SubstiTUBE® T8 Connected
Please take the time to read this user instruction. The instruction contains important information and notes regarding the installation and operation.
Important: To operate connected system, LEDVANCE Connected SENSOR is required:
- LEDVANCE Connected Sensor LB: maximum recommended mounting height: <4m
- LEDVANCE Connected Sensor HB: maximum recommended mounting height: 4m-14m
Please visit our website www.ledvance.com/substitube-connected for detailed installation instructions.
SubstiTUBE® T8 Connected is suitable to certain T8 G13 bi-pin base / EM (CCG) / Mains.
Key Information and Symbols
Symbol | Meaning | Remark |
---|---|---|
SubstiTUBE® Connected | Compatible with EM / Mains | |
EM | Electromagnetic = Conventional Control Gear | Go to 1. installation |
Mains | Remove ballast connect directly on 230V | Go to 2. installation |
Lamp not suitable for emergency operation | EM / Mains | |
Lamps suitable for 50/60Hz operation | EM / Mains | |
Lamps to be used in dry conditions or in a luminaire that provides protection | EM / Mains | |
Dimming not allowed | Only possible with LEDVANCE Connected Sensor | |
LED replacement starter | EM | |
Lamp not suitable for high frequency operation (ECG) | HF |
Technical Specifications
Replacement of T8 FL | Storage temperature (Ts) | Ambient temperature (Ta) |
---|---|---|
0.6m, 1.2m, 1.5m | -20° ... 80°C | -20° ... 50°C |
Hereby, LEDVANCE GmbH declares that the radio equipment is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: smartplus.ledvance.com/declaration-of-conformity.
Wireless radio used in Zigbee lamps/luminaires/components 2400 – 2483.5 MHz, max. RF output power 9.5dBm.
1. Installations on Electromagnetic ballast
Please ensure that for Electro Magnetic (EM) application existing fluorescent starter is replaced with SubstiTUBE® LED starter (included in each packaging).
Steps:
- EM (CCG) Installation:
- Remove existing starter.
- Insert new SubstiTUBE® LED starter.
- Install SubstiTUBE® T8 Connected lamp.
- Rotate lamp 90 degrees.
Important Notes for EM Installation:
- This lamp is designed for general lighting service (excluding for example explosive atmospheres).
- This lamp may not be suitable for use in all applications where a traditional fluorescent lamp has been used.
- The temperature range of this lamp is more restricted. In cases of doubt regarding the suitability of the application, the manufacturer of this lamp should be consulted.
- In case of multi-lamp luminaire application, measure tc max temperature of all installed lamps. Please use a flexible thermosensor (e.g. "Type K").
- Operation above tc max can lead to premature aging and failure of devices.
- SubstiTUBE® T8 Connected emits light only with a limited beam angle, not like a fluorescent tube with 360° output.
- Not usable in tandem circuitry.
2. Installations on Mains (without ballast)
Steps:
- Cut wires and remove ballast.
- Follow below instructions for Mains connection.
Mains Installation:
- Installation guide
- Connect LED Tube to Mains (L and N).
- For single lamp fixtures, connect 1x LED Tube.
- For multi-lamp fixtures, connect ≥2x LED Tube.
- Rotate lamp 90 degrees.
Warning! The fixture has been modified and can no longer operate the originally specified T8 Fluorescent lamp. Please use only OSRAM SubstiTUBE® LED.
Company Information
LEDVANCE GmbH
Steinerne Furt 62
86167 Augsburg, Germany
www.ledvance.com
LEDVANCE Ltd
Aquila House
22 Delta Crescent, Westbrook, Warrington
WA5 7NR, United Kingdom
Recycling information: Lamps and their accessories are recycled. Dispose of at collection points or recycling centers.