Single-phase Microinverter User Manual
About Microinverter
This system is composed of a group of microinverters that convert direct current (DC) into alternating current (AC) and feed it into the public grid. The system is designed for the incorporation of one microinverter per two PV modules. Each microinverter works independently and guarantees the maximum power generation of each PV module. This setup enables the user to directly control the production of a single PV module, consequently improving the flexibility and reliability of the system.
About the Manual
This manual contains important instructions for the HM-1000T/HM-1200T/HM-1500T Microinverter and must be read in its entirety before installing or commissioning the equipment. For safety purposes, only a qualified technician who has received training or has demonstrated competence may install and maintain this microinverter under the guidance of this document.
Other Information
Product information is subject to change without notice. This user manual will be frequently updated. Please refer to Hoymiles official website at www.hoymiles.com for the latest version.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

01

Single-phase Microinverter User Manual
CONTENTS

1. Important Notes

04

1.1 Product Range

04

1.2 Target User

04

1.3 Symbols Used

04

2. About Safety

05

2.1 Important Safety Instructions

05

2.2 Explanation of Symbols

06

2.3 Radio Interference Statement

06

3. About Product

07

3.1 About 4-in-1 Unit

07

3.2 Highlights

07

3.3 Terminals Introduction

07

3.4 Dimension (mm)

07

4. About Function

08

4.1 Work Mode

08

5. About Installation

09

5.1 Accessories

09

5.2 Installation Precautions

09

5.3 Required Space Distance

10

5.4 Grounding Considerations

10

5.5 Preparation

10

5.6 Pre-installation

11

5.7 Installation Steps

11

6. Troubleshooting

14

6.1 Troubleshooting List

14

6.2 Status LED Indicator

17

6.3 Insulation Resistance Detection

17

6.4 On-site Inspection (for qualified installer only)

18

6.5 Routine Maintenance

18

6.6 Microinverter Replacement

19

7. Decommissioning

20

7.1 Decommissioning

20

7.2 Storage and Transportation

20

7.3 Disposal

20

8. Technical Data

21

8.1 DC Input

21

8.2 AC Output

21

8.3 Efficiency, Safety and Protection

22

8.4 Mechanical Data

22

8.5 Features

22

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

02

Single-phase Microinverter User Manual

Appendix 1:

23

Installation Map

23

Appendix 2:

24

WIRING DIAGRAM ­ 230 VAC SINGLE-PHASE:

24

WIRING DIAGRAM ­ 230 VAC / 400 VAC THREE-PHASE:

25

WIRING DIAGRAM ­ 120 VAC / 240 VAC SPLIT-PHASE:

26

WIRING DIAGRAM ­ 120 VAC / 208 VAC THREE-PHASE:

27

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

03

Single-phase Microinverter User Manual

1. Important Notes
1.1 Product Range
This manual describes the assembly, installation, commissioning, maintenance and failure search for the following models of Hoymiles Microinverter:
· HM-1000T · HM-1200T · HM-1500T *Note: "1000" means 1000 W, "1200" means 1200 W, "1500" means 1500 W.
1.2 Target User
For safety purposes, only a qualified technician who has received training or has demonstrated competence may install and maintain this microinverter under the guidance of this document.
1.3 Symbols Used
The safety symbols in this user manual are shown below.

Symbol

Usage

Indicates a hazardous situation that can result in deadly electric shock hazards, other serious physical injury, or fire hazards.

Indicates directions which must be fully understood and followed in their entirety to avoid potential safety hazards, including equipment damage or personal injury.
Indicates that the described operation must not be carried out. The reader should stop, use with caution and fully understand the operations explained before proceeding.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

04

Single-phase Microinverter User Manual
2. About Safety
2.1 Important Safety Instructions
The HM-1000T/HM-1200T/HM-1500T Microinverter is designed and tested according to international safety requirements. However, certain safety precautions must be taken when installing and operating this microinverter. The installer must read and follow all instructions, precautions and warnings in this installation manual.
· All operations including transport, installation, start-up and maintenance must be carried out by qualified and trained personnel.
· Before installation, check the unit to ensure that it is free of any transport or handling damage, which could affect insulation integrity or safety clearances. Choose an installation location carefully and adhere to the specified cooling requirements. Unauthorized removal of necessary protections, improper use, and incorrect installation and operation may result in serious safety and shock hazards or equipment damage.
· Before connecting the microinverter to the power distribution grid, contact the local power distribution grid company to obtain the appropriate approvals. This connection must be made only by qualified technical personnel. It is the responsibility of the installer to provide external disconnect switches and Overcurrent Protection Devices (OCPD).
· Only one PV module can be connected to one input of the microinverter. Do not connect batteries or other power supply sources. The microinverter can be used only if all the technical characteristics are observed and applied.
· Do not install the equipment in adverse environments, such as environments that are flammable, explosive, corrosive, extremely hot or cold, or humid. Do not use the equipment when the safety devices do not work or are disabled.
· Always use personal protective equipment, including gloves and eye protection, while installing.
· Inform the manufacturer of non-standard installation conditions.
· Do not use the equipment if any anomalies are discovered while operating. Avoid temporary repairs.
· All repairs should be carried out by using only qualified spare parts, which must be installed in accordance with their intended use and by a licensed contractor or authorized Hoymiles service representative.
· Any liability arising from commercial components are delegated to their respective manufacturers.
· Any time the microinverter has been disconnected from the public network, please be extremely cautious, as some components can retain charge sufficient to create a shock hazard. Prior to touching any part of the microinverter, please ensure that surfaces and equipment are under safe touch temperatures and voltage potentials before proceeding.
· Hoymiles accepts no liability for damage due to incorrect or improper operation.
· Electrical Installation & Maintenance shall be conducted by a licensed electrician and shall comply with local wiring regulations.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

05

Single-phase Microinverter User Manual

2.2 Explanation of Symbols

Symbol

Usage
Treatment To comply with European Directive 2002/96/EC on Waste Electrical and Electronic Equipment and its implementation as national law, electrical equipment that has reached the end of its life must be separately collected and returned to an approved recycling facility. Any device no longer required must be returned to an authorized dealer or approved collection and recycling facility.
Caution Do not come within 8 inches of the microinverter for any length of time while it is in operation.

Danger of high voltages Danger to life due to high voltage in the microinverter.

Beware of hot surface The microinverter can become hot while operating. Avoid contact with metal surfaces while operating.
CE mark The microinverter complies with the requirements of the Low Voltage Directive for the European Union.
Read manual first Please read the installation manual first before installation, operation and maintenance.
2.3 Radio Interference Statement
This microinverter has been tested and found to comply with the limits for CE EMC, which provides reasonable protection against harmful energy. However, if not installed according to the instructions, the microinverter may cause harmful interference to radio equipment. There is no guarantee that such interference will not occur during a particular installation.
To confirm that the radio or television reception is affected by interference from this equipment, turn the equipment off and on to test it. If this equipment causes harmful interference to the radio or television equipment, try to correct the interference through one or more of the following measures:
1) Relocate the receiving antenna.
2) Increase the separation between the microinverter and the receiving antenna.
3) Place a shield between the microinverter and the receiving antenna, such as a metal / concrete roof.
4) Contact your dealer or an experienced radio/TV technician for help.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

06

Single-phase Microinverter User Manual
3. About Product
3.1 About 4-in-1 Unit
"Daisy-Chain 4-in-1 Unit Microinverter" with ultra-wide DC input operating voltage range (16 V­60 V) and low start-up voltage (22 V only). The Hoymiles 4-in-1 Unit Microinverter HM-1000T/HM-1200T/HM-1500T is a reliable solution for PV systems with an uneven number of panels, and offers high CEC weighted efficiency ­ 96.50% (peak efficiency 96.70%) in 2015.
3.2 Highlights
· Maximum output power up to 1000 W/1200 W/1500 W. Adapted to 60-cell & 72-cell PV panels. · Peak efficiency 96.70%. CEC weighted efficiency 96.50%. · Static MPPT efficiency 99.80%. Dynamic MPPT efficiency 99.76% in overcast weather. · Power factor (adjustable) 0.8 leading...0.8 lagging. · External antenna for stronger communication with DTU. · High reliability: NEMA 6 (IP67) enclosure. 6000 V surge protection.
3.3 Terminals Introduction

Object A B C
3.4 Dimension (mm)

Description AC Connector DC Connector AC Connectors

Unit: mm

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

07

Single-phase Microinverter User Manual
4. About Function
4.1 Work Mode
Normal: In this mode, the microinverter operates normally and converts DC power into AC power to support the household loads and feeds into the public grid. Zero Export Control: In this mode, the microinverter's generation is limited based on the current household loads, and there is no extra power fed into the public grid. Standby: There are several circumstances in which the microinverter will be in Standby mode: · The current condition contradicts with the microinverter operating requirements. · No household loads or the export control value has been set as "0" on the DTU in the Zero Export Control
mode.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

08

Single-phase Microinverter User Manual
5. About Installation
5.1 Accessories

Object

Description

A

AC Bus Cable, 12/10 AWG Cable

B

DC Extension Cable, 1 m

C

M8 × 25 Screws

D

AC Connector Unlocking Tool

E

Bus Connector Unlocking Tool

F

AC Sub Cap

G

AC Bus End Cap, IP67

*Note: All accessories listed above are not included in the package, and need to be purchased separately. Please contact our sales representative for pricing information. (M8 screws need to be prepared by installer-self.)

5.2 Installation Precautions

Please install the microinverter and all DC connections under the PV module to avoid direct sunlight, rain exposure, snow pile-up, UV, etc. Allow a minimum of 2 cm of space around the microinverter enclosure to ensure ventilation and heat dissipation.
*Note: For some countries, the DTU will be required to meet local grid regulations (e.g. G98/99 for UK).

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

09

Single-phase Microinverter User Manual
5.3 Required Space Distance

If the microinverters are installed on

a concrete roof or steel roof, their

communication with the DTU may be

slightly affected. Under such installation

conditions, it is better for the microinverters

to be installed 50 cm above the roof.

Otherwise, more DTUs may be required to 50 cm
ensure communication quality between the

DTUs and the microinverters.

Ground

5.4 Grounding Considerations
This microinverter is a Class I equipment with a basic isolation transformer, and this microinverter must be earthed. There is an earth wire inside the AC cable, so usually grounding can be done by directly using this wire. If the utility has any special requirements, grounding can be done by affixing the mounting bracket to the racking.
5.5 Preparation
Installation of this equipment is carried out based on the system design and the place in which the equipment is installed.
· Installation must be carried out with the equipment disconnected from the grid (power disconnect switch on) and with the PV modules shaded or isolated.
· Refer to the Technical Data to ensure that the environmental conditions fit the requirements of the microinverter (degree of protection, temperature, humidity, altitude, etc.)
· To avoid power de-rating due to an increase in the internal temperature of the microinverter, do not expose it to direct sunlight.
· To avoid overheating, always make sure that the air flow around the microinverter is not blocked.
· Do not install in places where gases or flammable substances may be present.
· Avoid electromagnetic interference that can compromise the correct operation of electronic equipment.
When choosing the installation position, comply with the following conditions:

· Only install on structures specifically conceived for PV modules (supplied by installation technicians).
· Install the microinverter underneath the PV modules to make sure that it operates in a shaded or shadowed environment. If this condition cannot be met, it may trigger the microinverter production derating.

Fig.1 Microinverter installation position

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

10

Single-phase Microinverter User Manual
5.6 Pre-installation
A) Plan the cable length to make the bus cable aligned with each PV module. B) Install the AC bus end cap:
· Use the bus connector unlocking tool to unlock the port upper cover.
· Loosen the three screws with a screwdriver. Untighten the cap as circled below, and remove the extra cable.
· Screw the cap back into the port, and insert the AC bus end cap.
· Plug the upper cover back to the bus connector.
5.7 Installation Steps Step 1. Attach Microinverter on Rail
A) Mark the approximate center of each panel on the frame. B) Fix the screw on the rail. C) Hang the microinverter on the screw
(as shown in the picture below), and tighten the screw. The silver cover side of the microinverter should be facing the panel. *Note: Please install the microinverter at least 50 cm above the ground/roof for better communication with the Hoymiles DTU. Step 2. Complete AC Connection
A) Attach the AC bus cable to the mounting rail, and affix the cable with ties.
B) Push the AC connector of the microinverter into the trunk cable connector until you hear a clicking sound.
C) If there is any vacant bus port, please insert the AC sub cap in the vacant plug to ensure waterproofing and dustproofing.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

11

Single-phase Microinverter User Manual

*Note: Under circumstances that require removing the inverter AC cable from bus port, please use the AC connector unlocking tool and insert the tool into the side of the AC port.
Step 3. Install AC End Cable

A) Prepare an AC end cable with proper length and insert one side of the cable into the cap. Match the L, N and Ground lines into the appropriate slots. Tighten the screws, and then reinsert the cap tightly in the port. Plug the upper cover back to the bus connector.

Coated with solder

B) Connect the other side of the AC end cable to the distribution box, and wire it to the local grid network. Step 4. Create an Installation Map

A) Peel the removable serial number label from each microinverter (the position of the label is shown below).

B) Affix the serial number label to the respective location on the installation map.

N S E W (circle one)

Panel Group: Azimuth: Tilt: Sheet _ of _

Customer Information:

DTU Serial Number:

Step 5. Connect PV Modules
A) Mount the PV modules above the microinverter.
B) Connect the PV modules' DC cables to the DC input side of the microinverter.
Step 6. Energize the System A) Turn on the AC breaker of the branch circuit. B) Turn on the main AC breaker of the house. Your system will start to generate power after about two
minutes of waiting time.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

12

Single-phase Microinverter User Manual
Step 7. Set Up the Monitoring System Refer to the DTU User Manual or DTU Quick Installation Guide, and Quick Installation Guide for S-Miles Cloud (Hoymiles Monitoring Platform) Online Registration to install the DTU and set up the monitoring system. Product information is subject to change without notice. (Download reference manuals at www.hoymiles. com.)

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

13

Single-phase Microinverter User Manual
6. Troubleshooting
This microinverter can only work with the new Hoymiles DTU (DTU-Pro, DTU-Lite and DTU-W100/DTU-G100) with the following serial number.

Model
DTU-Pro
DTU-G100 DTU-W100 DTU-Lite

Serial Number 10F7xxxxxxxx 10F8xxxxxxxx 10FAxxxxxxxx 10D2xxxxxxxx 10D3xxxxxxxx 10D6xxxxxxxx

6.1 Troubleshooting List

Alarm Code 121 125 126 127 128 129 130

Alarm Name
Over temperature protection
Grid configuration parameter error
Software error code 126
Firmware error
Software error code 128
Software error code 129
Offline

Suggestion
1. Check the ventilation and ambient temperature at the microinverter installation position.
2. If the ventilation is poor or the ambient temperature exceeds the limit, improve the ventilation and heat dissipation.
3. If both the ventilation and ambient temperature meet the requirements, contact your dealer or Hoymiles Technical Service Center.
1. Check if the grid configuration parameter is correct and upgrade again.
2. If the fault still exists, contact your dealer or Hoymiles Technical Service Center.
1. If the alarm occurs accidentally and the microinverter can still function normally, no special treatment is required.
2. If the alarm occurs frequently and cannot be restored, contact your dealer or Hoymiles Technical Service Center.
1. Check if the firmware is correct and upgrade again. 2. Check the communication between the DTU and Hoymiles Monitoring
System, as well as the communication between the DTU and the microinverter. Then try again. 3. If the fault still exists, contact your dealer or Hoymiles Technical Service Center.
1. If the alarm occurs accidentally and the microinverter can still function normally, no special treatment is required.
2. If the alarm occurs frequently and cannot be restored, contact your dealer or Hoymiles Technical Service Center.
1. If the alarm occurs accidentally and the microinverter can still function normally, no special treatment is required.
2. If the alarm occurs frequently and cannot be restored, contact your dealer or Hoymiles Technical Service Center.
1. Please check if the microinverter works normally. 2. Check the communication status between the DTU and Hoymiles
Monitoring System, or between the DTU and the microinverter. Try to make improvements if the communication is poor. 3. If the alarm occurs frequently and cannot be restored, contact your dealer or Hoymiles Technical Service Center.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

14

Single-phase Microinverter User Manual

1. If the alarm occurs accidentally, the grid voltage may be temporarily abnormal. The microinverter will automatically recover after grid voltage returns to normal.

141

Grid overvoltage

2. If the alarm occurs frequently, check whether the grid voltage is

within the acceptable range. If it is not, contact the local power

operator or change the grid overvoltage protection limit via the

Hoymiles Monitoring System after obtaining the consent of the local

power operator.

1. If the alarm occurs accidentally, the grid voltage may be temporarily

abnormal. The microinverter will automatically recover after grid

Grid overvoltage

voltage returns to normal.

142

(10-minute average

2. If the alarm occurs frequently, check whether the grid voltage is

value)

within the acceptable range. If it is not, contact the local power operator or change the grid overvoltage protection limit via the

Hoymiles Monitoring System after obtaining the consent of the local

power operator.

1. If the alarm occurs accidentally, the grid voltage may be temporarily abnormal. The microinverter will automatically recover after grid voltage returns to normal.

2. If the alarm occurs frequently, check whether the grid voltage is

143

Grid undervoltage

within the acceptable range. If it is not, contact the local power

operator or change the grid undervoltage protection limit via the

Hoymiles Monitoring System after obtaining the consent of the local

power operator.

3. If the fault still exists, check the AC switch or AC wiring.

1. If the alarm occurs accidentally, the grid frequency may be temporarily abnormal. The microinverter will automatically recover after grid frequency returns to normal.

144

Grid overfrequency

2. If the alarm occurs frequently, check whether the grid frequency

is within the acceptable range. If it is not, contact the local power

operator or change the grid overfrequency protection limit via the

Hoymiles Monitoring System after obtaining the consent of the local

power operator.

1. If the alarm occurs accidentally, the grid frequency may be temporarily abnormal. The microinverter will automatically recover after grid frequency returns to normal.

145

Grid underfrequency

2. If the alarm occurs frequently, check whether the grid frequency

is within the acceptable range. If it is not, contact the local power

operator or change the grid underfrequency protection limit via the

Hoymiles Monitoring System after obtaining the consent of the local

power operator.

1. If the alarm occurs accidentally, the grid frequency may be

temporarily abnormal. The microinverter will automatically recover

after grid frequency returns to normal.

146

Rapid grid frequency changes

2. If the alarm occurs frequently, check whether the grid frequency change rate is within the acceptable range. If it is not, contact the

local power operator or change the grid frequency change rate limit

via the Hoymiles Monitoring System after obtaining the consent of

the local power operator.

147

Power grid outage

Please check whether there is a power grid outage.

148

Grid disconnection

Please check whether the AC switch or AC wiring functions normally.

1. If the alarm occurs accidentally, the grid voltage may be temporarily abnormal. The microinverter will automatically recover after grid voltage returns to normal.

149

Island detected

2. If the alarms occur frequently on all the microinverters in your station, contact the local power operator to check whether there is a

grid island.

3. If the alarm still exists, contact your dealer or Hoymiles Technical Service Center.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

15

Single-phase Microinverter User Manual

1. Please make sure that the PV module open-circuit voltage is less than

or equal to the maximum input voltage.

205

Input port overvoltage

2. If the PV module open-circuit voltage is not within the normal range,

contact your dealer or Hoymiles Technical Service Center.

1. Please make sure that the PV module open-circuit voltage is less than

207

Input port undervoltage

or equal to the maximum input voltage. 2. If the PV module open-circuit voltage is not within the normal range,

contact your dealer or Hoymiles Technical Service Center.

1. Please confirm whether this port is connected to the PV module.

209

Port no input

2. If the PV module is connected, please check the DC cable connection

between this port and the PV module.

1. If the alarm occurs accidentally and the microinverter can still

301

Hardware error code 301

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

302

Hardware error code 302

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

303

Hardware error code 303

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

304

Hardware error code 304

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

305

Hardware error code 305

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

306

Hardware error code 306

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

307

Hardware error code 307

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

1. If the alarm occurs accidentally and the microinverter can still

308

Hardware error code 308

function normally, no special treatment is required. 2. If the alarm occurs frequently and cannot be restored, contact your

dealer or Hoymiles Technical Service Center.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

16

Single-phase Microinverter User Manual
6.2 Status LED Indicator
The LED flashes five times at startup. All green flashes (1s gap) indicate normal startup.
Status LED
(1) Startup Process · Five green flashes (0.3s gap): Startup success · Five red flashes (0.3s gap): Startup failure (2) Running Process · Fast green flashing (1s gap): Producing power. · Slow green flashing (2s gap): Producing power, but one input is abnormal. · Slow green flashing (4s gap): Producing power, but there is no communication with DTU. · Red flashing (1s gap): Not producing power, AC grid fault (voltage or frequency out of range). · Red flashing (0.5s gap): Non-grid abnormality fault. (3) Other Status · Alternating red and green flashing: Firmware is corrupted. *Note: All faults are reported to the DTU, refer to the local DTU app or S-Miles Cloud (Hoymiles Monitoring Platform) for more information. 6.3 Insulation Resistance Detection There is a resistance sensor in the microinverter to measure the resistance between the outputs of PV module and the ground. If there is a problem with PV module insulation, DC wiring or connectors of the module and so on, the resistance between the outputs of the module and the ground may decrease. If this resistance drops below a preset threshold, the microinverter will stop producing power and report this ground fault. This fault will persist until it is cleared on the S-Miles Cloud (Hoymiles Monitoring Platform). This fault will persist until the microinverter is rebooted. Please note that this fault cannot be cleared if the cause of the failure is still present. If the fault persists, contact your installer or Hoymiles for possible replacement.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

17

Single-phase Microinverter User Manual

6.4 On-site Inspection (for qualified installer only)
To troubleshoot an inoperable microinverter, follow the steps mentioned below.

Verify that the utility voltage and frequency are within ranges shown in the Technical Data 1
appendix of this microinverter.

Check the connection to the utility grid. Verify that the utility power is present at the microinverter in question by removing AC, then DC power. Never disconnect the DC wires 2 while the microinverter is producing power. Re-connect the DC module connectors and watch for five short LED flashes.

Check the AC branch circuit interconnection between all the microinverters. Verify that each 3
microinverter is energized by the utility grid as described in the previous step.

4

Make sure that any AC breakers are functioning properly and are closed.

5

Check the DC connections between the microinverter and the PV module.

Verify that the PV module DC voltage is within the allowable range shown in the Technical 6
Data appendix of this manual.

7

If the problem persists, please call Hoymiles customer support.

Do not try to repair the microinverter. If troubleshooting fails, please return it to the factory for replacement.

6.5 Routine Maintenance
1. Only authorized personnel are allowed to carry out the maintenance operations, and such personnel are responsible for reporting any anomalies.
2. Always use the personal protective equipment provided by the employer when carrying out maintenance.
3. During normal operation, check that the environmental and logistical conditions are correct. Make sure that these conditions have not changed over time and that the equipment is not exposed to adverse weather conditions and has not been covered with foreign bodies.
4. DO NOT use the equipment if any problems are found, and restore the proper conditions after resolving the problems.
5. Conduct an annual inspection of the various components, and clean the equipment with a vacuum cleaner or special brushes.

Do not attempt to dismantle the microinverter or make any internal repairs! In order to preserve the integrity of safety and insulation, the microinverters are not designed to allow internal repairs!

The AC output wiring harness (AC drop cable on the microinverter) cannot be replaced. If the cord is damaged, the equipment should be scrapped.

Maintenance operations must be carried out with the equipment disconnected from the grid (grid power switch on) and the PV modules obscured or isolated, unless otherwise indicated.

For cleaning, do not use rags made of filamentary materials or corrosive products that may corrode parts of the equipment or generate electrostatic charges.

Avoid temporary repairs. All repairs should be carried out by using only genuine spare parts.
If all microinverters connect to the DTU-Pro, the DTU can limit the output power imbalance of all microinverters between phases to below 3.68 kW if required. Please refer to the "Hoymiles Technical Note Limit Phase Balance" for more details.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

18

Single-phase Microinverter User Manual
Each branch should provide a circuit breaker, but a central protection unit is not required.
6.6 Microinverter Replacement
a. How to remove the microinverter. · De-energize the AC branch circuit breaker. · Remove the PV panel from the racking and cover the panel. · Use a meter to measure and make sure that there is no current flowing in the DC wires between the
panel and the microinverter. · Use the DC disconnect tool to remove the DC connectors. · Use the AC disconnect tool to remove the AC connectors. · Unscrew the fixing screw on the top of the microinverter and remove the microinverter from the PV
racking. b. How to replace the microinverter: · Please record down the new microinverter's SN. · Please make sure that the AC branch circuit breaker is off, and follow the microinverter installation
steps to install the replacement unit. · Go to the Monitoring Platform (if the customer already registered this station online) and access the
"Devices" page to find the device that you just replaced. Click the "Device Maintenance" button to jump to the new page and select "Replace Device". Enter the new microinverter's SN and click the "OK" button to complete the replacement.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

19

Single-phase Microinverter User Manual
7. Decommissioning
7.1 Decommissioning
Disconnect the microinverter from the DC input and AC output. remove all connection cables from the microinverter. remove the microinverter from the frame.
Pack the microinverter in the original packaging, or use a carton box that can support 5 kg of weight and can be fully closed if the original packaging is no longer available.
7.2 Storage and Transportation
Hoymiles packages and protects individual components by using suitable means to facilitate the transport and subsequent handling. Transportation of the equipment, especially by road, must be carried out by using means that are suitable for protecting the components (in particular, the electronic components) from violence, shocks, humidity, vibration, etc. Please dispose of the packaging elements in appropriate ways to avoid unforeseeable injury.
It is the customer's responsibility to examine the condition of the components transported. Upon receiving the microinverter, it is necessary to check the container for any external damage and verify the receipt of all items. Call the delivery carrier immediately if damage is detected or components are missing. If inspection reveals damage to the microinverter, contact the supplier or authorized distributor for a repair/return determination and instructions regarding the process.
The microinverter storage temperature is -40°C to 85°C.
7.3 Disposal
· If the equipment is not used immediately or is stored for long periods, ensure that it is correctly packed. The equipment must be stored in well-ventilated indoor areas that do not have characteristics that might damage the components of the equipment.
· Conduct a complete inspection when restarting after a long time or prolonged cessation of use.
· For scrapped equipment which is potentially harmful to the environment, please dispose of the equipment properly and in accordance with the regulations in force in the country of installation.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

20

Single-phase Microinverter User Manual
8. Technical Data

Warning: Be sure to verify the following before installing the Hoymiles Microinverter System.

Verify that the voltage and current specifications of the PV module match those of the microinverter.
The maximum open-circuit voltage rating of the PV module must be within the operating voltage range of the microinverter.
The maximum current rating at MPP is recommended to be equal to or less than the maximum input DC current. But the maximum short-circuit current must be equal to or less than the maximum input DC short-circuit current.
The output DC power of the PV module is NOT recommended to exceed 1.35 times the output AC power of the microinverter. Refer to the "Hoymiles Warranty Terms & Conditions" for more information.

8.1 DC Input

Model
Commonly used module power (W)
Peak power MPPT voltage range (V) Start-up voltage (V)
Operating voltage range (V) Maximum input voltage (V) Maximum input current (A) Maximum input short-circuit current (A) Maximum backfeed current to array (A)

HM-1000T Up to 310 (single panel)
27­48
4 × 10.5

HM-1200T Up to 380 (single panel)
29­48 22 16­60 60 4 × 11.5 4 × 15 0

HM-1500T Up to 470 (single panel)
36­48
4 × 11.5

8.2 AC Output

Model Rated output power (VA) Rated output current (A)
Nominal output voltage/range (V)
Nominal frequency/range (Hz) Power factor
Output current harmonic distortion Maximum units per branch

HM-1000T

HM-1200T

HM-1500T

1000

1200

1500

4.55@220 V 4.35@230 V 4.17@240 V

5.45@220 V 5.22@230 V 5.00@240 V

6.82@220 V 6.52@230 V 6.25@240 V

220/180­275 230/180­275 240/180­275

45­55 (under 50 Hz @ 220 V & 230 V) 55­65 (under 60 Hz @ 220 V & 230 V)

> 0.99 default 0.8 leading...0.8 lagging

< 3%

5@220 V 5@230 V 5@240 V

4@220 V 4@230 V 4@240 V

3@220 V 3@230 V 3@240 V

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

21

Single-phase Microinverter User Manual

8.3 Efficiency, Safety and Protection

Model Peak microinverter efficiency
CEC weighted efficiency Nominal MPPT efficiency Night time power consumption (mW)

HM-1000T

HM-1200T 96.70% 96.50% 99.80%
< 50

HM-1500T

8.4 Mechanical Data

Model Ambient temperature range (°C) Storage temperature range (°C)
Dimensions (W × H × D mm) Weight (kg)
Enclosure rating Cooling
Pollution degree

HM-1000T

HM-1200T

-40 to +65

-40 to +85

280 × 176 × 33

3.35

Outdoor NEMA 6 (IP67)

Natural convection (no fans)

PD3

HM-1500T

8.5 Features

Model Topology Communication Monitoring Warranty
Compliance

HM-1000T

HM-1200T

HM-1500T

High-Frequency Transformers

2.4 GHz Proprietary RF (Nordic)

Hoymiles Monitoring System (Hoymiles DTU is required)

12 years standard, 25 years optional

VDE-AR-N 4105:2018, EN 50549-1:2019, VFR2019, AS 4777.2:2015, IEC/EN 62109-1/-2, IEC/EN 61000-3-2/-3, IEC/EN-
61000-6-1/-2/-3/-4

*Note: Voltage and frequency ranges can be extended beyond nominal if required by the utility.

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

22

Single-phase Microinverter User Manual
Appendix 1: Installation Map

To sheet ____

To sheet ____ DTU Serial Number:

To sheet ____

Customer Information:

Panel type: Azimuth: Tilt: Sheet ___ of ___

To sheet ____

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

23

Single-phase Microinverter User Manual
Appendix 2: WIRING DIAGRAM ­ 230 VAC SINGLE-PHASE:

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

UUPPTOTO3 H3MH-M15-0105T0s 0PETRs ACPEBRRAANCCBHRCAIRNCCUHIT
CIRCUIT
BRRAANNCCHHEENNDDCCAAPP

PPHHAASSEE-L-L11

AACC BBRRAANNCCHH CCAABBLLEE BBRROOWWNN--LL BBLLUUEE -- NN YYEELLLLOOWW&&GGRREEENEN- G- G
AACC DDIISSTTRRIIBBUUTTIOIONNPAPNAENLEL OORRSSUUBBPAPANNELEL
GGRROOUUNNDD
NNEEUUTTRRAAL L L1

ETHETEHRENRENTECTOCONNNNEECCTTIIOONN TOTOBRBOROAADDBBAANNDDRROOUUTTEERR

DDTTUU UUPPTTOO2244HHMM-1-510500T0sTs

CCOONNNNEECCTTIIOONNTTOODDTUTU

5V

PPOOWWEERRAADDAAPAPTTEERR

W
MMEETTEERR

24

25

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

UP TO 3 HM-1500Ts PER UPACTOBR3AHNMCH-15C0I0RTCsUPIETR AC BRANCH CIRCUIT

UP TO 3 HM-1500Ts PER UPACTOBR3AHNMCH-15C0I0RTCsUPIETR AC BRANCH CIRCUIT
UUPP TTOO 33 HHMM--11550000TTssPPEERR AC BRANCH CIRCUIT AC BRANCH CIRCUIT

PPHHAASSEE-L-1L1 PPHHAASSEE-L-2L2

BBRRAANNCCHHEENNDDCCAAPP EETTHHEERRNNEETT CCOONNNNEECCTTIOIONN TTOOBBRROOAADDBBAANNDD RROOUUTTEERR

PPHHAASSEE-L-3L3

DTDUTU UUP PTOTO242H4 MHM-1-510500T0sTs

CONCONNECNTEICOTNIOTON DTOTUDPTOUWER

5V

POWEARDAADPATEPRATER

AACCBBRRAANNCCHHCCAABBLELE BBRROOWWNN -- LL BBLLUUEE--NN YYEELLLLOOWW&&GGRREEEENN--GG
AACCDDISITSRTIRBIUBTUIOTINONPAPNAENLEOLR ORSUSBUPBAPNAENLEL GGRROOUUNNDD NNEEUUTTRRAALL
L1 L2 L3
W
MMEETTEERR

Single-phase Microinverter User Manual
WIRING DIAGRAM ­ 230 VAC / 400 VAC THREE-PHASE:

Single-phase Microinverter User Manual
WIRING DIAGRAM ­ 120 VAC / 240 VAC SPLIT-PHASE:

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

UUP PTOTO3 H3MH-M15-0105T0s0PTEsR ACPBERRAANCCBHRCAINRCCUHIT
CIRCUIT
BBRRAANNCCHH EENNDDCCAAPP

PHPAHSAES-LE1-L&1&LL22

AC BRANCH CABLE BABRRCOOBWRWANNN- CL-HLCABLE BBLLUUEE--NN YYEELLLLOOWW&&GRGERENEE-NG - G
ACADC IDSITSTRRIBIBUUTTIIOONNPPAANNELEL OORRSSUUBBPPAANNEELL
GGRROOUUNNDD
NNEEUUTTRRAALL
L1 L2

EETTHHEERRNNEETT CCOONNNNEECCTTIIOONN TTOO BBRROOAADDBBAANNDD RROOUUTTEERR

DTUDTU UPUTPOT2O4 2H4MH-1M50-01T5s00Ts

CCOONNNNEECCTTIIOONN TTOODDTTUU

5V

PPOOWWEERRAADDAAPPATTEERR

W
MMEETTEERR

26

27

© 2021 Hoymiles Power Electronics Inc. All rights reserved.

UUPPTTOO3 3HMH-M15-0105T0s0PTEsR ACPEBRRAANCCBHRCAINRCCHUIT
CIRCUIT
UP TO 3 HM-1500Ts UPPTEOR3AHCMB-1R5A0N0TCsHPER AC BRCAINRCCHUCITIRCUIT
UUPPTTOO3 3HMH-M15-0105T0s0PTEsR ACPEBRRAANCCBHRCAINRCCHUIT
CIRCUIT
BBRRAANNCCHHEENNDDCCAAPP
ETHEERTHNEERTNCEOTNCNOENCNTEICOTNIOTNO BTROOBARDOBAADNBDANRDORUOTUERTER

PHPAHSAES-LE1-L&1&LL22

AACC BBRRAANNCCHHCCAABBLLEE BBRROOWWNN--LL BBLLUUEE -- NN
YYEELLLLOOWW&&GGRREEEENN- G- G

PHPAHSAES-LE1-L&1&LL33

AC ADCISDTIRSITBRUIBTUIOTNIOPNAPNAENLEOL R OSRUSBUPBAPNAENLEL
GGRROOUUNNDD
NNEEUUTTRRAALL
L1 L2 L3

PHPAHSAES-LE2-L&2&LL33

DTUDTU UUPPTTOO242H4MH-1M500-1Ts500Ts

COCONNNNEECCTTIOIONN TTOO DDTTUU

5V

PPOOWWEERR AADDAAPPATTEERR

W
MMEETTEERR

Single-phase Microinverter User Manual
WIRING DIAGRAM ­ 120 VAC / 208 VAC THREE-PHASE:



References