HRN-43 HRN-43N Voltage monitoring relay for complete control in 3P incl. asymmetry EN


File Info : application/pdf, 2 Pages, 558.71KB

PDF preview unavailable. Download the PDF instead.

Manual HRN-43 43N
EN

ELKO EP, s.r.o.
Palackého 493 769 01 Holesov, Vsetuly Czech Republic Tel.: +420 573 514 211 e-mail: elko@elkoep.com www.elkoep.com
Made in Czech Republic
02-51/2023

HRN-43 HRN-43N
Voltage monitoring relay for complete control in 3P incl. asymmetry

Characteristics
· Relay is designed to monitor voltage in 3-phase networks: HRN-43: delta connection 3× 400 V (without neutral) HRN-43N: star connection 3× 400/230 V (with neutral)
· Monitors level of voltage in two independent levels (Umax, Umin) overvoltage and undervoltage: system 3× 400 V: range 240 ­ 480 V system 3× 400/230 V: range 138 ­ 276 V
· Other monitored parameters: phase failure, sequence, asymmetry (adjustable, can be switched off )
· Setting the monitored lower level (Umin) in % of the set upper level Umax. · Adjustable time delay (eliminanting short-term drops and spikes). · Selectable function of output contacts (independently/in parallel). · Galvanically isolated supply voltage AC/DC 24 ­ 240 V, AC 400 V. · Output contact for each monitored voltage level.

Description
HRN-43N 1
2 3 4 5
17

6 1. Supply voltage terminals (A1-A2)

2. Supply voltage indication

7

8 9

3. Overvoltage/undervoltage, phase failure indication

10 4. Phase sequence indication

11 5. Phase asymmetry indication

12 6. Voltage monitoring terminals (N-L1-L2-L3)

13 7. Phase asymmetry monitoring (YES/NO)

14 15

8. Memory function

9. Output function setting

10. Hysteresis setting

11. Time delay Umax/Umin

12. Upper level setting (Umax)

16 13. Memory reset 14. Asymmetry setting

15. Lower level setting (Umin)

16. Output contact 2 (28-25-26)

17. Output contact 1 (16-15-18)

Connection
L1 L2 L3 N
Un + ­
HRN-43

Un +­
HRN-43N

Symbol
HRN-43 A1

16 18 26 28

HRN-43N A1

16 18 26 28

L1

3~

L2

<U

L3

L1 L2 L3

3~ <U

N

A2

15 25

A2

15 25

Technical parameters Supply
Supply terminals: Supply voltage: Consumption (max.): Supply voltage: Consumption (max.): Supply voltage tolerance: Measuring circuit Monitored terminals: Voltage system: Upper level setting (Umax): Lower level setting (Umin): Max. permanent voltage: Asymmetry: Peak overload (1 s): Time delay (t1): Time delay Umax/Umin (t2): Accuracy Setting accuracy (mech.): Repeat accuracy: Temperature dependance: Limit values tolerance: Hysteresis (fault to OK): Output Contact type: Current rating: Breaking capacity: Inrush current: Switching voltage: Power dissipation (max.): Mechanical life: Electrical life (AC1): Other information Operating temperature: Storage temperature: Dielectric strength:
supply ­ output output 1 ­ output 2 Operating position: Mounting: Protection degree: Overvoltage category: Pollution degree: Cross-wire section ­ solid/ stranded with ferrule (mm2): Dimensions: Weight: Standards:

400V UNI

HRN-43

HRN-43N

A1-A2 AC/DC 24 ­ 240 V (AC 50-60 Hz)
3 VA/1 W AC 400 V (50-60 Hz)
5 VA/2.5 W ­15 %; +10 %

L1-L2-L3 3× 400 V (50-60 Hz)
240 ­ 480 V

L1-L2-L3-N 3× 400 V/230 V (50-60 Hz)
138 ­ 276 V

35 ­ 99 %Umax

3× 480 V

adjustable, 5 ­ 20 % + OFF

600 V

350 V

fixed, max. 200 ms

adjustable, 0.1 ­ 10 s

5 % < 1 % < 0.1 %/°C (°F) 5 % selectable, 5 %/10 % from the upper range value

2× changeover/SPDT (AgNi) 16 A/AC1
4000 VA/AC1, 384 W/DC1 30 A/< 3 s
250 V AC/24 V DC 2.4 W
10.000.000 ops. 100.000 ops.

­20 .. 55 °C (­4 .. 131 °F) ­30 .. 70 °C (­22 .. 158 °F)

AC 4 kV AC 4 kV
any DIN rail EN 60715 IP40 front panel / IP20 terminals
III. 2 max. 1× 2.5, 2× 1.5/ max. 1× 2.5 (AWG 14) 90 × 52 × 65 mm (3.5 × 2 × 2.6) UNI ­ 148 g (5.2 oz), 400V ­ 248 g (8.7 oz) EN 60255-1, EN 60255-26, EN 60255-27

1 / 2

Function

Overvoltage - undervoltage

Umax

Hysteresis

L1 Umin
Umax

L2 Umin
Umax

L3 Umin

RESET 15-18 25-28

t1 t2 t1

t1 t2

LED U

Hysteresis
t1

t2

t1

MEMORY - ON (DIP2)

Function of output contacts: In order to monitor two levels of voltage, it is possible to select if output contact will respond to each level individually (see the diagram) or both contacts will switch in parallel (see diagram "phase sequence"). Selection via DIP switch ,,Output".
Graphs legend: L1, L2, L3 = 3-phase voltage RESET = memory reset t1 = time delay, fixed t2 = time delay Umax/Umin, adjustable 15-18 = output contact 1 25-28 = output contact 2 LED U = overvoltage/undervoltage indication

Phase sequence

100%

L1 0%
100%

L2

L3

0%

100%

L3

L2

0%

RESET t1
15-18 (25-28)
t1

LED

Phase asymmetry - failure

L2

L3

L3

L2

t1 t1
MEMORY - ON (DIP2)

L2 L3
t1

100%
L1 0%
100%
L2 0%
100%
L3 0%
100%

0%
Hysteresis

RESET
15-18 (25-28)

t1

t2

t1 t2

t1

t2

t1

LED

t2

t1

t2

t1

MEMORY - ON (DIP2)

Warning
This device is constructed for connection in 3-phase network AC 3× 400 V or AC 3× 400/230 V (according to the type) and must be installed according to norms valid in the state of an application. Installation, connection, setting and servicing must be carried out by qualified electrician staff only, which have perfectly understood the instructions and functions of the device. This device contains protection against overvoltage peaks and disturbing impulses in the power supply network. For the correct function of the protection of this device, there must be suitable protections of higher degrees (A,B,C) installed in front of them and according to the standards, interference of switching devices must be securely eliminated (contactors, motors, inductive loads, etc.). Before installation, make sure that the device is de-energized and the main switch is in the "OFF" position. Don`t install the device to sources of excessive electromagnetic interference. Ensure correct installation by perfect air circulation so that during continuous operation and a higher ambient temperature, the device does not exceed the maximum allowed operating temperature. For installation and setting use a screwdriver with a width of approx 2 mm. Keep in mind that this is a fully electronic device and approach accordingly with the installation. Non-problematic function of the device is also dependent on the previous method of transportation, storage, and handling. In case of any signs of damage, deformation, malfunction, or missing parts, don`t install this device and claim it at the dealer. The product must be treated as electronic waste at the end of its life.

Function of output contacts: The function is not applicable in the phase sequence monitoring, the contacts are switched in parallel. DIP switch ,,Output" is ignored.
Graphs legend: L1, L2, L3 = 3-phase voltage RESET = memory reset t1 = time delay, fixed t2 = time delay Umax/Umin, adjustable 15-18 = output contact 1 25-28 = output contact 2 LED = phase sequence indication
Function of output contacts: The function is not applicable in the phase asymmetry and failure monitoring, the contacts are switched in parallel way. DIP switch ,,Output" is ignored.
Graphs legend: L1, L2, L3 = 3-phase voltage RESET = memory reset t1 = time delay, fixed t2 = time delay Umax/Umin, adjustable
- adjustable asymmetry level 15-18 = output contact 1 25-28 = output contact 2 LED = asymmetry indication
Relay is designated to monitor 3-phase circuits. Type HRN-43 controls the interphase voltage, type HRN-43N controls voltage towards the neutral wire. Relay can monitor: voltage in two levels (overvoltage/undervoltage), phase sequence/failure and asymmetry. Each fault state is indicated by an individual LED. By DIP switch ,,Output" it is possible to select the function of output contacts: independent function (1× for overvoltage, 1× for undervoltage) or in parallel. Fixed time delay (t1) is applied when changing from fault to OK state or when de-energized. Adjustable time delay (t2) is applied, when changing from OK to fault state. This delay prevents incorrect behavior and oscillation of the output device during short-term voltage drops and peaks. Voltage monitoring The upper level Umax is set in the range 138 ­ 276 V (resp. 240 ­ 480 V for HRN-43) and the lower level Umin in the range of 35 ­ 99 %Umax. In case any phase deviates from this set band, after a set delay, output contact opens. Output contact again closes after returning back into the monitored band and exceeding fixed hysteresis (selectable by DIP switch ,,Hysteresis"). In the event of an outage in two or three phases, the output contacts will open immediately, regardless of the set delay t2. Phase sequence Monitors correctness of phase sequence. In case of unwanted change, output contacts open. In case of energization of a relay with incorrect phase sequence, contacts stay open. Asymmetry The level of asymmetry between individual phases is set in the range of 5 ­ 20 %. In case set asymmetry is exceeded, output contacts open and LED indicating asymmetry shines. Time delays t1, t2 and hysteresis are applied when returning to OK state. Monitoring asymmetry can be switched off by the DIP switch ,,ASYM".

Type of load
Contact material AgNi, 16A
Type of load
Contact material AgNi, 16A

cos   0.95
AC1 250V / 16A
AC13 250V / 6A

M AC2 250V / 5A
AC14 250V / 6A

M AC3 250V / 3A
K AC15 250V / 6A

AC5a uncompensated

AC5a compensated

230V / 3A (690VA)

x

M

DC1

DC3

24V / 16A

24V / 6A

2 / 2

HAL.230V
AC5b 800W
M DC5 24V / 4A

AC6a x
DC12 24V / 16A

AC7b 250V / 3A
DC13 24V / 2A

AC12 250V / 10A
DC14 24V / 2A



References

Acrobat Distiller 9.5.5 (Windows)