Introduction
Enclosed type switching power supplies possess a metal or plastic case for covering their internal PCB and will be installed inside the case of the end system. Mean Well's enclosed type power supplies include 2 different groups of power supplies, with built-in fan and without built-in fan, depending on their rated power or design concept.
Installation
- Before any installation or maintenance work, please disconnect your system from the utility. Ensure that it can't be re-connected inadvertently!
- Keep enough insulation distance between mounting screws and internal components of power supplies. Please refer to case drawing on specifications to receive the maximum length of mounting screw.
- Mounting orientations other than standard orientation or operate under high ambient temperature may increase the internal component temperature and will require a de-rating in output current. Please refer to the specification sheets to receive the optimum mounting position and information about the de-rating curve.
- Fans and ventilation holes must be kept free from any obstructions. Also a 10-15 cm clearance must be kept when the adjacent device is a heat source.
- Input and Output terminal specifications are provided in the following tables.
- Torque can be various due to different material; please refer to the following charts for recommendations for aluminum and iron.
- Recommended wires are shown in the table below. Note: Current each wire carries should be de-rated to 80% of the current suggested above when using 5 or more wires connected to the unit. Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact.
- Wiring: Wire color will vary by country; please refer to the table below for North America and European Harmonized standards. Ensure all wires are secured to prevent poor contact.
- For other information about the products, please refer to www.meanwell.com for details.
Input and Output Terminal Torque Specifications
Series | Input Terminal Screw | Input Screw Size | Input Suggested Torque | Output Screw Size | Output Suggested Torque |
---|---|---|---|---|---|
RSP-750 / 1000 / 1500 / 2000 / 2400 / 3000 SE-450 / 1000 / 1500 | M4 | 10-12kgf-cm | M4 | 10-12kgf-cm | |
HEP-600, HRP-300, HRPG-300, MSP-300 | M4 | 10-12kgf-cm | M4 | 10-12kgf-cm | |
SP-480, SP-750, SPV-1500, USP-500, RST-10000 | M4 | 10-12kgf-cm | M8 | 10-12kgf-cm | |
HRP-075 / 100 / 150 / 200, HRPG-150 / 200 | M3.5 | 8-10 kgf-cm | M3.5 | 8-10 kgf-cm | |
LRS-035 / 050 / 075 / 100 / 150 / 150F / 200 / 350 MSP-100 / 200 | M3.5 | 8-10 kgf-cm | M3.5 | 8-10 kgf-cm | |
NED-035 / 050 / 075 / 100, NET-035 / 050 / 075 | M3.5 | 8-10 kgf-cm | M3.5 | 8-10 kgf-cm | |
NES-025 / 035 / 050 / 075 / 100 / 150 / 200 / 350 QP-200 / 320 / 375 | M3.5 | 8-10 kgf-cm | M3.5 | 8-10 kgf-cm | |
RD-050 / 065 / 085 / 125, RID-050 / 065 / 085 / 125 RS-035 / 050 / 075 / 100 / 150 | M3 | 6-8 kgf-cm | M3 | 6-8 kgf-cm | |
RSP-075 / 100 / 150 / 200 / 320 SP-075 / 100 / 150 / 200 / 240 / 320, SPV-150 / 300 SE-100 / 200 / 350, HSP-250, PSP-600 | M3 | 6-8 kgf-cm | M3 | 6-8 kgf-cm | |
RSP-1600 | M3 | 6-8 kgf-cm | M3 | 6-8 kgf-cm | |
RD-035, RT-050 / 065 / 085 / 125 RQ-050 / 065 / 085 / 125 | M3 | 6-8 kgf-cm | M3 | 6-8 kgf-cm | |
TP-075 / 100 / 150, QP-100 / 150 RS-015 / 025 NES-015, USP-150 | M3 | 6-8 kgf-cm | M3 | 6-8 kgf-cm | |
ERP-350 | #6 | 8-10 kgf-cm | M4 | 10-12kgf-cm | |
HDP-190 / 240 | #6 | 8-10 kgf-cm | M4 | 10-12kgf-cm | |
NEL-200 / 300 | #6 | 8-10 kgf-cm | M3 | 8-10kgf-cm | |
ENP-120 / 180 / 240 / 360 | M2.6 | 4-5 kgf-cm | M4 | 10-12kgf-cm | |
HRP-450 / 600 HRPG-450 / 600 MSP-450 / 600 / 1000 SE-600 | M3 | 6-8kgf-cm | M4 | 10-12kgf-cm | |
HSP-150 / 200 / 300 HSN-200 / 300 | M3 | 6-8kgf-cm | M3.5 | 8-10kgf-cm | |
RSP-500 | M3.5 | 8-10kgf-cm | M4 | 10-12kgf-cm | |
RST-5000 | M4 | 10-12kgf-cm | M8 | 10-12kgf-cm | |
NEL-400 | #6 | 8-10kgf-cm | M3 | 8-10kgf-cm | |
UHP-200(R) / 350(R) | M3 | 5kgf-cm | M3.5 | 8kgf-cm | |
UHP-200A | M3.5 | 13kgf-cm | M3.5 | 8kgf-cm | |
CSP-3000 | M4 | 10-12kgf-cm | M6 | 13kgf-cm | |
UHP-500(R) / 750 / 1000 | M3 | 5kgf-cm | M4 | 10-12kgf-cm | |
HEP-600 / 1000 | M4 | 10-12kgf-cm | M4 | 10-12kgf-cm |
Torque Recommendations
A. Recommended torque for aluminum
Size of screw (Imperial units) | Recommend torque (kgf-cm) |
---|---|
3-56 | 2.3±20% |
4-40 | 3.0±20% |
4-48 | 3.3±20% |
5-40 | 4.5±20% |
5-44 | 4.7±20% |
6-32 | 5.6±20% |
6-40 | 6.3±20% |
8-32 | 10.4±20% |
8-36 | 10.8±20% |
A. Recommended torque for aluminum (Metric Units)
Size of screw (Metric Units) | Recommend torque (kgf-cm) |
---|---|
M2.5 | 2.2±20% |
M3 | 4.1±20% |
M3.5 | 6.5±20% |
M4 | 9.7±20% |
M5 | 19.5±10% |
M6 | 33.1±10% |
M7 | 55.3±10% |
M8 | 80.6±10% |
B. Recommend torque for iron
Size of screw (Imperial units) | Recommend torque (kgf-cm) |
---|---|
3-56 | 5.0±20% |
4-40 | 6.9±20% |
4-48 | 7.0±20% |
5-40 | 9.4±20% |
5-44 | 9.9±20% |
6-32 | 12.0±20% |
6-40 | 13.4±20% |
8-32 | 21.8±20% |
8-36 | 23.0±20% |
B. Recommend torque for iron (Metric Units)
Size of screw (Metric Units) | Recommend torque (kgf-cm) |
---|---|
M2.5 | 4.6±20% |
M3 | 8.8±20% |
M3.5 | 13.7±20% |
M4 | 20.4±20% |
M5 | 41.1±10% |
M6 | 69.1±10% |
M7 | 117.5±10% |
M8 | 169.4±10% |
If above mentioned is not enough due to special application, Nylok Blue Patch screw is recommended, and extra torque can be added if needed.
Recommended Wires
AWG | 18 | 16 | 14 | 12 | 10 | 8 |
---|---|---|---|---|---|---|
Rated Current of Equipment (Amp) | 6A | 6-10A | 10-16A | 16-25A | 25-32A | 32-40A |
Cross-section of Lead(mm²) | 0.75 | 1.00 | 1.5 | 2.5 | 4 | 6 |
Note: Current each wire carries should be de-rated to 80% of the current suggested above when using 5 or more wires connected to the unit. Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact.
Wiring
The wire color will vary by country; please refer to the table below for North America and European Harmonized standards.
North America | European Harmonized | |
---|---|---|
Live and ACL | Black | Brown |
Neutral and ACN | White | Blue |
PE and FG (Class I only) | Green | Green/yellow |
a) Connect the FG wire (green or green/yellow) of the power supply to PE (green or green/yellow); this step can be skipped when the unit is marked class II, ungrounded.
b) Connect the ACL wire (black or brown) of the power supply to Live (black or brown).
c) Connect the ACN wire (white or blue) of the power supply to Neutral (white or blue).
d) Make sure all wires are secured to prevent poor contact.
Wiring Diagram Description
The diagram illustrates a basic AC input connection for a Power Supply Unit (PSU). The input lines are labeled LIVE/HOT (Black or brown), NEUTRAL (White or blue), and PE (Green or green/yellow). These lines connect to the PSU's AC/L, AC/N, and FG terminals, respectively. A circuit breaker (CB) and a line connection (LINC) are shown in the path of the AC input to the PSU.
Warning / Caution
- Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do not remove the case of the power supply by yourself!
- Please do not install power supplies in places with high moisture or near the water.
- Please do not install power supplies in places with high ambient temperature or near fire source. The maximum ambient temperature please refer to their specifications.
- Output current and output wattage must not exceed the rated values on specifications.
- The ground(FG) must be connected to earth ground.
- All MW's PSUs are designed in accordance with EMC regulations and the related test reports are available by request. Since they are component power supplies and will be installed inside system enclosure, when they are integrated into a system, the EMC characteristics of the end system must be re-verified again.
- This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (a) This device may not cause harmful interference, and (b) this device must accept any interference received, including interference that may cause undesired operation.
- For series of LRS, NES, PSP, PSPA, RD, RSP, RS, SE that certified with BSMI approvals, flammability of V1 or above is required for surrounding equipment and operation of this equipment in a residential environment could cause radio interference.
Manufacturer and Branch Offices
Manufacturer
MEAN WELL ENTERPRISES CO., LTD.
No.28, Wuquan 3rd Rd., Wugu Dist.,
New Taipei City 24891, Taiwan
Tel: +886-2-2299-6100
Web: www.meanwell.com
Branch Offices
China
MEAN WELL (GUANGZHOU) ENTERPRISES CO., LTD.
2F, A Building, Yuean Industry Park, Huangcun, Dongpu Yown, Tianhe District, Gungzhou, China
Post Code: 510660
Tel: +86-20-2887-1200
Web: www.meanwell.com.cn
China
MEAN WELL (GUANGZHOU) ENTERPRISES CO., LTD.
No.11, Jingu South Road, Huadong Town, Huadu Distric, Guangzhou, Gungzhou, China
Tel: +86-20-3773-7100
Web: www.meanwell.com.cn
China
SUZHOU MEAN WELL TECHNOLOGY CO., LTD.
No.77, Jian-Ming Rd. Dong-Qiao, Pan-Yang Ind. Park, Huang-Dai Town, Xiang-Cheng District, Suzhou, Jiang-Su, China
Post Code: 215152
Tel: +86-512-6508-8600
Web: www.meanwell.cc
U.S.A.
MEAN WELL USA, INC.
44030 Fremont Blvd., Fremont, CA 94538, U.S.A.
Tel: +1-510-683-8886
Web: www.meanwellusa.com
Europe
MEAN WELL EUROPE B.V.
Langs de Werf 8, 1185XT Amstelveen, The Netherlands
Tel: +31-20-758-6000
Web: www.meanwell.eu
Declarations
Declaration of China RoHS Conformity
In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL is confirming and announcing the conformity to China RoHS, an Administrative Measures for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products.
Environment Friendly Use Period Label
[10-year use period label] Observing SJT 11364-2014, Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products. Observing SJ/Z 11388-2009, General Guidelines of Environment-friendly Use Period of Electronic Information Products Appendix B, adopting table look-up to verify the Environment Friendly Use Period.
Names and Contents of Hazardous Substances Lists
Part Name | Lead (Pb) | Mercury (Hg) | Cadmium (Cd) | Hexavalent Chromium (Cr6+) | Polybrominated biphenyls (PBB) | Polybrominated diphenyl ethers (PBDE) |
---|---|---|---|---|---|---|
PCB and its components | X | O | X | O | O | O |
Metal structure parts | X | O | O | O | O | O |
Plastic structure parts | O | O | O | O | O | O |
Accessories | O | O | O | O | O | O |
Cables | X | O | O | O | O | O |
O: The concentration of the hazardous substances within the homogeneous material of that product is less than the concentration limits set by GB/T 26572-2011.
X: The concentration of the hazardous substances within the homogeneous material of that product is over the concentration limits set by GB/T 26572-2011; however, it follows the standard advised by 2011/65/EU.
Declaration of China VOC Conformity
In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL is confirming and announcing the conformity to China's Standardization Administration Releases VOC Standards.
Standard No. | Name of the Standard |
---|---|
GB 30981-2020 | Limit of harmful substances of industrial protective coatings |
GB 33372-2020 | Limits for volatile organic compounds content in adhesive |
GB 38507-2020 | Limits for volatile organic compounds (VOCs) In printing ink |
GB 38508-2020 | Limits for volatile organic compounds content in cleaning agents |
Declaration of Five PBT TSCA Conformity
In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL hereby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6(h).
CAS No. | Substance Name |
---|---|
1163-19-5 | Decabromodiphenyl ether (DecaBDE) |
68937-41-7 | Phenol, isopropylated, phosphate (3:1) PIP (3:1) |
732-26-3 | 2,4,6-Tris (tert-butyl) phenol (2,4,6-TTBP) |
133-49-3 | Pentachlorothiophenol (PCTP) |
87-68-3 | Hexachlorobutadiene (HCBD) |