 x 4 1000 x 4 1000 x 4 800 x 4 1000 x 4 1000 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

700 x 4 1000 x 4 1000 x 4 800 x 4 1000 x 4 1000 x 4

Standby

Power On, Idling, Green Mode

Power On, Idling, Performance Mode

16  / Ch.

8  / Ch.

Pink Pseudo Noise

4  / Ch. 2  / Ch.

100 V / Ch.

70 V / Ch.

700 x 4 1000 x 4 1000 x 4 800 x 4 1000 x 4 1000 x 4

D SERIES 40:4

Line Current

Measured Power (W)

(A)

In

Out

Mains Voltage 100 VAC

0.2

7

0

0.6

59

0

0.8

78

0

5.1

502

350

7.2

709

500

7.6

754

500

7.0

689

400

7.1

701

500

7.5

738

500

Mains Voltage 120 VAC

0.2

7

0

0.5

59

0

0.7

77

0

4.2

497

350

5.9

700

500

6.3

743

500

5.7

679

400

5.8

690

500

6.1

726

500

Mains Voltage 208 VAC

0.3

7

0

0.5

58

0

0.5

77

0

2.2

486

350

3.1

681

500

3.3

723

500

3.0

662

400

3.0

673

500

3.2

707

500

Mains Voltage 230 VAC

0.3

7

0

0.4

58

0

0.5

77

0

2.2

474

350

3.0

664

500

3.2

705

500

3.0

649

400

3.0

659

500

3.2

694

500

Dissipated
7 59 78 152 209 254 289 200 238
7 59 77 147 199 243 279 190 226
7 58 77 136 181 223 261 173 207
7 58 77 124 164 205 249 159 194

Thermal Dissipation

BTU/hr

kCal/hr

24

6

201

51

267

67

518

131

714

180

868

219

986

249

684

172

812

205

24

6

200

50

263

66

503

127

681

172

829

209

953

240

648

163

772

195

25

6

198

50

263

66

464

117

617

155

759

191

892

225

589

148

707

178

25

6

197

50

263

66

423

106

558

141

701

176

850

214

544

137

661

166

44 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

Level

Load

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Rated power per channel
750 1500 2000 2000 2000

D SERIES 80:4

Line Current

Power Factor

Measured Power (W)

(A)

(%)

In

Out

Dissipated

Mains Voltage 100 VAC, 30 A

0.3

43

11

0

11

2.1

99

204

0

204

10.1

99

981

375

607

15.3

99

1492

749

743

14.9

99

1502

652

850

15.3

99

1539

625

914

15.2

99

1538

560

978

Thermal Dissipation

BTU/hr

kCal/hr

36

9

696

175

2070

522

2534

639

2900

731

3120

787

3337

841

750 1500 2000 2000 2000

2.2

98

211

0

211

720

181

Mains Voltage 120 VAC, 30 A

0.3

35

11

0

11

37

9

1.8

98

202

0

202

689

174

8.0

99

954

375

579

1977

499

12.6

99

1476

749

727

2480

625

14.4

99

1739

817

923

3148

794

14.7

99

1780

766

1014

3461

873

15.2

99

1839

739

1101

3755

947

750 1500 2000 2000 2000

1.8

98

211

Mains Voltage 208 VAC, 17.3 A

0.3

17

11

1.1

91

197

4.6

99

927

7.1

99

1436

9.3

100

1955

9.8

100

2087

10.3

100

2182

0
0 0 375 749 1000 1003 1001

211
11 197 552 687 955 1084 1181

719
39 673 1884 2345 3260 3698 4030

181
10 170 475 591 822 933 1016

750 1500 2000 2000 2000

1.1

92

204

Mains Voltage 230 VAC, 16 A

0.3

17

12

1.0

89

193

4.2

99

948

6.4

99

1443

8.1

99

1907

8.7

100

2052

9.4

100

2200

0
0 0 375 749 1000 1003 1000

204
12 193 573 694 906 1049 1201

695
39 660 1957 2369 3092 3580 4096

175
10 166 493 597 780 903 1033

1.0

89

204

0

204

695

175

45 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

Level

Load

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Rated power per channel
950 1900 3000 3000 3000

D SERIES 120:4

Line Current

Power Factor

Measured Power (W)

(A)

(%)

In

Out

Dissipated

Mains Voltage 100 VAC, 30 A

0.3

43

12

0

12

2.3

98

219

0

219

10.8

99

1059

475

584

19.2

99

1868

949

919

24.6

99

2389

1200

1189

25.7

99

2551

1151

1400

25.8

99

2576

1113

1463

Thermal Dissipation

BTU/hr

kCal/hr

40 749 1994 3136 4057 4776 4992

10 189 503 791 1023 1204 1259

950 1900 3000 3000 3000

2.4

98

231

Mains Voltage 120 VAC, 30 A

0.3 1.9 8.8 15.1 24.0 24.5 25.1

36

11

98

215

99

1035

99

1765

99

2817

99

2894

99

2980

0
0 0 475 949 1502 1437 1361

231
11 215 560 815 1315 1456 1619

789
39 734 1910 2783 4487 4969 5524

199
10 185 482 702 1131 1253 1393

950 1900 3000 3000 3000

2.0

97

226

Mains Voltage 208 VAC, 17.3 A

0.3 1.1 4.9 8.7 13.3 14.0 14.8

18

12

91

211

99

1001

99

1766

99

2687

99

2847

99

3046

0
0 0 475 949 1501 1500 1500

226
12 211 526 816 1186 1346 1546

773
42 720 1795 2786 4046 4594 5276

195
11 182 453 702 1020 1158 1330

950 1900 3000 3000 3000

1.2

93

221

Mains Voltage 230 VAC, 16 A

0.3

18

13

1.0

90

205

4.7

99

1003

7.7

99

1734

11.4

99

2562

12.8

99

2873

13.1

99

2993

0
0 0 475 949 1501 1499 1500

221
13 205 529 784 1061 1374 1493

754
43 698 1803 2676 3620 4688 5095

190
11 176 455 675 913 1182 1285

1.0

90

214

0

214

730

184

46 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix

Level

Load

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Standby Power on, Idling
Pink Pseudo Noise

16  / Ch. 8  / Ch. 4  / Ch. 2.67  / Ch. 2  / Ch.

LoadPilot Sine 20 kHz

8  / Ch.

Rated power per channel
1150 2300 4400 5000 4400

D SERIES 200:4

Line Current

Power Factor

Measured Power (W)

(A)

(%)

In

Out

Dissipated

Mains Voltage 100 VAC, 30 A

0.3

52

17

0

17

2.4

97

235

0

235

12.1

99

1192

588

604

22.3

99

2198

1174

1024

29.2

99

2853

1478

1375

29.2

99

2862

1399

1463

29.1

99

2826

1355

1472

Thermal Dissipation

BTU/hr

kCal/hr

58 802 2061 3493 4691 4991 5022

15 202 520 881 1183 1259 1266

1150 2300 4400 5000 4400

2.5

97

236

Mains Voltage 120 VAC, 30 A

0.3

48

17

2.0

97

227

12.0

99

1180

18.4

99

2144

30.0

99

3457

29.5

99

3439

29.9

99

3495

0
0 0 588 1174 1896 1752 1665

236
17 227 593 970 1561 1687 1830

807
58 775 2023 3310 5326 5756 6245

203
15 195 510 835 1343 1451 1575

1150 2300 4400 5000 4400

2.0

97

232

Mains Voltage 208 VAC, 17.3 A

0.3

27

18

1.2

92

222

5.7

99

1151

10.2

99

2055

16.2

99

3286

15.6

99

3171

16.0

99

3253

0
0 0 588 1174 1948 1752 1665

232
18 222 564 881 1338 1419 1589

790
60 757 1923 3005 4565 4843 5420

199
15 191 485 758 1151 1221 1367

1150 2300 4400 5000 4400

1.2

92

229

Mains Voltage 230 VAC, 16 A

0.3 1.2 5.1 9.2 15.9 16.0 16.0

23

18

92

222

98

1134

99

2053

99

3529

99

3564

99

3577

0
0 0 588 1174 2109 1935 1856

229
18 222 546 879 1420 1630 1722

780
61 757 1863 2999 4845 5561 5875

197
15 191 470 756 1222 1402 1481

1.1

90

228

0

228

777

196

47 D SERIES Lake Operation Manual rev 3.0.1

14. Appendix 14.3. Maintenance
During normal operation a D Series device provides trouble­free service. If the front panel display requires cleaning, use a soft cloth only; do not use solvent cleaners. The dust filters on both sides of the front panel, behind the grilles, should occasionally be removed and cleaned to ensure maximum airflow through the device. Disconnect the unit from mains power prior to removing dust the filter, and ensure the dust filter is replaced prior to turning the unit back on. In extreme cases it may be necessary to clean the inside of the device. This procedure should only be carried out by qualified service personnel. Internal cleaning may be necessary if the device has had prolonged operation in an extreme environment such as one where cracked oil smoke machines are in use. If the device is used in extreme conditions, it is recommended to have it serviced every three years as a preventative measure.
48 D SERIES Lake Operation Manual rev 3.0.1

15. Technical Specifications

15. Technical Specifications

General Processing / Network Number of amplifier channels Total burst power all channels (share among channels with RPM)
Max. Output Power (all ch.'s driven) 1) 2 ohms 2.67 ohms 4 ohms 8 ohms 16 ohms Hi-Z 70 V Hi-Z 100 V
Max. Output power bridged mode (all ch.'s driven) 1) 4 ohms 8 ohms 16 ohms
Max output power single channel (all models) 1) 2 ohms 2.67 ohms 4 ohms 8 ohms 16 ohms Hi-Z 70 V Hi-Z 100 V
Amplifier output modules (all models, all channels) Peak output voltage Max output current Rational Power Management (RPM)
Default voltage limitation (can be lifted with RPM configuration) Protection features
Amplifier platform Inter Sample Voltage Peak Limiter (ISVPL) Amplifier gain Pilot tone generation and analysis Load impedance analysis Temperature control
Audio Performance (Amplifier platform with digital input) THD + N 20 Hz - 20 kHz for 1 W THD + N at 1 kHz and 1 dB below clipping Dynamic range Channel separation (Crosstalk) at 1 kHz Frequency response (1 W into 8 ohm, 20 Hz - 20 kHz) Internal sample rate / Data path Product propagation delay AES 96 kHz / analog input
Lake processing Loudspeaker processing System tuning Input redundancy / Matrix System integration
Dante Audio Network Dante I/O Network topology / redundancy Sample rates / transport Network latency
Analog inputs Inputs Maximum input / digital reference Sampling rate / resolution Input impedance balanced / unbalanced THD + N (typical at 1 kHz unweighted) THD + N (typical at 20 Hz and 20 kHz unweighted)

D 200:4L
Lake / Dante 4 20000 W

D 120:4L
Lake / Dante 4 12000 W

D 80:4L
Lake / Dante 4 8000 W

4400 W 5000 W 4400 W 2300 W 1150 W 3300 W 4700 W

3000 W 3000 W 3000 W 1900 W 950 W 3000 W 3000 W

2000 W 2000 W 2000 W 1500 W 750 W 2000 W 2000 W

8800 W 8800 W 4600 W

6000 W 6000 W 3800 W

4000 W 4000 W 3000 W

4400 W 5900 W 4600 W 2300 W 1150 W 3300 W 4700 W

194 V

67 A
Share "total burst power" of the product freely among channels. Any channel can scale up to the "Max. output power single channel"

194 V

175 V

155 V

Current Average Limiter (CAL), Very High Frequency Protection (VHF), Direct Current Protection (DC),

Short Circuit Protection, Current-Clip Limiter, Voltage Clip Limiter, Temperature protection

Configurable Peak voltage threshold and profile Digital configurable amplifier gain 22 - 44 dB LoadPilot Yes Regulated fans and show must go on limitation (ATL, PTL)
< 0.05 % < 0.04 % > 114 dB > 70 dB +/- 0.05 dB 48 / 96 kHz / 32 bit floating point 1.61 / 1.68 ms
Up to 4 modules of Classic/linear-phase/FIR crossover, EQ, delay, LimiterMaxTM - peak and RMS limiters Group control with Raised CosineTM MESA EQTM asymmetric filters Automatic 4 level input redundancy / 4 input mixers Comprehensive 3rd party protocol over UDP Ethernet
8 x 8 Flexible topology / Supports daisy-chained and Dual redundant networks 48, 96 kHz / Uni + Multicast 0.25, 0.5, 1.0, 2.0, 5.0 ms
4 high quality inputs with Iso-Float ground isolation + 26 dBu / +21 dBu 96 kHz / 24 bit 20 / 10 kOhm 0.00022 % 0.00033 %

49 D SERIES Lake Operation Manual rev 3.0.1

15. Technical Specifications

AES Inputs Inputs Supported sample rates / resolution Sample rate conversion THD + N 20 Hz - 20 kHz unweighted
Rear panel interface Analog inputs AES inputs Output connectors
Ethernet ports Detachable mains cord
Front panel user interface System status indication Channel status indication Mute Power Select
Mains Power Nominal voltage Operating voltage Mains wall plug
Power supply features Soft start / Inrush power Power factor correction Regulated switch mode power supply (R.SMPS) Breaker Emulation Limiter (BEL) BEL max current threshold Power Average Limiter (PAL) Under Voltage Limiter (UVL) Mains undervoltage and overvoltage protection and mains glitch tolerance
Dimensions Rack rail to rear panel Overall all depth front­rear support
Weight Finish
Approvals

D 200:4L

D 120:4L

2 AES inputs (4 audio channels) 44.1, 48, 88.2, 96, 176.4, 192 kHz / up to 24 bit
0.00003 %

D 80:4L

4 x Terminal block connectors along input with +, ­ and ground 2 x Terminal block connectors
4 x 2 pole Terminal block connectors rated at 1000 V / 76 A (exceeding amplifier capacity) Can take up to 16 mm2 (6 AWG) cables
2 x EtherCon RJ45 100/1000 Base­T for the Lake Controller, Dante controller and/or DLM (3rd party protocol) Neutrik PowerCon rated at 250 V / 32 A

3 x tri-color LED. FRAME, TEMP, PSU for device status indication 3 x tri-color LED per channel. Status indication separated for channel LOAD, AMP, SIGNAL status Per channel touch button for MUTE control and tri-color LED for indication Touch button for ON/STANDBY control and tri-color LED for power state indication Touch button and LED for bi-directional device software select functionality

100 ­ 240 V AC 50 ­ 60 Hz 70 ­ 265 V AC 45 ­ 66 Hz
Selectable on order CEE 7/7 "Schuko" 230 V / 16 A, NEMA L5­30 "Twistlock" 125 V / 30 A, NEMA 5­15P 125 V / 15 A (D 80:4 only), NEMA 5­20P 125 V / 20 A (D120:4 only), NEMA 6­20P 250 V / 20 A, AS/NZS 3112 230 V / 15 A (Aus/Nz), BS 546 230 V / 16 A (India), C­30P 125V / 30A (Japan)

Yes / Max 8 A

> 0.98 for mains power > 400 W

Yes

Configurable current threshold and breaker profile

32 A

25 A

Yes

Yes

Yes

15 A

W: 483 mm (19"), H: 88 mm (2 U), D: 424 mm (16") D: 463 mm

16.5 kg (36 lbs)

15.8 kg (35 lbs)

14.5 kg (32 lbs)

Black painted steel chassis with grey painted steel front with detachable grille

CE, ETL (ANSI/UL, CSA), PSE, RCM

Note 1): Lab.gruppen burst power (1 kHz, 25 ms burst power @ 150 BPM, 12 dB Crest factor) All specifications are subject to change without notice.

50 D SERIES Lake Operation Manual rev 3.0.1

15. Technical Specifications

General Processing / Network Number of amplifier channels Total burst power all channels (share among channels with RPM)
Max. Output Power (all ch.'s driven) 1) 2 ohms 2.67 ohms 4 ohms 8 ohms 16 ohms Hi-Z 25 V Hi-Z 70 V Hi-Z 100 V
Max output power single channel 1) 2 ohms 2.67 ohms 4 ohms 8 ohms 16 ohms Hi-Z 25 V Hi-Z 70 V Hi-Z 100 V
Amplifier output modules (all channels) Peak output voltage Max output current
Rational Power Management (RPM)
Default voltage limitation (can be lifted with RPM configuration) Protection features
Amplifier platform Inter Sample Voltage Peak Limiter (ISVPL) Amplifier gain Pilot tone generation and analysis Load impedance analysis Temperature control
Audio Performance (Amplifier platform with digital input) THD + N 20 Hz - 20 kHz for 1 W THD + N at 1 kHz and 1 dB below clipping Dynamic range Channel separation (Crosstalk) at 1 kHz Frequency response (1 W into 8 ohm, 20 Hz - 20 kHz) Internal sample rate / Data path Product propagation delay AES 96 kHz / analog input
Lake processing Loudspeaker processing System tuning Input redundancy / Matrix System integration
Dante Audio Network Dante I/O Network topology / redundancy Sample rates / transport Network latency
Analog inputs Inputs Maximum input / digital reference Sampling rate / resolution Input impedance balanced / unbalanced THD + N (typical at 1 kHz unweighted) THD + N (typical at 20 Hz and 20 kHz unweighted)
AES Inputs Inputs Supported sample rates / resolution Sample rate conversion THD + N 20 Hz - 20 kHz unweighted

D 40:4L
Lake / Dante 4 4000 W

D 20:4L
Lake / Dante 4 2000 W

D 10:4L
Lake / Dante 4 1000 W

800 W 1000 W 1000 W 1000 W 700 W 500 W 1000 W 1000 W

500 W 500 W 500 W 500 W 425 W 500 W 500 W 250 W

250 W 250 W 250 W 250 W 250 W 250 W 250 W 175 W

850 W 1150 W 1750 W 1350 W 700 W 500 W 1450 W 2000 W

850 W 1150 W 1600 W 1100 W 600 W 500 W 1400 W 1000 W

850 W 1000 W 1000 W 1000 W 600 W 500 W 1000 W 700 W

150 Vpk

142 Vpk

142 Vpk

30 Apk

30 Apk

30 Apk

Share "Total burst power" of the product freely among channels. Any channel can scale up to the "single channel max power"

145 Vpk

100 Vpk

65 Vpk

Current Average Limiter (CAL), Very High Frequency Protection (VHF), Direct Current Protection (DC),

Short Circuit Protection, Current-Clip Limiter, Voltage Clip Limiter, Temperature protection

Configurable Peak voltage threshold and profile Digital configurable amplifier gain 22 - 44 dB Yes Yes Temperature regulated fans (front-to-rear airflow) and show must go on limitation (ATL, PTL)
< 0.05 % < 0.04 % > 112 dB > 70 dB +/- 0.05 dB 96 kHz / 32 bit floating point 1.61 / 1.68 ms
Up to 4 modules of Classic/linear-phase/FIR crossover, EQ, delay, LimiterMaxTM - peak and RMS limiters Group control with Raised CosineTM MESA EQTM asymmetric filters Automatic 4 level input redundancy / 4 input mixers Comprehensive 3rd party protocol over UDP Ethernet
8 x 8 Flexible topology / Supports Dual redundant networks 48, 96 kHz / Uni + Multicast 0.25, 0.5, 1.0, 2.0, 5.0 ms
4 high quality inputs with Iso-FloatTM ground isolation + 26 dBu / +21 dBu 96 kHz / 24 bit 20 / 10 kOhm 0.00022 % 0.00033 %
4 AES inputs 44.1, 48, 88.2, 96, 176.4, 192 kHz / up to 24 bit 0.00003 %

51 D SERIES Lake Operation Manual rev 3.0.1

15. Technical Specifications

Back panel interface Analog inputs AES inputs Output connectors Ethernet ports Detachable mains cord
Front panel user interface System status indication Channel status indication Mute Power Select
Mains Power Nominal voltage Operating voltage Mains wall plug
Power supply features Soft start / Inrush power Power factor correction Regulated switch mode power supply (R.SMPS) Breaker Emulation Limiter (BEL) BEL max current threshold Power Average Limiter (PAL) Under Voltage Limiter (UVL) Mains undervoltage and overvoltage protection and mains glitch tolerance
Dimensions Rack rail to rear panel Overall depth front-rear support
Weight Finish
Approvals

D 40:4L

D 20:4L

D 10:4L

4 x Terminal block connectors analog input with +, - and ground
4 x Terminal block connectors analog input with +, - and ground 4 x 2 pole Terminal block connectors rated at 1000 V / 41 A (exceeding amplifier capacity) Can take up to 8 mm2 (8.2 AWG) cables 2 x EtherCon RJ45 Lake Controller, Dante controller and/or DLM (3rd party protocol) Detachable locking 3-pin IEC rated at 250 V / 16 A

3 x tri-color LED. FRAME, TEMP, PSU for device status indication 3 x tri-color LED per channel. Status indication separated for channel LOAD, AMP, SIGNAL status Per channel touch button for MUTE control and tri-color LED for indication Touch button for ON/STANDBY control and tri-color LED for power state indication Touch button and LED for bi-directional device software select functionality
100 - 240 V AC 50 - 60 Hz 70 - 265 V AC 45 - 66 Hz Selectable on order CEE 7/7 "Schuko" 230 V / 16 A, NEMA 5-15 125 V / 15 A, BS1363-A 250 V / 13 A, IA16A3 250 V / 16 A, AU/NZ 250 V / 10 A, JP 125 V / 15 A, CPCS-CCC 250 V / 10 A

Yes

> 0.98 for mains power > 300 W

Yes

Yes

15 A

7 A

7 A

Yes

Yes Yes

W: 483 mm (19"), H: 44 mm (1 U), D: 425 mm (16.7") D: 463 mm

8.3 kg (18.3 lbs)

7.9 kg (17.3 lbs)

7.8 kg (17.1 lbs)

Black painted steel chassis with grey painted steel front with detachable grille

CE, ETL (ANSI/UL, CSA), PSE, RCM, BIS, CCC

Note 1): Lab.gruppen burst power (1 kHz, 25 ms burst power @ 150 BPM, 12 dB Crest factor) All specifications are subject to change without notice.

52 D SERIES Lake Operation Manual rev 3.0.1

16. Warranty and support
16. Warranty and support
16.1. General
This product is manufactured by Lab.gruppen, and it is warranted to be free from any defects caused by components or factory workmanship, under normal use and service, for a period of ten (10) years from date of purchase from an authorized Lab.gruppen dealer. If the product fails to perform as specified during the warranty period, Lab.gruppen will undertake to repair, or at its option, replace this product at no charge to its owner, provided the unit is returned undamaged, shipping prepaid, to an authorized service facility or to the factory. This warranty shall be null and void if the product is subjected to: repair work or alteration by a person other than those authorized by us; mechanical damage including shipping accidents; war, civil insurrection, misuse, abuse, operation with incorrect AC voltage; incorrect connections or accessories; operation with faulty associated equipment; or exposure to inclement weather conditions. Damage due to normal wear and tear is not covered by the warranty. Units on which the serial number has been removed or defaced will not be eligible for warranty service. Lab.gruppen shall not be responsible for any incidental or consequential damages. Lab.gruppen's responsibility is limited to the product itself. Lab.gruppen takes no responsibility for any loss due to cancellation of any events, or rent of replacement equipment or costs due to a third party's or customer's loss of profit, or any other indirect cost or losses however incurred. Lab.gruppen reserves the right to make changes or improvements in design or manufacturing without assuming any obligation to change or improve products previously manufactured. This warranty is exclusive, and no other warranty is expressed or implied. This warranty does not affect the customer's statutory rights. International Warranties Please contact your supplier or distributor for this information, as rights and disclaimers may vary from country to country.
16.2. Technical assistance and service
16.2.1. International service
If your Lab.gruppen product requires repair, contact your Lab.gruppen dealer or distributor, visit http://labgruppen.com/support or contact Lab.gruppen by phone or email to obtain details for the nearest authorized service center.
53 D SERIES Lake Operation Manual rev 3.0.1

16. Warranty and support
16.2.2. Factory service
In the event a Lab.gruppen product requires factory service, you may contact Lab.gruppen's service department for return instructions and a Return Authorization number. Please note for product return: 1. Use the original packing. 2. Include a copy of the sales receipt, your name, return address, phone and fax number, email address and
description of the defect. 3. Mark the Return Authorization number on the outside of the packing. Ship the product prepaid to: Music Group Innovation Sweden AB Faktorvägen 1 SE-434 37 Kungsbacka Sweden Phone: +46 300 56 28 00 service@labgruppen.com www.labgruppen.com
54 D SERIES Lake Operation Manual rev 3.0.1

Notes
Notes
55 D SERIES Lake Operation Manual rev 3.0.1

Notes
Notes
56 D SERIES Lake Operation Manual rev 3.0.1

labgruppen.com
Lab.gruppen adopts a policy of continuous improvement and product specification is subject to change. RPM, R.SMPS, PFC, CDM, BEL, UVL, CAFÉ, ESP, ISVPL, Iso­Float, Raised Cosine, MESA EQ, LimiterMax and LoadLibrary are trademarks of Lab.gruppen AB. All other trademarks remain the property of their respective owners.
Copyright © 2017 MUSIC Group Innovation Sweden AB. All rights reserved.

Item no. OM­DSERIES­LAKE



References

PDFium PDFium