SKE4-Modbus Guide-240202 (V2.07)
SKE4 Steam Humidifier
Modbus Communication Module User Guide
SKE4-Modbus Guide-240202 (V2.07)

SKE4 Steam Humidifier
Modbus Communication Module User Guide
Introduction
The SKE4 Modbus Communication Module User Guide provides information for using Neptronic® communication feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic SKE4 devices. The SKE4 Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus: · Data Model. The SKE4 Steam Humidifier Modbus server data model uses only the Modbus Registers table. · Register Address: o As per protocol base (base 0); for PLC add 1 to protocol base. o As per holding register (base 400001).
Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.
· Function Codes. The SKE4 Steam Humidifier Modbus server supports a limited function codes subset comprising: o Read Holding Registers (0x03) o Write Single Register (0x06) o Write Multiple Registers (0x10)
· Exception Responses. The SKE4 Steam Humidifier Modbus server supports the following exception codes: o Illegal data address o Illegal data value o Slave device busy
· Serial Line. The SKE4 Steam Humidifier Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer. o The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1. o The supported baud rates are 9600, 19200, 38400, and 57600. o The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2. o In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
· Addressing. The SKE4 Steam Humidifier device only answers at the following address: o The device's unique address (1 to 246) that can be set through the device menu or through holding register index 0.

www.neptronic.com

Page | 1

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Modbus Registers

Table Glossary

Name W RO Unsigned Signed
Bit String

Description

Name

Writable Register
Read Only Register
For range of values from 0 to 65,535, unless otherwise specified
For range of values from -32,768 to 32,767, unless otherwise specified
For registers with multiple values using bit mask (example, flags)

ASCII MSB LSB MSW
LSW

Description For registers containing ASCII (8-bit) characters Most Significant Byte Least Significant Byte Most Significant Word
Least Significant Word

Modbus Registers Table

Protocol Holding Base Register

Description

0

400001 Modbus Address and Product Type

1

400002 Device Baud Rate

2

400003

Modbus Slave Communication Port Configuration

3

400004 Product Name (characters 8 & 7)

4

400005 Product Name (characters 6 & 5)

5

400006 Product Name (characters 4 & 3)

6

400007 Product Name (characters 2 & 1)

Data Type

Units, Limits, State Texts

Writable Default Value

Unsigned

MSB = Product type, not writable LSB = Modbus Address (1 to 247), writable

W

Unsigned 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud Scale 100 Rate Detection Value/100 (e.g. 38400 baud = 384)

W

19200

Unsigned

0 = No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit

W

No parity, 2 Stops bits

ASCII MSB = char 6, LSB = char 7

W

ASCII MSB = char 4, LSB = char 5

W

ASCII MSB = char 2, LSB = char 3

W

ASCII MSB = char 0, LSB = char 1

W

www.neptronic.com

Page | 2

Protocol Holding Base Register

Description

7

400008

Product Actual Firmware Version (in Integer x100)

8

400009

Product Actual EEPROM Version (in Integer x100)

2000

402001 Control Signal

2001

402002 Room RH Signal

2002

402003 Supply RH Signal

2003

402004 Water Level Signal

2004

402005 Water Level Low Signal

2005

402006 Water Level High Signal

2006

402007 Water Temperature Signal

2007

402008 Foam Signal

2008

402009 SSR Temperature Signal

2009

402010 Cabinet Temperature Signal

2010

402011 Current Sensor 1 Signal

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 100
Unsigned Scale 100

1 to 65535 (e.g. 100) 1 to 65535 (e.g. 100)

Unsigned Units: Volt (V), Range: 0V to 15V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Units: Volt (V), Range: 0V to 15V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Units: Volt (V), Range: 0V to 15V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Units: Hz, Range: 0 to 30000Hz Scale 1 Value x 1 (e.g. 10Hz = 10)

Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)

Unsigned Unit: Volt (V), Range: 0V to 3.30V Scale 1000 Value x 1000 (e.g. 1V = 1000)

Writable Default Value

RO

RO

RO

0V

RO

0V

RO

0V

RO

0Hz

RO

0V

RO

0V

RO

0V

RO

0V

RO

0V

RO

0V

RO

0V

Page | 3

Protocol Holding Base Register

Description

2011

402012 Current Sensor 2 Signal

2012

402013 Board Temperature Signal

2013

402014 Main Power Supply

4000

404001 Power Output Feedback Signal

4001

404002 Heater SSR Stage

6000

406001 Control Input

6001

406002 Control Min

6002

406003 Control Max

6003

406004 Control Bias

6004

406005 Room RH

6005

406006 Room RH Min

6006

406007 Room RH Max

6007

406008 Room RH Bias

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Unit: Volt (V), Range: 0V to 3.30V Scale 1000 Value x 1000 (e.g. 1V = 1000)
Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)
Unsigned Unit: Volt (V), Range: 0V to 40V Scale 10 Value x 10 (e.g. 2V = 20)
Unsigned Unit: Volt (V), Range: 0V to 10V Scale 1000 Value x 1000 (e.g. 2V = 2000)
Unsigned Unit: %, Range: 0% to 100% Scale 100 Value x 100 (e.g. 10% = 1000) Unsigned Unit: %, Range: 0% to 100% Scale 100 Value x 100 (e.g. 10% = 1000)
Unsigned Unit: %, Range: 0% to 100% Scale 100 Value x 100 (e.g. 10% = 1000)
Unsigned Unit: %, Range: 0% to 100% Scale 100 Value x 100 (e.g. 10% = 1000)
Signed Unit: %, Range: -10% to 10% Scale 100 Value x 100 (e.g. 10% = 1000)
Unsigned Unit: % RH, Range: 0% RH to 100% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)
Unsigned Unit: % RH, Range: 0% RH to 100% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)
Unsigned Unit: % RH, Range: 0% RH to 100% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)
Unsigned Unit: % RH, Range: -10% RH to 10% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)

Writable Default Value

RO

0V

RO

0V

RO

0V

RO

0V

RO

0%

RO

0%

W

0%

W

0%

W

0%

RO

0% RH

W

0% RH

W

0% RH

W

0% RH

Page | 4

Protocol Holding Base Register

Description

6008

406009 Supply High Limit RH

6009

406010 Supply High Limit RH Min

6010

406011 Supply High Limit RH Max

6011

406012 Supply High Limit RH Bias

6012

406013 Water Temperature

6013

406014 Water Temperature Bias

6014

406015 SSR Temperature

6015

406016 Cabinet Temperature

6016

406017 Current Sensor 1

6017

406018 Current Sensor 2

6018

406019 Board Temperature

6019

406020 Power Output Feedback Bias

6020

406021 Power Output Feedback Min

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Writable Default Value

Unsigned Unit: % RH, Range: 0% RH to 100% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)

Unsigned Unit: % RH, Range: 0% RH to 100% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)

Unsigned Unit: % RH, Range: 0% RH to 100% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)

Signed Unit: %, Range: -10% RH to 10% RH Scale 100 Value x 100 (e.g. 10% RH = 1000)

Unsigned Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F Scale 100 Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

Signed Unit: ºC/ºF, Range: -10°C to 10°C or -18°F to 18°F Scale 100 Value x 100 (e.g. 5°C = 500 or 14ºF = 1400)

Signed Unit: ºC/ºF, Range: -20°C to 100°C or -4°F to Scale 100 212°F, Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

Signed Scale 100
Unsigned Scale 100

Unit: ºC/ºF, Range: -20°C to 100°C or -4°F to 212°F Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)
Unit: Amps (A), Range: 0A to 150A Value x 100 (e.g. 10A = 1000)

Unsigned Unit: Amps (A), Range: 0A to 150A Scale 100 Value x 100 (e.g. 10A = 1000)

Unsigned Scale 100
Unsigned Scale 1000

Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)
Unit: V, Range: -1V to 1V Value x 100 (e.g. 10V = 1000)

Unsigned Unit: V, Range: 0V to 10V Scale 1000 Value x 100 (e.g. 10V = 1000)

RO

0% RH

W

0% RH

W

0% RH

W

0% RH

RO 50°C or 122°F

RO

0°C or 32°F

RO

0°C or 32°F

RO

0°C or 32°F

RO

0A

RO

0A

RO

0°C or 32°F

W

0V

W

0V

Page | 5

Protocol Holding Base Register

Description

6021

406022 Power Output Feedback Max

6022

406023 Power Output Feedback

6023 6024

406024 Water Level 406025 Water Probe Low Pos Reading

6025

406026 Water Probe High Pos Reading

6026

406027 Water Probe Abs Low Pos Reading

6027

406028 Water Probe Abs High Pos Reading

6028 6029 6030 6031

406029 Room RH Network Reading 406030 Room RH Setpoint 406031 Room RH Unoccupied Setpoint 406032 Room RH Vacant Setpoint

6032

406033 Room Demand Proportional Gain

6033

406034 Room Demand Integral Time

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Unit: V, Range: 0V to 10V Scale 1000 Value x 100 (e.g. 10V = 1000)

Unsigned Unit: %, Range: 0% to 100% Scale 100 Value x 100 (e.g. 10% = 1000)

Unsigned Unit: %, Range: 0% to 120% Scale 10 Value x 10 (e.g. 10% = 100)

Unsigned Unit: Hz, Range: 0 to 30000 Hz Scale 1 Value x 1 (e.g. 1 Hz = 1)

Unsigned Unit: Hz, Range: 0 to 30000 Hz Scale 1 Value x 1 (e.g. 1 Hz = 1)

Unsigned Unit: Hz, Range: 0 to 30000 Hz Scale 1 Value x 1 (e.g. 1 Hz = 1)

Unsigned Unit: Hz, Range: 0 to 30000 Hz Scale 1 Value x 1 (e.g. 1 Hz = 1)

Unsigned Scale 100
Unsigned Scale 100
Unsigned Scale 100

Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)
Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)
Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)

Unsigned Scale 100
Unsigned Scale 10

Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000)
No Unit, Range: 1 to 200 Value x 10 (e.g. 10 = 100)

Unsigned Unit: Seconds (sec), Range: 0 to 900 sec Scale 10 Value x 10 (e.g. 10 sec = 100)

Writable Default Value

W

0V

RO

0%

RO

78%

RO

30000Hz

RO

30000Hz

RO

30000Hz

RO

30000Hz

W

0% RH

W

40% RH

W

30% RH

W

20% RH

W

20

W

0 sec

Page | 6

Protocol Holding Base Register

Description

6034

406035 Room Demand Derivative Time

6035

406036 Room Demand

6036

406037 Supply High Limit Network Reading

6037

406038 Supply High Limit Setpoint

6038

406039 Supply High Limit Proportional Gain

6039

406040 Supply High Limit Integral Time

6040

406041 Supply High Limit Derivative Time

6041

406042 Supply High Limit Demand

6042

406043 Humidity Control Network Demand

6043

406044 Humidity Control Network High Limit

6044

406045 Humidity Demand

6045

406046 SDU Fan Off Delay

6046

406047 System Power Output

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 10
Unsigned Scale 100 Unsigned Scale 100 Unsigned Scale 100 Unsigned Scale 10
Unsigned Scale 10
Unsigned Scale 10
Unsigned Scale 100 Unsigned Scale 100
Unsigned Scale 100
Unsigned Scale 100
Unsigned Scale 1
Unsigned Scale 100

Unit: Seconds (sec), Range: 0 to 60 sec Value x 10 (e.g. 10 sec = 100)
Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000) Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000) Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000) No Unit, Range: 1 to 200 Value x 10 (e.g. 10 = 100)
Unit: Seconds (sec), Range: 0 to 900 sec Value x 10 (e.g. 10 sec = 100)
Unit: Seconds (sec), Range: 0 to 60 sec Value x 10 (e.g. 10 sec = 100)
Unit: % RH, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000) Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000) Unit: Minutes (min), Range: 5 to 20 mins Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)

Writable Default Value

W

0 sec

RO

0% RH

W

0% RH

W

80% RH

W

10

W

0 sec

W

0 sec

RO

0% RH

W

0%

W

100%

RO

0%

W

5 min

RO

0%

Page | 7

Protocol Holding Base Register

Description

6047

406048 System Steam Capacity

6048

406049 Boiler Demand

6049

406050 Boiler Capacity

6050

406051 Boiler Power Output

6051
6052 6053 6054
6055
6056 6057 6058
6059
6060 6061 6062

406052 Boiler Run Time (0)

406053 406054 406055

Boiler Run Time (1) Boiler Run Time (2) Boiler Run Time (3)

406056 Boiler On Time (0)

406057 406058 406059

Boiler On Time (1) Boiler On Time (2) Boiler On Time (3)

406060 Boiler Service Run Time (0)

406061 406062 406063

Boiler Service Run Time (1) Boiler Service Run Time (2) Boiler Service Run Time (3)

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 10 Unsigned Scale 100 Unsigned Scale 10 Unsigned Scale 100 Unsigned Scale 100
Unsigned Scale 100
Unsigned Scale 100

Unit: kg/hr or lb/hr, Range: 0 to 3000 kg/hr or 0 to 6614 lb/hr Value x 10 (e.g. 10kg/hr = 100 or 10lb/hr = 100) Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000) Unit: kg/hr or lb/hr, Range: 0 to 3000 kg/hr or 0 to 6614 lb/hr Value x 10 (e.g. 10kg/hr = 100 or 10lb/hr = 100)
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)
Units: Hours (h), Range: 0 to 2147483647 h Value x 100 (e.g. 10 h = 1000)
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h Value x 100 (e.g. 10 h = 1000)
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h Value x 100 (e.g. 10 h = 1000)
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h
Units: Hours (h), Range: 0 to 2147483647 h

Writable Default Value

RO

0 kg/hr or 0 lb/hr

W

0%

RO

0 kg/hr or 0 lb/hr

RO

0%

RO

0h

RO

0h

RO

0h

Page | 8

Protocol Holding Base Register

Description

6063
6064 6065 6066
6067

406064 Boiler Service On Time (0)

406065 406066 406067

Boiler Service On Time (1) Boiler Service On Time (2) Boiler Service On Time (3)

406068 Boiler Minimum Steam Output

6068

406069 Boiler Drain Interval

6069

406070 Boiler Drain Volume

6070

406071 Boiler Max Steam Output

6071

40672 Boiler Idle Time Drain

6072

406073 Boiler Idle Temperature Setpoint

6073

406074 Boiler Blowdown Rate

6074

406075 Boiler Service Interval

6075

406076 Room Demand Proportional Band

6076

406077 HRL Temperature

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Writable Default Value

Unsigned Units: Hours (h), Range: 0 to 2147483647 h Scale 100 Value x 100 (e.g. 10 h = 1000)

RO

Units: Hours (h), Range: 0 to 2147483647 h

Units: Hours (h), Range: 0 to 2147483647 h

Units: Hours (h), Range: 0 to 2147483647 h

Unsigned Unit: %, Range: 1 to 25% Scale 1 Value x 1 (e.g. 1% = 1)

W

Unsigned Units: Hours (h), Range: 0 to 24 h Scale 1 Value x 1 (e.g. 1 h = 1)

W

Unsigned Unit: %, Range: 25 to 100% Scale 1 Value x 1 (e.g. 30% = 30)

W

Unsigned Unit: %, Range: 0 to 100% Scale 1 Value x 1 (e.g. 1% = 1)

W

Unsigned Unit: Hours (h), Range: 0 to 72 h

Scale 1 Value x 1 (e.g. 1 h = 1)

W

Unsigned Unit: ºC/ºF, Range: 0°C to 60°C or 32°F or 140°F Scale 1 Value x 1 (e.g. 5°C = 500 or 10ºF = 1000)

W

Unsigned Unit: %, Range: 0% to 100% Scale 1 Value x 1 (e.g. 10% = 10)

W

Unsigned Unit: Hours (h), Range: 1000 to 3000 h Scale 1 Value x 1 (e.g. 1500 h = 1500)

W

Unsigned Unit: %, Range: 1% to 100% Scale 10 Value x 100 (e.g. 10% = 100)

RO

Signed Unit: ºC/ºF, Range: -40°C to 260°C or -40°F to Scale 100 500°F, Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)

RO

0h
5% 6h 100% 100% 24h 0°C or 32°F 0% 1000h 5% 0°C or 32°F

Page | 9

Protocol Holding Base Register

Description

6077

406078 Supply High Limit Proportional Band

6078

406079 HRL Humidity

6079

406080 Modbus TCP IP Keep Alive Time Out

6080

406081 Humidity Demand Low Dead Band

6081

406082 Network Timeout

6082

406083 Water Level Replace Interval

6083
6084 6085 6086
6087

406084 Boiler Manual Calibration Time (0)

406085 406086 406087

Boiler Manual Calibration Time (1) Boiler Manual Calibration Time (2) Boiler Manual Calibration Time (3)

406088 HRL Temperature Bas

6088

406089 HRL Humidity Bias

6089

406090 Fill Delay

6090

406091 Clean Valve Delay

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Writable Default Value

Unsigned Scale 10 Unsigned Scale 100 Unsigned Scale 1 Unsigned Scale 100 Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1
Signed Scale 10 Signed Scale 10 Unsigned Scale 1 Unsigned Scale 1

Unit: %, Range: 1% to 100% Value x 100 (e.g. 10% = 100)
Unit: %, Range: 0% RH to 100% RH Value x 100 (e.g. 10% RH = 1000) Unit: Minutes (min), Range: 1 to 1440 mins Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 0% to 100% Value x 100 (e.g. 10% = 1000)
Unit: Seconds (sec), Range: 1 to 900 sec Value x 1 (e.g. 10sec = 10)
Unit: Days, Range: 1 to 7 days Value x 1 (e.g. 1 day = 1)
Unit: Hours (h), Range: 0 to 21474836.47 h Value x 1 (e.g. 1 h = 1)
Unit: Hours (h), Range: 0 to 21474836.47 h
Unit: Hours (h), Range: 0 to 21474836.47 h
Unit: Hours (h), Range: 0 to 21474836.47 h
Unit: ºC/ºF, Range: -10°C to 10°C or -18°F to 18°F Value x 10 (e.g. 5°C = 50 or 14ºF = 140)
Unit: %RH, Range: -10%RH to 10%RH Value x 10 (e.g. 5%RH = 50)
Unit: Minutes (min), Range: 1 to 15 mins Value x 1 (e.g. 5 mins = 5)
Unit: %, Range: 0% to 80% Value x 1 (e.g. 10% = 10)

RO

10%

RO

0% RH

W

5 min

W

1%

W

900 sec

W

3day

RO

0h

W

0°C or 32°F

W

0%RH

RO

0 min

W

50%

Page | 10

Protocol Holding Base Register

10000

410001 Air Flow

Description

10001

410002 Supply High Limit

10002

410003 Interlock

10003

410004 Binary External Demand

10004

410005 Water Leak Detection

10005

410006 Thermal Cutout

10006

410007 RS485 Interface

10007

410008 Ethernet Interface

10008

410009 Contactors PCB Fuse

10009

410010 Control PCB Fuse

11000 11001 11002

411001 Alarm Warning Relay 411002 Service Warning Relay 411003 Water Level Valve

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1

0 = Closed 1 = Open
0 = Closed 1 = Open
0 = Closed 1 = Open
0 = 0% 1 = 100%
0 = Ok 1 = Leak
0 = Closed 1 = Open
0 = No 1 = Yes
0 = No 1 = Yes
0 = Normal 1 = Blown Fuse
0 = Normal 1 = Open Fuse
0 = Off 1 = On 0 = Off 1 = On 0 = Off 1 = On

Writable Default Value

RO

Closed

RO

Closed

RO

Closed

RO

0%

RO

Ok

RO

Closed

RO

No

RO

No

RO

Normal

RO

Normal

RO

Off

RO

Off

RO

Off

Page | 11

Protocol Holding Base Register

Description

11003

411004 Tank Water Valve

11004

411005 Drain Cooler Valve

11005

411006 Drain Pump

11006

411007 Drain Valve

11007

411008 Main Contactor

11008

411009 Heater Stage 1

11009

411010 Heater Stage2

11010

411011 Heater Stage 3

11011

411012 SDU Fan

11012

411013 Alarm LED

11013

411014 Power LED

11014

411015 Buzzer

12000

412001 Manual Water Calibration State

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1

0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On 0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Ok 1 = Required

Writable Default Value

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Off

RO

Ok

Page | 12

Protocol Holding Base Register

Description

12001

412002 Water Level Low

12002

412003 Water Level High

12003

412004 Foam Sensor

12004 12005 12006

412005 SDU Fan Fault 412006 Boiler Service Operation 412007 Boiler Service Due

12007

412008 Foam

12008

412009 HRL Lock Setpoint

12009

412010 Network Control State

12010

412011 Inhibit Resistive Probe

12011

412012 Notify Alarm

12012

412013 Notify Warning

12013

412014 Notify App Msg

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1

0 = Inactive 1 = Active
0 = Inactive 1 = Active
0 = NoFoam 1 = Foam
0 = Off 1 = On
0 = Not Allowed 1 = Allowed
0 = No 1 = Yes
0 = Ok 1 = Detected
0 = Unlock 1 = Lock
0 = Normal 1 = Fault
0 = No 1 = Yes
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On

Writable Default Value

RO

Inactive

RO

Inactive

RO

NoFoam

RO

Off

W

Allowed

RO

No

RO

Ok

W

Unlock

W

Normal

W

No

W

Off

W

Off

W

Off

Page | 13

Protocol Holding Base Register

Description

12014

412015 Boiler Line Rinse

12015

412016 AntiFreeze Warning

15000

415001 System Log Verbose Level

15001

415002 Modbus Server Units

15002

415003 Control Signal Type

15003

415004 Room RH Signal Type

15004

415005 Supply RH Signal Type

15005

415006 Control Profile

15006

415007 Modulating High Limit Profile

15007

415008 Occupancy State

www.neptronic.com

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 1 Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1

0 = Off 1 = On
0 = Inactive 1 = Drain
0 = None 1 = Emergency 2 = Alert 3 = Critical 4 = Error
0 = Metric 1 = Imperial
0 = 0-10Vdc 1 = 2-10Vdc 2 = 4-20mA 3 = 0-20mA
0 = 0-10Vdc 1 = 2-10Vdc 2 = 4-20mA 3 = 0-20mA
0 = 0-10Vdc 1 = 2-10Vdc 2 = 4-20mA 3 = 0-20mA
0 = ExternAnalog 1 = ExternNetwork 2 = InternAnalog
0 = Disabled 1 = ExternAnalog 2 = ExternNetwork
0 = Occupied 1 = Unoccupied

5 = Warning 6 = Notice 7 = Info 8 = Debug
3 = InternNetwork 4 = HRL 5 = Custom 3 = InternAnalog 4 = InternNetwork 5 = Custom 2 = Vacant 3 = Off

Writable Default Value

W

On

RO

Inactive

W

Debug

W

Metric

W

0-10Vdc

W

0-10Vdc

W

0-10Vdc

W

ExternAnalog

W

Disabled

RO

Occupied

Page | 14

Protocol Holding Base Register

Description

15008

415009 Room RH Source

15009

415010 Room RH Setpoint Source

15010

415011 Supply High Limit Reading Source

15011

415012 Supply High Limit Setpoint Source

15012

415013 Humidity Control Demand Source

15013

415014 Humidity Control High Limit Source

15014

415015 Humidity Control Cutout State

15015

415016 SDU Fan Target

15016

415017 Boiler Request

15017

415018 Boiler State

15018

415019 Boiler Fill Mode

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Writable Default Value

Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1
Unsigned Scale 1

0 = None 1 = RoomRH
0 = None 1 = Internal
0 = None 1 = SuppyHLRH
0 = None 1 = Internal
0 = None 1 = ControlInput
0 = None 1 = ControlInput
0 = Off 1 = Normal 2 = LowLimit
0 = None 1 = SDUFan
0 = None 1 = Reset Alarms 2 = Drain 0 = Off 1 = Idle 2 = LineRinse 3 = TankRinse 4 = Filling
0 = OneShot 1 = Pulsed

2 = Network 3 = HRL
2 = ControlInput

W

None

W

None

2 = Network

W

None

2 = ControlInput

W

None

2 = RoomDemand 3 = Network

W

ControlInput

2 = SupplyHLDemand 3 = Network

W

None

3 = HighLimit 4 = NoAirFlow 5 = Interlock

RO

Off

W

None

3 = Reset Counters

4 = Filling

W

5 = WaterCalib

5 = Draining

6 = Heating 7 = Boiling

RO

8 = Alarm

None Off

W

Pulsed

www.neptronic.com

Page | 15

Protocol Holding Base Register

Description

15019

415020 Boiler Alarm

15020 15021 15022 15023 15024 15025 15026 15027

415021 Boiler Idle Tank Rinse On 415022 Boiler Idle Tank Rinse Off 415023 Water Probe Auto Calib. 415024 System Power State 415025 Water Level Probe Warning 415026 Water Level Probe Failure 415027 Water Level Probe Alarm 415028 Boiler Startup Tank Rinse

SKE4 Steam Humidifier
Modbus Communication Module User Guide

Data Type

Units, Limits, State Texts

Unsigned Scale 1
Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1
Unsigned Scale 1 Unsigned Scale 1 Unsigned Scale 1
Unsigned Scale 1 Unsigned Scale 1

0 = Normal 1 = FailedPump 2 = FillTimeout 3 = BlockedPiping 4 = HeatTimeout 5 = Overheat
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Off 1 = On
0 = Ok 1 = Replace
0 = None 1 = Capacitive
0 = Ok 1 = Defect
0 = Off 1 = On

6 = WaterLeak 7 = Service 8 is Reserved 9 = TankBlocked 10 = RefillDelay
2 = Resistive 3 = Both 2 = NoCalib

Writable Default Value

RO

Normal

W

Off

W

Off

W

On

W

Off

RO

Ok

RO

None

RO

Ok

W

Off

www.neptronic.com

Page | 16