Instruction Sheet
Subject: Ice Level Management Kit Installation
ELECTRONIC BIN THERMOSTAT INSTALLATION INSTRUCTIONS FOR CUBE, NUGGET OR FLAKE ICE MACHINES
Overview
This kit reduces overfill and condensation issues and can be used on a Manitowoc or Koolaire ice machine installed on an ice dispenser or bin.
Safety Precautions
Warning: Authorized Service Representatives are obligated to follow industry standard safety procedures, including, but not limited to, local/national regulations for disconnection / lock out / tag out procedures for all utilities including electric, gas, water and steam.
DANGER: Disconnect electric power to the ice machine at the electric switch box before proceeding. Failure to disconnect the power at the main power supply disconnect could result in serious injury or death. The power switch DOES NOT disconnect all incoming power.
Ice Level Management Kit Installation
- Remove all ice from dispenser or bin.
- Disconnect all power to the ice machine and dispenser at the service disconnect or fuse/breaker panel.
- Move the ice machine and dispenser/bin away from the wall for easier access.
- Remove all panels and control box cover.
- If an ice machine is already installed on the dispenser/bin, raise and support the right side of the ice machine. Install the mounting bracket on the right-hand side of the dispenser/bin 6" from the right rear corner. Compress the bracket to the thickness of the dispenser wall and tighten the two screws.
- Route thermistor wire out back of the ice machine/dispenser/bin (lower the ice machine, if supported). Remove unused knockout on the ice machine back panel, install romex connector and route wire into the ice machine compressor compartment.
- Normally the controller can be mounted on the bulkhead flange. If not, a suitable area must be found for your model. Use controller bracket to locate mounting holes on the flange of the bulkhead. Drill two 9/32" diameter holes. Do not mount the controller, at this time.
- Route the four wires from the temperature control to the control box (insuring that the wires will not come in contact with any refrigeration tubing).
- The electronic control receives line voltage power from L1 and L2 on the ice machine:
- Contactor: Connect thermostat L1 (brown) and L2 (blue) wires to contactor (incoming line voltage side) L1 and L2.
- Incoming Power: Disconnect incoming power line wire nuts. When present remove quick-connect fittings from brown and blue wires and strip 1/2" of insulation from the wires. Connect incoming power L1, ice machine L1, and thermostat L1 (brown) wires together with wire nut. Connect incoming power L2, ice machine L2, and thermostat L2 (blue) wires together with wire nut.
- Connect ice machine to electronic controller LC and LNO terminals:
Caution: When a jumper wire is connected from line voltage to LC, it must be removed before installing the bin switch wires. Verify the wiring matches the diagram displayed.
Manitowoc Models
- Disconnect the red male/female connector for the bin switch wire and connect the red male wire from the controller to the red female bin switch wire.
- Connect the white male bin switch wire to the white female wire of the controller.
KoolAire Models
- Cut the red bin switch wire 3 inches from molex connector on bin switch.
- Strip wires and install male and female crimp connectors supplied in kit.
- Connect male and female connectors from the bin thermostat into the newly installed terminals.
Nugget or Flake Models
NOTE: Flake ice machines can not be used on a dispenser.
BIN THERMOSTAT
- Disconnect L1 wire from bin thermostat and connect to the red male wire from the controller.
- Connect white female wire of the controller to the bin thermostat.
TOGGLE SWITCH
- Disconnect L1 wire from toggle switch and connect to the red male wire from the controller.
- Connect white female wire of the controller to the toggle switch.
Wiring Diagram Descriptions:
- Manitowoc Models Wiring: Describes connecting the red male/female bin switch wire and white male bin switch wire from the controller to the bin switch wire.
- Koolaire Models Wiring: Describes cutting the red bin switch wire, stripping wires, installing connectors, and connecting male/female connectors from the bin thermostat.
- Nugget or Flake Models (Bin Thermostat) Wiring: Describes disconnecting L1 from the bin thermostat and connecting it to the red male wire from the controller, and connecting the white female wire of the controller to the bin thermostat.
- Nugget or Flake Models (Toggle Switch) Wiring: Describes disconnecting L1 from the toggle switch and connecting it to the red male wire from the controller, and connecting the white female wire of the controller to the toggle switch.
- K-Series Control Board Diagram: A wiring diagram shows a K-Series control board with terminals for voltage (115V, 240V), LC, LNO, LNC. It indicates where to connect sensor leads (red and black) and bin switch/thermostat/toggle switch wires.
- Koolaire Models Wiring Diagram: A wiring diagram for Koolaire Models shows an electronic control unit with LC and LNC terminals. It illustrates connections using male and female connectors, including a red and black lead, and a connection to a curtain switch.
- Nugget/Flake Models Wiring Diagram: A wiring diagram for Nugget/Flake Models shows an electronic control unit with LC and LNC terminals, labeled 'CONNECT TO LC TERMINAL'. It shows connections to a thermostat or bin switch, and to safety controls.
- Restore all power to the ice machine and dispenser at the service-disconnect or fuse/breaker panel.
- With two screws, secure the controller bracket assembly to the flange of the bulkhead.
- Refer to Setting Control Setpoint Values and program the thermostat.
- Reinstall the control box cover and all panels.
Setting Control Setpoint Values
To view and adjust setpoint, follow these steps:
- Press MENU, select and set the OFF temperature. Press the up or down arrows to change the setpoint value (38° F / 3° C recommended). Press MENU to save the new value and advance to the next parameter code.
- Scroll to the ON parameter. Press the up or down arrows to change the ON setpoint value (40° F / 5° C recommended). Press MENU to save the setting and advance to the next parameter code.
- Scroll to the SF screen. Press up or down arrows to set the SF (sensor failure) operation:
- 0 = Shuts off on sensor failure - Flake, nugget or cube ice
- 1 = Continues to run on sensor failure - 0 is recommended for all applications although cube ice can use this setting.
- Press MENU to save the new value and advance to the next parameter code.
- Scroll to the ASd (anti short cycling delay) screen. Press the up or down arrow to change the ASd (anti short cycling delay) time: Numbers are minutes; a minimum of one minute is required and recommended. Press MENU to save the setting, then wait 30 seconds for the control to revert to the default temperature setpoint display.
Important: If MENU is not pressed after changing the setpoint value, the control reverts to the previous setpoint value.
Warning: Do not use sensor failure setting 1 (one) with nugget ice machines. Overfilling can result in the ice machine dislodging and falling from the dispenser during ice agitation.
Note: The time delay is active anytime power is interrupted and restored or the control cycles the ice machine off.
Restricting Control Adjustment
The jumper position determines if the touch pad is locked or unlocked. To change function, disconnect power to the controller, move the jumper to the desired function and reapply power to the controller.
- Locked - Jumper contacts one pin.
- Unlocked - Jumper contacts both pins.
Illustration Description: Illustration showing jumper positions for restricting control adjustment: 'Locked' shows the jumper contacting a single pin, and 'Unlocked' shows the jumper contacting both pins.
Troubleshooting
If the control system does not function properly, verify the control is wired and set up properly. If the problem persists, use the following procedures to determine the cause of the problem.
Warning: Line voltage is present inside the control. Contact with line voltage can cause injury or death.
Follow these troubleshooting procedures in the order presented. Do not skip any of the steps in the procedures.
-
Check for proper voltage to the control.
- Remove the cover by loosening the four cover screws.
- Use an AC voltmeter to check the voltage between the common and 120V or 240V terminals.
- The voltage must be between 102 and 132 volts for 120V applications; 177 and 264 volts for 208/230V applications.
- If the voltage reading is not within the required range, check the power source and input power wires for problems.
-
Check for Fault Codes
If the LCD displays an alarm or fault code (SF or EE):
Fault Code Definition Solution SF flashing alternately with OP Open temperature sensor or sensor wiring See Step 3. Cycle power to reset control SF flashing alternately with SH Shorted temperature sensor or sensor wiring See Step 3. Cycle power to reset control EE Program failure Reset the control by pressing MENU. If problem persists cycle power to reset control. If problem isn't resolved, replace the control. -
Test thermistor resistance.
- Disconnect thermistor from control.
- Measure the temperature at thermistor.
- Measure resistance of thermistor.
- Compare temperature and resistance to the chart. Replace thermistor if values are not in the proper range.
Thermistor Resistance Chart Description: A graph titled 'TEMPERATURE °F' vs. 'RESISTANCE (OHMS)' displays a positive linear relationship. At 500 Ohms, the temperature is 20°F; at 700 Ohms, it's 40°F; at 900 Ohms, it's 60°F; at 1100 Ohms, it's 80°F; at 1300 Ohms, it's 100°F. The graph extends up to 120°F.
-
Check for proper operation.
Important: Perform Steps 1, 2 and 3 before performing these steps:
- Disconnect the load from the output relay terminals.
- Verify the touch pad is unlocked, "Restricting Control Adjustment" on page 3.
- Reconnect the sensor leads and supply power to the control.
- Replace the cover.
- Check the control settings for proper values.
- Press MENU until ASd appears and set the delay to 0, press menu to save the setting.
- Press MENU until ON appears. Press MENU and then use the up and down arrows to change the setpoint temperature above and below the sensor temperature until the relay energizes and de-energizes.
- If the output relay does not perform as indicated, replace the control.
- If proper operation of the control is verified, reconnect the load.