Installation & Operation Manual Leak Detector
TCB-LD1UPE
English

TOSHIBA R32 refrigerant leakage detector (Hereafter "Leak Detector")
Thank you for purchasing this TOSHIBA Leak Detector. Read the installation procedures before proceeding with installation. In particular, please carefully read the "Safety Precaution" * This Leak Detector is only for being combined with TOSHIBA Air conditioner. After reading these instructions, be sure to keep them in a safe place.
CONTENTS
1 Safety precaution ..............................................................................2 2 Specification ......................................................................................5 3 Accessory parts ................................................................................6 4 Installation precautions ....................................................................7 5 Mounting ..........................................................................................12 6 Self-diagnostics table .....................................................................15 7 Set up ...............................................................................................16 8 Operation .........................................................................................17

1-EN

1

1 Safety precaution

· Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner.
· Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire. Please understand the following details (instructions and symbols) before reading the body
text, and follow the instructions.

Indication

Meanings of identification

WARNING

The warnings indicate that if you fail to operate properly and follow the instructions in the warnings, it may cause serious personal injury or death.

CAUTION

The caution Indicates that if you fail to operate properly and, it may cause serious personal injury or property damage. (*1)

*1: Property damage includes loss of buildings, family property, poultry, and pets.

WARNING

· Before carrying out the installation, maintenance, repair or removal work, set the circuit breaker to the OFF position. Otherwise, electric shocks may result.
· Place a "Work in progress" sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
· Wear protective gloves and safety work clothing during installation, servicing and removal.
· This Leak Detector must be installed in accordance with National Wiring Regulations. · Connect and fix the specified cables for wiring securely. · Do not allow the connection to be exposed to external force from the cables. · Select an installation location which is rigid and strong enough to support or hold this
Leak Detector, and select a location for easy maintenance.
· Use only the parts specified by Toshiba Carrier Corporation supplied accessories. · Disassembly and Modification of this Leak Detector is not permitted under any
circumstances.
· This Leak Detector must be installed by the sales dealer or installer. · Repairs must be carried out only by the method specified by Toshiba Carrier Corporation. · Only replace parts specified by Toshiba Carrier Corporation when replacing parts. · Torch detectors (or other open flame detectors) should not be used when checking for
refrigerant leaks.
· This Leak Detector should be securely installed in accordance with this manual. · In case of an abnormal condition (such as a burning smell), stop the indoor unit and turn
the breaker OFF.
· When devices that use flammable refrigerants are installed in unventilated areas, ensure the refrigerants do not accumulate and present the risk of fire or explosion, even in the unlikely event that refrigerant does happen to leak.
· Do not operate wet hands. · Do not splash water on the Leak Detector or use it in the bathroom.

2

2-EN

CAUTION
· Gases and vapours other than the target refrigerant gas, may cause semi-conductor sensors to react. Sensors exposed to silicon fumes may be permanently damaged. The accumulation of volatile organic compounds resulting from human occupation in a poorly ventilated room may cause inaccurate operation. Adequate room ventilation should be maintained at all times.
· Ground yourself to discharge static electricity before performing any wiring. · Do not install the Leak Detector in places with direct sunlight or where the ambient
temperature is more than 40°C or is less than 0°C. Follow 2.Specification · The connecting cable must not touch piping directly. · Install this Leak Detector horizontally. · The warranty does not cover the product if it falls from an elevated location. · Do not use the Leak Detector at the following locations. Because may lead to severe
decrease in functionality and damage to parts. · Location where condensation occurs · Location where flammable gases, etc. may leak · Location where corrosive gases, etc. may leak · Location with lots of water or oil droplets (including machine oil) · Steamy locations · Location where voltage fluctuation frequently occurs · Location where there is a machine producing electromagnetic radiation · Location where droplets of organic solvents spread · Location where acidic or alkaline solutions or special sprays are frequently used · Locations where dust easily accumulates or Extremely dusty · The semi-conductor sensor may react or malfunction if exposed to gases other than the refrigerant gas or to steam. Accordingly, the following must be avoided when installing. · Using in atmospheres where silicone gases (siloxane, etc.) may occur
The Leak Detector may malfunction or operate incorrectly if items such as adhesives, hair products, rubbers, or putties with silicone in them are used in the vicinity of the Leak Detector. · Exposing to organic solvents/chloric gases Alcohols, VOCs, Chloric gases, etc., can be the cause of malfunction or incorrect operation. Large amounts of organic solvents are produced by paints, floor waxes, etc., when building or renovating structures, so ensure the area is properly dried and ventilated before installing the Leak Detector. · Polluting with alkaline metals (especially salt mist)

3-EN

3

 Precaution for operation
WARNING
· Do not block the slit for gas detecting. (It will be unable to detect refrigerant leaks and may result in a fire.)
· Do not power off the air conditioner even if it is not used for a long time. The Leak Detector will not operate.
· The buzzer starting to sound indicates that there has been a refrigerant leak. Ignition or fire may result as the concentration of refrigerant increases, so the area should be ventilated and evacuated as quickly as possible.
· If a leak is suspected, all naked flames should be removed and extinguished. · When someone may touch the air conditioner due to maintenance, etc., do not allow
spray to get onto the Leak Detector or use flammable gases near the Leak Detector. Also make sure that the breaker is turned off when performing maintenance on the air conditioner or Leak Detector. · Do not use sprays or chemicals when cleaning.

4

4-EN

2 Specification

Dimension Weight Temperature/humidity range
Power source Buzzer sound level

86W x 120H x 30D mm 0.11 kg 0°C to 40°C / 20% to 80% (no condensation) *Indoor use only. DC 13 V to 18 V (Supplied from indoor unit) 65dB (A) at 1 m

 Parts name

3

12

30

86

60

Slit for buzzer sound and Gas detecting

Main PCB

2 - 4.2 x 8.7 hole

4 3

120

1 7

Buzzer

Refrigerant sensor

Rear cover

Case

Sensor module

1 Operation LED If this LED is turning on green light, it indicates that the Leak Detector is power supplied and running.
2 Malfunction LED If this LED is turning on red light, it indicates that any problem is occurs. Details is referred in "8.Operation".
3 Alarm lamp (Buzzer sound stop button) If the sensor detect refrigerant leakage, this lamp blinks and buzzer sounds a warning sound. Push this switch to stop warning sound, but this warning sound can not be killed unless refrigerant density is decrease sufficiency.

5-EN

5

3 Accessory parts

No.

Part name

1 Screws M4 x 25

Image illust

2 Wood screw M3.8 x 16

Ø6.5

Ø8.0

3 Plastic stud

4

Wire terminal 1 (Inner diameter 6.5 mm) for AWG22 ~ AWG16

5

Wire terminal 2 (Inner diameter 8.0 mm) for AWG20 ~ AWG14

6 M3 washer

7 Connecting wire

8

CD-ROM media manual *Includes 24 languages of manual

9

Installation & Operation Manual (This manual)

6

Quantity 2 2 2 6 6 2 3 1 1
6-EN

4 Installation precautions
 Installation locations Refrigerants are significantly heavier than air. Therefore in order for the sensor to operate as effective as possible the refrigerant detector must be positioned at a low level inside the room, where the indoor air conditioning unit is fitted. See diagram showing recommend installation guidelines.

Do NOT install inside bathrooms

Typical Hotel Application
Do NOT install below desks or shelves
X
Bathroom Bed

Do NOT install next to door openings

X
Unit
X
Cupboard
X

Do NOT install next to or inside cupboard doors

X
Living Area

Do NOT install near windows or
vents

X
Do NOT install next to or below desks or mirrors

· You need to observe the regulations of the local governments, state and country that govern the installation of Leak Detector when installing the Leak Detector. You must ensure that
installation complies with all relevant rules and regulations.

7-EN

7

Indoor Unit

Indoor Unit

h0

Leak Detector

h0

10 m*

300 mm

300 mm

* It must be placed within a horizontal distance of 10 meters and on the wall in the room where the indoor unit is installed. However, when it does not enter the field of view on a straight line from the Leak Detector, it is within 7 meters at the shortest horizontal distance without obstacles and installed on the wall in the room where the indoor unit is installed.
· The alarm shall always be 15 dBA louder than the room background noise. Leak detector can generate 65 dBA alarm. (Sound pressure level, measured at a distance of 1 m from the alarm.) If the surrounding environment is noisy in a particular room, we recommend that you use an external alarm (by local power supply) in that room.
· This Leak Detector has output terminals to external ventilation and an external alarm. When taking safety measures using external ventilation or an external alarm, install
according to " Basic wiring diagram".

8

8-EN

· Keep a space around the Leak Detector as detailed on the figure shown below.

CASE

Rear Cover

50 mm or more

50 mm or more

Wall

50 mm or more 300 mm or less (298 mm or less)

Floor

Floor

· Install so the Leak Detector is within 300 mm of the floor. This is stipulated in regulations. · Install this Leak Detector horizontally. · Do not block the slit for gas detecting or place objects immediately in front of the gas
detector as this will mean leaks will not be detected.
· This Leak Detector should be mounted in a position where it can be easily accessed for maintenance and repairs.
· Avoid the following locations for installation. · By a window, etc. exposed to direct sunlight or external airflow · In the shadow or backside of objects deviated from the room airflow · Location where condensation occurs (The Leak Detector is not moisture proof or drip proof)
· Location near heat source · Uneven surface · Location where there is a danger of mechanical damage being inflicted on the Leak
Detector
· Location where there is a danger of the generation of contaminants such as silicone gases (siloxane, etc.), organic solvents/chloric gases, etc.
· Do not install the Leak Detector in a place where smoke, chemical agent, or organic solvent is present.
Do not use gas equipment using combustion gas (LPG etc.) such as propane, butane, or
methane, an insecticide, or sprays or paints containing siloxane, near the Leak Detector.
The refrigerant leak detection sensor operates mistakenly, causing the air conditioner not to
operate.

Refer to the installation instructions supplied with the outdoor unit for details about the location for installing the Leak Detector.

9-EN

9

 Basic wiring diagram · Interconnecting cable wire are produced locally. · Using the specified wires, ensure to connect the wires and fix wires securely, so that the
external tension to the wires does not affect the connecting part of the terminals. Incomplete connection or fixation may cause.
Leak Detector

External ventilation device
+
- DC12 V~DC24 V

Connecting wires (Accessory)

Indoor Unit
AB

External buzzer device

+
- DC12 V~DC24 V

AB
Remote controller

Output connector can be connected the external device (Ventilation, external buzzer device and etc.) When the Leak Detector detects leakage, outputs the signal to these device. When the buzzer is stopped, Output 1(CN64) will keep to output, Output 2(CN65) will stop to
output.
So the external buzzer is recommended to connect to Output 2 (CN65)

 Output signal table

Status of the Leak Detector
Monitoring (Normal) Preparing (Startup) Advance notice of the life of refrigerant leak detection sensor Refrigerant leak detection sensor exceeding its life of the product Abnormal Refrigerant leak detection
After cancelled alarm sound *1 : It is 0.5 seconds interval.

Operation LED
ON Blinking*1

Leak Detector operation

Malfunction LED

Alarm lamp

Alarm sound

OFF OFF

OFF OFF

OFF OFF

External output

Output 1 Output 2 (CN64) (CN65)

OFF

OFF

OFF

OFF

Remote controller
status
Normal Normal

ON

Blinking*1

OFF

OFF

OFF

OFF

Notice code

Indoor unit
operation
Normal Normal
Normal

Outdoor unit
operation
Normal Normal
Normal

ON ON/Blinking*1
ON
ON

ON ON OFF OFF

OFF OFF Blinking*1 Blinking*1

OFF OFF Ringing OFF

OFF OFF ON ON

OFF OFF ON OFF

J31

Normal

Normal

J29

Normal

Normal

J30

Stop /

Normal /

Circulate operation Stop (system lock)

J30

Stop /

Normal /

Circulate operation Stop (system lock)

10

10-EN

 Basic wiring limitation

Remote controller wiring  Type of wiring

Ext output wiring  Type of wiring

· Use cables of 0.5 to 2.0 mm2 (Min. 0.5 mm2) · Use cables of 0.75 to 2.0 mm2 (Min. 0.75 mm2)

 Total wire length : 300 m or less

 Total wire length : 100 m or less

· Maximum length between Leak Detector and header indoor unit (DN14=1) : 100 m

Status

Leak Detector side

External equipment side

Rating

Terminal name

Terminal

Circuit example

Condition

Output1 (CN64) Maximum Voltage: DC 25 V Maximum Current: 0.2 A
Output2 (CN65) Maximum Voltage: DC 25 V Maximum Current: 0.2 A

Output 1 or 2

non porarity

DC12 V ~ DC24 V

100 m or less / 0.75 mm2

Relay

Rated coil
Voltage DC12 V ~ 24 V

Correct wiring diagrams Indoor unit

Wirings as shown below are prohibited

Indoor unit

Indoor unit

Remote controller

Leak Detector

Indoor unit

Indoor unit

Remote controller

Leak Detector

Indoor unit

Indoor unit

Leak Detector Leak Detector

Leak Detector

(Group connecting)

Leak Detector

· Only one Leak Detector can connect to one Indoor unit. · Only one Leak Detector can connect in one group connecting.

(Group connecting) Leak Detector

CAUTION
· After refrigerant piping has been connected, do not turn on the power until gas leakage check is finished. If refrigerant gas leaks, then Leak Detector in the system will operate, causing air conditioner not to operate.

11-EN

11

5 Mounting

1 Please use a connecting wire (accessory) and an interconnecting cable (procured locally)
to connect to indoor unit terminal board cable. If crimping tools are not available, please use other reliable methods for connection. Do not only use the insulating tape to connect; otherwise it can be dangerous.
Since the Leak Detector cable has no polarity that is OK if the indoor unit's terminal A and terminal B are inversely connected.
Leak Detector

Terminal block

A

W

for remote controller

B

B

cable in indoor unit

Interconnecting cable (Procured Locally)
· Use non-polarity 2-core cable. · Use 0.5 mm2 - 2.0 mm2 cable.

Connecting section

Connecting wire (Accessory) W : White B : Black

2 Remove rear cover from body to refer to the step 1 to 3 shown as below figure.
Keep screw and body until process 5.
Upper hook

Side hook

Side hook

Step 2
Step 3 : Unlock the upper hook to pull the body

Rear cover Step 2 : Unlock the side hook
Leak Detector Body Step 1: Remove the bind screw

12

12-EN

In case of mounting to wall box
3 In case of mounting to wall box, cut the plastic stud in the accessory to a suitable length
for filling the gap between the rear cover and the wall box. Then use the M4 screws in the accessory to fix the rear cover to the wall box through the plastic stud.

Plastic stud Connecting cable Rear cover Screws M4×25

Wall Wall box (Procured locally)

Approx. 80 mm

This "Approx. 80 mm" is requirement length for Servicing.

Please loosen the surplus cable at out of rear cover.

In case of mounting to wall directly
In case of mounting to wall directly, cut and remove the side wall of rear cover which pass the cable wire. Connecting cable wire is passed through this groove on rear cover. Then use M3.8 wood screw in the accessory to fix the rear cover to the wall so as to take care not to pinch among wall and rear cover.

Wall Connecting cable Rear cover

Wood screws M3.8×16

Approx. 80 mm This "Approx. 80 mm" is requirement length
for Servicing. Please loosen the surplus cable at out of rear cover.

Rear side of rear cover
Connecting cable wire is passed through this groove on rear cover so as not to pinch among wall and rear cover. It is recommended that fix cable wire with tape etc..

Cut and remove the side wall of rear cover which pass the wire

13-EN

13

4 Insert communication cable of indoor unit to the connector CN41 on PCB of the
Leak Detector, Confirm the terminal number of indoor unit and connect the Leak Detector cable correctly. (The Leak Detector may be damaged if connecting the power supply of indoor unit.) If connect the Leak Detector to external device, communication cable of those is inserted to the connector CN64 or CN65.
Refrigerant sensor
Gather the cable wire and store to this space.
* Do not touch, damage, or dirty the top of sensor. It may cause that detecting performance is decreased.
5 Mount the Leak Detector body to rear cover. And be careful not to pinch the cable among
the body and rear cover. Finally, tighten the bind screw to body.

Connecting cable
Leak Detector body Bind screw *When mount Leak Detector body to rear cover, take care not to pinch connecting cable among body and rear cover.

14

14-EN

6 Self-diagnostics table
 Self-diagnostics table The LEDs light as follows according to the status of the Leak Detector. Please contact the service man and inform the status of the Leak Detector. Then take appropriate measures for solution. * please keep the status of the Leak Detector and do not cancel it until service man take
measures.

Operation LED
(Green)

Malfunction LED (Red)

or

Alarm lamp (Red)

: ON

: OFF

: Blinking

Status

Solution

Preparing

The Leak Detector is preparing to operate. Preparation continues for 30 seconds after powering up.

Monitoring

The normal status.

Leaking

Refrigerant is leaking. Start ventilating immediately. You should contact our sales/ service team or an authorized dealer.

Abnormal

There is an abnormality with the Leak Detector. It may be unable to detect refrigerant leakage so you should contact our sales/service team or an authorized dealer.

End of service life is approaching
End of service life

The refrigerant sensor is about to reach the end of its service life. Contact our sales/service team or an authorized dealer to arrange for replacement of the Leak Detector.
The refrigerant sensor reached the end of its service live. Contact our sales/service team or an authorized dealer to arrange for replacement of the Leak Detector.

15-EN

15

7 Set up
 Test run (Inspection mode) After installation is complete, use following procedure to confirm that the Leak Detector is operating properly.
Start

Powering up to the indoor unit

Operation LED lights up.

No

(Blinking for a few seconds)

Yes

Malfunction LED dose not light up.

No

Yes
Start inspection mode. Press the reset switch for at least 5 seconds and
then release. (Please use a precision screwdriver, etc.)

Power is not being supplied. Check the wiring with the indoor unit.
Or the Leak Detector is abnormal. Replace the main PCB.
The refrigerant sensor is abnormal. Replace the refrigerant sensor module.
If the sensor module is replaced and it does not work properly, replace the main PCB.

Alarm lamp is blinking.

No

(Alarm lamp will be 2 minutes.)

Yes

Alarm sound is ringing.

No

(Alarm sound will be 10 seconds.)

Yes

Operation LED is blinking.

No

Yes
Check the display of the outdoor unit. (For details, please refer to the Installation Manual
for outdoor units.)

Exit inspection mode. Press the alarm lamp switch for at least 5 seconds.
(60 minutes after starting inspection mode, it will exit.)

Alarm lamp turns off. (If still blinking)
Yes Operation checks complete

No
16

The alarm lamp is abnormal. Replace the main PCB
The buzzer is abnormal. Replace the main PCB
The Operation lamp is abnormal. Replace the main PCB
The Leak Detector is abnormal. Replace the refrigerant sensor module. If the sensor module is replaced and it does not work properly, replace the main PCB.
16-EN

8 Operation
 Overview
· Read this manual carefully for safe use. · Read this manual as well as operating manual supplied with indoor units and outdoor units. · Be sure to read the "Safety Precaution" before use. · Keep this manual with operating manual supplied with indoor units and outdoor units in a
safe place.
Before operating the unit, read these Operating Instructions thoroughly and keep them for future reference. In case of malfunction of this appliance, do not repair by yourself. Contact the sales or service dealer for repair and disposal.
 Prohibited matters in Operation
WARNING
· Disassembly and modification of this Leak Detector is not permitted under any circumstances.
· Do not operate with wet hands. · Do no splash water on the Leak Detector or use it in the bathroom. · Do not block the slit for the gas detecting. (It will be unable to detect refrigerant leaks and
may result in a fire.) · Do not power off the air conditioner even if it is not used for a long time. The Leak Detector
will not operate. · When someone may touch the air conditioner due to maintenance, etc., do not allow spray
to get onto the Leak Detector or use flammable gases near the Leak Detector. Also make sure that the breaker is turned off when performing maintenance on the air conditioner or Leak Detector. · Do not use sprays or chemical when cleaning.
 Matters to be observed in Operation
WARNING
· The buzzer starting to sound indicates that there has been a refrigerant leak. Ignition or fire may result as the concentration of refrigerant increases, so the area should be ventilated and evacuated as quickly as possible. Also contact the manager of the facility and the person responsible for servicing.
· If a leak is suspected, all naked flames should be removed and extinguished.

17-EN

17

CAUTION
· This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
· This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance.
· Cleaning and user maintenance shall not be made by children without supervision. · This equipment is not suitable for use in locations where children are likely to be present.

 Leak Detector status and operation

Status of the Leak Detector
Monitoring (Normal) Preparing (Startup) Advance notice of the life of refrigerant leak detection sensor Refrigerant leak detection sensor exceeding its life of the product Abnormal
Refrigerant leak detection
After cancelled alarm sound *1 : It is 0.5 seconds interval.

Operation LED

Leak detector operation

Malfunction LED

Alarm lamp

Alarm sound

ON Blinking*1

OFF OFF

OFF OFF

OFF OFF

External output Output 1 Output 2 (CN64) (CN65)

OFF

OFF

OFF

OFF

Remote controller
status
Normal
Normal

ON

Blinking*1

OFF

OFF

OFF

OFF Notice code

Indoor unit
operation
Normal Normal
Normal

Outdoor unit
operation
Normal Normal
Normal

ON ON / Blinking*1
ON

ON ON OFF

ON

OFF

OFF

OFF

OFF

OFF

Blinking*1 Ringing

OFF OFF ON

Blinking*1

OFF

ON

OFF OFF ON OFF

J31

Normal

Normal

J29

Normal

Normal

J30

Stop / Circulate operation

Normal / Stop (system lock)

J30

Stop / Circulate operation

Normal / Stop (system lock)

· Once the refrigerant is detected, the alarm lamp will not be released even if the concentration returns to normal.
The above operation is also continued for external output 1, remote control, indoor unit, and outdoor unit.
· Once the refrigerant is detected, be sure to replace the refrigerant sensor module. It cannot be detected correctly.
· The estimated service life of the Leak Detector is 10 years. If use so as not to observe this manual, service life may be shorter than that of estimated.
· If the Leak Detector exceeds the estimated service life and the operation indicates it, contact the managers of both building and system and exchange the sensor module to new one
(refer to Service Manual).

18

18-EN

 Procedure stopping buzzer The buzzer can be stopped by pressing the alarm lamp switch for at least 2 seconds.
Alarm lamp
 Warning in Operations WARNING
· When a gas alarm occurs, immediately ventilate the area and evacuate from the room. Also contact the manager of the facility and the person responsible for servicing.