Siemens SiPass Integrated Dual Reader Interface Module (ADD5100)
Brand: Siemens
Document Type: Installation Manual
1. Product Description
The ADD5100 is a Reader Interface Module used as part of a Siemens integrated access control and security solution. It provides an interface between an Advanced Access Controller (ACC), up to 2 card readers, and other devices used to secure and monitor a door.
When a cardholder presents their access card at a reader (connected to an ADD5100), the ADD5100 interprets the encoded information and sends this data to the ACC. The ACC then checks its validity. If the appropriate permissions have been assigned to the cardholder, the ACC sends a message back to the ADD5100, allowing it to unlock the door and permit access.
1.2 Product Numbers
6FL7820-8CA10 ADD5100 – Dual Reader Interface Module and base-plate, 24 V DC
1.3 Prerequisites
- Devices to be connected to the ADD5100.
- Cabling (RS485).
1.4 Required Tools & Material
- Medium-duty drill and associated drill-bits (if required).
- 4 to 6 mounting screws or standoffs (approx. 4mm).
- Flat-blade terminal screwdriver.
- Wire cutters.
- Cable strippers.
1.5 Expected Installation Time
30 minutes
1.6 Mounting Instructions
- Remove the ADD5100 from its carton and discard the packaging material.
- Place the ADD5100 (base-plate) against the surface to which it is to be affixed and mark the location of the mounting holes. If being mounted within a cabinet, align the ADD5100 base-plate with the holes located on the cabinet backplane and proceed to step 3. It is recommended that you affix the ADD5100 in at least four of the six mounting locations.
⚠️ WARNING: Do not apply power to the ADD5100 or associated components at this stage.
- Select the appropriate drill bit according to the mounting surface / hole size and drill the holes in the locations marked (if required).
- Fasten the ADD5100 (base-plate) to the surface using the correct type of screws or standoffs for the surface.
- Connect the cabling to the ADD5100 PCB (as described in the next section titled 'Wiring').
- Apply power to the ADD5100 and test its operation. This step may require installation and programming of the access control host software. The firmware and configuration are carried out using the FLN Field Service Tool.
1.7 Wiring
ℹ️ It is recommended that you wear a grounding strap while carrying out this procedure.
- Connect an IN reader to the READER1 INTERFACE port and an OUT reader to the READER2 INTERFACE port if the ADD5100 has been configured to operate as a Dual Reader Interface. Alternatively, connect RS232 or RS485 output readers to the SMARTCARD RDR INTERFACE port. The readers must be wired correctly as outlined in the Reader Wiring tables in this installation sheet.
- Connect the Request to Exit (REX) switch to the REX port.
- Connect the door contact device to the DOOR/C port.
- Connect auxiliary inputs (if required) to the AUX IN1 / AUX IN2 / AUX IN3 ports. Listed end-of-line resistors must be connected to the wires of each input device if they are to be supervised.
- Connect the FLN wires (from the ACC) to the RS485 BUS port.
- Connect the door strike / lock to the RELAY port. Ensure that power is also provided to the door lock / strike, and that this power supply is sufficiently rated to handle the load. If the door lock is likely to draw excess current or produce large voltage spikes, a diode bridge rectifier may need to be fitted.
- Connect the auxiliary output device (if required) to the RELAY2 port.
- If the FLN cable is long or subject to high noise, ensure that the jumper across link LK5 (EOL) has been made.
- Connect the active and neutral wires from the Power Supply Unit (PSU) to the +Vdc IN port. Ensure the polarity of the connection is made correctly.
- Check all connections thoroughly.
- Power can now be applied to the ADD5100.
1.8 Reader Wiring
The following table outlines industry standard reader wiring to the ADD5100 (Reader 1 and 2):
Reader Output Type | D0+ | D1- | GRN | RED | 0V | 12V |
---|---|---|---|---|---|---|
Wiegand | D0 | D1 | GRN | RED | 0V | 12V |
Magstripe (ABA Track II - Clock & Data) | RCP | RDP | GRN | RED | 0V | 8V/12V |
Bar Code (Differential - Pulse) | D+ | D- | GRN | RED | 0V | 8V/12V |
The following table outlines the reader wiring to the ADD5100 for RS485 output readers:
Reader Output Type | 12V | 8V/12V | 0V | TX/+ | RX/- | RTS | CTS | E Shield |
---|---|---|---|---|---|---|---|---|
RS485 | 12V | 8V/12V | 0V/GND | + or A | - or B | n/a | n/a | Shield |
1.9 Wiring of monitored input
The diagram illustrates the wiring of a monitored input to the ADD5100. It shows the IN1+ and IN1- terminals. The input signal wire's shielding is connected to the housing earth, while the input itself (e.g., door contact) is insulated from the shielding. Terminating resistors (R) are indicated for the input lines.
- Connect the shielding to the housing earth.
- Insulate the shielding at the input (e.g., door contact), do not connect it.
- DC: Door contact.
- R: Terminating resistors each 22 kOhm.
1.10 Links and Jumpers
The following table outlines the link settings for the ADD5100:
Link | Description | Normal Operation | Alternative Operation |
---|---|---|---|
LK1 | No Link - link included for future enhancement. | - | - |
LK3 | Reset - This link allows the unit to be manually reset. | Jumper off | Reset - by placing the jumper across this link the unit will automatically reset. |
LK4 | EOL Termination (Smart Card Reader) - This link allows the SMARTCARD RDR INTERFACE communications channel to be terminated in noisy or lengthy comms. | SMARTCARD RDR INTERFACE port not terminated. (EOL SRI) | SMARTCARD RDR INTERFACE port terminated. (EOL SRI) |
LK5 | EOL Termination (Bus) - This link allows the RS485 BUS communications channel to be terminated in noisy or lengthy comms. | RS485 BUS port not terminated. (EOL485) | RS485 BUS port terminated. (EOL485) |
LK6 | Passback Input - Passive / Active - This link allows "Passback Input" to be configured as an active or passive device. | Passive device connected (Jumper ON) | Active device connected (Jumper OFF) |
LK7 | Door Frame Input - This link allows "Doorframe Input" to be configured as an active or passive device. | Passive device connected (Jumper ON) | Active device connected (Jumper OFF) |
LK8 | Auxiliary Input 1 - This link allows "Auxiliary 1 Input" to be configured as an active or passive device. | Passive device connected (Jumper ON) | Active device connected (Jumper OFF) |
LK9 | Auxiliary Input 2 - This link allows "Auxiliary 2 Input" to be configured as an active or passive device. | Passive device connected (Jumper ON) | Active device connected (Jumper OFF) |
LK10 | Auxiliary Input 3 - This link allows "Auxiliary 3 Input" to be configured as an active or passive device. | Passive device connected (Jumper ON) | Active device connected (Jumper OFF) |
LK11 | Memory Clear and Reset - Short the 2 solder joints where the pins for link LK11 used to be. By shorting these joints, the ADD5100 will completely reset and the programmed memory will be cleared. Please note that the ADD5100 will need to be re-programmed for operation after a full reset. | - | - |
LK12 | No Link - General Purpose link included for future enhancement. | - | - |
1.11 Supported Card Formats
The following table outlines the supported card formats for the ADD5100. Please note the formats supported will depend directly upon the firmware, which has been downloaded.
Card Technology | Format |
---|---|
Bar Code | 2 of 5 3 of 9 |
Magstripe | Encrypted Facility Credit |
HID Proximity | Encrypted Facility CerPass SiPass |
Indala Proximity | 26-bit 36-bit Asco Corporate 1000 Siemens STG (*) |
Cotag Proximity | Siemens 52-bit encrypted 27 bit |
Siemens Proximity | 27 bit Encrypted |
MIFARE | CSN32 CSN40 |
MIFARE Smart | Sector - Siemens 52-bit |
Siemens | Siemens |
Asset ID Proximity | IBMAssetID1 |
125 Khz Proximity | CerPass |
Miro | CerPass |
Hitag1 | Cerpass |
Hitag2 | CerPass |
Legic | CerPass |
(*) for use in UL installations
1.12 LEDs
The following table describes the operation of the LEDs located on the ADD5100:
LED | Brief Description |
---|---|
POWER | The POWER led is illuminated when power has been applied to the DRI. |
ACTIVITY | This LED indicates whether the initial instruction set has been downloaded. If power is applied and the LED blinks quickly, the DRI instruction set (firmware) needs to be downloaded. If the LED is blinking slowly, approximately once per second, a firmware set has already been downloaded. |
COMMS | The COMMS led flashes when the DRI is communicating with the ACC to which it has been connected (via an FLN). |
1.13 Recommended Cable Specifications
The following table outlines the cable recommended for connection of an integrated security system:
Communication Type | Core | Pairs | AWG | Stranding | Wire Type | Insulation | Shield | Jacket |
---|---|---|---|---|---|---|---|---|
RS485 | 4 | 2 | 28 | 7 x 36 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / braided shield | PVC |
6 | 3 | 28 | 7 x 36 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / braided shield | PVC | |
8 | 4 | 28 | 7 x 36 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / braided shield | PVC | |
RS232 | 4 | 2 | 24 | 7 x 32 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / no braid | PVC |
6 | 3 | 24 | 7 x 32 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / no braid | PVC | |
8 | 4 | 24 | 7 x 32 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / no braid | PVC | |
RS422 | 4 | 2 | 24 | 7 x 32 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / no braid | PVC |
6 | 3 | 24 | 7 x 32 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / no braid | PVC | |
8 | 4 | 24 | 7 x 32 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / no braid | PVC | |
RJ-45 | 8 | 4 | 24 | Solid | Bare Copper | Polyethylene | Unshielded | PVC |
RJ-12 | 8 | 4 | 24 | Solid | Bare Copper | Polyethylene | Unshielded | PVC |
8 | 4 | 24 | 7 x 32 | Tinned Copper | Polyethylene | Aluminum foil- Polyester tape / no braid | PVC | |
Wiegand / Reader | 6 | 3 | 28 | 7 x 36 | Tinned Copper | Foam Polyethylene | Aluminum foil- Polyester tape / braided shield | PVC |
Power (12/24 V DC) | 2 | 1 | 18 | 19 x 30 | Tinned Copper | Foam Polyethylene | Unshielded | PVC |
The previous table provides a guideline for selecting an appropriate cable type only. Other cable types are also compatible with the system and can be used to achieve the same results.
1.14 Programming and Firmware Download
The ADD5100 is programmed using the stand-alone “Field Service Tool” application. Please refer to the respective User's Guide for more Information.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are made.
Diagram Descriptions
ADD5100 PCB Layout and Dimensions
The diagram shows the physical layout of the ADD5100 circuit board. It indicates dimensions of approximately 105mm x 90mm for the board itself. Key components and connectors are labeled: POWER, ACTIVITY, COMMS LEDs; various jumpers (LK1-LK12); RESET button; RS485 BUS, AUXILIARY SERIAL INTERFACE, +Vdc IN, READER1 INTERFACE, READER2 INTERFACE, RELAY1, RELAY2, DC OUT, DOOR/C, REX, AUX IN1, AUX IN2, AUX IN3, BATTERY ports. It also shows the base-plate with mounting holes and overall dimensions of 125mm (4.92") x 50mm (1.97").
ADD5100 Port Locations
This diagram highlights the location of each port on the ADD5100 board. A table below the diagram lists each port by name (e.g., +Vdc IN, RS485 BUS, Reader Interface 1, RELAY 1) and provides a brief description of its function.
Wiring of Monitored Input
The diagram illustrates the wiring for a "monitored input" connection to the ADD5100. It shows the IN1+ and IN1- terminals. The input signal wire's shielding is connected to the housing earth, while the input itself (e.g., door contact) is insulated from the shielding. Terminating resistors (R) are indicated for the input lines.