nVent RackChiller RDHX PRO Active, Right Hinged, 42U, 600W
Data Solutions
CATALOG NUMBER: 10630-204
The nVent RackChiller RDHX PRO Active is a rear door cooling unit offered in standard sizes for 42U and 47U racks, with 600mm and 800mm widths. These units are 250mm deep and weigh under 170Kg. Rear door coolers are compact, requiring no additional floor space or ceiling headroom, and can eliminate the need for CRAH units and other room cooling equipment in data centers.
Each unit is equipped with 12 axial brushless DC fans, designed for reduced stress on components and increased lifecycle. For maintenance, nVent has implemented an innovative, tool-less, hot-swappable system for fan replacement, as well as for other critical components like PSUs and the main controller. This design maximizes uptime and reduces service costs.
The rear door cooler can also be retrofitted to most third-party racks. It offers the smallest footprint of any rear door cooler on the market with the highest kilowatt cooling capacity.
FEATURES
- Rear Door Cooler Chilled Water
- Hot-swappable components simplify repair and maximize availability
- Designed for efficient operation at increased facility water temperatures
- Combination with direct to chip liquid cooling
- Modular standard - easy to adapt to individual requirements
- Fans, power supplies, controller and control valve all are hot-swappable
- Automatic fan speed and valve opening control
- 7" high resolution touch screen interface
- Hydraulic and electric connection through top or bottom
- Monitoring via Ethernet interface (Web browser, Modbus TCP, SNMP v2c) and Modbus RTU
PRODUCT ATTRIBUTES
- Product Type: Air/Liquid Heat Exchanger
- Product Family: RackChiller
- Rack Height: 42U
- Color Code: RAL 7021
- Protection Rating: IP20
- Supply Voltage: 195 – 277V
- Coolant Feed: Bottom; Top
- Finish: Powder Coated
- Material: Steel
- Package Quantity: 1
ADDITIONAL PRODUCT DETAILS
For trouble-free operation of the air/liquid heat exchanger, the quality requirements of the coolant must be maintained. The selection of appropriate anti-corrosion and frost protection agents depends on the environment in which the unit is used and on the external chiller.
At coolant temperatures below 14 °C, there is an increased risk of condensation. nVent recommends using a condensate management package.
WARNING
nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property damage, serious bodily injury and death and/or void your warranty.