There is low pressure, not enough air, or the compressor does not stop. | - [ ] The tank drain valve is open.
- [ ] There is a leak in the fittings.
- [ ] There is a prolonged or excessive use of air.
- [ ] The compressor is not large enough.
| - Close the drain valve.
- Check fittings with soapy water. Tighten or reseal leaking fittings. DO NOT OVERTIGHTEN.
- Decrease the amount of air used.
- Check the air requirement of the accessory. If it is higher than the CFM and the pressure supplied by the compressor, you need a larger compressor. Most accessories are rated at 25% of the actual CFM while running continuously.
|
Air leaks from the regulator or the regulator does not regulate air pressure. | - [ ] There is a hole in the air hose,
- [ ] The tank leaks.
- [ ] The seals are blown,
- [ ] The valve leaks.
- [ ] There is a leaking or worn piston.
- [ ] The internal parts of the regulator are dirty or damaged.
| - Check and replace if necessary.
- WARNING: Immediately replace the tank. DO NOT attempt to repair.
- Replace the compressor assembly.
- Replace the compressor assembly.
- Replace the compressor assembly.
- Replace the regulator or internal parts.
|
The regulated pressure gauge reading drops when the air accessory is being used. | - [ ] This is normal.
- [ ] The compressor is not large enough.
| - If the pressure drops too low, adjust the regulator while the accessory is used.
- Check the air requirement of the accessory. If it is higher than the CFM and the pressure supplied by the compressor, you need a larger compressor. Most accessories are rated at 25% of the actual CFM while running continuously.
|
The pressure relief valve opens. | - [ ] The tank pressure exceeds the normal rating pressure.
- [ ] The pressure switch is stuck.
| - Replace the pressure switch.
- Replace the pressure switch.
|
The motor will not run, | - [ ] Tank pressure exceeds the preset pressure switch limit,
- [ ] The fuse is blown or the circuit breaker tripped.
- [ ] The check valve is stuck in the open position.
- [ ] The wire gauge in the cord is wrong or the extension cord length is excessive.
- [ ] There are loose electrical connections.
- [ ] The motor's thermal overload protection has tripped.
- [ ] The motor, capacitor or safety valve is defective.
| - The motor will start automatically when the tank pressure drops below the tank cut-in pressure.
- Replace the blown fuse or reset the circuit breaker. Do not use a fuse or circuit breaker with a higher rating than specified for your branch circuit.
- Check for proper fuse; type T fuse is acceptable.
- Check for low voltage and proper extension cord size.
- Disconnect other applications from the circuit. Operate the compressor on a dedicated circuit.
- Remove and clean or replace.
- Check for proper gauge and extension cord length.
- Contact an authorized service center.
- Turn the air compressor off, unplug the power cord and wait until the motor has cooled down. Plug in the power cord only after the motor has cooled down.
- Have the compressor serviced by a qualified technician.
|