1.

DESCRIPTION

The BA334G is a field mounting intrinsically safe, one input

Rate Totaliser which will function with a wide variety of

sensors. The instrument can display rate of flow and total

flow in the same or different engineering units.

This abbreviated instruction sheet is intended to assist with installation, a comprehensive instruction manual describing safety certification, system design and configuration may be downloaded from the BEKA website or may be requested from the BEKA sales office.

The BA334G Rate Totaliser has IECEx, ATEX, UKEX, ETL and cETL intrinsic safety certification for use in flammable gas and dust atmospheres. The certification information label, which is located on the top of the instrument assembly, shows the certification numbers and codes. Other certifications may be shown. Copies of certificates may be downloaded from the BEKA website.

Typical certification information label

2.

INSTALLATION

The BA334G Rate Totaliser has a robust IP66 glass reinforced

polyester (GRP) carbon loaded enclosure incorporating an

armoured glass window & stainless steel fittings. It is suitable

for exterior surface mounting in most industrial environments,

or pipe mounting using an accessory kit.

If the enclosure is not bolted to an earthed post or structure, the earth terminal on the cable entry bonding plate, which may be assembled on the inside or outside of the enclosure, should be connected to local earthed metalwork or to the plant's potential equalising conductor.

Terminals A1, A2, A3 and A4 are only fitted when the Rate Totaliser includes optional alarms. Similarly terminals C1, C2, C3 and C4 are only fitted when the instrument has an optional 4/20mA output. See full manual for details.

A

A

DISPLAY

A

A

Step A Unscrew the four captive 'A' screws and separate the indicator assembly and the back-box.

B

B

Insulated stud for joining cable screens

Earth

B

stud

B

Step B Secure the enclosure back-box to a flat surface with M6 screws through the four 'B' holes. Alternatively use a pipe mounting kit.

Step C Remove the temporary hole plug and install an appropriate IP rated cable gland or conduit fitting. Feed the field wiring through the cable entry.

A

A Step D

Terminate field wiring on the

instrument assembly. Replace

the assembly on the enclosure

back-box and tighten the four

A

A 'A' screws.

Fig 1 BA334G installation procedure

Abbreviated Instruction for
BA334G intrinsically safe field mounting Rate Totaliser

P

E

Issue 2 24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk
web: www.beka.co.uk

122

Optional

84

stainless

25

steel

legend

plate.

120 DISPLAY

90

19

Four M6 clearance holes for

106

surface mounting.

To remove the scale card carefully pull the tab perpendicularly away from the instrument assembly. See Fig 2 for the location of the scale card tab.

Two M20 x 1.5 tapped cable

90

entries. Supplied with an IP66 stopping plug and one

temporary hole plug.

pulse input + Add link to
energise pulse input

Optional

A1 +

6 A2

5 4 A3

+

3 A4

Alarm 1 1
2
Alarm 2 RS1
RS2

4/20mA output

P1

C4 P2

C3

+

C2 C1

Optional

+

Power supply

External reset + Pulse output

Scale Card tab

E P
Fig 4 Inserting scale card into instrument assembly To replace the scale card carefully insert it into the slot shown in Fig 2. Force should be applied evenly to both sides of the scale card to prevent it twisting. The card should be inserted until about 2mm of the transparent tab remains protruding.

Fig 2 Dimensions and terminal connections

EMC
For specified immunity all wiring should be in screened twisted pairs with screens earthed at one point within the safe area.

Hazardous area

Safe area

DISPLAY

RS2 RS1

Proximity detector

65 43 +

21 ++

Switch contact/ open collector
OR Voltage pulse
N
S Magnetic pick-off

65 43 +
No link

External reset

Single channel positive polarity 28V: 93mA Zener Barrier
+ Power supply
Single channel positive polarity 28V: 93mA Zener Barrier
Remote reset in safe area

Fig 3 Typical measurement loop
Scale card The instrument's units of measurement and tag information are shown above the display on a slide-in scale card. New instruments are fitted with a scale card showing the information specified when the instrument was ordered, if this was not provided a blank scale card will be fitted which can easily be marked on-site. Custom printed scale cards are available from BEKA associates.

3.

OPERATION

The BA334G is controlled and configured via four front panel

push buttons. In the display mode i.e. when the instrument

is displaying flow the push button functions are:

) + & Grand total - shows Lo followed by least significant 8 digits of the 16 digit grand total.

) + * Grand total - shows Hi followed by the most significant 8 digits of the 16 digit grand total. If Local Grand Total Reset CLr Gtot in the instrument configuration menu has been activated, operating the ) and * buttons for ten seconds will result in Clr. no being displayed with the no flashing. Operating the & or * button will change the display to CLr . YE5, the ) button will then reset the grand total to zero which will be confirmed by a brief display of Gt Clrd.

& + * If Local Total Reset CLr tot in the instrument configuration menu has been activated, operating the & and * buttons for three seconds will reset the total display to zero and clear any pulses stored in the optional pulse output. The Grand Total is not reset.

( + & Shows in succession, firmware version number, instrument function totali5e and any output accessories that are fitted: -A Dual alarm outputs -P Pulse output (always fitted) -c 4/20mA output

( + * Provides direct access to the alarm setpoints when the Rate Totaliser is fitted with optional alarms and the AC5P setpoints function has been enabled.

( + ) Access to configuration menu

Display mode

DISPLAY

( )

)

code

(

0000

Security Code
Enter code by pressing
& or * & (
to move to next digit. Code 0000
allows direct access to the menu

4. CONFIGURATION
Rate Totalisers are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site. Fig 5 shows the location of each function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information and for description of optional outputs. Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Rate Totaliser's security code is set to default 0000 the first parameter function will be displayed. If the instrument is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.

Unless otherwise specified menu functions are shown on the upper display

Alarms functions appear here

4/20mA output functions appear here

()

)

)

)

)

)

)

)

)

)

)

)

)

)

)

)

)

&

function

* &

input

*

&

update

* &

di5p-1

* &

di5p-2

* &

dp

* &

factor

* &

5cale-t

* &

5cale-r

* &

t-ba5e

* &

filter

* &

clp off

* &

loc clr

*

&

pul5e op

* &

clrgtot

* &

code

*

*

& r5et def

()

()

)

()

()

()

()

()

()

()

()

()

()

()

)

(

()

()

()

5td

inp. type

* &

debounce

0 . 5

total

on

00000000

001 . 00

001 . 00

001 . 00

tb-01

24

000 . 0

clr tot

* &

clr gtot

clr. no

0000

0000

()

()

()

()

()

op. col

default

off

off

0000

Function
& or *
to select Function of rate totaliser
5td Linear
lin 16 segment lineariser

Input

Debounce

& or *
to select Input type
op. col Open Collector.
volt5 l Pulse <1V >3V
volt5 h Pulse <3V >10V
coil Magnetic pick-off.
pr. det Proximity detector.
contact Switch contact.

& or *
to select level of debounce.
default heavy light

Update
& or *
to select interval between display updates, may be set to 0.5, 1, 2, 3, 4 or 5 seconds

Upper Display
& or *
to select whether rate or total is shown on the upper display

Lower Display
& or *
to turn lower display
on or off

Decimal point
& or *
to select position of
decimal point and
( to toggle
between rate and total displays

K-factor
& or *
to select value and
( to move
to next digit or decimal point
Note: When lin is
selected 16 values for factor may be entered

Total scale factor
Divides factor to produce total display
Press
& or *
to adjust value and
( to move
to next digit or decimal point

Rate scale factor
Divides factor to produce rate display
Press
& or *
to adjust value and
( to move
to next digit or decimal point

Timebase
& or *
to select rate display
timebase
tb-01 for flow/sec
tb-60 for flow/min
tb-3600 for flow/hour

Filter
& or *
to adjust value of each
digit and
( to transfer
control to other digit
First digit: filter magnitude
second digit: step response
Note: While making
adjustments the filtered rate display is shown on lower display so stability can be assessed

Clip off
Rate display below which totalisation is inhibited
Press
& or *
to adjust value of each digit
and ( to
move to next digit

Local total reset
& or *
to turn the local total reset function on or off. When on, total display is reset to zero when
& and *
are operated simultaneously
in display mode for more than 3 seconds

Local grand total reset
& or *
to turn the local grand total reset function
on or off. When on, grand total display may be reset to zero when
) and *
are operated simultaneously in display mode for more than
10 seconds

&

Clear grand total
Press
& or *
to select ye5 to reset grand total to zero
Confirm instruction by entering 5ure.
Press
& or *
to adjust each
digit and (
to move to next digit

Define Security Code
Enter by pressing
& or * and ( to
move to next digit

Reset configuration
to factory defaults
Confirm instruction by entering 5ure.
Press
& or *
to adjust each
digit and (
to move to next digit

)

)

)

)

enbl

* &

5ource

* &

divide

* & duration

*

()

()

()

()

Fig 5 Configuration menu
The BA334G is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU. It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations
UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).

Manuals and datasheets can be downloaded from http://www.beka.co.uk/ba334g

Fig 5 Configuration menu

off

5caled

1000

0 .1

Pulse Enable
* or &
to toggle between on and oFF

Source or Divides scaled output pulse output pulse

Duration of each pulse

* or &
to select pulse source.
5CALEd Input pulse frequency may be divided and duration extended.
OR
dirECt Synchronous retransmission of input pulse without scaling

* or &
to select frequency dividing factor for scaled output pulse
1 10 100 1000 10000

* or &
to select duration of scaled output pulse in ms
0 . 1 0 . 5
1 2 . 5
5 10 25 50 100 250 500

These functions only appear in sub-menu when pulse 5ourCE
is configured as 5CALEd

