R95C 8-Port Discrete Bimodal to IO-Link Hub

Dec 15, 2022 — Compact bimodal to IO-Link device converter that connects discrete inputs and sends the value to the IO-Link Master. • Enabled Delay Modes: ON/OFF Delay, ...

R95C 8-Port Discrete Bimodal to IO-Link Hub -- Instruction Manual

R95C IO-Link Hub


File Info : application/pdf, 6 Pages, 2.15MB

PDF preview unavailable. Download the PDF instead.

227446
R95C 8-Port Discrete Bimodal to IO-Link Hub

Instruction Manual

· Compact bimodal to IO-Link device converter that connects discrete inputs and sends the value to the IO-Link Master
· Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable Oneshot, ON/OFF Pulse-stretcher and Totalizer
· Measurement Metrics: Count, Events Per Minute (EPM), and Duration · Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any
of the eight ports, Discrete Out, or the host white wire output · Outputs a discrete value as received from IO-Link Master Process Data Out · Discrete input/output can be independently configured as NPN or PNP · Rugged over-molded design meets IP65, IP67, and IP68 · Connects directly to a sensor or anywhere in-line for ease of use · R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link
devices into an IO-Link system

Models

Housing
R95

Function
C

Converter
8B21

Control
K

Connector
Q

C = Converter

8B21 = 8-port, bimodal, 2 inputs, 1 output

K = IO-Link

Q = M12 integral quick disconnect

Overview
The R95C-8B21-KQ hub connects two discrete channels to each of the eight unique ports, providing access to monitoring and configuring those ports with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/ Host connection.

Configuration

For more information, see P/N 227447 R95C-8B21-KQ IO-Link Data Reference Guide and P/N 227506 R95C-8B21-KQ IODD Files.

Figure 1. Logic Flow

Input State

Delay Mode · Disabled · On/Off Delay · On/Off/Retriggerable One-shot · On/Off Pulse Stretcher · Totalizer

Measurement Statistics

Discrete 2 Selection

Input

Ouput

Process Data Input
Process Data Input

Mirroring Enable

Enabled

Mirroring

Measurement Statistics · Count · RPM · Duration
Process Data In · Discrete 1 and 2 Input State (active/inactive) · Selected Measurements [1]..[4]
Process Data In · Discrete 2 Output State (active/inactive) · Discrete 1 Input State (active/inactive) · Selected Measurements [1]..[4]
Mirroring - Discrete 2 Output · Port/Channel selected state driven to Pin 2 (F)

Disabled

Host Mirroring Enable

Enabled

Process Data Output

Process Data Out - Discrete 2 Output · Process Data Out selected state driven to Pin 2 (F)

Host Mirroring Host Mirroring - Discrete Host Out · Port/Channel selected state driven to Pin 2 (M)

Table 1: Measurements ­ Female Pins Port 1-Port 8 Pin Number: Description
Pin 4 ­ Discrete 1
Pin 2 ­ Discrete 2

IO Metric Count Value Duration Value
Events per Minute Value
Reset Metrics Count Value Duration Value

Description
Running count of the received input pulses Duration of the last input pulse in µs with 500 µs granularity Running count of the number of pulses received averaged over one minute Range: 1 to 37,500
· Do Not Reset · Reset Running count of the received input pulses Duration of the last input pulse in µs with 500 µs granularity

Original Document 227446 Rev. A

15 December 2022

227446

Port 1-Port 8 Pin Number: Description Table 2: Pin Configuration ­ Female Input Port 1-Port 8 Pin Number: Description Pin 4 ­ Discrete 1
Pin 2 ­ Discrete 2
Table 3: Pin Configuration ­ Male Output Pin Number: Description Pin 2 ­ Discrete Host Out
2

IO Metric Events per Minute Value Reset Metrics

R95C 8-Port Discrete Bimodal to IO-Link Hub
Description Running count of the number of pulses received averaged over one minute Range: 1 to 37,500
· Do Not Reset · Reset

Name I/O Selection
Discrete 1 Delay Mode
Discrete 1 Delay Timer 1 Discrete 1 Delay Timer 2 I/O Selection
Discrete 2 Delay Mode
Discrete 2 Delay Timer 1 Discrete 2 Delay Timer 2 Mirroring Enable
Mirroring Port Selection
Mirroring Channel Selection Mirroring Inversion

Values
· NPN Input · PNP Input
· Disabled · On/Off Delay · On One-shot · Off One-shot · On Pulse-stretcher · Off Pulse-stretcher · Totalizer · Retriggerable On One-shot · Retriggerable Off One-shot
Discrete 1 On Delay, One-shot, Pulse-Stretcher Time, or Totalizer Count
Discrete 1 Off Delay or Totalizer Time
· NPN Input · PNP Input · NPN Output with Pull Up · PNP Output with Pull Down · NPN Output with Push/Pull · PNP Output with Push/Pull
· Disabled · On/Off Delay · On One-shot · Off One-shot · On Pulse-stretcher · Off Pulse-stretcher · Totalizer · Retriggerable On One-shot · Retriggerable Off One-shot
Discrete 2 On Delay, One-shot, Pulse-stretcher Time, Or Totalizer Count
Discrete 2 Off Delay or Totalizer Time
· Disabled · Enabled
· Port 1 · Port 2 · Port 3 · Port 4 · Port 5 · Port 6 · Port 7 · Port 8
· Pin 4 ­ Discrete 1 · Pin 2 ­ Discrete 2
· Not Inverted · Inverted

Name Host Mirroring Enable
Host Mirroring Port Selection
Host Mirroring Channel Selection Host Mirroring Inversion Host Mirroring Polarity

Values
· Disabled · Enabled
· Port 1 · Port 2 · Port 3 · Port 4 · Port 5 · Port 6 · Port 7 · Port 8
· Pin 4 ­ Discrete 1 · Pin 2 ­ Discrete 2
· Not Inverted · Inverted
· PNP · NPN

www.bannerengineering.com - Tel: + 1 888 373 6767

P/N 227446 Rev. A

R95C 8-Port Discrete Bimodal to IO-Link Hub

Pin Number: Description

Name Host Mirroring Output Type

Values
· Open Collector · Push/Pull

IO-Link®
IO-Link® is a point-to-point communication link between a master device and a sensor and/or light. It can be used to automatically parameterize sensors or lights and to transmit process data. For the latest IO-Link protocol and specifications, please visit www.io-link.com.
For the latest IODD files, please refer to the Banner Engineering Corp website at: www.bannerengineering.com.

Mechanical Installation
Install the R95C 8-Port Hub to allow access for functional checks, maintenance, and service or replacement. Do not install the R95C 8-Port Hub in such a way to allow for intentional defeat.
All mounting hardware is supplied by the user. Fasteners must be of sufficient strength to guard against breakage. Use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R95C 8-Port Hub accepts M4 (#8) hardware. See the figure below to help in determining the minimum screw length.

MOUNTING SCREW

17.0 mm

CAUTION: Do not overtighten the R95C 8-Port Hub's mounting screw during installation. Overtightening can affect the performance of the R95C 8-Port Hub.

Wiring

Port 1-Port 8 -- Female

Pin

1

1

2

2 3

4

3 4

Signal Description 18 V DC to 30 V DC Discrete 2 (IN/OUT) Ground
Discrete 1 (IN)

Male
2 3

Pin

1

1

2

3

4 4

Signal Description 18 V DC to 30 V DC Banner-specific Ground
IO-Link

Status Indicators
The R95C 8-Port Discrete Bimodal to IO-Link Hub has matching amber LED indicators on both sides for each discrete device port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the IO-Link communication.

8

7

6

5

Device LEDs (x8)

4

3

2

1

Com LED (x1 near M12 male)
Power LED (x1 near M12 male)

P/N 227446 Rev. A

www.bannerengineering.com - Tel: + 1 888 373 6767

3

R95C 8-Port Discrete Bimodal to IO-Link Hub

Discrete Device Amber LEDs

Indication Status

Off

Discrete OUT is inactive

Solid Amber Discrete OUT is active

IO-Link Communication Amber LED Indication Off Flashing Amber (900 ms On, 100 ms Off)

Status IO-Link communications are not present IO-Link communications are active

Power Indicator Green LED

Indication Off Solid Green

Status Power off Power on

Specifications
Supply Voltage 18 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current 500 mA per port maximum
Discrete Output Load Rating 100 mA
Supply Protection Circuitry Protected against reverse polarity and transient voltages
Leakage Current Immunity 400 µA
Indicators Green: Power Amber: IO-Link communications Amber: Discrete OUT status
Connections (8) Integral 4-pin M12 female quick disconnect (1) Integral 4-pin M12 male quick-disconnect connector
Construction Coupling Material: Nickel-plated brass Connector Body: PVC translucent black
Vibration and Mechanical Shock Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell) Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Certifications
Banner Engineering Europe Park Lane, Culliganlaan 2F bus 3, 1831 Diegem, BELGIUM
Turck Banner LTD Blenheim House, Blenheim Court, Wickford, Essex SS11 8YT, Great Britain

Environmental Rating IP65, IP67, IP68 NEMA/UL Type 1
Operating Conditions Temperature: ­40 °C to +70 °C (­40 °F to +158 °F) 90% at +70 °C maximum relative humidity (non-condensing) Storage Temperature: ­40 °C to +80 °C (­40 °F to +176 °F)
Required Overcurrent Protection

WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application per the supplied table. Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply. Supply wiring leads < 24 AWG shall not be spliced. For additional product support, go to www.bannerengineering.com.

Supply Wiring (AWG)
20 22 24 26 28 30

Required Overcurrent Protection (Amps)
5.0 3.0 2.0 1.0 0.8 0.5

4

www.bannerengineering.com - Tel: + 1 888 373 6767

P/N 227446 Rev. A

R95C 8-Port Discrete Bimodal to IO-Link Hub
Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.

Accessories

Cordsets

4-Pin Threaded M12 Cordsets--Double Ended

Model
MQDEC-401SS MQDEC-403SS MQDEC-406SS MQDEC-412SS MQDEC-420SS MQDEC-430SS

Length
0.31 m (1 ft) 0.91 m (2.99 ft)
1.83 m (6 ft) 3.66 m (12 ft) 6.10 m (20 ft) 9.14 m (30.2 ft)

Style
Male Straight/Female Straight

MQDEC-450SS

15.2 m (49.9 ft)

Dimensions
40 Typ. [1.58"]
M12 x 1 ø 14.5 [0.57"] 44 Typ. [1.73"]
M12 x 1 ø 14.5 [0.57"]

Pinout Female

2 1

4

3

Male

1 2
4 3
1 = Brown 2 = White 3 = Blue 4 = Black

Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.

P/N 227446 Rev. A

www.bannerengineering.com - Tel: + 1 888 373 6767

5

R95C 8-Port Discrete Bimodal to IO-Link Hub
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE. Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com. For patent information, see www.bannerengineering.com/patents.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
· Reorient or relocate the receiving antenna. · Increase the separation between the equipment and receiver. · Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. · Consult the dealer or an experienced radio/TV technician for help.
Industry Canada
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation. Cet appareil est conforme à la norme NMB-3(B). Le fonctionnement est soumis aux deux conditions suivantes : (1) ce dispositif ne peut pas occasionner d'interférences, et (2) il doit tolérer toute interférence, y compris celles susceptibles de provoquer un fonctionnement non souhaité du dispositif.
© Banner Engineering Corp. All rights reserved

