IPPON Na+ TA Series: Single-Phase Online UPS with Sodium-Ion Batteries

The IPPON Na+ TA is a single-phase online Uninterruptible Power Supply (UPS) system that provides stabilized power with a pure sine wave output. It is designed to reliably protect critical and expensive equipment, such as server systems and sensitive computer peripherals, ensuring high efficiency and longevity through the use of advanced sodium-ion batteries.

Advantages of Sodium-Ion Batteries

Sodium-ion batteries offer several advantages over traditional lead-acid batteries:

Key Features and Specifications

The Na+ TA series is equipped with features for optimal performance and management:

Front Panel Description

The front panel of the Na+ TA UPS features:

Rear Panel Connections

The rear panel includes:

Technical Specifications

Model Na+ TA 6K Na+ TA 10K
ID 2049881 2049882
Topology Online Online
Output Power (VA/W) 6000 VA / 6000 W 10000 VA / 10000 W
Nominal Voltage 208/220/230/240 V 208/220/230/240 V
Voltage Stability (Battery Mode) ±1% ±1%
Nominal Frequency 50/60 Hz 50/60 Hz
Frequency Stability (Battery Mode) ±0.1% ±0.1%
Waveform Pure Sine Wave Pure Sine Wave
Transfer Time 0 ms 0 ms
Crest Factor 3:1 3:1
THD (Battery Mode) <3% (Linear Load) <3% (Linear Load)
Output Connections Terminal Block Terminal Block
Input Voltage 208/220/230/240 V 208/220/230/240 V
Voltage Range (50% Load) 110-300 V 110-300 V
Voltage Range (100% Load) 176-276 V 176-276 V
Frequency Range 40-70 Hz 40-70 Hz
Input Connector Terminal Block Terminal Block
Battery Type Sodium-Ion Sodium-Ion
Installed Batteries 48V / 3.6Ah x 5 pcs 48V / 4.8Ah x 5 pcs
Runtime (30% Load) 19 min 15.5 min
Runtime (50% Load) 11 min 9.5 min
Runtime (70% Load) 7 min 7 min
Runtime (100% Load) 4 min 3.5 min
Charge Time (Full Discharge) <1 hour (at +25°C) <1 hour (at +25°C)
Overload Protection (Line Mode) 102-110%: Bypass in 30 min; 110-130%: Bypass in 10 min; 130-150%: Bypass in 30 sec; >150%: Bypass in 200 ms 102-110%: Bypass in 30 min; 110-130%: Bypass in 10 min; 130-150%: Bypass in 30 sec; >150%: Bypass in 500 ms
Overload Protection (Battery Mode) 102-110%: Bypass in 1 min; 110-130%: Bypass in 10 sec; 130-150%: Bypass in 3 sec; >150%: Bypass in 200 ms 102-110%: Bypass in 10 min; 110-130%: Bypass in 1 min; 130-150%: Bypass in 10 sec; >150%: Bypass in 500 ms
Overload Protection (Bypass Mode) 40 A Breaker 63 A Breaker
Surge Protection 585 Joules 585 Joules
Efficiency (100% Load) >95% (Line Mode) >94.5% (Line Mode)
Efficiency (ECO Mode) ≥98.5% ≥98%
PC Communication Yes Yes
Supported OS Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, MAC, and others supporting RS-232 or USB communication protocols. Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, MAC, and others supporting RS-232 or USB communication protocols.
User Interface RS-232, USB RS-232, USB
Optional Card Slot Yes Yes
ECO Mode Yes Yes
EPO Function Yes Yes
Dimensions (W x H x D) 190 x 450 x 700 mm 190 x 450 x 700 mm
USB Cable Length 1200 mm 1200 mm
Net Weight 29.7 kg 33.9 kg
Gross Weight 33 kg 37 kg
Cooling Forced Air Forced Air
Noise Level <55 dB <55 dB
IP Rating IP20 IP20
Operating Temperature -20°C to +40°C -20°C to +40°C
Operating Humidity 0-95% (Non-condensing) 0-95% (Non-condensing)
Operating Altitude 0-4000 m 0-4000 m
Storage Temperature -30°C to +60°C -30°C to +60°C
Storage Humidity 0-95% (Non-condensing) 0-95% (Non-condensing)
Storage Altitude 0-4000 m 0-4000 m
Safety Compliance TP TC 004/2011 (Low Voltage Equipment), TP TC 020/2011 (Electromagnetic Compatibility), TP EAEС 037/2016 (Restriction of Hazardous Substances) TP TC 004/2011 (Low Voltage Equipment), TP TC 020/2011 (Electromagnetic Compatibility), TP EAEС 037/2016 (Restriction of Hazardous Substances)

Package Contents

Optional Accessories

Model Numbers: 2049881 (Na+ TA 6K), 2049882 (Na+ TA 10K), 2049895, 2069485, 2069980

PDF preview unavailable. Download the PDF instead.

Na TA 6K 10K leaflet Adobe PDF Library 17.0 Adobe InDesign 18.4 (Windows)